VX Series On-board Sensor LED Kit Installation Instructions This installation guide is valid for the following kits: K-12-VX-X4X-XX K-13-VX-X4X--XX K-14-VX-X4X--XX K-18-VX-X4X--XX Warnings Ensure power is off before starting installation or attempting any maintenance. Risk of Electric Shock, Suitable for damp locations. All work should be performed by a qualified electrician. This product must be installed in accordance with NEC and your local codes by a person familiar with the construction and operation of the product and hazards involved. Kit Components The LED Retrofit Assemblies are provided fully assembled and consists of a reflector, LED light strip, driver, bonding tether and electrical disconnect. Sensor Electrical Disconnect Driver Bonding Tether (1) LED Sensor Assembly LED Light Strip Reflector (profile may vary from the version shown) Bonding Tether (1) LED Satellite Assembly LED Light Strip Hardware (3) Quarter-turn Fasteners (8) #8x1/2” self drilling screw (1) Bracket Set (2) Lens (Optional) Min. 2.75” The VX Series retrofit kit is designed to fit 1x2, 1x3, 1x4 and 1x8 Strip Fixture channels that have a minimum width of 2.75” and a minimum, depth of 1.625”. Min. 1.625” End View Page 1 80-30056 VX Series On-board Sensor LED Kit Installation Instructions Warnings WARNING FAILURE TO FOLLOW THESE INSTRUCTIONS AND WARNINGS MAY RESULT IN DEATH, SERIOUS INJURY OR SIGNIFICANT PROPERTY DAMAGE. For your protection, carefully read these warnings and instructions in their entirety before installing or maintaining this equipment. These instructions do not attempt to cover all installation and maintenance situations. If you do not understand these instructions or if additional information is required, contact Energy Solutions International customer service department at (888)308-9197. WARNING: This retrofit must be installed by a qualified electrician in accordance with any NEC, CEC, state, and/or local code requirements. This retrofit kit is not for use with all fixture bodies. WARNING: Risk of fire or electric shock. Installation requires knowledge of luminaire electrical systems. If not qualified, do not attempt installation. Contact a qualified electrician. WARNING: Risk of fire or electric shock. Never connect to, disconnect from or service while circuit equipment is energized. WARNING: Risk of fire or electric shock. Luminaires wiring, power supply, or other electrical parts may be damaged when drilling for installation of retrofit assembly hardware. Inspect wiring and components for damage. WARNING: Risk of personal injury. This equipment may have sharp edges. Wear gloves to prevent cuts or abrasions when removing from carton, handling and maintaining this equipment. Do not install in a damaged fixture • This equipment must be installed in accordance with all federal, state and local laws, regulations and codes • Proper grounding is required to ensure personal safety •All service shall be performed by qualified service personnel •This equipment must be installed and modified in accordance with all federal, state and local laws, regulations and codes by a professional who is familiar with the construction and operation of this product and any hazards involved NOTICE: Do not install with total power input greater than power rating of original fixture WARNING: To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects. WARNING: Only those open holes indicated in the photographs and/or drawings may be made or altered as a result of kit installation. Do not leave any other open holes in an enclosure of wiring or electrical components WARNING: Risk of fire or electric shock. Install this kit only in the luminaires that have the construction features and dimensions shown in the photographs and/or drawings. Host fixture prior to retrofit Page 2 80-30056 VX Series On-board Sensor LED Kit Installation Instructions Disassembly The disassembly involves removing and discarding the ballast cover, ballast, socket-bars and wiring of the host fixture . Dispose of according to state and local code requirements. Please recycle all reusable parts. Host Fixture Shell 1. Shut off power to existing fixture. Disconnect the black and the white power supply wires to existing ballast. 2. Remove and discard the host fixture lamp(s). 3. Remove and discard the host fixture parts. Remove the ballast cover. Remove the socket-bars. If the channel has endplates they may need to be removed prior to removing the socket-bars. Remove the ballast, wiring and the sockets. Reinstall endplates if necessary. 1. Install Brackets Remove ballast cover, ballast, socket-bars and wiring Assembly The brackets are provided as a set and can be easily separated by bending them where they join. Attach one bracket at each end of the fixture and one in the center using the provided self-tapping screws (Fig. 1). 2. Install LED Sensor Assembly Connect the bonding tether to the host fixture housing with a self-drilling screw and torque to 14 inch pounds. Connect the black lead from the Electrical Disconnect to the black branch wire and connect the white lead from the Electrical Disconnect to the white branch lead. (See appendix on next page for wiring diagrams). Figure 1 Install the brackets Orange Disconnect Mounting Tabs Position the wires with the orange disconnect under the center bracket and slide the Sensor Assembly onto the tabs in the center bracket. (Fig. 2). Secure the other end of the LED Sensor Assembly with a quarter-turn fastener. 3. Install LED Satellite Assembly Connect the bonding tether to host channel. Connect the Orange disconnects. Secure the LED Satellite Assembly at each end with a quarter-turn fastener. Figure 2 - Attach LED Sensor Assembly Tabs in Reflector 4. Install Optional Lens If the LED Retrofit Assembly is provided with an optional lens, it can be installed by snapping it onto the reflector tabs as shown 5. Electrically activate the fixture Optional Lens Figure 3 - Lens attachment Page 3 80-30056 VX Series On-board Sensor LED Kit Installation Instructions Picture of Completed Installation Supply Appendix - Wiring Diagrams Appendix A - Wiring diagram BEFORE retrofit installation Driver Supply Splice Connections White Black White Electrical Disconnect Black Ground LED Light Strip Low Voltage (+) Low Voltage (-) Appendix B - Wiring diagram AFTER retrofit installation Page 4 80-30056