SECTION [26 10 00] [16290] POWER MONITORING AND CONTROL PART 1 - GENERAL 1.1 SCOPE A. 1.2 This section defines power metering for low and medium voltage use in AC systems. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. B. [Related Sections include the following: 1. Section [26 13 13] [16341] – Medium-Voltage Circuit Breaker Switchgear] 2. Section [26 13 16] [16341] – Medium-Voltage Fusible Interrupter Switchgear 3. Section [26 13 19] [16341] – Medium-Voltage Vacuum Interrupter Switchgear 4. Section [26 23 00] [16430] – Low Voltage Switchgear 1.3 SUBMITTALS A. Provide product information prior to fabrication and installation. Product data shall include all dimensions, electrical ratings and maintenance data (if applicable). B. Submit shop drawings and product data for approval and final documentation in the quantities listed according to the Conditions of the Contract. Customer name, customer location and customer order number shall identify all transmittals. C. [Final Documents: Record documentation to include wiring diagrams, instruction and installation manuals [and certified test reports]]. 1.4 RELATED STANDARDS A. 1.5 This product is UL-certified to Standard UL 61010B-1, based on the specification in Chapter 8.2 (Technical Data). UL File No.:E228586. The device is designed and manufactured for application in industrial environments as defined in the standard EN 50081. The device is designed and manufactured in accordance with the international standard IEC 60688, EN60688, and DIN EN 60688. QUALITY ASSURANCE A. Manufacturer Qualifications: Manufacturer of this equipment shall have a minimum of 5 years experience producing similar electrical equipment. B. Comply with requirements of latest revisions of applicable industry standards. 1.6 DELIVERY, STORAGE AND HANDLING A. Store and handle in strict compliance with manufacturer’s instructions and recommendations. Protect from potential damage from weather and construction operations. If the meters are installed in equipment, store the equipment so condensation will not form on or in it. If necessary, apply temporary heat where required to obtain suitable service conditions. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. [The medium voltage power meter shall be type SIMEAS P by Siemens or pre-approved equal. Approved manufacturers are as follows: 1. SIEMENS 2. . ] July 25, 2016 Medium Voltage Metering [Project Name] [26 10 00] [16290]-1 2.2 COMPONENTS A. Power Meter 1. The meter(s) shall be panel flush mounted & provide following functions: a. Measurement of voltage, current, active & reactive power, frequency, active & reactive energy, power factor, symmetry factor, voltage and current harmonics up to the 21st and total harmonic distortion b. [Extended measurement memory 1Mbyte. [Optional depending on order selection]] c. [Battery [Optional depending on order selection]] d. [Real-time module measured values and states will be recorded with time stamps. [Optional depending on order selection]] e. Single-phase, three-phase balanced or unbalanced connection, four-wire connection f. PROFIBUS-DP or MODBUS RTU/ ASCII communication protocol. g. Simple parameterization via RS485 communication port using Windows XP software program. h. Graphic display with background illumination with up to 20 programmable screens B. Selectable Screen Types 1. 2 or 4 measured values in one screen 2. One list screen for minimum, average and maximum values 3. Two types of screens for harmonics 4. One screen for oscilloscope function (sampled values or R.M.S. values) 5. One screen serving as phasor (vector) diagram 6. Up to 20 screen types can be programmed. Switching from one screen to another can be automatic or manual C. Memory Read-Out 1. Separate functions integrated in the configuration software, enable a read-out of the following information: a. Mean values b. Mean values of power c. Oscilloscope recordings d. State information of binary channels e. Limit value violations f. Log entries D. Display and Evaluation 1. All values and information read out via the software are shown automatically in tabular and graphical manner together with the time stamp on the screen. The context menu offers some functions (masking of signals, copy, zoom, measuring functions) for easy analysis of measured values and state information. 2. The following measured values can be shown in graphical manner: a. Mean values b. Mean values of power c. Oscilloscope recordings d. State information of binary channels e. The following information are shown in tabular form: f. Limit value violations g. Log entries E. Export Function 1. The software also enables a function for the export of transmitted values and state information into an ASCII file. This ASCII file can be used in other applications, e.g. MSExcel. Oscilloscope recordings can be exported into COMTRADE formatted files. PART 3 - EXECUTION July 25, 2016 Medium Voltage Metering [Project Name] [26 10 00] [16290]-2 3.1 INSTALLATION A. 3.2 … ADJUSTMENTS AND CLEANING A. 3.3 … TESTING A. 3.4 … WARRANTY A. 3.5 Equipment manufacturer warrants that all goods supplied are free of non-conformities in workmanship and materials for six years from date of shipment. [STARTUP SERVICES] A. Engage a factory authorized service representative to perform startup service. B. Train Owner's maintenance personnel on procedures and schedules for energizing and de-energizing, troubleshooting, servicing and maintaining equipment and schedules. C. Verify that switchgear is installed and connected according to the Contract Documents. D. Verify that electrical control wiring installation complies with manufacturer's submittal by means of point-to-point continuity testing. Verify that wiring installation complies with requirements in Division [26] [16] Sections. E. Complete installation instructions.] and startup checks according to manufacturer's written END OF SECTION July 25, 2016 Medium Voltage Metering [Project Name] [26 10 00] [16290]-3