INSTITUTION OF GAS ENGINEERS AND MANAGERS IGEM/UP/1A Edition 3 Communication XXXX IGEM/TSP/13/282 Founded 1863 Royal Charter 1929 Patron Her Majesty the Queen STRENGTH TESTING, TIGHTNESS TESTING AND DIRECT PURGING OF LPG/AIR, NATURAL GAS AND LPG INSTALLATIONS. MOP UP TO 60 MBAR, VOLUME UP TO 1 m3 AND DIAMETER UP TO 150 mm DRAFT FOR COMMENT 1 This draft Standard IGEM/UP/1A Edition 3 has been prepared by a Panel under the chairmanship of Andy Durber. 2 This Draft for Comment is presented to Industry for comments which are required by 6th December 2013, and in accordance with the attached Reply Form. 3 This is a draft document and should not be regarded or used as a fully approved and published Standard. It is anticipated that amendments will be made prior to publication. It should be noted that this draft Standard contains intellectual property belonging to IGEM. Unauthorised copying or use by any unauthorised person or party is not permitted. 4 This is a copyright document of the Institution of Gas Engineers and Managers. Enquiries should be addressed in the first instance to: Nick Cowling IGEM IGEM House 26-28 High Street Kegworth Derbyshire, DE74 2DA Tel: 0844 375 4436 Fax: 01509 678198 Email: nick@igem.org.uk Attached is the Draft for Comment of IGEM/UP/1A – “Strength testing, tightness testing and direct purging of LPG/Air, Natural Gas and LPG installations. MOP up to 60 mbar, volume up to 1 m3 and diameter up to 150 mm” and the associated comment form. We wish to make it as easy as possible for those of you representing industry bodies to issue the draft to your Members. You can either forward this email with attachment complete or forward it without the attachment and invite them to visit our website via http://www.igem.org.uk/technical-standards/standards-development/drafts-for-comment.aspx where the Draft and Comment Form are posted. Organisations to which this Draft has been circulated: Organisation AIGT Association of Registered Gas Installers BSI/GSE/30 CIBSE CIPHE DNO Collaboration Forum Energy Institute ENA EUSkills Gas Forum Gas Safe Register GIRSAP GISG HSE HVCA ICOM National Grid Northern Gas Networks Ofgem Organisation of Professional Gas Operatives SBGI Scotia Gas Networks UKLPG Wales and West Utilities YPN IGEM COUNCIL Membership Committee Marketing Committee Audit Committee TCC GTDC GMC GUC IGEM/UP/1A Edition 3 Communication XXXX Strength testing, tightness testing and direct purging of LPG/Air, Natural Gas and LPG installations. MOP up to 60 mbar, volume up to 1 m3 and diameter up to 150 mm Draft for Comment Founded 1863 Royal Charter 1929 Patron: Her Majesty the Queen IGEM/UP/1A Edition 3 Communication XXXX Strength testing, tightness testing and direct purging of LPG/Air, Natural Gas and LPG installations. MOP up to 60 mbar, volume up to 1 m3 and diameter up to 150 mm Draft for Comment Price Code: C10H © The Institution of Gas Engineers and Managers IGEM House High Street Kegworth Derbyshire, DE74 2DA Tel: 0844 375 4436 Fax: 01509 678198 Email: general@igem.org.uk Copyright © 2013, IGEM. All rights reserved Registered charity number 214001 All content in this publication is, unless stated otherwise, the property of IGEM. Copyright laws protect this publication. Reproduction or retransmission in whole or in part, in any manner, without the prior written consent of the copyright holder, is a violation of copyright law. ISBN 978 1 905903 XX X ISSN 0367 7850 Published by the Institution of Gas Engineers and Managers Previous Publications: Communication 1645 (1998) – 1st Edition Communication 1701 (2003) – 2nd Edition Communication 1717 (2005) – 2nd Edition, Reprint with Amendments For information on other IGEM Standards please visit our website, www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) CONTENTS SECTION PAGE 1 Introduction 1 2 Scope 5 3 Legal and allied considerations 9 4 Test equipment and criteria 10 5 Strength testing 10 6 7 5.1 Determination of STP 10 5.2 11 11 11 Decision whether to strength test • 5.2.1 New installations and extensions • 5.2.2 Existing installations 5.3 Method, pressure, duration and test criteria for strength testing 11 5.4 Testing separate components or sub-assemblies 11 5.5 Procedures 12 Tightness testing 14 6.1 15 15 15 General 6.1.1 New installations and extensions 6.1.2 Existing installations 6.2 Installation volume (IV) 6.2.1 General 6.2.2 Calculations 15 15 16 6.3 Tightness test pressure (TTP) 17 6.4 Selection of pressure gauges 17 6.5 Test criteria 6.5.1 New installations and extensions 6.5.2 Existing installations 18 18 18 6.6 20 20 21 Tightness test duration (TTD) 5.6.1 New installations and extensions 5.6.2 Existing installations 6.7 21 21 22 22 23 Procedures 6.7.1 By-passing components 6.7.2 Ambient conditions 6.7.3 Testing new installations and extensions 6.7.4 Testing existing installations 6.8 Appliance connector 25 Direct purging 28 7.1 General 28 7.2 Planning and supervision 28 7.3 Site precautions 7.3.1 Warning notices and label 7.3.2 Electrical and fire 29 29 30 IGEM, IGEM House, High Street, Kegworth, Derbyshire DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) APPENDIX 7.4 Designing and positioning purge points, hoses and vent stacks 30 7.5 Verification of purge flow rate 31 7.6 Identification of purge gas cylinders 32 7.7 Gas detectors, oxygen analysers and other electronic equipment 32 7.8 Gas appliances 32 7.9 Determination of the purge volume, purge flow rate and purge time32 7.10 Vent gas testing 34 7.11 34 34 35 Purging procedures when venting to outside 7.11.1 Direct purging from air to gas i.e. commissioning 7.11.2 Direct purging from gas to air i.e. de-commissioning 7.12 Dealing with meters within pipework sections 7.12.1 Replacement meter with associated pipework maintained at positive pressure 7.12.2 Replacement meter with associated pipework not maintained at a positive pressure 7.12.3 Purging a new meter 37 37 38 39 1 Glossary, acronyms and symbols 42 2 References 45 3 Indirect purging with nitrogen 47 4 Tightness test durations for a water gauge using the concept of “no perceptible movement” (for new installations only) 48 FIGURES 1 Relative pressure levels 2 2 Algorithm to select testing and purging standards 2 3 Typical schematic NG installations 7 4 Flowchart/decision algorithm for strength testing 13 5 Flowchart/decision algorithm for tightness testing of new installations and extensions 26 Flowchart/decision algorithm for tightness testing of existing installations 27 7 Flowchart for direct purging of air to gas 40 8 Flowchart for direct purging of gas to air 41 1 Method, pressure, duration and test criteria for strength testing 11 2 Installation volume (IV) of meters 16 3 Volume of 1 m length of pipe 17 4 Selection of pressure gauges (typical data) 18 6 TABLES IGEM, IGEM House, High Street, Kegworth, Derbyshire DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) 5 Determination of maximum allowable pressure drop (test criteria) on existing installations 19 6 Tightness test duration (TTD) for new installations and extensions 20 7 Tightness test duration (TTD) for existing installations 21 8 Let-by test period 23 9 Minimum purge flow rate 33 10 Flammable limits and safe purge end points 34 11 Flammability limits and safe purge end points for indirect purge 48 IGEM, IGEM House, High Street, Kegworth, Derbyshire DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) SECTION 1 : INTRODUCTION 1.1 This Standard supersedes IGE/UP/1A Edition 2, Communication 1701 and IGE/UP/1A Edition 2 Reprint with Amendments, Communication 1715 which are obsolete. It complements the IGEM/UP/1 Edition 3. 1.2 This Standard has been drafted by a Panel appointed by the Institution of Gas Engineers and Managers’ (IGEM’s) Gas Utilization Committee, subsequently approved by that Committee and published by the authority of the Council of the Institution. 1.3 IGEM/UP/1 deals with all aspects of strength and tightness testing of selected 1st, 2nd and 3rd family gases at a maximum operating pressure (MOP) not exceeding 16 bar. It deals with all aspects of purging those gases but there is no limit on MOP for purging. Note: It has been recognised that certain activities outlined in IGEM/UP/1 are only required for “large” installations and/or higher pressures and/or other gases and, therefore, the text of IGEM/UP/1A Edition 3 can be much simpler due to the limited scope. IGEM/UP/1A deals with strength and tightness testing and direct purging of Liquefied Petroleum Gas/Air (LPG/Air), Natural Gas (NG) and Liquefied Petroleum Gas (LPG) installations of volume not exceeding 1 m3 (0.5 m3 for LPG installations) and maximum operating pressure (MOP) of not exceeding 60 mbar on industrial and commercial premises. Note: In the United Kingdom LPG/Air is typically 1st family gas, NG is 2nd family gas and LPG is a 3rd family gas. NG is lighter than air and LPG/Air and LPG are both heavier than air. IGEM/UP/1A is intended to assist the operative in understanding and identifying the particular activities of strength and tightness testing and direct purging related to a particular installation. Note: Strength testing ensures that pipework can withstand, with respect to integrity, the pressures it could experience under fault conditions. A result of carrying out a strength test is that the subsequent tightness test is carried out at Operating Pressure (OP) and not at higher pressures. For IGEM/UP/1A applications, the strength and tightness tests may be carried out separately or be combined or be carried out concurrently. Referring to Figure 2, note how OP is shown to oscillate about the set point (SP). Note also that MOP can be declared at any value from OP to a limit below maximum incidental pressure (MIP). IGEM/UP/1B deals with all aspects of tightness testing and direct purging of small Liquefied Petroleum Gas/Air (LPG/Air), NG and Liquefied Petroleum Gas (LPG) installations with or without a meter of maximum badged capacity not exceeding 16 m3 h-1 and supply MOP (MOPu) not exceeding 2 bar. IGEM/UP/1C deals with strength testing, tightness testing and direct purging of meter installations (as defined in IGEM/G/1), containing either NG or LPG, of volume not exceeding 1 m3 and MOP not exceeding 7 bar. Note: IGEM/UP/1C is most useful for those NG or LPG meter installations that have a means of isolation on the outlet, are out of scope of IGEM/UP/1B and where there is no desire to test the installation pipework downstream of the meter installation. Figure 1 will assist in selecting the appropriate standard. Note: For a new system of installation pipework, the onus is on the designer to establish both the maximum incidental pressure (MIP) and MOP. For an existing system of installation pipework, the onus is on the designer/owner of the installation to ensure that any increase in pressure within the installation will not result in OP exceeding MOP of the system and on the gas transporter/meter asset manager (GT/MAM) to ensure that any change in their pressure regimes due to fault conditions will not jeopardise the safety of the downstream installation. This involves effective communication between the GTs/MAMs and installation designers/owners. 1 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) Start LPG installation on a boat, small craft, (up to 24 m in length) or other vessels? PD 5482-3 or BS EN ISO 10239 Yes No Is supply MOP ≤ 2 bar (for LPG/air and NG) AND Ø ≤ 35 mm AND Meter badged capacity ≤ 16 m3 h-1 AND volume ≤ 0.035 m3 AND OP ≤ 21 mbar (for LPG/Air and NG) OR OP ≤ 37 mbar (for LPG)? Yes IGEM/UP/1B Edition 3 Yes IGE/UP/1A Edition 2 No Is MOP ≤ 60 mbar AND Ø ≤ 150 mm AND volume ≤ 1 m3 (for LPG/Air and NG) OR volume ≤ 0.5 m3 (for LPG)? No NG or LPG? Yes Meter installation with supply MOP ≤ 7 bar AND with volume ≤ 1 m3 AND with no PE included AND isolated at the outlet Yes IGEM/UP/1C No No IGE/UP/1 Edition 2 V less than or equal to nominal diameter volume MOP NG OP LPG Maximum Operating Pressure Natural Gas Operating pressure Liquefied petroleum gas mbar mm m3 millibar millimetre cubic metre Note 1: If it is preferred IGE/UP/1 Edition 2 can be used rather than IGE/UP/1A Edition 2, IGEM/UP/1B Edition 3 or IGEM/UP/1C or PD 5482-3 or BS EN ISO 10239. It is necessary to check the scope of referenced Standards before proceeding. Note 2: Operating pressures listed are nominal for the installations and will vary around the regulator set point (see Figure 2). FIGURE 1 - ALGORITHM TO SELECT TESTING AND PURGING STANDARDS 2 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) STP MIP OP MOP SP Note: = = = = = Strength test pressure Maximum incidental pressure (e.g., as declared by the GT/MAM/Supplier) Operating pressure Maximum operating pressure Set point of the regulator. This is extracted from IGEM/TD/13 and simplified for the purposes of IGEM/UP/1A. FIGURE 2 - RELATIVE PRESSURE LEVELS 1.4 This Standard makes use of the terms “must”, “shall” and “should” when prescribing particular procedures. Notwithstanding Sub-Section 1.7: the term “must” identifies a requirement by law in Great Britain (GB) at the time of publication the term “shall” prescribes a requirement which, it is intended, will be complied with in full and without deviation the term “should” prescribes a requirement which, it is intended, will be complied with unless, after prior consideration, deviation is considered to be acceptable. Such terms may have different meanings when used in legislation, or Health and Safety and Executive (HSE) Approved Code of Practice (ACoPs) or guidance, and reference needs to be made to such statutory legislation or official guidance for information on legal obligations. 1.5 The primary responsibility for compliance with legal duties rests with the employer. The fact that certain employees, for example “responsible engineers”, are allowed to exercise their professional judgement does not allow employers to abrogate their primary responsibilities. Employers must: 1.6 have done everything to ensure, so far as it is reasonably practicable, that “responsible engineers” have the skills, training, experience and personal qualities necessary for the proper exercise of professional judgement have systems and procedures in place to ensure that the exercise of professional judgement by “responsible engineers” is subject to appropriate monitoring and review not require “responsible engineers” to undertake tasks which would necessitate the exercise of professional judgement that is not within their competence. There should be written procedures defining the extent to which “responsible engineers” can exercise their professional judgement. When “responsible engineers” are asked to undertake tasks which deviate from this they should refer the matter for higher review. It is now widely accepted that the majority of accidents in industry generally are in some measure attributable to human as well as technical factors in the sense that actions by people initiated or contributed to the accidents, or people might have acted in a more appropriate manner to avert them. It is therefore necessary to give proper consideration to the management of these human factors and the control of risk. To assist in this, it is recommended that due regard be paid to HSG48 and HSG65. 3 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) 1.7 Notwithstanding Sub-Section 1.4, this Standard does not attempt to make the use of any method or specification obligatory against the judgement of the responsible engineer. Where new and better techniques are developed and proved, they should be adopted without waiting for modification to this Standard. Amendments to this Standard will be issued when necessary, and their publication will be announced in IGEM’s Journal and other publications as appropriate. 