Memorial Hermann Best Practices July, 2013 SECTION 26 13 16 MEDIUM VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR PART 1 - GENERAL 1.01 A. 1.02 Metal Enclosed Load Interrupter Switch, free-standing, single, duplex, selector, or lineup as shown on the drawings. RELATED SECTIONS A. Section 26 05 00: Common Work Results for Electrical B. Section 26 05 13: Medium Voltage Cable C. Section 26 05 73: Power System Studies D. Section 26 12 13: Liquid Filled, Medium Voltage Transformers E. Section 26 12 16: Dry Type, Medium Voltage Transformers F. Section 26 13 19: Medium Voltage Vacuum Interrupter Switchgear 1.03 . WORK INCLUDED REFERENCES A. ANSI/IEEE C37.20.2 - Standard for Metalclad and Station Type Cubicle Switchgear B. ANSI/IEEE C37.20.3 - Standard for Metal Enclosed Interrupter Switchgear C. ANSI/IEEE C37.20.4 - Standard for Indoor AC Switches for Use in Metal Enclosed Switchgear D. ANSI/IEEE C37.22 - Preferred Ratings for Indoor Medium Voltage Switches Used in Metal Enclosed Switchgear E. ANSI/IEEE C37.57 - Metal Enclosed Interrupter Switchgear Assemblies - Conformance Testing F. ANSI/IEEE C37.58 - Conformance Test procedures for Indoor AC Medium Voltage Switches for Use in Metal Enclosed Switchgear G. ANSI/IEEE 48 - Standard Test Procedures and Requirements for High-Voltage AlternatingCurrent Cable Terminations H. ANSI Z55.1 - Gray Finishes for Industrial Apparatus and Equipment I. ANSI C1 / NFPA 70 - National Electrical Code J. ANSI C2 - National Electrical Safety Code K. ANSI / NECA 1 - Practices for Good Workmanship in Electrical Construction L. NEMA SG5 - Power Switchgear Assemblies M. NEMA SG6 - Power Switching Equipment MEDIUM VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR 26 13 16 - Page 1 Memorial Hermann Best Practices July, 2013 1.04 A. Provide a minimum of 8 copies of the following documents, where applicable, to Owner for review and evaluation in accordance with general requirements of Division 01 and Division 26: 1. Front view and floor plan of switchgear 2. Switchgear anchoring locations 3. Conduit and busway entry / exit locations 4. Location of shipping splits 5. One-line and three-line diagrams of switchgear bus and protective devices 6. Switchgear ratings including: a. Short circuit rating b. System voltage rating c. Continuous current rating 7. Protective device schedule including: a. Device type b. Sensor and trip rating c. Location within the switchgear d. Cable quantity and size capabilities for each device 8. Panel drawing showing all major protection, instrumentation, and control devices mounted within the switchgear 9. Schematic diagram showing power, metering, and control circuits for the switchgear and circuit breakers 10. Bill of Material listing (including quantity, location, catalog number, and ratings) of all major protection, instrumentation and control devices 11. Switchgear nameplate schedule B. Submit product data (8 copies) C. Submit manufacturer's installation instructions. (8 copies) 1.05 A. 1.06 PROJECT RECORD DOCUMENTS Submit a minimum 8 copies of record information including: 1. As-built record drawings as follows: a. Front View b. Floor Plan c. Elementary Diagram showing power, metering and control circuits d. Switchgear internal wiring diagrams e. Bill of Material f. One Line Diagram g. Three Line Diagram 2. Instruction books on major components 3. Installation drawings 4. Certified test reports 5. Recommended renewal parts information OPERATION AND MAINTENANCE DATA A. Provide minimum 8 copies of installation, operation and maintenance procedures to owner in accordance with general requirements of Division 01 and Division 26. B. Submit operation and maintenance data based on factory and field testing, operation and maintenance of specified product. 1.07 . SUBMITTALS QUALITY ASSURANCE MEDIUM VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR 26 13 16 - Page 2 Memorial Hermann Best Practices July, 2013 A. Manufacturer: Company specializing in medium voltage load interrupter switchgear with at least five years documented experience. B. Provide listing by Underwriters Laboratories for 5KV or 15KV class medium voltage load interrupter switchgear. 1.08 DELIVERY, STORAGE, AND HANDLING A. Switchgear shall be provided with adequate lifting means and shall be able to be rolled or moved into installation position and bolted directly to floor without using floor sills. B. Deliver, store. Protect, and handle products in accordance with recommended practices listed in manufacturer's Installation and Maintenance Manuals. C. Deliver each switchgear lineup in shipping sections for ease of handling. Each section shall be mounted on shipping skids. D. Inspect and report concealed damage to carrier within specified time. E. Store in a clean, dry space. Maintain factory protection or cover with heavy-duty plastic, minimum 6 mil, to keep out dirt, water, construction debris, and traffic. Heat enclosures to prevent condensation. F. Handle switchgear in accordance with manufacturer's written instructions to avoid damaging equipment, installed devices, and finish. Lift only by installed lifting provisions. 