RTB Remote Trouble Buzzer Product Installation Drawing Document 50953 Rev B 5/18/00 ECN 00-154 Make certain to remove all power (AC and batteries) before connecting/disconnecting the RTB Remote Trouble Buzzer to the host fire alarm control panel. RTB - Remote Trouble Buzzer Terminal Connections The RTB is a Remote Trouble Buzzer which provides a green AC Power LED and a yellow Trouble LED along with a piezo sounder, all of which mimic the condition of the host control panel. The RTB can be mounted remotely in a single-gang electrical box. Four RTB terminals are provided for connection to a host fire alarm control panel as illustrated below. RTB Cover Plate RTB Cover Plate DC Ground (GND) AC Power LED (AC) Trouble LED (TBL) Piezo Sounder (BUZ) Note: All four connections in the above illustration are made to a terminal block on the host control panel main circuit board. The panel terminals are labeled similar to the labels shown above in parentheses. Single-gang Electrical Box Power Requirements The RTB is intended to mimic the corresponding indicators on the host fire alarm control panel. RTB connections must only be made to host control panel outputs which provide this feature. The following table lists the voltage and current requirements for each terminal on the RTB. Refer to the host panel's manual to ensure that it supports the RTB as well as for power specifications and wiring information and include the RTB voltage and current requirements in the host panel's battery calculations. RTB Te r mina l Conne ct ion Volt a ge Cur r e nt R a nge Buzze r 24 VDC 3 - 16 mA Tr ouble LED 24 VDC 3 - 20 mA AC Powe r LED 24 VDC 3 - 20 mA DC Gr ound 0 VDC 0 VDC