1.8 Requests for interpretation of this Standard in relation to matters within its scope, but not precisely covered by the current text, should be addressed in writing to Technical Services, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA and will be submitted to the relevant Committee for consideration and advice, but in the context that the final responsibility is that of the engineer concerned. If any advice is given by or on behalf of IGEM, this does not relieve the responsible engineer of any of his or her obligations. 1.9 This Standard was published in January 2013. 4 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) SECTION 2 : SCOPE 2.1 This Standard covers strength and tightness testing, and purging of installations containing LPG/air, NG or LPG. Note: 2.2 For other gases, IGEM/UP/1 applies. This Standard applies to any section of an installation downstream of the outlet of the emergency control valve (ECV). Note: This includes any primary or secondary meter installation. For pressures exceeding 75 mbar on the inlet to the section being tested, the length of pipework between a valve being used to isolate that section and the first regulator downstream of that valve is limited to a maximum length of 3 m unless it has been pre-tested for strength and tightness prior to assembly. Typical installations are shown in Figure 3. This Standard does not apply to distribution mains, service pipes or service pipework, for which the appropriate Standard, i.e. IGEM/TD/3, IGEM/TD/4 or UKLPG CoP 22 applies. 2.3 This Standard applies to installations/sections of an installation (that may include meter installations) having the following: volume not exceeding 1 m3 for LPG/air and NG installations and 0.5 m3 for LPG installations, including any meter and any allowance for fittings MOP not exceeding 60 mbar at the outlet of the first regulator pipework of nominal bore not exceeding 150 mm. 2.4 This Standard covers the testing of any installation sections of an installation where IV can be calculated or a conservative estimate i.e. over estimate, can be made. 2.5 This Standard applies to strength testing and/or tightness testing in the following circumstances: new installations routine testing of existing installations alteration to, replacement of, or re-use of, existing installations new extensions to existing installations prior to any work on existing installations where there is a known or suspected gas escape where there has been a complete loss of supply pressure i.e. upstream of the ECV, or of installation pressure immediately before purging of installations (except when taking components permanently out of service). Note: If considering strength testing existing pipework, refer to clause 5.2.2. 5 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) 2.6 This Standard applies to direct purging in the following circumstances: new installations alteration to, replacement of or re-use of existing installations new extensions to existing installations where there has been a complete loss of installation pressure where there is the possibility of air being present in an installation where an installation is to be taken out of service temporarily or permanently. 2.7 All pressures quoted are gauge pressures, unless otherwise stated. 2.8 Italicised text is informative and does not represent formal requirements. 2.9 Appendices are informative and do not represent formal requirements unless specifically referenced in the main sections via the prescriptive terms ‘must’, ‘shall’ or ‘should’. 6 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) (a) Typical installation. MOPu 75 mbar. Installation MOP 60 mbar Strength test if New or Extension. Tightness test and Purge to IGEM/UP/1A. M ECV F S R A MIV AECV (If fitted) AIV (b) Typical installation. 75 mbar < MOPu 2 bar Installation MOP 60 mbar (c) Example section installation. 2 bar < MOPu Section installation MOP 60 mbar ECV S F R MIV M A AECV AIV IV MOPu emergency control valve safety device (see BS 6400) filter regulator meter inlet valve meter appliance additional emergency control valve appliance isolation valve isolation valve supply MOP. < Network meter installation installation pipework less than less than or equal to Note 1: Certain installations will incorporate an under pressure shut-off device. Note 2: A meter may not be fitted on LPG installations. Note 3: Where a component or sub-assembly (meter installation component, meter “skid” unit, etc.) has been pre-tested and not subsequently modified (such as by cutting threads or welding) and has appropriate certificates of conformity available, the strength testing of such a component/assembly need not be undertaken but a visual examination of joints, general condition, suitability, etc. is recommended prior to installing and subsequent tightness testing as for a new installation. Permanent marking, for example by manufacturer’s badging/stamping, may be deemed as certification of conformity. FIGURE 3 - TYPICAL INSTALLATIONS 7 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) SECTION 3 : LEGAL AND ALLIED CONSIDERATIONS 3.1 This Standard is set out against a background of legislation in force in GB at the time of publication. Similar considerations are likely to apply in other countries where reference to appropriate national legislation is necessary. All relevant legislation must be applied and relevant ACoPs, official Guidance Notes and referenced codes, standards, etc. shall be taken into account. Note: Appendix 2 is relevant in this respect. Where British Standards, etc. are quoted, equivalent national or international standards, etc. equally may be appropriate. 3.2 Any person engaged in strength testing, tightness testing or purging of pipework must be a competent person. Note: Any person carrying out the installation of gas pipework and associated fittings must be competent to do so. Where gas installation work is carried out in properties covered by the Gas Safety (Installation and Use) Regulations (GS(I&U)R), the persons carrying out that work must be a “member of a class of persons” as specified by those Regulations. At the time of publication of this Standard, the body with HSE approval to operate, and which maintains, a register of businesses in the GB who are "members of a class of persons" is the Gas Safe Register. Thus, it is essential that all businesses or self-employed gas installers be registered with Gas Safe if GS(I&U)R apply. Persons who are deemed competent to carry out gas work under GS(I&U)R are those who hold a current certificate of competence in the type of activity to be conducted issued under the ACoP arrangements, or by a certification body accredited by the United Kingdom Accreditation Service (UKAS) for the Accredited Certification Scheme (ACS). 3.3 Consideration shall be given to the environmental impact of methane and other hydrocarbons in the atmosphere. Releases should be minimised to levels required to achieve prescribed purge end points. 3.4 If at any stage in the tightness testing or purging process there is any potential for fuel gas or a fuel gas/air mixtures being released into the atmosphere, for example adjusting the pressure for a let by test, it will need to be vented ensuring the following safety precautions are taken throughout the process: avoid any accumulation of gas within confined spaces advise the responsible person for the premises or other persons in the area of the above of the intent to purge and that there may be a smell of gas. prevent inadvertent operation of any electrical switch or other appliance extinguish all potential sources of ignition ensure that there is no smoking or naked lights ensure good ventilation by opening doors, windows, passive stack ventilation systems, etc. 8 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) SECTION 4 : TEST EQUIPMENT AND CRITERIA 4.1 TEST EQUIPMENT 4.1.1 Any gauge or gas detector shall: be suitably ranged if appropriate, be zeroed at atmospheric pressure at the start of each test be appropriate for the gas under test be suitable for the atmosphere in which they are to be used be calibrated for the gas on which it will be used in accordance with the manufacturer’s instructions. Any electronic gauge or gas detector shall be calibrated at least every 12 months, or otherwise as specified by the manufacturer, and a calibration certificate should be available. Note: 4.1.2 4.1.3 For the purposes of this Standard, one of the following gauges shall be used: Fluid (Water) gauge reading in 0.5 mbar increments Electronic gauge reading to 1 decimal place Electronic gauge reading to 2 decimal places. Any electronic gauge shall: be operated within the manufacturer’s specification for ambient temperature be stabilized at the ambient temperature as specified by the gauge manufacturer, prior to the test being carried out. Note: 4.1.4 Fluid (water) gauges do not require calibration but do need to be kept well maintained. Electronic gauges may be prone to drifting due to changes in ambient temperature. In the following situations, electronic test equipment shall be certified for use in a hazardous area (intrinsically safe): when seeking the source of a known or suspected gas escape, using a gas detector where it is known or suspected that the location in which the equipment is to be used could contain a flammable atmosphere that may be ignited by the use of equipment that is not certified for use in hazardous areas when a hazardous area is imposed by the gas installation or other installations/situations that require the use of such certified equipment and the equipment is to be used within the designated zone of that hazardous area when it is anticipated that the area in which the equipment will be located will be left unattended at any time during the test/purge when a risk assessment indicates that the use of certified equipment is essential. The decision on whether electronic equipment, for example pressure gauges and gas detectors, can be of a type not certified for use in a hazardous area, may be complex and is not an issue that can be developed in IGEM/UP/1A. Note: Fluid (water) gauges can always be used if there is any doubt about the use of electronic pressure gauges that are not certified for use in hazardous areas. Use of electronic pressure gauges that are not certified for use in hazardous areas, placed in the open air or in well ventilated environments and located in a position that will not cause the ignition of any flammable atmospheres may be acceptable for a number of the above situations, subject to a suitable risk assessment. 9 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) A hazardous area is an area in which explosive mixtures are, or may be expected to be, in quantities such as to require special precautions for the construction, installation and use of electrical apparatus or other sources of ignition. Detailed guidance on hazardous areas relating to gas installations can be found in IGEM/SR/25 and IGEM/UP/16. 4.1.5 Any equipment, including the sample line, shall be checked for integrity immediately prior to measurement. Only proprietary leak detection fluids (LDFs) shall be used that comply with BS EN 14291 and should be compatible with the materials to which it is to be applied. LDFs containing more than 30 parts per million of halogens shall not be used on stainless steel components. LDFs containing ammonia shall not be used on copper or brass components. To avoid subsequent corrosion, care shall be taken to ensure that LDF is wiped off pipe and fittings after use. Note 1: A pH value of 7.0 or less indicates absence of ammonia. Note 2: Detergents and soap solutions such as “washing-up” liquids are not suitable. Note 3: Certain chemicals (for example, ammonia and chlorides) used in some LDFs can cause unwanted effects such as stress corrosion cracking. 4.2 TEST CRITERIA 4.2.1 Consideration shall be given to whether the installation is new or existing and the type of fuel being tested. Test criteria for strength testing and tightness testing are given in Sections 5 and 6 respectively. 4.2.2 IGEM/UP/1A Edition 3 continues to adopt the concept of “gauge readable movement”. When using a water gauge, it is possible to reduce the duration of tests for new installations and extensions by adopting the concept of “no perceptible movement” in which case Appendix 4 shall be used. 4.2.3 For “let-by tests” and ‘appliance connector tests’, the pass criteria shall be “no perceptible movement” during the test period. Note: A movement of 0.25 mbar or less on a fluid (water) gauge is considered to be “not perceptible”. Therefore, if the gauge is seen to move, it can be inferred that the pressure within the installation has altered by more than 0.25 mbar. It follows that, where a gauge that can register perceptible movement of less than 0.25 mbar i.e. an electronic gauge, is used, the pass criteria of “no perceptible movement” has to be considered to be a maximum of 0.25 mbar except for those gauges that read to one decimal place when “no perceptible movement” is considered a maximum of 0.2 mbar. 10 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) SECTION 5 : STRENGTH TESTING New pipework, designed in accordance with current relevant standards, will have been designed to withstand the strength test pressure (STP). However, particular components within the pipework may need to be removed for the strength test (see Sub-Section 5.4). In addition, appliances may not be designed to withstand the STP. Strength testing is used to identify any major flaw in the construction of a new installation, prior to tightness testing. A strength test permits a fall in pressure limited to the value given in Table 1. Note 1: It is advisable to combine the strength and tightness tests i.e. immediately follow the strength test with the tightness test. This may save a little time by not requiring a stabilization period for the tightness test. The requirements given in Sections 4 and 5 assume a separate test for each (although some guidance is included for combining the tests) and the principles equally apply for a combined test. Note 2: It is also permitted to carry out the tightness test concurrently with the strength test. This would mean carrying out the tightness test at STP, applying the greater of the required stabilization and test times but not both, and applying the tightness test pass/fail criteria (a pass indicating that both the strength and tightness tests are satisfactory). However, there will be a minority of installations that will fail the tightness test that would have passed if the tests had been carried out separately or simply combined. IGEM/UP/1A does not describe the method of carrying out the tests concurrently. Preparations for the tightness test will need to be made prior to carrying out the strength test if the tests are to be combined or if they are to be carried out concurrently. Some leak detection fluids (LDFs) have an adverse effect on certain pipework materials. Consequently, any residual fluid shall be washed thoroughly off the pipe. If necessary, for example when joints are broken, temporary electrical continuity bonds shall be installed before testing. For the purposes of this section, it is assumed that, due to the low test pressure involved, the strength test is carried out pneumatically. For hydrostatic testing, the procedures and criteria in IGEM/UP/1 shall be applied. Note: 5.1 Hydrostatic testing is not necessary for installations capable of being tested to IGEM/UP/1A and is not recommended due to the subsequent need to dry the pipework. DETERMINATION OF STP STP shall be as given in Table 1. This Standard assumes that MOP equates to design pressure (DP). Where DP is quoted and is in excess of MOP, the value of DP shall be used in the calculation of STP. Where a booster or compressor is included anywhere downstream of, or within, the installation pipework being tested, the maximum back pressure shall not exceed 75 mbar. Where DP is greater than MOP and exceeds 75 mbar, or where the maximum back pressure exceeds 75 mbar, the installation shall be tested in accordance with IGEM/UP/1. Note: IGEM/UP/2 explains the principles of this back pressure but its value would need to be determined from equipment manufacturers and/or system designers. 