1.09 PROJECT CONDITIONS (SITE ENVIRONMENTAL CONDITIONS) A. Follow applicable NEMA, ANSI, and NECA standard practices before, during, and after switchgear installation. B. Switchgear shall be located in well-ventilated areas, free from excess humidity, dust, and dirt and away from hazardous materials. Ambient temperature of area will be between minus [30] and plus [40] degrees C. Indoor locations shall be protected to prevent moisture from entering enclosure. 1.10 A. 1.11 A. 1.12 SEQUENCING AND SCHEDULING Provide a written detailed description of scheduled installation, testing, and startup dates. WARRANTY Manufacturer warrants equipment to be free from defects in materials and workmanship for greater of 1 year from date of installation or 18 months from date of delivery. EXTRA MATERIALS/ACCESSORIES A. Provide a list of recommended maintenance materials. B. Provide one set of spare fuses for each type and size of fuse installed. Provide an adequately sized storage cabinet with hinged door to house the spare fuses. PART 2 - PRODUCTS 2.01 A. . MANUFACTURERS Eaton/Cutler-Hammer MEDIUM VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR 26 13 16 - Page 3 Memorial Hermann Best Practices July, 2013 B. Square D C. Siemens D. Products of manufacturers not listed as approved will be considered for approval if technical data is submitted at least two weeks before bid date. Substitutions will not be considered after this period. 2.02 A. PRIMARY INCOMING LINE SECTION - The load interrupter switch shall have an incoming terminal compartment with NEMA drilled pads. Refer to the drawings for specific wire size and type. The terminal compartment may be part of the switch structure unless shown otherwise. The terminals shall be radial feed, unless otherwise indicated. B. Provide a set of intermediate class surge arresters mounted inside the terminal section and grounded to the metal structure. Arrestors KV rating shall match the equipment ratings shown on the drawings. Arrestors shall be equal to GE TRANQUELL(r). C. When part of a unit substation, the load interrupter switch is close-coupled to transformer as shown on the drawings. Provide kirk-key interlocking transformer secondary main circuit breaker such that fuse compartment cannot be opened unless secondary breaker is open and interupter switch is open. Switch finish shall match transformer finish. D. Non-Loadbreak Selector Switches 1. For 5 or 15kV ratings, furnish a two-position non-loadbreak selector switch for the selection of two incoming sources in series with the load break MVS switch where shown on contract drawing. The selector switch shall have the same continuous current rating as the load interrupter switch in the same structure. Interlocking shall be supplied so that the selector switch can only be operated with the load interrupter switch in the open position. Also, neither the main door nor the load interrupter switch shall be able to be closed without the selector switch being positively locked in one of the two source positions. E. Duplex Switchgear Assembly 1. Furnish, where shown on the drawings, a duplex switchgear assembly configuration consisting of two (2) load interrupter switches with common load side bus to feed one load circuit, which shall be fused. Key interlocks shall be supplied to prevent opening the front door of each vertical section containing one of the two switches unless both switches are locked open. 2.03 A. 2.04 A. . EQUIPMENT RATINGS Ratings - The load interrupter switch ratings shall be as follows: 1. Nominal System Voltage and Bus Current rating shall be 15 kV, 1200 ampers, unless otherwise indicated on the drawings. 2. System Type: - solidly grounded wye 3. Basic Impulse Level (BIL) - 5kV - 60 BIL or 15kV - 95 BIL. 4. Momentary Current - 40kA asymmetrical for 5kV and 15kV 5. Fault Close Current - 40kA asymmetrical for 5kV and 15 kV CONSTRUCTION The load interrupter switch assembly shall be metal enclosed front accessible or rear accessible}, full height, self-supporting sections constructed of ANSI/IEEE C37.20.3 sheet steel doors, barriers, and side covers, and bolted frame. Each section shall be adequately braced and shall MEDIUM VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR 26 13 16 - Page 4 Memorial Hermann Best Practices July, 2013 have adequate ventilation to prevent distortion of the cubicle doors and windows under operating conditions. B. The load interrupter switch shall be fused. The switch shall be two position, 3-pole, gang operated with a stored energy quick make/quick break mechanism that opens and closes the switch regardless of speed at which the operating handle is moved. Switch shall be operated from the front of the cubicle by means of a non-removable operating handle. C. Provide non-metallic phase barriers form the full length of the switch blade and fuse for each pole. D. The double air-interrupter switch shall be rated as 15 kV, 1200 ampers unless otherwise indicated in the drawings. It shall consist of two 2-position (open, close), 3-pole, gang-operated, air interrupter switches, equipped with stored-energy mechanisms. Switches shall be key interlocked so that both switches must be open to access the fuses. E. Where used on a unit substation with an alternate source of power to the secondary bus, the switch shall be key interlocked with the secondary main such that the main must be open to access fuses. 