KON^AR KONCAR – MEDIUM VOLTAGE APPARATUS, Inc. MEDIUM VOLTAGE DISCONNECTOR SWITCHES for indoor installation Series RSN General Information Disconnector switches are part of traditional medium voltage assortment. They have been designed and manufactured in accordance with IEC 62271 – 103 (2003). Disconnector switch is an apparatus which is capable of closing and breaking load currents up to rated current level, at cosφ = 0,7, as well as currents of off-load transformers, cables and overhead lines and closed loop currents. Under fault conditions the disconnector switch can carry the short circuit current for a considerable short time, but it is not capable of breaking it. The disconnector switch in series with HRC fuses can break the short circuit current, where blown fuse in any phase automatically causes three-pole tripping of the disconnector switch. In open position the disconnector switch provides required visible insulating distance between contacts. This feature enables the use of disconnector switch at the network points where visible insulating distance is required. In these cases the disconnector switch can take over all nominal current breaking operations which would otherwise require the circuit breaker. Fuse-switch combination also successfully replaces the combination of circuit breaker – disconnector at the network points where rapid auto-reclosure is not required. Basic Characteristics Disconnector switch has the following basic characteristics: - small dimensions, due to linear contact movement quick arc quenching and high switching capability, due to two serial breaking points in each pole, as well as gas-generating insulating material in quenching cambers high availability and reliability, due to simple construction and quality of material minimal maintenance disconnector switches can be equipped with earthing blades and HRC fuses; auxiliary switches at disconnector switches with spring charging-energy storing mechanism the tripping release can be fitted Disconnector switches series RSN are manufactured in following versions: - version n – for back cell wall installation - version b – for lateral cell wall installation - version s – for front cell wall installation Earthing blades can be fitted to any of the versions listed above, at upper or lower side. Construction and Mode of Operation The poles are attached to the base frame by two post insulators series JOr (epoxy cast resin ribbed insulators). The operating mechanism with operating levers is also attached to the base frame. Operating mechanisms for disconnector switches series RSN: - m1 – turn-over mechanism m2 – spring charging – energy storing mechanism (suitable for remote control) RSN; Catalogue Eng. 2005; Page(s) 1/9 The disconnector switch type RSN 24n – m2 Od with energy storing mechanism type m2 is presented at the Fig.2. LEGEND: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. base frame post insulator connection point movable insulating cylinder operating rods insulating screen main shaft operating regulation lever operating mechanism’s main shaft operating mechanism type m2 HRC fuse insulating screen between poles / 24 kV only lower fuse carrier The movement transmission between the main shaft (Pos.10) and moving contact is enabled by telescope operating rod (Pos.6) which consists of two parts and ensures linear movements of moving contact during switching operations. Fig. 2. Disconnector switch type RSN 24n – m2 Od Current Path and Arc Quenching The pole cross-section at current breaking (in open position) is displayed at Fig. 3. LEGEND: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. a) closed position b) opening upper connection point lower connection point upper fixed contact lower fixed contact moving contact quenching chamber lower supressor quenching chamber upper supressor insulating cap / 24kV only insulating cone upper movable insulating cylinder lower movable insulating cylinder c) open position Fig. 3. Pole cross section - RSN 24n – m2 Od During tripping operation the movable insulating cylinders (10) with moving contacts (5) of the switch disconnector are moving towards lower position, by means of operating rods (Fig. 3. – Pos. a). RSN; Catalogue Eng. 2005; Page(s) 2/9 After contact separation during the linear movements, the two arcs connected in series occur at the ends of fixed contacts and both ends of moving contact, in the narrow slots between arcing contact rings made of special wolfram alloy. Both arcs are quickly quenched, due to released gases from insulating parts at the both sides of slots. Insulating material used for arcing chambers has high gas-generating properties. Also, no layers of soot occur even after numerous switching operations, which enables the quenching time stays short enough. The supressors (Pos. 6 and 7) prevent the released gases to enter the space between contacts. Serial connection of two breaking points at each pole doubles the arc extension speed in relation to contact separation speed, so there is no need for additional delaying arcing contacts. When the moving contact is almost at the end of its stroke, the insulating cap (Pos.8) goes down to final place between contacts, and provides additional insulation between contacts. Serial connection of two breaking points has also a favourable effect at closing operation. The speed of contact movement is doubled, and the pre-arcing times considerably short. These features enable that minimal energy is released in disconnector switch during closing operation. Operating Mechanisms The two kinds of operating mechanisms can be built in disconnector switches series RSN: - - turn-over m1 – the closing and opening operations are performed by two pressure springs, which are turned by coupler or regulating lever until they reach neutral position and overcome the friction angle. From this position the springs discharge instantaneously and turn the main shaft to position closed or open, depending on their previous position. The way of closing is presented at Fig. 4. spring