11 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) 5.2 DECISION WHETHER TO STRENGTH TEST 5.2.1 New installations and extensions A strength test shall be carried out on any new installation or extension except for components that have been pre-tested or have been removed to avoid over pressurisation, for example appliances. Note: Where a component or sub-assembly (meter installation component, meter “skid” unit, etc.) has been pre-tested and not subsequently modified and has appropriate certificates of conformity available, the strength testing of such a component/assembly need not be undertaken but a visual examination of joints, general condition, suitability, etc. is recommended prior to installing and subsequent tightness testing as for a new installation (see Sub-Section 5.4). Permanent marking, for example by manufacturer’s badging/stamping, may be deemed as certification of conformity. 5.2.2 Existing installations 5.2.2.1 A strength test shall not be carried out on an existing installation unless the installation has been subjected to repairs involving new sections of pipework, etc. that cannot be tested separately or the OP is to be increased to a level not previously covered by strength testing. 5.2.2.2 Strength testing of an existing installation shall not be undertaken without first undertaking a suitable risk assessment which shall establish that the installation will withstand STP without catastrophic failure. Note: IGE/SR/24 provides general guidance on risk assessment techniques. 5.2.2.3 If it is decided to strength test an existing installation, and if the system has been de-commissioned or has lost all pressure, it shall be purged with air or nitrogen (N2) using the correct procedures (a suitable procedure for purging with N2 is given in Appendix 3), before testing. 5.3 METHOD, PRESSURE, DURATION AND TEST CRITERIA FOR STRENGTH TESTING 5.3.1 The strength test pressure (STP), duration (STD) and criteria shall be as given in Table 1. 5.3.2 The upstream fault pressure shall be known and MIP of the section to be tested shall be at least this value. Note: GAS LPG/Air or NG LPG * Either this value will have been formally recorded previously or the relevant GT will need to be consulted. MOP STP STABILIZE STD MAXIMUM PERMITTED DROP ≤ 21 mbar 82.5 mbar 5 mins* 5 mins 20% STP > 21 mbar 5 mins* 5 mins 20% STP ≤ 60 mbar (greater of) 120 mbar and 2.5 MOP ≤ 60 mbar 165 mbar 5 mins* 5 mins 20% STP Where surrounding conditions are stable, the responsible engineer may judge the installation to have stabilised before the time periods given. Note: A pressure drop of 20% STP or less indicates general integrity but any significant drop means that the tightness test is liable to fail and the cause needs to be found and rectified. TABLE 1 - PRESSURE, DURATION AND TEST CRITERIA FOR STRENGTH TESTING 12 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) 5.4 TESTING SEPARATE COMPONENTS OR SUB - ASSEMBLIES Any component or sub-assembly that could be internally damaged by STP shall be removed prior to carrying out the strength test. Such a component or sub-assembly shall be, or be proved to have been, tested separately to an appropriate standard. Note 1: Components such as regulators, meters, non-return valves (NRVs), automatic isolation valves, safety shut-off valves (SSOVs), etc, may need to be removed and replaced with spool pieces or sealed off with an appropriate fitting. Note 2: When the item(s) subsequently is(are) connected to the pipework section, it is not necessary to repeat the strength test for the whole section before carrying out a tightness test, provided the connections are inspected carefully during the tightness test. Such connections, if welded, will need to have been subject to non-destructive testing (NDT) to a standard equivalent to that used for the rest of the section. 5.5 PROCEDURES 5.5.1 A thorough survey of the pipework section, to detect any major integrity defect, shall be carried out before testing, including, as appropriate, inspection of certificates, NDT, etc. Note: This survey may entail checking the accuracy of any plans, any other information provided and the mechanical integrity of installations. As far as is reasonably practicable, joints should be exposed during the strength test and indications of leakage sought using LDF. 5.5.2 It shall be ensured that all pipework and components have been designed, installed and anchored to withstand STP. 5.5.3 Before testing, the following actions shall be taken: where necessary, remove any component that is not to be included in the test (see Sub-Section 5.4). Install spool pieces or blanks ensure all isolation valves are plugged securely or blanked off and the valves are in the open position to ensure the body is tested ensure there is a means of pressurising the system with air incorporate (in the connection of the pressurisation medium to the section) suitably adjusted regulators and a full flow safety valve(s) to prevent pressurisation above STP. 5.5.4 Appropriate gauges shall be provided to evaluate the test, duplicated where necessary. Gauges shall be certificated for calibration and, if appropriate, zeroed before use. 5.5.5 If the strength test is being combined, or is to be carried out concurrently, with with the tightness test, all the preparations and all necessary calculations for the tightness test (see Section 5) shall be carried out. 5.5.6 A final inspection of the pipework section shall be carried out to ensure that it is ready for the test. 5.5.7 The pipework section shall be pressurised slowly and the pressure maintained at STP for 5 mins. 5.5.8 After 5 mins, the pressure source shall be disconnected from the pipework section and the 5 minute strength test duration (STD) shall start. The gauge shall be monitored for the full test duration. 5.5.9 If the pressure drop exceeds 20% STP, joints, glands, etc. shall be tested for leakage, using LDF (see also the Note to Table 1). Once any repairs are complete, a further strength test may be carried out which shall be in accordance with the above requirements. 13 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) 5.5.10 Following a satisfactory strength test, the pressure in the pipework section should be reduced to OP if the pipework is to have a tightness test carried out immediately. The tightness test may then be carried out, having adjusted the stablization time, in accordance with Section 5, i.e the tests are combined. Otherwise, the pressure shall be vented and pipework left in a safe condition until the tightness test is to be carried out. Any component removed (see Sub-Section 5.4) shall be replaced if the tightness test is carried out immediately or if it is required to be in place for the tightness test. 5.5.11 The strength test shall be documented and included in any site Health and Safety File. Results should be recorded on a formal certificate, a copy of which should be given to the owner/operator of the pipework tested. Note: IGEM publishes suitable triplicate certificates in pads. STP and MOP shall be recorded clearly and be available for reference by any party subsequently working on the installation. Note: This algorithm does not show all necessary steps and the full requirements in Section 4 apply. FIGURE 4 - FLOWCHART/DECISION TESTING ALGORITHM FOR STRENGTH 14 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) SECTION 6 : TIGHTNESS TESTING Tightness testing is carried out to ensure that pipework has a leak rate below a level which could ever be considered to form a hazard caused by the size of the leak, assuming adequate ventilation of the pipework has been provided. On a new installation, the test is to verify that, within tolerances caused by the finite time for testing and the accuracy of instruments, pipework is, predominately, gas tight i.e. has, nominally, zero leakage. On an existing installation, the test is to verify that, within tolerances caused by the finite time for testing and the accuracy of instruments, pipework is, nominally, gas tight within acceptable limits. Note: The test may be against isolation valves which may be relatively old and worn, so a defined maximum level of leakage is permitted. Even if the tightness test result is satisfactory, a smell of gas or a gas detector indicating the presence of gas is not acceptable. Some LDFs have an adverse effect on certain pipework materials. Consequently, any residual fluid shall be washed thoroughly off the pipe. If necessary, for example when joints are broken, temporary electrical continuity bonds shall be installed before tightness testing. 6.1 GENERAL 6.1.1 New installations and extensions Normally, testing of a new installation or extension should be carried out using air. A pipework section may be tested without certain components fitted, for example by testing before they are installed. The components then should be installed, the section re-pressurised and the joints checked with LDF at OP (see the principles as detailed in Sub-Section 5.4). Note: All new installations/extensions have to be strength tested prior to being tightness tested. 6.1.2 Existing installations 6.1.2.1 A thorough survey of the pipework section, to detect any major integrity defect, shall be carried out before testing. Note: This survey may entail checking the accuracy of any plans, any other information provided and the mechanical integrity of the installation. 6.1.2.2 If the pipework section contains fuel gas, it shall be tested with the fuel gas. 6.1.2.3 If the pipework section is at atmospheric pressure and may contain air/fuel gas mixture or air, it shall be tested assuming the installation contains air. Note: See Appendix 5 for typical scenarios. 6.1.2.4 Where it is not necessary to test any component of a meter installation, such a component shall be isolated at the meter installation outlet valve/meter outlet valve (MIOV/MOV), as appropriate. 6.1.2.5 If new pipework is connected to existing pipework and cannot be isolated from the existing pipework for the purpose of tightness testing, the existing pipework shall be tested as if new. 15 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) 6.1.2.6 Where a tightness test includes the section of pipework between an ECV and the primary meter regulator, that section shall be tested at its OP using LDF or a gas detector (see clause 4.1.4). 6.2 INSTALLATION VOLUME (IV) 6.2.1 General 6.2.1.1 The estimation of IV involves surveying the whole of the pipework section to be tested, unless it is a very simple section (for example, one straight length of pipe). The total IV (IVt) (m3) should be calculated to two significant figures with “rounding” being upwards only. Note: 6.2.1.2 It is not advisable to round the calculations of IV of individual parts of a section as this may cause the test to be more onerous than necessary. Note shall be taken of the relevant dimensions of all components including any: meter pipe fitting, including any regulator, bend, tee, etc . pipework exposed to direct sunlight or high temperature Note: The tightness test result is valid only if the temperature of the section remains stable throughout the period of the test. inaccessible section of pipework. Note: For inaccessible pipework where there are different sizes of pipework of unknown length, always assume the largest size for the maximum length. 6.2.1.3 When existing pipework is to be extended, then unless the new section can be isolated from the existing section (allowing each section to be treated as separate installation volumes), the total volume of the new and existing sections will have to be less than 1 m3 (otherwise, IGEM/UP/1 shall be applied). 6.2.2 Calculations IV total (t) = IV meter (m) + IV calculated as follows: (a) pipe (p) + IV fittings (f) and the total IV (IVt) (m3) shall be IV of meters (IVm) Use Table 2 or for other meters, consult the meter manufacturer. DESIGNATION OF METER G4/U6 G10/U16 G16/U25 G25/U40 G40/U65 G65/U100 G100/U160 RD or turbine E6 Note: IVm (m3) 0.008 0.025 0.052 0.105 0.129 0.270 0.304 Equivalent length of pipe based on connection size (see Table 3) 0.0024 The values above are based on the largest case sizes of meters typically in use in the UK. For “Tin-case” meters, the installation volumes will need to be calculated from the case dimensions. “Tin-case” meters all measure in imperial units, will be dated pre-1980 and may be larger in volume. TABLE 2 – TYPICAL INSTALLATION VOLUME (IV) OF METERS 16 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) IV of pipe (IVp) (b) For a 1 m length of pipe, obtain the volume of the particular pipe as given in Table 3. Multiply the value given by the length of the pipe in the section. Note: Data obtained from a manufacturer or other appropriate source may be used instead of Table 3. MATERIAL AND NOMINAL SIZE OF PIPE (mm) (in) Steel/stainless steel/CSST VOLUME OF 1 m LENGTH OF PIPE (m3) MATERIAL AND NOMINAL SIZE OF PIPE (mm) VOLUME OF 1 m LENGTH OF PIPE (m3) PE 15 ½ .00024 20 .00019 20 ¾ .00046 25 .00033 25 1 .00064 32 .00053 32 1¼ .0011 55 .0016 40 1½ .0015 63 .0021 50 2 .0024 75 .0029 65 2½ .0038 90 .005 80 3 .0054 125 .01 100 4 .009 180 .02 125 5 .014 150 6 .02 Copper 15 .00014 22 .00032 28 .00054 35 .00084 42 .0012 54 .0021 67 .0033 76 .0043 108 .0087 TABLE 3 - VOLUME OF 1 m LENGTH OF PIPE (c) IV of valves, fittings, pressure vessels, accumulators, etc. (IVf) Add any additional volume caused by such components. In the event that IVf cannot be calculated, add an additional 10% of the pipe volume (IVp). (d) Total IV (IVt) IVt = IVm + IVp + IVf 17 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) Example: A simple system. Meter is U65, volume of valves and fittings is unknown. INSTALLATION VOLUME Meter (IVm) U65 Diaphragm Meter Pipework (IVp) 12 m of 80 mm (Steel) 10 m of 35 mm (Copper) IVm = 12 x 0.0054 = 10 x 0.00084 = IVp = Fittings (IVf) 0.1 x IVp Total volume (IVt) IVm+ IVp + IVf 6.3 0.100 m3 0.0648 m3 0.0084 m3 0.0732 m3 IVf = 0.00732 m3 IVt = 0.181 m3 TIGHTNESS TEST PRESSURE (TTP) TTP shall be OP of the pipework. 6.4 TIGHTNESS TEST DURATION (TTD) 6.4.1 New installations and extensions TTD shall be as specified in Table 4 or Table 5 as appropriate when using air as the test medium. 