2.05 A. One set of three (3) current limiting power fuses {{GE Type EJO}} shall be mounted in separate compartment within each switch unit. B. Fuses shall be accessible through a hinged door mechanically interlocked with interrupter switch such that entry may be accomplished by de-energizing the switch. On switch feeding unit substations that have a possible 2nd source of power, a warning sign shall be placed on the door indicating that fuses may be energized when switch is open. Fuses shall be rated as indicated on the drawings and suitable for use on circuit having short-circuit capacity of 250, 500 or 750 MVA symmetrical at 5kV or 15kV. C. Fuses shall be accessible through a hinged door mechanically interlocked with interrupter switch such that entry may only be accomplished by de-energizing the switch. Current rating of fuses as indicated on drawings and shall be suitable for use on circuit having short-circuited capacity as noted on the drawings. D. Fuses shall be held in position with provision for removal and replacement from the front without the use of special tools. 2.06 . FUSES MAIN BUS A. All phase bus conductors shall be tin-plated copper and be mounted on NEMA rated cyclophenolic epoxy insulators. Bus connections shall be bolted with a minimum of 2 bolts. The bus shall be braced to withstand the effects of a short circuit within the ratings of the equipment. All bus shall be insulated with sleeve type insulation. Where joints are made, the joints shall be covered with molded covers. B. The full-length ground bus conductor shall be copper directly fastened at the front of each vertical section. A 4/0 AWG two hole, long barrel compression lug shall be provided at each end of the ground bus. Ground bus shall be sized such that a line-to-ground or double line-to-ground fault current of 125% of 3 phase fault current rating shall be cleared by maximum size fuse possible without damage to the bus or supports. C. Provide glass polyester standoff insulators on switches and fuse mountings D. Provide removable insulated boots for all terminations. MEDIUM VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR 26 13 16 - Page 5 Memorial Hermann Best Practices July, 2013 2.07 A. The switch shall be NEMA 1 for indoor use., NEMA 2, drip proof for indoor use or NEMA 3R for outdoor use. B. Provide each vertical section with a sloped weatherproof roof with labyrinth shaped joints. All exterior openings shall be screened with rodent barriers. Provide a minimum of (1) 250 watt, 120 volt space heater in each vertical section each thermostatically controlled. Provide ventilated openings to allow airflow in each vertical section. The ventilated covers shall be externally removable for safe access to the filter media. C. A large shatter-resistant inspection window made of Lexan shall be provided in the door of each switch section to allow operator viewing of the switch blade position without opening the door. D. Individual doors shall be provided for the switch and fuse compartments. A mechanical interlock shall be provided to prevent access to the live side of the switch when the switch is in the "on" position or the fuse compartment door is open. Additionally, a horizontal safety barrier between the two compartments shall be provided. All steel doors shall have concealed hinges and captive hardware to secure the door in the closed position. E. Provisions for padlocking the load interrupter switch in either the open or close position shall be provided. F. The structure shall be provided with a removable lifting means and be suitable for jacking or rolling into position. G. Permanent non-corrosive nameplate. All units shall have the appropriate hazardous danger signs prominently displayed on the exterior and interior of each section. H. Louvered, penetration resistant, vents on indoor units. Louvered, penetration resistant, vents with removable filters on outdoor units. Walk-in enclosure shall have power exhaust fans sized for a minimum of 4 air changes per hour. I. Provide relays, meters, control switches as required, mounted on a front hinged panel. To the extent possible while meeting the requirements of the specifications, , relays shall be provided by the same manufacturer for all power distribution equipment provided for this project. Meters shall be provided by the same manufacturer for all power distribution equipment provided for this project. 