MPS™-100 Bi-Directional Grid-Tied Inverter

advertisement
MPS™-100 Bi-Directional Grid-Tied Inverter
For Single & Dual DC Input 100 kW Systems
The MPS™-100 series of bi-directional inverters are
storage applications. The MPS™-100 is configurable as a
single or dual DC input inverter. Each input is settable
as either a battery or PV with maximum power point
tracking (MPPT).
Integrated Solution
Dynapower’s MPS™-100
integrated solution containing all required AC breakers
and protective features as well as DC disconnects and
and energy storage integrators a cost advantage when
compared to non-integrated systems requiring additional
add-on items.
Dynamic Transfer
Dynapower’s proprietary Dynamic Transfer algorithm
monitors the grid stability and within 16 ms of detecting
a grid disturbance will disconnect from the grid
connection and transition to stand alone mode on the
load connection. The transition is seamless to the
critical loads.
Experience
Standard Features
•
•
•
•
•
Integrated AC Breaker with
Shunt Trip
Integrated DC Disconnect
Integrated DC Pre-Charge
Integrated DC Input Fuses
DynaCloudTM - cloud-based remote
monitoring and diagnostics
Available Options
•
•
•
•
Integrated Transformer
Black Start
Revenue Grade Power Meter
AC Pre-Charge Circuit - permits
MPS-100 to be used as a
DC voltage source
Having provided over 50% of the domestic gridtied power electronics for battery energy systems
the Dynapower Energy Management team brings
an unchallenged level of expertise and unrivaled
knowledge base to our customers.
Dynapower’s engineering team has designed and
delivered energy storage systems globally including
Asia, North America, Oceania and Australia of
systems sized from 25 kW to 36,000 kW.
www.DynapowerEnergy.com
MPS™-100
Bi-Directional Grid-Tied Inverter
DC Voltage
280 - 600 VDC
DC Current
DC Current, Each Input
DC Voltage Ripple
<1%
Grid Connection
AC Line Voltage
AC Line Frequency
480 VAC 3 Phase, +10%, -12%
60 Hz (57 - 60.5 Hz) Field Settable
Continuous AC Current
137 ARMS
Overload AC Current
180 ARMS
Continuous AC Power
100 kW
Overload AC Power
Power Factor
Current Harmonics
150 kW
0 - 1.00 Leading or Lagging
IEEE 1547 Compliant, <5% THD
>96.5%
Operating Tempature
Cooling
Rated Max Elevation
Enclosure
Dimensions (HxWxD)
Weight
-10-45°C
Forced Air Cooled
1,000 Meters (consult factory for higher)
NEMA 3R (Outdoor)
63 x 41 x 26 inch w/o Transformer
900 lbs
Safety Features
Faults
Standards Compliance
Safety Features
AC Over Voltage, AC Under Voltage,
AC Under Frequency, AC Over Frequency,
AC Overload, Over-tempature,
DC Over Voltage, DC Over Current,
Ground Fault
IEEE 1547, Listed to UL 1741
Anti-islanding w/ UL Compliant trip points
User Interface
Front Panel
Remote Communication
Remote Monitoring
7” Touch Screen with Status LEDs
ModBus TCP, DNP3, IEC-61850
DynaCloudTM - Real time monitoring
with automated alerts and data logging.
Analog I/O
3 Analog Inputs, 3 Analog Outputs
Digital I/O
3 Digital Inputs, 3 Relay Outputs
About Dynapower Company
Dynapower is a vertically integrated company focused on quality and continuous
improvement – all products are designed, manufactured and tested in our state-of-the
art 155,000 square foot facility in South Burlington, VT. Our customer-focused business
provides the highest quality equipment and unparalleled after-sale service and support
including 24-hour technical support to our global customer base.
www.DynapowerEnergy.com
DP100kW-SS-3192013