18 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) LPG/Air (SMG) Up to 0.12 >0.12 0.18 >0.18 0.24 >0.24 0.30 >0.30 0.36 >0.36 0.42 >0.42 0.48 >0.48 0.54 >0.54 0.60 >0.60 0.66 >0.66 0.72 >0.72 0.78 >0.78 0.84 >0.84 0.90 >0.90 1 IV (m3) NG Up to 0.06 >0.06 0.09 >0.09 0.12 >0.12 0.15 >0.15 0.18 >0.18 0.21 >0.21 0.24 >0.24 0.27 >0.27 0.3 >0.3 0.33 >0.33 0.36 >0.36 0.39 >0.39 0.42 >0.42 0.45 >0.45 0.48 >0.48 0.51 >0.51 0.54 >0.54 0.57 >0.57 0.6 >0.6 0.63 >0.63 0.66 >0.66 0.69 >0.69 0.72 >0.72 0.75 >0.75 0.78 >0.78 0.81 >0.81 0.84 >0.84 0.87 >0.87 0.9 LPG TIGHTNESS TEST DURATION (TTD) (mins) Up to 0.01 >0.01 0.02 >0.02 0.03 >0.03 0.04 >0.04 0.05 >0.05 0.06 >0.06 0.07 >0.07 0.08 >0.08 0.09 >0.09 0.1 >0.1 0.11 >0.11 0.12 >0.12 0.13 >0.13 0.14 >0.14 0.15 >0.15 0.16 >0.16 0.17 >0.17 0.18 >0.18 0.19 >0.19 0.20 >0.20 0.21 >0.21 0.22 >0.22 0.23 >0.23 0.24 >0.24 0.25 >0.25 0.26 >0.26 0.27 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 TABLE 4 - TIGHTNESS TEST DURATION (TTD) FOR NEW INSTALLATIONS AND EXTENSIONS USING FLUID GAUGES WITH 0.5 MBAR INCREMENTS OR ELECTRONIC GAUGE READING TO 1 DECIMAL PLACE IV (m3) LPG/Air (SMG) Up to 0.60 >0.60 0.90 >0.90 1 TIGHTNESS TEST DURATION (TTD) (mins) LPG/Air (SNG) or NG LPG Up to 0.30 >0.30 0.45 >0.45 0.60 >0.60 0.75 >0.75 0.90 >0.90 1 Up to 0.09 >0.09 0.13 >0.13 0.18 >0.18 0.22 >0.22 0.27 >0.27 0.31 >0.31 0.36 >0.36 0.40 >0.40 0.45 >0.45 0.49 >0.49 0.50 2 3 4 5 6 7 8 9 10 11 12 TABLE 5 - TIGHTNESS TEST DURATION (TTD) FOR NEW INSTALLATIONS AND EXTENSIONS USING AN ELECTRONIC GAUGE READING TO 2 DECIMAL PLACES 19 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) 6.4.2 Existing installations TTD shall be as specified in Table 6 using air or fuel gas as the medium. IV (m3) TIGHTNESS TEST DURATION (mins) LPG/air or NG Installation Test using air Test using NG Test using air Test using LPG 2 3 5 2 2 3 6 4 5 10 14 19 3 5 7 9 8 9 10 5 6 6 N/A N/A 0.15 >0.15 ≤0.3 >0.3 ≤0.45 >0.45 ≤0.5 >0.5 ≤0.6 >0.6 ≤0.75 >0.75 ≤0.9 >0.9 ≤1 Note: LPG Installation The above times are calculated based on the principle of using either a fluid gauge with 0.5 mbar increments or electronic gauge reading to 1 decimal place and align with the allowable pressure drops given in Tables 9 and 10. This does not preclude the use of a more accurate gauge but the tightness test duration and maximum allowable pressure drop remain the same. TABLE 6 - TIGHTNESS TEST INSTALLATIONS 6.5 PROCEDURES 6.5.1 By-passing components DURATION (TTD) FOR EXISTING If there is any component in the system to be tested that could trap pressure, for example a regulator, a non-return valve, etc., the component concerned shall be by-passed temporarily to equalize the pressure either side of the component. All valves shall be open, by-passed or removed. When constructing a by-pass, particular care shall be taken to use materials/components and security (via anchorage, etc.) suitable for the test pressure. Note: Account will not normally need to be made for hose relaxation. Care shall be taken to avoid damage to regulator diaphragms, filters, etc. 6.5.2 Ambient conditions Where a system includes above ground pipework, the test shall be carried out when ambient conditions are stable. Testing shall not be carried out if pipework would be exposed to direct sunlight or other heat source during the test period. 20 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) 6.5.3 Testing new installations and extensions Note: Where a combined strength and tightness test is being carried out, steps (a) to (c) will be within strength testing, steps (d) and (f) will not be necessary and step (e) will involve a reduced stabilization time. The following procedure shall be carried out: (a) Seal of the outlet of the section isolation valve / inlet to the section to be tested with an appropriate fitting. Visually inspect the installation and ensure all sections to be tested are connected, all joints are correctly made and any exposed gasways (for example, open ends) on the installation are sealed with an appropriate fitting. Note: The scope of IGEM/UP/1A now includes appliances. Appliances do not, therefore, need to be isolated from the test section but the advice in Sub-Section 6.6 applies. (b) Open all valves within the section. (c) Connect a suitable pressure gauge to a pressure test point on the section (see clause 4.4.1). (d) Slowly raise the pressure in the section with air to the at least TTP (see Sub-Section 6.3) then turn off the pressure source. (e) Allow the pressure and temperature within the section to stabilise for a period equivalent to the tightness test duration (TTD) (see Sub-Section 6.4) or for 6 minutes, whichever is the longer. The test procedure shall not proceed until a stable reading is obtained. Note: There may still be a slight increase or decrease in the pressure reading on the gauge during this period as the installation stabilises. Further time may need to be allowed until a stable reading is obtained. Where surrounding conditions are stable, the responsible engineer may judge the installation to have stabilised before the time periods given. (f) If necessary, at the end of the stabilisation period re-adjust the pressure to the TTP then turn off the pressure source. (g) Check for any movement (fall) of the gauge reading over the TTD. (h) If the pressure drop on the gauge is less than or equal to the values of GRM given Table 7 the section shall be deemed to have passed the test. Otherwise, the section shall be deemed to have failed the test. 21 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) TYPE OF GAUGE GRM (mbar) Fluid (increments of 0.5 mbar) Electronic (1 decimal place) Electronic (2 decimal places) 0.5 0.5 0.05 Note 1: The resolution of a gauge is different to its GRM. The resolution is the minimum pressure change that it is possible to read on the display. Note 2: Account will need to be taken of variable atmospheric conditions and other nearby heat sources (see 6.6.2). Note 3: The gauge has to remain in the same position for the duration of the test. Note 4: If there is an increase in the pressure reading on the gauge during this period the installation may still be stabilising and further time will need to be allowed until a stable reading is obtained. Once a stable reading is obtained this stage in the test procedure will have to be repeated. TABLE 7 - TEST CRITERIA FOR NEW INSTALLATIONS (i) If the section fails the test, stop the test and either: trace and repair the escapes(s) and re-test the section, or the section must be left safe and the relevant section of the installation disconnected and all exposed gasways sealed off with an appropriate fitting. If the section passes the test, de-pressurise the system. (j) Connect the complete installation and remove the pressure gauge and any temporary by-pass and re-seal the test points / connections. (k) Re-pressurise the section with air to OP and check any joint affected by actions following the test with LDF, repairing any escape. (l) Record the results of the tightness test on a formal certificate and pass a copy to the responsible person. Note: (m) IGEM publishes suitable triplicate certificates in pads. If the section is connected to a live gas supply, immediately carry out a commissioning purge in accordance with Section 7. If the section is not connected to a live gas supply or the section is not to be immediately purged, it must be made safe by disconnecting and sealing all exposed gasways with an appropriate fitting. Example New pipework. IV = 0.52 m3. Water gauge. If OP is 40 mbar, STP will be 100 mbar (2.5 MOP = 2.5 X 40 = 100 > 82.5 mbar – Table 1). Stabilization time for strength test from Table 1 is 5 mins. STD from Table 1 is 5 mins with pressure drop limited to 20% STP = 20 mbar (Table 2). TTD is 18 minutes (Table 6). Pressurise to 100 mbar and maintain for 5 mins strength test stabilization time. Isolate pressurisation and monitor for 5 mins with an end pressure 80 mbar for a successful strength test. Lower the pressure by venting until pressure is 40 mbar. 22 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) Commence tightness test stabilization time (18 minutes less 10 minutes already taken for strength test) = 8 minutes. Once stabilization is complete, carry out the tightness test over 18 minutes with the gauge dropping by less than 0.5 mbar (Table 4). If test fails, trace and repair the leak and re-test. This will entail a full 18 mins stabilization as fresh air (or N2) will be in the pipe from re-pressurisation, following the repair. Finally, replace any items removed from the pipework, and remove any by-passes. Re-pressurise the system with air and test disturbed joints with LDF. The pipework is now ready for purging. 23 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) 6.5.4 Testing existing installations The following procedure shall be carried out: (a) Visually inspect the installation and ensure all sections to be tested are connected, all joints are correctly made and any exposed gas ways (for example, open ends) on the installation are sealed with an appropriate fitting. Turn off all appliances. Note: The scope of IGEM/UP/1A includes appliances. Appliances do not, therefore, need to be isolated from the test section but the advice in Sub-Section 6.6 applies. (b) Turn off the upstream section isolation valve. (c) Connect a suitable pressure gauge to a pressure test point on the section (see clause 4.4.1). (d) Carry out a let-by test of the closed section isolation valve as follows: adjust the pressure to approximately 50% OP close the section isolation valve, if not already closed, and note the gauge reading Note: If the pressure requires reducing to achieve the required test pressure at this stage or any stage in the tightness testing process then any potential fuel gas or fuel gas/air mixtures that are to be released will need to be vented to a safe area. See clause 3.4 for guidance on the necessary safety precautions to be taken. Check for any perceptible movement (rise) of the gauge reading (see clause 4.2.3) over the period given in Table 8. IV (m3) >0.5 >0.8 ≤0.5 ≤0.8 ≤1.0 LET-BY TEST PERIOD (mins) 2 3 4 TABLE 8 - LET-BY TEST PERIOD If there is no perceptible movement of the gauge reading the valve shall be deemed to have passed the test. Otherwise, the valve shall be deemed to have failed the test. If the valve fails the test the cause shall be investigated and rectified. In this situation the valve shall be checked for let-by by disconnecting its outlet union and applying LDF to the valve barrel or ball. If let-by is confirmed on an ECV connected to the end of a NG service pipe, the appropriate Gas Emergency Service Call Centre shall be immediately notified to enable them to arrange an effective repair. On no account shall anyone other than an authorised operative working on behalf of the Gas Emergency Service Provider (ESP) attempt to remove, repair or dismantle the valve. If let-by is confirmed on a MIV, the MAM shall be immediately notified to enable them to arrange an effective repair. On no account shall anyone other than an authorised operative working on behalf of the MAM attempt to remove, repair or dismantle the valve. In any event, if let-by is confirmed, the valve shall be repaired / replaced before repeating this let-by test and proceeding with the tightness test. If the repair cannot be completed, the installation must be made safe by disconnecting the installation, as appropriate, and sealing all open ends with an appropriate fitting and suspending further tests. 24 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) Note: (e) If the valve appears satisfactory but there is still an increase in the pressure reading on the gauge during this period, the pressure and/or temperature within the installation may be stabilising. Time will need to be allowed until a stable reading is obtained. Once a stable reading is obtained this stage in the test procedure will have to be repeated. A major decrease in pressure is probably attributable to an escape on the installation that will need to be rectified before restarting the test. Slowly raise the pressure in the section with air or fuel gas, as appropriate, to the TTP (see Sub-Section 6.3) then turn off the pressure source. Note: It is important not to permit air into pipework containing fuel gas or a fuel gas / air mixture and not to permit fuel gas into pipework containing air or a fuel gas / air mixture unless the installation is fully purged to either fuel gas or air as appropriate, before the next stage of any works commences. For example, if during tightness testing there may be a fuel gas / air mixture in the pipework this must be fully purged to air prior to exposing any gasways. Air or fuel gas/air mixtures have to be prevented from entering the upstream. (f) Allow the pressure and temperature within the section to stabilise or a period equivalent to the tightness test duration (TTD) (see Sub-Section 6.4) or for 6 minutes, whichever is the longer. The test procedure shall not proceed until a stable reading is obtained. Note: There may still be a slight increase or decrease in the pressure reading on the gauge during this period as the installation stabilises. Further time may need to be allowed until a stable reading is obtained. Where surrounding conditions are stable, the responsible engineer may judge the installation to have stabilised before the time periods given. (g) If necessary, at the end of the stabilisation period re-adjust the pressure to the TTP then turn off the pressure source. (h) Check for any movement (fall) of the gauge reading over the TTD. If the pressure drop on the gauge does not exceed the values given in Tables 9 or 10 and there is no smell of gas, the installation shall be deemed to have passed the test.. Otherwise, the section shall be deemed to have failed the test. Note: Tables 9 and 10 use the value of IV and the volume of the smallest occupied space or 60 m3 (if there is no occupied space), as appropriate, to determine the maximum allowable pressure drop. If there is an increase in the pressure reading on the gauge during this period the installation may still be stabilising and further time will need to be allowed until a stable reading is obtained. Once a stable reading is obtained this stage in the test procedure will have to be repeated. 