charging – energy storing mechanism m2, (suitable for remote tripping) – the switching operation is performed by two systems of springs which are charged simultaneously. When the spring charging is complete, the closing spring performs the closing operation immediately. The tripping spring remains charged in order to enable tripping operation either manually or remotely (on purpose, by push-button and tripping release, or automatically – by tripping release triggered from HRC fuse striking needle or impulse from protection). The tripping procedure is presented at Fig.5. Operating mechanisms of disconnector switches series RSN are simple and reliable, so they guarantee faultless operation of apparatus under any service condition. a) open position b) ready to close c) closed position Fig.4. Disconnector switch RSN 24 s with turn-over operating mechanism type m1 RSN; Catalogue Eng. 2005; Page(s) 3/9 a) open position b) ready to close c) closing position Fig.5. Disconnector switch RSN 24 s with energy storing operating mechanism type m2 Technical Characteristics RSN 12 RSN 24 Rated voltage 12 kV 24 kV Rated frequency 50 Hz 50 Hz Rated power frequency withstand voltage (50 Hz) to the earth and between poles 28 kV 50 kV to the earth and between poles 75 kV 125 kV across insulating distance 85 kV 145 kV Rated current 630 A 630 Rated breaking capacity at cosφ>0,75 400 A 400 Breaking current of off-load transformer 10 A 7A Rated making capacity (ampl.) 50 kA 6 kA Short time withstand current 1s (Eff.) 20 kA 16 kA Rated peak withstand current (ampl.) 50 kA 40 kA Rated impulse withstand voltage 1,2/50 µs If the disconnector switch is equipped with HRC fuses, the rated current of the switch-fuse combination. The breaking capacity of switch-fuse combination equals the breaking capacity of the fuse, in accordance with IEC 62271-105. RSN; Catalogue Eng. 2005; Page(s) 4/9 Type Designations The type designations indicate the version of the disconnector switch, as well as its basic accessories. The scheme of type designation generating is presented at Fig. 6. RSN ●● ● ●● ●● ●● Earthing blades: Zg Zd at upper side at lower side Fuses: Og at upper side Od at lower side Operating mechanism: m1 turn-over m2 energy storing Version (way of installation): n b (s) Rated voltage to the back cell wall to the lateral cell wall to the front cell wall* 12 kV 24 kV Basic series designation *on special customer’s request only Fig. 6. Type designations of switch disconnectors series RSN Additional Equipment Besides the main accessories, which are visible from type designation (HRC fuses and earthing blades) the disconnector switches can be equipped with the following: - auxiliary switches for main blades as well as earthing blades (6-pole, 9-pole or 13-pole, as displayed at Fig.7.) - Voltage tripping release (available for secondary voltages 220V/50Hz; 110V/50Hz; 220V=; 110V=; 60V=; 48V= ; 24V=) SNL VI bn SNL IX en SNL XIII fn Fig.7. Auxiliary switches for disconnector switches series RSN – standard versions RSN; Catalogue Eng. 2005; Page(s) 5/9 LEGEND: SNL – Auxiliary switch (see versions available at Fig. 7) Oi – Tripping release (to be delivered on request) Ti – Tripping push-button (to be installed at site, by customer) Fig. 8. Tripping circuit for RSN with push-button and tripping release and auxiliary switch type SNL VI bn Installation and Operation Drives Three types of drives can be used to operate disconnector switches series RSN (version n): - manual toggle joint drives type S-5 and S-15 - electric motor drive type EMP-20 - air-blast drives type Zp 8/9 or Zp 10/13 (today almost not in use). Drive Toggle joint Air-blast S-5 Disconnector switches series RSN – main blades m1 x m2 Earthing blades S-15 x x x EMP 20 x x x x Zp 10/13 Zp 8/9 x x Disconnector switches intended to be built laterally are operated directly from the main shaft. Disconnector switches intended to be built at the front cell wall are operated by operating regulation lever attached to the main shaft. Detail data regarding drives are available in separate catalogue. Ordering Data The full type designation (in accordance with Fig.6) containing the following data is required: Rated voltage (12 or 24 kV) Version (way of installation) – n, b or s - Type of operating mechanism (m1 or m2) - HRC fuses, at lower or upper side (Od or Og), if required - Earthing blades, at lower or upper side (Zg or Zd), if required Other data required: - Auxiliary switches (in accordance with Fig.7) for main blades and earthing blades, if required - Data regarding tripping release (secondary voltage) if required IMPORTANT NOTE: The following versions of disconnector switches are available as standard. (Any other only on special customer’s request). Rated voltage 12 kV installation to back cell wall (version n) Rated voltage 24 kV installation to lateral cell wall (version b) installation to back cell wall (version n) installation to lateral cell wall (version b) RSN 12 n m1 Zd RSN 12 b Zd RSN 24 n m1 Zd RSN 24 b Zd RSN 12 n m2 Od RSN 12 b Od RSN 24 n m2 Od RSN 24 b Od RSN; Catalogue Eng. 2005; Page(s) 6/9 Dimensional Drawings Fig. 9. Disconnector switches with turn-over mechanism m1, type RSN 24 n-m1, RSN 24 n-m1 Zd and RSN 24 n-m1 Zg Fig. 10. Disconnector switch with energy storing mechanism m2, type RSN 24 n-m2 RSN; Catalogue Eng. 2005; Page(s) 7/9 Fig. 11. Disconnector switch with energy storing mechanism m2, type RSN 24 n-m2 Og Fig. 12. Disconnector switch with energy storing mechanism m2, type RSN 24 n-m2 Od RSN; Catalogue Eng. 2005; Page(s) 8/9 Fig. 13. Disconnector switch with turn-over mechanism m1, type RSN 12 b-m1 Zd Fig. 14. Disconnector switch with energy storing mechanism m2, type RSN 12 b-m2 Od All data in this catalogue are subject to change. Obligatory drawings and technical data we provide on request. KON^AR KONČAR – ELEKTRIČNI APARATI SREDNJEG NAPONA d.d. Borongajska bb, 10000 Zagreb, Hrvatska Tel. + 385 1 23 34 867; Fax. + 385 1 23 31 058 e-mail: prodaja@koncar-easn.hr RSN; Catalogue Eng. 2005; Page(s) 9/9