2.08 A. 2.09 . ENCLOSURE FINISH All enclosure surfaces shall be thoroughly cleaned of scale, oil, grease, rust and other foreign matter prior to painting and then treated with phosphoric acid, etched, and cleaned. An electrostatic powder 2-5 mill thick coating shall be applied and oven cured. Finish shall be ANSI 61 light Gray. Paint finish shall be rated for 1,000 hours salt spray per ANSI C37.20.3. CIRCUIT MONITOR A. Where electronic power monitor is indicated on the drawings, provide a Cutler-Hammer IQ Analyzer 6600, GE KVC2, or approved equal meter, mounted as required. Refer to Section 26 09 15, Electronic Power Monitor, for acceptable manufacturers. B. Provide a customer metering compartment with front hinged doors. Provide multi-function electronic relays unless otherwise indicated on the drawings. C. Electronic power monitor shall be as specified in section 26 09 13. MEDIUM VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR 26 13 16 - Page 6 Memorial Hermann Best Practices July, 2013 2.10 A. One (1) terminal pad per phase shall be provided for attaching contractor-supplied cable terminal lugs for a maximum of two (2) conductors per phase of the sizes indicated on the drawings. Sufficient space shall be allowed for contractor supplied electrical stress relief termination devices. B. Small wiring, fuse blocks and terminal blocks within the vertical section shall be furnished as indicated on the drawings. Each control wire shall be labeled with wire markers. Terminal blocks shall be provided for owner's connections to other apparatus. C. The switchgear shall be wired with type SIS #14 AWG, stranded, except where larger size wire is specified. CT circuits shall be #10 AWG. The switchgear shall be provided with terminal blocks for outgoing control connections. Wire markers shall be provided for each end of all control wires. D. Current transformer wiring shall use shorting type terminal blocks. E. Protective Relays: Provide instruments as indicated on drawings for each switch. 2.11 A. 2.12 A. 2.13 . WIRING/TERMINATIONS INSTRUMENT TRANSFORMERS Current Transformers: The current transformer assembly shall be insulated for the full voltage rating of the switchgear. Relaying and metering accuracy shall conform to ANSI Standards. Voltage transformers are fixed mounted with primary current-limiting fuses and shall have ratio as required to deliver secondary voltage of 120V at rated bus voltage. The transformers shall have mechanical rating equal to the momentary rating of the switch and shall have metering accuracy per ANSI Standards. High accuracy and/or ratios below 300:5 - two per phase. ACCESSORIES AND ADDITIONAL FEATURES Each load interrupter switch shall include: 1. Dust resistance enclosure 2. UL labeled as service entrance switchgear 3. Plastic Mimic bus 4. Weather resistance enclosure 5. Rear doors. (identical to front) 6. Vertical barriers 7. Auxiliary switches, 2-NO 2-NC 8. Space heaters with thermostat 9. Operations counter 10. Bottom closure plates 11. Rodent barriers 12. Tamper resistant hardware 13. Porcelain insulators 14. Provide a control power transformer to power space heaters on outdoor enclosure 15. Provide metering as indicated on drawings 16. Provide motor operators for the switch(es) as indicated on the drawings 17. Provide motor operators and an automatic transfer scheme as indicated on the drawings 18. Louvered, penetration resistant, vents with removable filters on indoor units 19. The neutral bus, where required, shall be full size and installed on 600 volt insulators 20. Provide infrared scanning ports 21. The load interrupter switch shall be installed in a metal clad switchgear assembly. See section 26 13 19 for assembly details and requirements. TESTING MEDIUM VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR 26 13 16 - Page 7 Memorial Hermann Best Practices July, 2013 A. Each load interrupter switch shall receive all routine commercial tests in accordance with applicable ANSI standard. B. Manufacturer shall provide 10 certified copies of factory test reports. PART 3 - EXECUTION 3.01 EXAMINATION A. Visually inspect switchgear for evidence of damage and verify that surfaces are ready to receive work. B. Visually inspect to confirm that all items and accessories are in accordance with specifications and drawings. C. Verify field measurements are as shown on drawings and as instructed by manufacturer. D. Verify that required utilities (e.g., control voltage for heater circuits on outdoor switchgear) are available, in proper location, and ready for use. E. Beginning of installation means installer accepts existing surface conditions. 3.02 INSTALLATION A. Install in accordance with manufacturer's instructions, applicable requirements of the National Electrical Code, National Electrical Safety Code, ANSI/NECA 1, and in accordance with recognized industry practices. B. Use jumper cables, as provided by the switchgear manufacturer, to connect the primary surge arresters. C. Bending of high-voltage cables should be avoided or minimized. All necessary bends should meet at least the minimum radii specified by the cable manufacturer. 3.03 FIELD QUALITY CONTROL A. Visually inspect for physical damage. B. Perform mechanical operator tests in accordance with manufacturer's instructions. C. Check torque of all bolted bus connections, including cable terminations. D. Touch-up paint all chips and scratches with manufacturer-supplied paint and leave remaining paint with owner. E. Verify key interlock operation. F. Perform insulation resistance tests per manufacturer's published instructions. G. Perform low frequency withstand tests according to ANSI/IEEE C37.20.2, paragraph 5.5. H. Provide field service, start-up, and training for load interrupter switchgear. END OF SECTION . MEDIUM VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR 26 13 16 - Page 8