25 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) IV (m3 ) TTD TTD (Test Using (Test Using Air) Fuel Gas) VOLUME OF SMALLEST OCCUPIED SPACE (RV) (m3) 10 15 20 25 30 35 40 45 50 55 ≥60 0.7 1.0 1.4 1.7 2.1 2.4 2.8 3.1 3.5 3.9 4.2 0.7 1.1 1.5 1.9 2.3 2.7 3.1 3.5 3.9 4.3 4.7 0.6 0.9 1.2 1.5 1.9 2.2 2.5 2.8 3.1 3.5 3.8 >0.25 0.3 0.5 0.7 1.0 1.3 1.5 1.8 2.1 2.3 2.6 2.9 3.1 >0.3 0.7 1.1 1.5 1.8 2.2 2.6 3.0 3.4 3.7 4.1 4.5 0.6 0.9 1.3 1.6 1.9 2.3 2.6 2.9 3.3 3.6 3.9 0.5 0.8 1.1 1.4 1.7 2.0 2.3 2.6 2.9 3.2 3.5 0.6 0.9 1.2 1.5 1.9 2.2 2.5 2.8 3.1 3.5 3.8 0.5 0.8 1.1 1.4 1.7 2.0 2.3 2.6 2.9 3.1 3.4 >0.55 0.6 0.5 0.7 1.0 1.3 1.5 1.8 2.1 2.3 2.6 2.9 3.1 >0.6 0.6 0.9 1.3 1.6 1.9 2.2 2.6 2.9 3.2 3.6 3.9 0.6 0.9 1.2 1.5 1.8 2.1 2.4 2.7 3.0 3.3 3.6 0.5 0.8 1.1 1.4 1.7 1.9 2.2 2.5 2.8 3.1 3.4 0.5 0.8 1.1 1.4 1.7 2.0 2.3 2.6 2.9 3.2 3.5 0.5 0.8 1.1 1.4 1.6 1.9 2.2 2.5 2.8 3.0 3.3 0.5 0.7 1.0 1.3 1.5 1.8 2.1 2.3 2.6 2.9 3.1 0.5 0.8 1.1 1.3 1.6 1.9 2.2 2.5 2.7 3.0 3.3 0.5 0.7 1.0 1.3 1.5 1.8 2.1 2.3 2.6 2.9 3.1 0.15 2 2 >0.15 0.2 >0.2 0.25 3 0.35 >0.35 0.4 >0.4 2 3 5 0.45 >0.45 0.5 >0.5 0.55 6 0.65 >0.65 0.7 >0.7 4 5 8 0.75 >0.75 0.8 >0.8 0.85 6 9 >0.85 0.9 >0.9 0.95 6 >0.95 1.0 10 Note 1: For RV between two stated values, assume the lower value e.g. for RV = 42 m3, use 40 m3. Note 2: For a fluid gauge, where appropriate, round the maximum allowable pressure drop downwards to the next lower 0.5 mbar e.g. for 1.3 mbar, use 1.0 mbar, for 1.8 mbar, use 1.5 mbar. TABLE 9 - DETERMINATION OF MAXIMUM ALLOWABLE PRESSURE DROP (TEST CRITERIA) ON EXISTING LPG/AIR AND NG INSTALLATIONS 26 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) IV (m3 ) TTD TTD (Test Using (Test Using Air) Fuel Gas) 0.15 3 5 >0.15 0.2 >0.2 0.25 5 10 >0.25 0.3 >0.3 0.35 >0.35 0.4 >0.4 7 14 0.45 >0.45 0.5 9 19 VOLUME OF SMALLEST OCCUPIED SPACE (RV) (m3) 10 15 20 25 30 35 40 45 50 55 ≥60 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.9 2.1 2.3 2.5 0.6 0.9 1.2 1.5 1.9 2.2 2.5 2.8 3.1 3.4 3.8 0.5 0.7 1.0 1.2 1.5 1.7 2.0 2.2 2.5 2.7 3.0 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.9 2.1 2.3 2.5 0.5 0.7 1.0 1.2 1.5 1.7 2.0 2.2 2.5 2.7 3.0 0.4 0.6 0.8 1.1 1.3 1.5 1.7 2.0 2.2 2.4 2.6 0.3 0.5 0.7 0.9 1.1 1.3 1.5 1.7 1.9 2.1 2.3 0.4 0.7 0.9 1.2 1.4 1.6 1.9 2.1 2.4 2.6 2.8 Note 1: For RV between two stated values, assume the lower value e.g. for RV = 42 m3, use 40 m3. Note 2: For a fluid gauge, where appropriate, round the maximum allowable pressure drop downwards to the next lower 0.5 mbar e.g. for 1.3 mbar, use 1.0 mbar, for 1.8 mbar, use 1.5 mbar. TABLE 10 - DETERMINATION OF MAXIMUM ALLOWABLE PRESSURE DROP (TEST CRITERIA) ON EXISTING PROPANE INSTALLATIONS (i) If the section fails the test, stop the test, and either: trace and repair the escapes(s) and re-test the section, or the section must be left safe and the relevant section of the installation disconnected and all exposed gasways sealed off with an appropriate fitting. If the section passes the test, carry out the following test any joint within an enclosed space of 10 m3 of less, for example an adequately ventilated duct or a small storeroom, with LDF or a gas detector (see clause 4.1.4). If air is the test medium, only LDF can be used. The criteria for acceptance is no bubble using LDF or no perceptible movement from 0% LFL on the 0 – 10% scale for a gas detector. (j) When pipework passes through an inadequately ventilated area, reliance shall not be placed on the outcome of the pressure drop on the gauge documented in (i) alone. One or more of the following procedures shall be used: if access is available to all joints in the area, test each joint using LDF or a gas detector (see clause 4.1.4). If air is the test medium, only LDF can be used. The criteria for acceptance is no bubble using LDF or no perceptible movement from 0% LFL on the 0 – 10% scale for a gas detector or, if not practicable, physically isolate any inaccessible pipework section in the area without reliance on valves, for example by spading off, then test the section as if new pipework or, if not practicable, test the whole installation as if new pipework. These additional tests help ensure in all instances, pipework in an inadequately ventilated area shall be proven to be gas tight to at least the standards for a new installation. 27 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) Note : Where necessary, for example when entering an inadequately ventilated area, due attention must be paid to the Confined Spaces Regulations. (k) Where there is no access to any particular section, the section shall be physically isolated without reliance on the use of valves, for example by spading off, then tested separately as a new section with respect to TTD. (l) Remove the pressure gauge any temporary by-pass and re-seal the test points / connections. Ensure the section is pressurised with either air or fuel gas to OP, as appropriate, and check any joint affected by actions following the test with LDF, repairing any escape. (m) Record the results of the tightness test on a formal certificate and pass a copy to the responsible person. Note: (n) IGEM publishes suitable triplicate certification in pads. If the section installation is connected to a live gas supply, either: if the section contains or potentially contains fuel gas or a fuel gas/air mixture and work is to be completed on the section or the section is to be permanently decommissioned, immediately carry out a decommissioning purge in accordance with Section 7. The section must then be made safe by disconnecting and sealing all exposed gasways with an appropriate fitting; or if the section contains or potentially contains air, fuel gas or a fuel gas / air mixture and no work further work is to be completed on the section, immediately carry out a commissioning purge in accordance with Section 7; or if the section is known to contain fuel gas only, no further action is required. If the section is not connected to a live gas supply, but may contain a fuel gas or a fuel gas / air mixture, immediately carry out a decommissioning purge in accordance with Section 7. The section must then be made safe by disconnecting and sealing all exposed gasways with an appropriate fitting. Example An existing section is to be tested using gas, having an installation volume of 0.48 m3 and passing through a smallest occupied space of dimension 3 m x 3 m x 2.55 m, using a water gauge. Volume of space TTD Maximum allowable pressure drop = = = (3 X 3 X 2.55) = 22.95 m3 4 minutes (Table 8) 1.4 mbar (Table 5). 28 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) 6.6 APPLIANCE CONNECTOR 6.6.1 This section applies to appliances connectors with an installation volumes not exceeding: LPG / air - 0.24 m3 NG - 0.12 m3 LPG - 0.03 m3 For pipework volumes exceeding those listed above, the appliance connector shall be tightness tested in accordance with clause 6.5. 6.6.2 Before commissioning or re-commissioning any appliance, a tightness test shall be carried out on the pipework in the appliance connector after the AIV. For new installations a strength test, tightness test and purge certificate shall be obtained for the upstream pipework prior to commencing work on the appliance connector. Note 1: The prescribed tightness test does not guarantee tightness of joints downstream of any SSOV within an appliance. Note 2: The manufacturing standards for gas appliances allow a very small leakage, for practical reasons. This could create a discernible pressure drop when complete systems are tested, particularly if the pipework and appliance internal volume is small. 6.6.3 Visually inspect the appliance connector and ensure all sections to be tested are connected, all joints are correctly made and any exposed gas ways (for example, open ends) on the appliance connector are sealed with an appropriate fitting. If there is any component in the system to be tested that could trap pressure, for example a regulator, a non-return valve, etc., the component concerned shall be by-passed temporarily to equalize the pressure either side of the component (see clause 6.5.1). 6.6.4 Turn off the AIV 6.6.5 Connect a suitable pressure gauge to a pressure test point on the appliance connector (see clause 4.4.1). 6.6.6 Carry out a let-by test of the closed AIV as follows: adjust the pressure to approximately 50% OP close the AIV, if not already closed, and note the gauge reading. Note: If the pressure requires reducing to achieve the required test pressure at this stage or any stage in the tightness testing process then any potential fuel gas or fuel gas/air mixtures that are to be released will need to be vented to a safe area. See clause 3.4 for guidance on the necessary safety precautions to be taken. Check for any perceptible movement (rise) of the gauge reading (see clause 4.2.3) over the next 2 minute period If there is no perceptible movement of the gauge reading the AIV shall be deemed to have passed the test. Otherwise, the AIV shall be deemed to have failed the test. If the AIV fails the test the cause shall be investigated and rectified. In this situation the valve shall be checked for let-by by disconnecting its outlet union and applying LDF to the valve barrel or ball. In any event, if let-by is confirmed, the AIV shall be repaired / replaced before repeating this let-by test and proceeding with the tightness test. 29 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) If the repair cannot be completed, the appliance must be made safe by disconnecting the appliance and sealing all exposed gasways with an appropriate fitting and suspending further tests. Note: 6.6.7 If the AIV appears satisfactory but there is still an increase in the pressure reading on the gauge during this period, the pressure and/or temperature within the installation may be stabilising. Time will need to be allowed until a stable reading is obtained. Once a stable reading is obtained this stage in the test procedure will have to be repeated. A major decrease in pressure is probably attributable to an escape on the installation that will need to be rectified before restarting the test. Slowly raise the pressure in the appliance connector with air or gas, as appropriate, to the TTP (see Sub-Section 6.3) then turn off the pressure source. Note: It is important not to permit air into pipework containing fuel gas or a fuel gas / air mixture and not to permit gas into pipework containing air or a fuel gas / air mixture unless the installation is fully purged to either fuel gas or air as appropriate, before the next stage of any works commences. For example, if during tightness testing there may be a fuel gas / air mixture in the pipework this must be fully purged to air prior to exposing any gasways. Air or fuel gas / air mixtures have to be prevented from entering the upstream supply 6.6.8 Allow 2 minutes for the pressure and temperature within the installation to stabilise, if necessary, at the end of the stabilisation period re-adjust the pressure to the TTP. If the AIV has been turned on to re-adjust the pressure then turn off the valve. The test procedure shall not proceed until a stable reading is obtained. Note: There may still be a slight increase or decrease in the pressure reading on the gauge during this period as the installation stabilises. Further time may need to be allowed until a stable reading is obtained. Where surrounding conditions are stable, the responsible engineer may judge the installation to have stabilised before the time period given. 6.6.9 Check for any perceptible movement (fall) of the gauge reading (see clause 4.2.3) over the next 2 minute period. If there is no perceptible movement (fall) of the gauge reading and there is no smell of gas the appliance connector shall be deemed to have passed the test. Otherwise, the appliance connector shall be deemed to have failed the test. 6.6.10 If the appliance connector fails the test, either: trace and repair the escapes(s) and re-test the appliance connector, or the appliance must be made safe by disconnecting the appliance and sealing all exposed gasways with an appropriate fitting. 6.6.11 Remove the pressure gauge and any temporary by-pass and re-seal any test points / connections. Ensure the section is pressurised with either air or fuel gas to OP, as appropriate, and check any joint affected by actions following the test with LDF, repairing any escape. 6.6.12 Upon completion of the test: if the appliance connector contains or potentially contains air, fuel gas or a fuel gas/air mixture and no work further work is to be completed on the appliance connector, immediately carry out a commissioning purge in accordance with Section 7 and commission / re-commission the appliance in accordance with the manufacturer's instructions and in compliance with GS(I&U)R; or 30 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) if the appliance connector is known to contain fuel gas only, commission / recommission the appliance in accordance with the manufacturer's instructions and in compliance with GS(I&U)R; or if the appliance cannot be commissioned/re-commissioned the appliance must be made safe by disconnecting and sealing all exposed gasways with an appropriate fitting, carrying out a decommissioning purge in accordance with Section 7, as required, on the appliance connector. Attach an appropriate label to the appliance indicating it is not commissioned. 31 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) Note: This algorithm does not show all necessary steps and the full procedures in Section 6 apply. FIGURE 5 - FLOW CHART/DECISION ALGORITHM FOR TIGHTNESS TESTING OF NEW INSTALLATIONS AND EXTENSIONS 32 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) Note: This algorithm does not show all necessary steps and the full procedures in Section 6 apply. FIGURE 6 - FLOW CHART/DECISION ALGORITHM TESTING OF EXISTING INSTALLATIONS FOR TIGHTNESS 33 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) SECTION 7 : DIRECT PURGING This section deals with direct purging with air or fuel gas. If, for any reason, the purge is not complete, it will be necessary to carry out an indirect purge using N2, guidance on which is provided in Appendix 3. These Procedures assume that the system will be pressurised during purging. However, methods using suction (eduction) may also be appropriate (see IGE/SR/22). 7.1 GENERAL 7.1.1 The environmental impact of releasing methane into the atmosphere shall be considered and the volume of vented gas should be minimised and, where practicable, NG should be flared. 7.1.2 For LPG/Air and LPG, reference should be made to the advice contained in Appendix 7 when assessing safety. Heavier-than-air gases shall be flared. 7.1.3 A tightness test of pipework must be carried out immediately prior to any purge admitting fuel gas. Vent points and flare points shall be leakage tested. Note: This equally applies when admitting N2 to be followed by fuel gas (see Appendix 3). 7.1.4 The pressure created during purging shall not exceed MOP of any pipework being purged. 7.1.5 If compressed air from a cylinder is used for purging to air, the air shall be supplied through high capacity regulators, appropriate precautions being taken. 7.1.6 Where pipework is to be taken permanently out of use, it shall be isolated physically, for example by spading or removing a section of pipework and sealing the ends. De-commissioned pipework shall be left purged to air. 7.1.7 Where pipework is to be taken temporarily out of service for repairs or alterations, a let-by test shall be carried out on any valve(s) to be used to isolate the section (see clause 7.6.2(c)). Where pipework is left unattended, it shall be isolated physically, for example by spading or, where not practicable, by reliably locking off to prevent unauthorised operation. 7.2 PLANNING AND SUPERVISION 7.2.1 A full description of the system pipework shall be available and the accuracy of plans and other available information shall be checked. 7.2.2 Purging of a primary meter shall be carried out only with the prior agreement of its owner. 7.2.3 Purging shall be planned carefully and the following procedures shall be undertaken: determine the required number of operatives survey the pipework section to establish that it is in a satisfactory condition. Any defect shall be corrected before any purging is undertaken, unless decommissioning check for the existence of a “ring main” system. If a ring main exists, divide/sectionalise the “ring main” to enable complete purging 34 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) except for the simplest of purging operations, prepare a written procedure for the operation. If it is anticipated that cutting or welding of any part of the system may take place after completion of purging, a purging certificate should be issued. 7.2.4 During the purging operation, all other work on the section being purged shall be prohibited. 7.2.5 The complete purge procedure shall be continuous (except as given in the Notes to clause 7.11.1(b) and 7.11.2(d) and the minimum purge volume rates given in Table 11 shall be achieved. Note: It is not a requirement to purge at MOP. In general, if purge points are sized adequately, the minimum required velocity will be achieved more easily at lower pressures. If it becomes immediately apparent that a direct purge will not achieve the required flow rate, the restriction may be removed and the purge re-started. Otherwise, an indirect purge via N2 shall be carried out (see Appendix 3). Consequently, planning shall take into account the need for sufficient quantities of N2 to be available. Throughout purging, it should be ensured that the pressure does not fall to a level that could affect the operation of any appliance installed upstream of the section being purged. 7.2.6 Purge points shall be located at the remote end of each branch of pipework to be purged. 7.2.7 Purge points shall be located as close as possible to the extremities of the section to be purged to enable a complete purge. 7.2.8 When purging with air, it must be ensured that air will not enter the GT’s distribution network. 7.2.9 Planning shall cover the progression of the purging operation through any meter and/or branched pipework (which should be purged in reducing order of diameter). Note: Special care is needed to ensure that any branch interconnection is purged fully. 7.3 SITE PRECAUTIONS 7.3.1 Warning notices and labels 7.3.1.1 Appropriate “No smoking” and/or “No naked lights” signage shall be displayed prominently around any vent and the overall area where purging will take place. 7.3.1.2 Any valve to or from the section to be purged shall be labelled clearly, for example “Do not operate – purging in progress”. 7.3.2 Electrical and fire 7.3.2.1 An appropriate communications system shall be used for co-ordinating remote activities associated with purging. Where appropriate, due regard shall be paid to the suitability of this and any other electrical equipment for use in a hazardous area (see Sub-Section 4.1.4). 7.3.2.2 Any fitted electrical continuity bonds shall be maintained throughout the purging operation. 35 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) 7.3.2.3 Sufficient and appropriate fire extinguishers shall be situated near the vent point(s). 7.4 DESIGNING AND POSITIONING PURGE POINTS, HOSES AND VENT STACKS 7.4.1 Precautions shall be taken to reduce, as far as possible, the hazards associated with venting, for example by avoiding venting close to property air intakes, or to any potential sources of ignition such as street lamps and electrical plant. If there is any doubt about the minimum clearance to ignition sources, reference should be made to IGE/SR/23. Any electrical switch or isolator in the vicinity of the vent outlet shall not be operated during purging. Purged fuel gas shall be flared whenever a potential hazard cannot be eliminated (see also clauses 7.1.1 and 7.1.2). Consideration should be given to potential complaints of smell arising from any purging operation. 7.4.2 Purge points, associated vents, hoses, vent stacks and flame arrestors shall be sized to permit sufficient flow in order to maintain the required purge flow rate. In the absence of more definitive guidance, Table 11 should be used. Note: Where the minimum required size of purge hose and vent stack cannot be achieved, multiple vents may be used. These may be operated simultaneously, provided each point is supervised and communications are adequate to enable a safe purge. Any valve used in the purge process should be full bore, where possible. 7.4.3 If flaring, the flare stack should be fitted with a suitable in-line flame arrestor to BS EN 12874. If venting but not flaring, the vent stack should terminate with a suitable flame arrestor. Note: Where the purge flow rate can be guaranteed, it may not be necessary to fit an arrestor but suitable additional precautions are required (see IGE/UP/1). 7.4.4 Any vent stack shall incorporate a full bore control valve and sample point. 7.4.5 For flaring, the arrestor shall be fitted at least 2 m upstream of the discharge end and a source of ignition provided. 7.4.6 Any purge hose shall be of sufficient diameter to minimise pressure loss through the vent pipe and shall be: suitable for containing the fuel gas earthed suitably to avoid sparking, if necessary, for example for externally armoured hose. gas tight secured firmly to the purge point Note: Unsecured push-on connections are not acceptable. Hose materials that may generate static electricity, for example PE, shall not be used. Note: The possibility of generating static electricity increases as the purge velocity increases. 7.4.7 The vent/flare outlet shall be located in open air and terminate at least 2.5 m above ground. Any vent outlet shall be located at least 5 m downwind of any potential ignition source. 7.4.8 Precautions shall be taken to prevent vented gas drifting into buildings. 36 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) 7.4.9 7.4.10 When flaring, the flame shall be at a location that minimises heat radiation effects that could lead to danger to persons or property. When purging volumes of pipework and appliance control trains less than 0.035 m3, purging may be carried out directly into a well ventilated internal area without the use of a purge hose, vent stack or flame arrestor, in accordance with Appendix 6. 7.5 VERIFICATION OF PURGE FLOW RATE 7.5.1 A method of verifying that the required purge velocity (Table 11) is achievable shall be available and shall be one of the following: a suitably sized “volume” meter (used in conjunction with a timer to enable the flow rate to be calculated) already fitted in the section of pipework to be purged or a sufficiently sized “rate of flow” meter, i.e. capable of passing well in excess of the purge flow rate or other suitable flow measuring device fitted downstream of the purge point(s), such as an independent positive displacement or turbine meter. Note: Provided there is confidence that the required purge flow rate (Table 11) will be achieved, a timed passage of purge gas may be used at the discretion of a responsible, competent person. 7.5.2 A test of the vent gas shall always be carried out (see Sub-Section 7.10). 7.6 IDENTIFICATION OF PURGE GAS CYLINDERS When the purge gas is supplied from a cylinder, special care shall be taken to ensure that the cylinder does not contain the wrong gas, for example oxygen. Cylinders of air shall be checked in this respect, before use. Note: 7.7 This can be achieved, for example by using an oxygen detector, or by confirmation of the contents of the cylinder from the supplier, etc. GAS DETECTORS AND OTHER ELECTRONIC EQUIPMENT Any gas detector or other electronic equipment shall: where necessary, be certified for use in a hazardous area (see clause 4.1.4) have its batteries tested prior to use be operated in accordance with the manufacturer’s instructions and by a trained competent person capable of interpreting the results obtained be zeroed at the commencement of each test and have its zero checked at the finish of each test be tested, overhauled and calibrated in accordance with the manufacturer’s instructions. 37 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) 7.8 GAS APPLIANCES Where a connected appliance is identified which has not been commissioned, either it must be: disconnected from the gas supply or sealed off with an appropriate fitting with an appropriate label attached indicating the appliance is not commissioned, or the appliance commissioned in accordance with the manufacturer's instructions and in compliance with GS(I&U)R. 7.9 DETERMINATION OF THE PURGE VOLUME, PURGE FLOW RATE AND PURGE TIME 7.9.1 The purge volume (PV) is the total volume that should be passed through the installation to ensure a safe air to gas ratio. The volume of the purge equipment (IVh) should be included in determining the purge volume. Note: Purge equipment include items such as purge hoses/pipes, meters, vent stacks etc. The principles in Section 6.2.2 may be used for calculating IVh. PV = 1.5 x (IVt + IVh). 7.9.2 To ensure that the effect of stratification does not impair the purging of the pipework, it should be confirmed that the velocity of the purging medium through the pipe is above a minimum level (0.6 m s-1). Note: 7.9.3 Although velocity is not easily measured in such a situation, it can be related to purge flow rate which can be monitored with a flow meter or a timing method (see Table 11). The minimum purge flow rate (Qp) through the pipework section shall be determined from Table 11. The largest diameter pipe in the section shall be used to determine the value. Note: If Qp is not achieved, the purge time and volume of purge gas required will be excessive and, even then, a satisfactory purge may not be achieved as the minimum velocity required, the key factor, will also not be achieved. Largest nominal diameter (mm) Minimum purge gas flow rate (Qp) (m3 h-1) Purge point nominal bore Purge hose/vent stack nominal bore Flame arrestor nominal bore Note: 20 25 32 40 50 80 0.7 1.0 1.7 2.5 4.5 11.0 20 20 20 20 25 25 100 125 150 30.0 38.0 25 40 40 20.0 20 20 20 20 40 40 40 50 50 20 20 20 20 50 50 50 50 50 While the dimensions of nominal bore are ideal, it may be necessary to defer to the relevant design standard which may not require such dimensions. In any event, the minimum required purge velocity has to be achieved. TABLE 11 - MINIMUM PURGE FLOW RATE 7.9.4 Where necessary (see clause 7.5.1) the maximum purge time (PT) shall be calculated as follows: Max PT (sec) = PV (m3) x 3600 Qp 38 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) Note: This is the maximum time (purge time) it will take before a vent gas test indicates a sufficient quantity of fuel gas or air as appropriate to indicate completion of the purge. Example. Calculation of purge time What is the maximum purge time of 75 m of 80 mm nominal bore steel pipe? There is a U25 diaphragm meter fitted and the purge hose is 10 m of 25 mm nominal bore hose. From Sub-Section 5.2 IVp =75 x 0.0054 IVf =10% x IVp PV of pipework =1.5 x (0.405 + 0.0405) Meter cyclic volume PV of meter =5 x cyclic volume (= 5 x 0.01) Purge hose volume =10 x 0.00064 PV of purge hose =1.5 x 0.0064 Total purge volume is, thus ( 0.6683 + 0.05 + 0.0096) Minimum purge flow rate Maximum purge time = 0.73 x 3600 11 =0.405 m3 =0.0405 m3 =0.6683 m3 =0.01 m3 =0.05 m3 =0.0064 m3 =0.0096 m3 =0.73m3 (rounding up) = 11 m3h-1 (Table 9) = 238.9 seconds =3 minutes 59 seconds 7.10 VENT GAS TESTING 7.10.1 The criteria given in Table 12 shall be used when testing the vent gas. Note: FUEL GAS LPG/Air Table 12 is intended to ensure safe conditions, but not necessarily efficient combustion performance. FLAMMABILITY LIMITS LOWER LIMIT UPPER LIMIT % GAS IN AIR % GAS IN AIR 2.0 10.0 NG 4.5 15.5 Propane 2.1 10.0 SAFE PURGE END POINTS DIRECT PURGE DIRECT PURGE AIR TO GAS GAS TO AIR 90% fuel gas < 10% LFL (0.2% gas in air) 90% fuel gas < 40% LFL (1.8% gas in air) 90% fuel gas < 10% LFL (0.2% gas in air) TABLE 12 - FLAMMABILITY LIMITS AND SAFE PURGE END POINTS 7.11 PURGING PROCEDURES WHEN VENTING TO OUTSIDE 7.11.1 Direct purging from air to gas i.e. commissioning The procedure assumes that, prior to purging, any purge point and any valve on any connected vent stack is closed, that the section isolation valve(s) is/are closed and that any other valve within the section is open. Typical purge equipment arrangements are illustrated in Appendix 8. Throughout the purge operation, steps should be taken to ensure that any upstream pipework or appliance will not be affected by the purging operation. 7.11.1.1 The following procedure shall be carried out: (a) Ensure that a satisfactory tightness test (Section 6) has been carried out, immediately before starting the purge. (b) Open all purge points on the section being purged and open valves on connected vent stacks then open the section isolation valve, to admit gas. Simultaneously, start the chosen method of measuring the flow of purge gas (Sub-Section 7.5), i.e.; start a timer and 39 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) read the in-line meter or read the flow meter rate. Note: If using a flow meter, it will be immediately apparent if the minimum required purge volume rate is not being achieved. In this case, it may be possible to stop the purge by turning off the section isolation valve and quickly (and without significant mixing of air and gas) rectify the reason for the incomplete purge and re-start the purge (from the beginning) without resorting to a decommissioning purge (see (d) below). (c) After half the estimated purge time has elapsed (or earlier if desired), start testing the concentration of fuel gas in the vent gas using a suitable gas detector. (d) Stop the purge by closing the vent stack valve(s) (and record the on-line meter reading, if applicable) when a level of fuel gas, as indicated in Table 12 for safe purge end point, is achieved, or the metered purge volume has passed. Note: Any method has to be verified by a satisfactory vent gas sample. If Table 12 concentrations are not achieved within the purge time (or by the time the purge volume has passed) an incomplete purge is indicated. In this case, close the section isolation valve(s) and immediately purge the section with N2 in accordance with Appendix 3. Before repeating steps (a) to (d), identify and rectify the reason for the incomplete purge. Note1: For any "partially complete" purge, the pipework will contain a mixture of gas and air that is potentially hazardous. If it is possible to rectify the problem without opening the gasway, then it may be acceptable to so rectify and re-start the purge from the beginning. In the intervening period, it is imperative that the gasway is not opened, that any section isolation valve is not opened, that the section is not left unattended and that site precautions remain in place. An overall risk assessment is required which, if sufficient assurance of safety is not indicated, will lead to an indirect purge using N2 (see Appendix 3). Note2: The reason for an incomplete purge is likely to be insufficient velocity of the fuel gas. Check the purge time recorded against any meter reading/ flow rate recorded. Any metered reading less than PV is suspect. Any flow rate less than PV expressed as a flow rate is also suspect. If both are satisfactory, re-check the calculations. If no problem is found, it is likely that the actual design of the section is not as assumed when calculating PV. Note 3: In conjunction with a stopwatch for metered flow, all the above methods will serve to confirm that the purge flow rate is the minimum required (see Table 9). (e) Close all purge points, disconnect vent stacks, remove all purge equipment and plug or cap any exposed gasways with an appropriate fitting. Test any disturbed joints with LDF or a gas detector (see clause 4.1.4). Note 1: A gas detector is not permitted to move from zero or 0% LFL on a scale no less accurate than 0% to 10% LFL. Note 2: Disconnected purge equipment (hoses, meters, etc.) will need to be purged of fuel gas. (f) Rectify the cause of any detected escapes or smell of gas. (g) Commission any connected appliances or seal the outlet of the pipework and label all pipework termination points to indicate that gas is on and purged up to each point. Confirm that outlets from appliance isolation valves and/or branches are sealed with an appropriate fitting. (h) Complete an appropriate purging certificate. Note: IGEM publishes suitable triplicate certificates in pads. 40 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) 7.11.2 Direct purging from gas to air i.e. de-commissioning The procedure assumes that, prior to purging, any purge point and any valve on any connected vent stack is closed, that the section isolation valve is closed and that any other valve within the section is open. Any appliance attached to the section shall be turned off. Throughout the purge operation, steps should be taken to ensure that any upstream pipework or appliance will not be affected by the purging operation. 7.11.2.1 The following procedure shall be carried out: (a) Carry out a let-by test on the section isolation valve(s), to prove its/their integrity (see clause 7.6.4 (c)). (b) Ensure the section isolation valve(s) is/are turned off. (c) Ensure OP of the section will not be exceeded. Note: (d) This will require a suitable gauge to be fitted as close as practicable to the air inlet point. Limiting the pressure can, normally, be achieved with the use of a lowpressure air blower(s) or, in the case of refillable cylinder(s)/tank(s), with the use of a suitable regulator that can be accurately set to a pressure at or below OP. Low-pressure air blower(s), cylinder(s)/tank(s), and regulator(s) need to be sized to pass the required purge flow rate. Open all purge points and valves on connected vent stacks then admit air. Simultaneously, start the chosen method of "measuring" the flow of air (see Sub-Section 7.5) i.e.; start a timer and read the in-line meter or read the flow meter rate. Note: If using a flow meter, it will be immediately apparent if the minimum required purge volume rate is not being achieved. In this case, it may be possible to stop the purge by turning off the air supply and quickly (and without significant mixing of air and gas) rectify the reason for the incomplete purge and re-start the purge (from the beginning) without resorting to a decommissioning purge (see (f) below). (e) After half the estimated purge time has elapsed (or earlier if desired), start testing the concentration of fuel gas in the vent gas using a suitable gas detector. (f) Stop the purge by isolating the air supply (and record the in-line meter reading, if applicable) when a level of gas, as indicated in Table 10 for safe purge end point, is achieved or the metered purge volume has passed, whichever occurs first. Note: Any method has to be verified by a satisfactory vent gas sample. If Table 12 concentrations are not achieved within the purge time (or by the time the purge volume has passed) an incomplete purge is indicated. In this case, close the section isolation valve(s) and immediately purge the section with N2 in accordance with Appendix 3. Before repeating steps (a) to (d), identify and rectify the reason for the incomplete purge. Note1: For any "partially complete" purge, the pipework will contain a mixture of gas and air that is potentially hazardous. If it is possible to rectify the problem without opening the gasway, then it may be acceptable to so rectify and re-start the purge from the beginning. In the intervening period, it is imperative that the gasway is not opened, that any section isolation valve is not opened, that the section is not left unattended and that site precautions remain in place. An overall risk assessment is required which, if sufficient assurance of safety is not indicated, will lead to an indirect purge using nitrogen (see Appendix 3). 41 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) Note2: The reason for an incomplete purge is likely to be insufficient velocity of the fuel gas. Check the purge time recorded against any meter reading/ flow rate recorded. Any metered reading less than PV is suspect. Any flow rate less than PV expressed as a flow rate is also suspect. If both are satisfactory, re-check the calculations. If no problem is found, it is likely that the actual design of the section is not as assumed when calculating PV. Note 3: Provided there is confidence that the required purge flow rate (Table 11) will be achieved, a timed passage of purge gas may be used at the discretion of a responsible, competent person. (g) Close all purge points, disconnect vent stacks, remove all purge equipment and plug or cap any exposed gasways with an appropriate fitting. Test any disturbed joints with LDF. Seal or disconnect pipework from the gas supply, sealing all ends with an appropriate fitting. Decommission in accordance with these Procedures. (h) Label all pipework to show that it has been de-commissioned. (i) Complete an appropriate purging certificate. Note: IGEM publishes suitable triplicate certificates in pads. 42 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) AIR TO GAS Commissioning Start Ensure that a satisfactory tightness test has been carried out. Vent stacks and hoses correctly located. Warning notices, barriers, fire extinguishers available and checked. Test meters and gas detectors checked. Carry out all preparation work. (7.1, 7.2, 7.3, 7.4, 7.5) Calculate: Purge volume (7.6) Purge flow rate (7.6) Purge time (7.6) Open purge points and vent valves. Immediately admit fuel gas at correct flow rate. Monitor gas pressure. Do not allow to exceed OP. Monitor gas flow rate. If correct flow rate cannot be achieved, abandon purge and use indirect method. Sample at vent point after half the purge time. After satisfactory vent gas test, close vent point valve and remove purge hose from vent. Check purge is complete. (see Table 12) Test all disturbed joints and joints in ducts for leaks. Complete records and inform responsible person of position. Note: This algorithm does not show all necessary steps and the full procedures in Section 7 apply. FIGURE 7 - FLOWCHART FOR DIRECT PURGING OF AIR TO GAS 43 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) GAS TO AIR De-commissioning Start Vent stacks and hoses correctly located. Warning notices, barriers, fire extinguishers available and checked. Test meters and gas detectors checked. Carry out all preparation work. (7.1, 7.2, 7.3, 7.4, 7.5) Calculate: Purge volume (7.6) Purge flow rate (7.6) Purge time (7.6) Isolate gas supply. Carry out let-by test. Open purge points and vent valves. Immediately admit air at correct flow rate. Monitor gas pressure. Do not allow to exceed OP. Monitor gas flow rate. If correct flow rate cannot be achieved, abandon purge and use indirect method. Sample at vent point after half the purge time. After satisfactory vent gas test, close vent point valve and remove purge hose from vent. Check purge is complete. (see Table 12) Complete records and inform responsible person of position. Note: This algorithm does not show all necessary steps and the full procedures in Section 7 apply. FIGURE 8 - FLOWCHART FOR DIRECT PURGING OF GAS TO AIR 44 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) APPENDIX 1 : GLOSSARY, ACRONYMS AND SYMBOLS GLOSSARY All definitions are given in IGEM/G/4 which is freely available by downloading a printable version from IGEM’s website, www.igem.org.uk. Recommended and legacy gas metering arrangements are given in IGEM/G/1 which is freely available by downloading a printable version from IGEM’s website, www.igem.org.uk. ACRONYMS ACoP ACS ECV GRM GS(I&U)R GT HSE IGEM IV LDF LFL LPG LPGA MAM MIP MIV MOP MOV NDT NG OP PE PT PV RD RV SDR SP SSOV STD STP TTD TTP UK UKAS Approved Code of Practice Accredited Certification Scheme Emergency control valve Gauge readable movement Gas Safety (Installation and Use) Regulations Gas transporter Health and Safety Executive Institution of Gas Engineers and Managers Installation volume Leak detection fluid Lower flammable limit Liquefied petroleum gas Liquefied Petroleum Gas Association Meter asset manager Maximum incidental pressure Meter inlet valve Maximum operating pressure Meter outlet valve Non-destructive testing Natural Gas Operating pressure Polyethylene Purge time Purge volume Rotary displacement Room volume Standard dimension ratio Set point Safety shut-off valve Strength test duration Strength test pressure Tightness test duration Tightness test pressure United Kingdom United Kingdom Accreditation Service. SYMBOLS Qp N2 V diameter less than greater than equal to or greater than less than or equal to minimum purge flow rate Nitrogen volume. 45 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) SUBSCRIPTS/SUFFICES/UNITS f p m t d L m3 m3 h-1 ft3 ft3 h-1 m mm in mins mbar fittings, etc. pipe meter total nominal bore flange to flange dimension cubic metre cubic metre per hour cubic feet cubic feet per hour metre millimetre inch minute millibar. 46 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) APPENDIX 2 : REFERENCES Care needs to be taken to ensure that the latest editions of the relevant documents are used. A2.1 LEGISLATION Construction (Design and Management) Regulations 1994 Control of Substances Hazardous to Health Regulations 1995 as amended in 1997 and 1998 A2.2 Note: This applies to all work activities. It places general duties on employers to ensure, so far is reasonably practicable, the health safety and welfare of their employees and the health and safety of members of the public who may be affected by the activity. Dangerous Substances and Explosive Atmospheres Regulations 2002 Electricity at Work Regulations 1989 Gas Safety (Installation and Use) Regulations 1998 Note: These apply to domestic and commercial premises. For industrial premises, the requirements of these Regulations could be considered relevant in any investigation under the Health and Safety at Work etc. Act. The Regulations set out detailed requirements for gas installation work. In particular, they require that anyone carrying out such work must be competent to do so. They also prescribe circumstances in which a soundness(tightness) test and purge must be carried out. Management of Health and Safety at Work Regulations 1999 Workplace (Health, Safety and Welfare) Regulations 1992. Pressure Equipment Regulations 1999 Pressure Systems Safety Regulations 2000 Note: For cylinders etc., Carriage of Dangerous Goods (Classification, Packaging and Labelling) and Use of Transportable Pressure Receptacles Regulations 1996 (as amended), the Transportable Pressure Vessel Regulations 2001 may also be relevant. ACOPS AND GUIDANCE NOTES HSG48 Human factors in industrial safety. BRITISH STANDARDS (ABBREVIATED TITLES) A2.4 Health and Safety at Work etc. Act 1974 A2.3 Gas Act 1995 BS 6891 Low pressure pipework in domestic premises BS EN 12874 Flame arresters BS EN 60079 Electrical apparatus for explosive gas atmospheres. IGEM PROCEDURES AND RECOMMENDATIONS IGE/UP/1 Edition 2 Strength testing, tightness testing and direct purging of industrial and commercial gas installations IGEM/UP/1B Edition 3 Tightness testing and direct purging of small Liquefied Petroleum Gas/Air, Natural Gas and Liquefied Petroleum Gas installations IGEM/UP/2 Edition 2 Installation pipework on industrial and commercial premises IGE/SR/22 Purging operations for distribution and storage IGE/SR/23 Venting of Natural Gas IGE/SR/24 Risk assessment techniques IGEM/TD/13 Edition 2 Pressure regulating installations for Natural Gas, Liquefied Petroleum Gas and Liquefied Petroleum Gas/Air IGEM/G/1 Definitions for the end of a network, meter installation, and installation pipework. fuel gases in transmission, 47 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) APPENDIX 3 : INDIRECT PURGING WITH NITROGEN (N2) An indirect purge is necessary if: the direct purge has been unsuccessful a direct purge is unlikely to be achieved successfully, for example where inadequatelysized purge points are fitted. A3.1 Make the installation and the surroundings safe and implement fallback plans. A3.2 Check the calculations, survey the installation and inspect equipment to endeavour to identify the cause of failure of the direct purge. If the cause is identified and can be rectified, (for example following calculation error, blocked hose, closed valve, restrictive purge points, etc.), the direct purge can be repeated. Note: A3.3 Take additional care at purge gas vent point due as a flammable mixture may occur at a different stage in the operation. Ensure the indirect purge is a complete displacement purge using volume based measurement of N2 and vent gas testing. Pay particular attention to any dead-legs. Take precautions to prevent asphyxiation, especially in basements and confined spaces. Take precautions to prevent N2 entering parts of the installation upstream of the section being purged. A3.4 Start with the largest diameter pipe and progress to the smallest. Ensure a minimum volume equal to 1.5 times the swept volume of the pipework is available. A3.5 As a guide, a standard 1.5 m long N2 bottle usually has a capacity of 6.5 m3. The maximum through a high capacity single-stage regulator is typically, 1 m3 per minute. A3.6 The criteria given in Table 13 apply when testing the vent gas. A3.7 Following the indirect purge, identify the reason for any failure of the direct purge. This may necessitate sectionalising the installation to identify blockages etc. A3.8 Following the indirect purge, if hot work is to be undertaken, take care in case small pockets of gas remain in the pipe due to the effects of stratification or due to the effect of dead-legs. A3.9 When undertaking any work following an indirect purge, take suitable precautions to account for the presence of N2. A3.10 Once the purge to Nitrogen is complete, it is advisable to either then: purge to air and ensure the oxygen level is at least 20%, or label the pipework to indicate that it contained N2. 48 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) FUEL GAS LPG/Air NG Propane FLAMMABILITY LIMITS LOWER LIMIT UPPER LIMIT % GAS IN AIR % GAS IN AIR 2.0 4.5 2.1 10.0 15.5 10 SAFE PURGE INDIRECT PURGE FROM FUEL GAS TO N2 3.5% gas in N2 7.5% gas in N2 3.5% gas in N2 END POINTS INDIRECT PURGE FROM N2 TO FUEL GAS 90% fuel gas in N2 90% fuel gas in N2 90% fuel gas in N2 TABLE 13 - FLAMMABILITY LIMITS AND SAFE PURGE ENDS POINTS FOR INDIRECT PURGE 49 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) APPENDIX 4 : TIGHTNESS TEST DURATIONS FOR A WATER GAUGE USING THE CONCEPT OF “NO PERCEPTIBLE MOVEMENT”(FOR NEW INSTALLATIONS ONLY) For clarity, IGE/UP/1A Edition 2 adopts the concept of “gauge readable movement”. This is because the meaning of “no perceptible movement” is open to differing interpretation with respect to electronic gauges, which are seeing increased usage. However, in the case of a water gauge, the use of “no perceptible movement” is an established and understood concept. When testing a new installation, using this concept for a water gauge has the benefit of significantly reducing the test times from those given in Table 4 which are based on GRM. The table below gives the equivalent values for “no perceptible movement”. Any movement of the gauge during the test time indicates the installation has failed the tightness test. LPG/Air (SMG) Up to 0.12 >0.12 0.18 >0.18 0.24 >0.24 0.30 >0.30 0.36 >0.36 0.42 >0.42 0.48 >0.48 0.54 >0.54 0.60 >0.60 0.66 >0.66 0.72 >0.72 0.78 >0.78 0.84 >0.84 0.90 >0.90 1 IV (m3) NG Up to 0.06 >0.06 0.09 >0.09 0.12 >0.12 0.15 >0.15 0.18 >0.18 0.21 >0.21 0.24 >0.24 0.27 >0.27 0.3 >0.3 0.33 >0.33 0.36 >0.36 0.39 >0.39 0.42 >0.42 0.45 >0.45 0.48 >0.48 0.51 >0.51 0.54 >0.54 0.57 >0.57 0.6 >0.6 0.63 >0.63 0.66 >0.66 0.69 >0.69 0.72 >0.72 0.75 >0.75 0.78 >0.78 0.81 >0.81 0.84 >0.84 0.87 >0.87 0.9 >0.9 0.93 >0.93 0.96 >0.96 1.0 LPG TIGHTNESS TEST DURATION (TTD) (mins) Up to 0.01 >0.01 0.02 >0.02 0.03 >0.03 0.04 >0.04 0.05 >0.05 0.06 >0.06 0.07 >0.07 0.08 >0.08 0.09 >0.09 0.1 >0.1 0.11 >0.11 0.12 >0.12 0.13 >0.13 0.14 >0.14 0.15 >0.15 0.16 >0.16 0.17 >0.17 0.18 >0.18 0.19 >0.19 0.20 >0.20 0.21 >0.21 0.22 >0.22 0.23 >0.23 0.24 >0.24 0.25 >0.25 0.26 >0.26 0.27 >0.27 0.28 >0.28 0.29 >0.29 0.3 2 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 16 16 17 TABLE 14 - TIGHTNESS TEST DURATION (TTD) FOR NEW INSTALLATIONS AND EXTENSIONS USING NO PERCEPTIBLE MOVEMENT 50 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) APPENDIX 5 : INSTALLATIONS AT ATMOSPHERIC PRESSURE CONSIDERATIONS/SCENARIOS GS(I&U)R require a tightness test to always proceed a purge. The following gives advice on scenarios which may be encountered. A5.1 INSTALLATION KNOWN TO CONTAIN AIR ONLY Initial tightness test of installation using TTD for an installation containing air (Table 6). Actions following initial successful test: A5.2 No gas ways to be exposed to the atmosphere (e.g. no work to be undertaken) direct purge the installation to fuel gas - commissioning purge (Section 7) achieve satisfactory safe purge end point (>90% Gas) purging for at least the maximum purge time or until PV has been passed Gas ways to be exposed to the atmosphere (e.g. work to be undertaken) undertake & complete any work tightness test installation using TTD for an installation containing air (Table 9) direct purge the installation to fuel gas - commissioning purge (Section 7) achieve satisfactory safe purge end point (>90% Gas) purging for at least the maximum purge time or until PV has been passed INSTALLATION CONTAINS OR POTENTIALLY CONTAINS GAS / AIR MIXTURE Initial tightness test of installation using TTD for an installation containing air (Table 6) Actions following successful test: No gas ways to be exposed to the atmosphere (e.g. no work to be undertaken) direct purge the installation to fuel gas - commissioning purge (Section 7) achieve satisfactory safe purge end point (>90% Gas) purging for at least the maximum purge time or until PV has been passed Gas ways to be exposed to the atmosphere (e.g. work to be undertaken) direct purge the installation to air - de-commissioning purge (Section 7) achieve satisfactory safe purge end point (<40% LFL) purging for at least the maximum purge time or until PV has been passed undertake & complete any work 51 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) A5.3 tightness test installation using TTD for an installation containing air (Table 9) direct purge the installation to fuel gas - commissioning purge (Section 7) achieve satisfactory safe purge end point (>90% Gas) purging for at least the maximum purge time or until PV has been passed INSTALLATION KNOW TO CONTAIN FUEL GAS ONLY Initial tightness test of installation using TTD for an installation containing gas (Table 6) Actions following initial successful test: No gas ways to be exposed to the atmosphere (e.g. no work to be undertaken) Pressurise system - No further action required Gas ways to be exposed to the atmosphere (e.g. work to be undertaken) direct purge the installation to air - de-commissioning purge (Section 7) achieve satisfactory safe purge end point (<40% LFL) purging for at least the maximum purge time or until PV has been passed undertake & complete any work direct purge the installation to fuel gas - commissioning purge (Section 7) achieve satisfactory safe purge end point (>90% Gas) purging for at least the maximum purge time or until PV has been passed tightness test installation using TTD for an installation containing air (Table 9) 52 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) APPENDIX 6 : PURGING SMALL VOLUMES A6.1 LPG/Air mixtures In accordance with clause 7.4.10 and where the OP at the inlet of the purge valve does not exceed 21 mbar, the following procedure can be used for purging: (a) Within the vicinity of the purging activity ensure the following safety precautions are taken throughout the purging process: avoid any accumulation of gas within confined spaces advise the responsible person for the premises or other persons in the area of the above of the intent to purge and that there may be a smell of gas. prevent inadvertent operation of any electrical switch or other appliance extinguish all potential sources of ignition ensure that there is no smoking or naked lights ensure good ventilation by opening doors, windows, passive stack ventilation systems, etc. Note: These precautions are applicable even if a source of ignition is held adjacent to the purged gas, as a mixture of un-ignited gas/air may be released until a suitable mixture is achieved. (b) Ensure that all appliances are turned off before commencing with the purge. (c) Slowly turn on the gas supply and note the position of the test dial or test drum on diaphragm meters. (d) From a suitable purge point on the installation turn on a burner control tap on an appliance with an open burner. The purge gas mixture shall be ignited at the burner as soon as possible, by holding a source of ignition adjacent to the burner head or by continually operating the appliances ignition system. Note: It may be necessary, in certain situations, to connect a temporarily installed burner to a suitable point on the installation, for example, on installations with no appliances fitted, where the appliance(s) is fitted with a flame supervision device or where there are no open burners. Confirm the presence of gas, for example, by observation of the burner igniting. Turn off the appliance burner control tap. During the purging operation, the area in which the purge gas is being released shall not be left unattended. (e) Return to the meter and note the volume of gas that has passed. (f) Continue steps (d) and (e) until the correct PV has been passed (see Table 5). (g) Ensure every branch of pipework is purged following the aforementioned procedure. (h) Establish a stable flame picture at each appliance. Where an appliance is identified which has not been commissioned, either it must be: disconnected from the gas supply or sealed off with an appropriate fitting with an appropriate label attached indicating the appliance is not commissioned, or the appliance commissioned. 53 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) A6.2 Natural Gas In accordance with clause 7.4.10 and where the OP at the inlet of the purge valve does not exceed 21 mbar, the following procedure can be used for purging: (a) Within the vicinity of the purging activity ensure the following safety precautions are taken throughout the purging process: avoid any accumulation of gas within confined spaces advise the responsible person for the premises or other persons in the area of the above of the intent to purge and that there may be a smell of gas. prevent inadvertent operation of any electrical switch or other appliance extinguish all potential sources of ignition ensure that there is no smoking or naked lights ensure good ventilation by opening doors, windows, passive stack ventilation systems, etc. Note: These precautions are applicable even if a source of ignition is held adjacent to the purged gas, as a mixture of un-ignited gas/air may be released until a suitable mixture is achieved. (b) Ensure that all appliances are turned off before commencing with the purge. (c) Slowly turn on the gas supply and note the position of the test dial or test drum on diaphragm meters or the meter reading on ultrasonic meters. (d) Select the appropriate purge activity based on the installation volume: Installation Volumes ≤ 0.02 m3 From a suitable purge point on the installation either turn on a burner control tap on an appliance with an open burner or loosen the appropriate fitting sealing the gas way. If purging by opening a burner control tap, it is permissible to hold a source of ignition adjacent to the burner head or to continually operate the appliances ignition system to attempt to ignite the purged gas/air mixture. Note: This not only serves to assist the operative in determining whether the PV has been passed but will limit the amount of un-ignited purge gas that will be released. Confirm the presence of gas, for example, by observation of the burner igniting and/or by use of a gas detector to confirm a safe purge end point of ≥ 90% fuel gas. Turn off the appliance burner control tap or tighten the appropriate fitting, testing with LDF as required. During the purging operation, the area in which the purge gas is being released shall not be left unattended. Installation Volumes > 0.02 m3 ≤ 0.035 m3 From a suitable purge point on the installation turn on a burner control tap on an appliance with an open burner. The purge gas mixture shall be ignited at the burner as soon as possible, by holding a source of ignition adjacent to the burner head or by continually operating the appliances ignition system. Note: It may be necessary, in certain situations, to connect a temporarily installed burner to a suitable point on the installation, for example, on installations with no appliances fitted, where the appliance(s) is fitted with a flame supervision device or where there are no open burners. 54 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) Confirm the presence of gas, for example, by observation of the burner igniting. Turn off the appliance burner control tap. During the purging operation, the area in which the purge gas is being released shall not be left unattended. (e) Ensure every branch of pipework is purged following the aforementioned procedure. (f) Establish a stable flame picture at each appliance. Where an appliance is identified which has not been commissioned, either it must be: disconnected from the gas supply or sealed off with an appropriate fitting with an appropriate label attached indicating the appliance is not commissioned, or the appliance commissioned. 55 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) A6.3 LPG In accordance with clause 7.4.10 and where the OP at the inlet of the purge valve does not exceed 37 mbar, the following procedure can be used for purging: (a) Within the vicinity of the purging activity ensure the following safety precautions are taken throughout the purging process: avoid any accumulation of gas within confined spaces advise the responsible person for the premises or other persons in the area of the above of the intent to purge and that there may be a smell of gas. prevent inadvertent operation of any electrical switch or other appliance extinguish all potential sources of ignition ensure that there is no smoking or naked lights ensure good ventilation by opening doors, windows, passive stack ventilation systems, etc. Note: These precautions are applicable even if a source of ignition is held adjacent to the purged gas, as a mixture of un-ignited gas/air may be released until a suitable mixture is achieved. (b) Ensure that all appliances are turned off before commencing with the purge. (c) Slowly turn on the gas supply and when a meter is installed note the position of the test dial or test drum on diaphragm meters or the meter reading on ultrasonic meters. (d) From a suitable purge point on the installation turn on a burner control tap on an appliance with an open burner. The purge gas mixture shall be ignited at the burner as soon as possible, by holding a source of ignition adjacent to the burner head or by continually operating the appliances ignition system. Note: It may be necessary, in certain situations, to connect a temporarily installed burner to a suitable point on the installation, for example, on installations with no appliances fitted, where the appliance(s) is fitted with a flame supervision device or where there are no open burners. Confirm the presence of gas, for example, by observation of the burner igniting. Turn off the appliance burner control tap. During the purging operation, the area in which the purge gas is being released shall not be left unattended. (e) Upon establishing the presence of gas: if the installation includes a meter, return to the meter and note the volume of gas that has passed continuing steps (d) and (e) until the correct PV has been passed (see Table 5). if the installation does not include a meter proceed to step (f). (f) Ensure every branch of pipework is purged following the aforementioned procedure. (g) Establish a stable flame picture at each appliance. Where an appliance is identified which has not been commissioned, either it must be: disconnected from the gas supply or sealed off with an appropriate fitting with an appropriate label attached indicating the appliance is not commissioned, or the appliance commissioned. 56 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) APPENDIX 7 : PURGING HEAVIER-THAN-AIR GASES – RISK ASSESSMENT A7.1 FLAMMABILITY RANGE Differing fuel gases have very different flammable ranges and, when working with these various gases, it is essential that the range is understood as well as having gas detection equipment suitable for the gas being monitored. A7.2 DENSITY (SPECIFIC GRAVITY) The densities of gases vary dependant on their temperatures, so it is normal to refer to density relative to air. Air has a density of 1. Gases with lower density are lighter-than-air and gases with a higher density are heavier-than-air. A7.3 PROPERTIES OF LPG The most common of the heavier than air gases in use are known as Liquefied Petroleum Gas, or LPG, (3rd family gases). BS 4250 is the specification for commercial butane and propane, but gases outside this specification are often used for special purposes. They are stored in the liquefied state under pressure. The actual pressure in the storage container, known as the vapour pressure, is dependent upon the specification of the actual LPG and the temperature of the stored liquid. These procedures apply only to the pipework downstream of the first stage pressure regulator in a vapour system. They do not apply to the storage tank, the high pressure pipework feeding the first stage regulator, or to any part of a system containing LPG in the liquid phase. LPG vapour is, normally, used for gas supplies to gas fired equipment. This vapour may be generated by natural vaporisation of the liquefied LPG, or for large industrial offtakes by the use of an in line vaporiser where the latent heat required is provided from an external source. Some LPG may contain small quantities of heavy hydrocarbons that do not readily vaporise, often described as "heavy ends". Where they are present, these heavy ends will concentrate in the bottom of storage vessels used for natural vaporisation systems, or in the base of external vaporisers. In abnormal situations, or where the plant operators fail to drain the system regularly, they may be carried over into the gas supply pipework. Where heavy ends are found in downstream pipework specialist advice is required to ensure that they are removed and disposed of in a safe manner. A permit to carry out such work is required to be issued by an authorised competent person. Note: A7.4 Heavy ends are, normally, only associated with LPG produced from refinery operations and are not present in LPG produced from natural gas liquids. ASSESSMENT OUTCOME If the assessment indicates that safety would be compromised, the heavierthan-air gas shall be purged indirectly seeking specialist advice if necessary. 57 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) APPENDIX 8 : TYPICAL PURGE EQUIPMENT SETUP FIGURE 9 – TYPICAL EQUIPMENT FOR AIR TO GAS PURGE 58 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) FIGURE 10 - TYPICAL EQUIPMENT FOR GAS TO AIR PURGE (COMPRESSED AIR/NITROGEN) 59 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk IGEM/UP/1A Edition 3 (Draft for Comment) FIGURE 11 - TYPICAL EQUIPMENT FOR GAS TO AIR PURGE (FAN) 60 IGEM, IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk