Centrifugal Roof Exhaust Fans Series L Low Silhouette April 2016 Series L Centrifugal Roof Exhaust Fans low silhouette, centrifugal roof exhaust fans provide the industry’s broadest performance and durability for general Series L, clean air applications. These products undergo life testing, assuring these fans will provide years of reliable performance. extensive Typical Installations Benefits • Educational Facilities • Quick motor and drive access • Warehouses • Excellent weather resistance • Office Buildings • Certified for severe duty applications • Shopping Centers Table of Contents 2 Unique Construction Features . . . . . . . . . . . . . . . .3-5 Severe Duty Dimensions and Installation . . . . .11-12 Standard Installation . . . . . . . . . . . . . . . . . . . . . . . . 6 Dimensions Severe Duty Option . . . . . . . . . . . . . . . . . . . . . . . . . 7 LD/LDP Direct Drive . . . . . . . . . . . . . . . . . . . .13-15 Vari-Green Motor and Control Options . . . . . . . . .8-9 LB/LBP Belt Drive . . . . . . . . . . . . . . . . . . . . . .16-25 Options and Accessories . . . . . . . . . . . . . . . . . . . . 10 Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . .26-27 Unique Construction Features Fabra Hood Style • Hinged Hood - All sizes feature a hood which may be hinged to provide quick access to the motor and drive assembly. Access may be gained by simply removing two of the four hood fasteners or all fasteners for complete removal. Louvered Penthouse Style • Hinged Cover - All sizes feature an aluminum cover which may be hinged to provide quick access to the motor and drive assembly. Covers are fastened down with a quick release hood latch. • Large Interior Dimensions - All sizes allow complete accessibility. Interior dimensions offer clearance for inspection, cleaning, or maintenance of the motor, wheel, belt(s), and drives. • Large Interior Dimensions - All sizes allow complete accessibility from above. Interior dimensions offer clearance for inspection, cleaning, or maintenance of the motor, wheel, belt(s), and drives. • Strength & Weather Resistance - The hood is designed with arched panels manufactured of heavy gauge, precision roll formed steel with interlocking edges. Each interlocking rib creates a tight, weather resistant seal. Heavy gauge steel support members provide structural strength. • Strength & Weather Resistant - Each unit features storm resistant aluminum louver blades with mitered corners. For decades, our storm resistant blades have proven highly effective. Each sturdy extruded aluminum louver blade has a material thickness of 0.080 inches. Greenheck’s interlocking rib design combines four material thicknesses with I-beam design principles producing a hood far superior in strength to conventional designs (an important feature in high wind and snow load regions). Greenheck’s louvered penthouse hoods feature heavy gauge extruded aluminum louvers with mitered corners for a clean, finished appearance and weather resistant construction. Formed channels adjacent to the ribs provide water drainage to ensure weather tightness. Hoods are available in galvanized steel, coated steel, or aluminum construction. Greenheck Fan Corporation certifies the models LD, LDP, LB, and LBP shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program. The interior vertical edge of the curb cap forms the throat and weathershield. Each corner is also shielded to prevent leakage. Penthouses are available in aluminum for lasting durability and appearance. *UL is optional and must be specified. Models LD, LDP, LB, and LBP are listed for electrical (UL/cUL 705) File no. E40001. 3 Unique Construction Features Fabra Hood Style 1 1 9 6 2 12 10 13 11 5 2 8 LD 9 15 Vari-Green Motor 11 14 13 4 LB 8 13 9 4 6 3 13 10 11 LDP 7 Vari-Green Motor 9 5 Louvered Penthouse Style 3 LBP 4 Unique Construction Features Standard Construction Features 1 Fabra Hood Style Models LD and LB have a rib-lock galvanized housing. Hood panels are interlocked and attached to sturdy galvanized rails. (Aluminum housings are optional). 2 Hinged Access The entire hood assembly on models LD and LB can be hinged open for access to the internal fan components. 3 Louvered Penthouse Models LDP and LBP penthouse style housings are constructed of heavy extruded aluminum louvers with mitered and welded corners. 4 Hood Cover Models LDP and LBP aluminum hood covers are hinged and removable for access. 5 Drive Frame Constructed from heavy gauge galvanized steel. Belt adjustment is accomplished by loosening fasteners, sliding the motor plate, and retightening fasteners. 6 Fan Shaft Precisely sized, ground, and polished so the first critical speed is at least 25% over the maximum operating speed. Close tolerances between the shaft and bearing result in longer bearing life. 7 Bearings 100% factory tested and designed specifically for air handling applications with a minimum L10 life in excess of 100,000 hours (L50 average life of 500,000 hours). 8 Curb Cap Curb cap has prepunched mounting holes to ensure correct attachment to the curb. 9 Motor All motors are carefully matched to the fan load to provide years of trouble-free operation. 10 Drive Assembly Drives are oversized 150% of driven horsepower. Machined cast iron pulleys are factory set to the required RPM and are adjustable for final system balancing. Belts are static free and oil resistant. 11 Wheel An aluminum, backward inclined, non-overloading, centrifugal wheel is utilized to deliver maximum efficiency. Each wheel is statically and dynamically balanced. 12 Vibration Isolators Support the drive assembly and wheel without steel to steel contact providing long life and quiet operation. 13 Birdscreen Galvanized rigid wire protects the fan’s discharge from birds or small objects. (Aluminum birdscreen is optional). 14 Windband Lower windband assembly ensures weathertight and rigid unit construction. 15 Disconnect Switch NEMA-1 switch is factory mounted. Wiring from the motor to the disconnect enclosure is provided as standard. All wiring and electrical components comply with the National Electric Codes (NEC) and are UL Listed or Recognized. Conduit Chase A large diameter conduit for installing electrical wiring through the curb cap into the motor compartment. (Not shown) 5 Standard Installation Models LB, LD, LBP, and LDP exhaust fans are designed to meet the needs of general clean air applications. Tests have been conducted to ensure safe and reliable fans capable of withstanding normal exhaust conditions. When roofing materials extend to the top of the curb, roof curbs should be 11⁄2 in. (38 mm) (3/4 in. (19 mm) on a side) less than the unit curb cap to allow for roofing and flashing. For recommended duct size, damper size, and roof opening dimensions, refer to CAPS or the performance data pages. Installation must include a means for inspecting, cleaning, and servicing the exhaust fan. Due to the varying airstreams encountered in commercial ventilation, system designers must be aware of national, state, and local codes and guidelines governing these installations. Local code authorities should be consulted before proceeding with any ventilation project. 6 8 to 12 in. (203 to 305 mm) 3/4 in. (19 mm) Damper 1 1/4 in. (32 mm) Recommended Duct and Damper Size Recommended Roof Opening 1 1/4 in. (32 mm) Severe Duty Option Specifically designed for applications with extremely high structural design load requirements. The severe duty models LDP and LBP are far superior to any centrifugal roof exhaust fan currently in the market. The LBP/LDP may be used in any application which requires a fan to endure high winds with the potential of wind blown debris. The louvered housing has been tested in accordance with the following Miami-Dade test protocols: • Large Missile Impact Test - TAS-201-94 • Uniform Static Air Pressure - TAS-202-94 • Uniform Cyclic Wind Loading - TAS-203-94 To meet the above protocols, the severe duty fan must be mounted on a severe duty roof curb, which is attached directly to the building structure. Maximum design load is 140 psf. NOTICE OF ACCEPTANCE NUMBER 14-0514.07 Available on sizes • LDP 60 though 120 • LBP 10 through 30 Weights and dimensions will vary from standard LDP and LBP construction. Severe Duty Installation Models LDP and LBP severe duty exhaust fans are designed to meet the needs of general clean air applications. Tests have been conducted to ensure safe, rugged and reliable fans capable of withstanding severe exhaust conditions. Installation must include a means for inspecting, cleaning, and servicing the exhaust fan. Due to the varying airstreams encountered in commercial ventilation, system designers must be aware of national, state, and local codes and guidelines governing these installations. Local code authorities should be consulted before proceeding with any ventilation project. 3/4 INCH (19 MM) THROAT DIMENSION (ROOF OPENING) 1-3/4 INCH (44 MM) 1-3/4 INCH (44 MM) OUTSIDE CURB DIMENSION 12, 18 OR 24 INCHES 1 INCH (25 MM) INSULATION (305, 457, 610 MM) ROOF OPENING 4 IN. 4 IN. (102 MM) (102 MM) CORRUGATED ROOF DECK CONCRETE ROOF TRUSS RECOMMENDED DUCT & DAMPER SIZE 1-1/4 INCH (32 MM) 2-1/2 INCH (64 MM) 4 IN. (102 MM) 6 INCH x 3 INCH (152 MM x 76 MM) 2-1/2 INCH (64 MM) 1-3/4 INCH (44 MM) 4 IN (102 MM) STEEL MOUNTING ANGLE (12 GAUGE MINIMUM) 7 Vari-Green® Motor Option Model LD/LDP Features Greenheck’s electronically commutated (EC) Vari-Green (VG) motor combines motor technology, controllability and energy-efficiency into one single low maintenance unit and is the industry’s first fully controllable motor. When combined with Greenheck’s Series L fans, all the CFM and static pressure ranges of a belt drive can be attained with the benefits of a direct drive. 1. Dial on Motor Control - a potentiometer (dial on motor control) is mounted on the motor for easy speed adjustment for system balance. Simply turn the dial. There are no belts and pulleys to adjust. 2. Control Wire Inputs - the motor accepts a 0-10V DC signal from Building Automated Systems or other controls to adjust motor speed. Motor Information HP 1/6 1/4 1/2 RPM 1725 1725 1725 Voltage 115, 208-240, 277 115, 208-240, 277 115, 208-240, 277 HZ 50/60 50/60 50/60 2 1 Benefits Note: As motor speed is turned down, efficiency stays high as compared to an AC motor that decreases dramatically. • Operates cooler than a standard AC motor at lower RPMs. A cooler motor has longer motor life and reduces energy consumption. • 80% usable RPM turndown versus 30%, see Motor Turndown Comparison chart at right. • Series L fans with Vari-Green motors can provide all the CFM and static pressure ranges of a comparable belt drive. • Maintenance costs are reduced as there are no belts or bearings to replace and no pulleys to adjust. • Direct drive fans are often preferred where maintenance access is difficult. • Provides a solution for demand controlled ventilation applications. Comparisons: Belt, Direct Drive with PSC and Direct Drive with Vari-Green Motor Turndown Comparison 50% 500 100% LD-120 with PSC 400 Not recommended 300 EEnergy S Savings LB-14 Single Phase* 200 LD-120 with 100 0 0 350 FAN SPEED (RPM) 1750 * GB is a belt driven fan The length of each curve indicates the practical turndown range. Data is for 1/2 hp motors with load of 0.35 Bhp at full speed Constant Volume Life Cycle Analysis Three Year Cost Comparison $2,000 1,750 1,500 1,250 1,000 Vari-Green Advantages 750 • • • • 500 Initial cost is similar to a belt drive Lower operating cost No maintenance, no belts, pulleys or bearings Easy RPM adjustment 75% 600 INPUT POWER (WATTS) Operates on AC power that’s converted to DC— providing a more efficient motor operation as compared to an AC operation. • The motor can attain up to 85% efficiency and reduce energy consumption. • Watt savings of 30-70% depending on RPM. 250 $0 CUBELB121 14 CUELD121-A5 120-A5 CUELD121-VG 120-VG Initial Cost Maintenance cost over three years Operating cost over three years Analysis is based on operating costs for a period of three years where the fans operate continuously at 1725 rpm, 24/7, with an energy rate of $0.10/kWh. Maintenance on the LB-14 is estimated at $65/yr. Note: Example is based on a relative cost. Use and installation variables may produce different results. 8 Vari-Green® Control Options Vari-Green® Controls Transformer - Provides 24V power from the existing line voltage at the fan to the Vari-Green motor and controls. Dual voltage primary (120/240V) transformer provided with the fan. Remote Dial - Allows for remote, manual airflow adjustments. Wall plate with dial may be mounted in a standard 2x4 inch electrical junction box. Two Speed Control with Integral Transformer Control allows motor to be set at two independent speeds (high or low). Meets minimum airflow requirements with the ability to bump up to high speed in an emergency or meet maximum airflow requirements, or reset down to low for energy conservation. Constant Pressure Control - Control a fan with a Vari-Green motor to maintain either a constant static pressure (variable volume) or constant velocity pressure (constant airflow). The constant pressure control is available with an integral or remote pressure transducer which provides excellent installation flexibility. Inputs include remote override (digital, dry contact) and remote setpoint (analog, 0-10V). Outputs include fan speed (0-10V), pressure/airflow reference (analog, 0-10V), and relay output (digital, 0.5A rating). Contact fans@greenheck.com for more information. Daily Operating Comparison: Variable Volume and Constant Volume % of Operation Applications requiring constant pressure or variable volume can utilize Series L fans with Vari-Green motors and Vari-Green Variable Volume controls. Demand Operating Analysis Variable VolumeCost vs. Constant Volume control ventilation $ 2,000 systems reduce the 1,750 amount of energy used 1,500 by decreasing the 1,250 speed of the fan when demand is low. This in 1,000 turn lessens the amount 750 of conditioned air 500 exhausted and further 250 reduces total operating $0 costs associated with Constant Variable Volume Volume air conditioning and Heating Cost heating in multistoried Cooling Cost buildings such as Fan Operating Cost hotels, multifamily Example of potential savings complexes, institutional based on a northeast city in facilities, and high rise the USA using Vari-Green commercial buildings. components for variable volume. The Vari-Green constant pressure control is preprogrammed and easy to install for applications that include venting dryers, bathrooms, residential type kitchen space or industrial process exhaust. Hypothetical (Hotel Bathroom) Variable Volume - Load Shape 100 80$$$$$$$$$$$$$$$$$$$$$$$$ 60$$$$$$$$$$$$$$$$$$$$$$$$ 40$$$$$$$$$$$$$$$$$$$$$$$$ 20$$$$$$$$$$$$$$$$$$$$$$$$ 0%$$$$$$$$$$$$$$$$$$$$$$$$ 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Time of Day Series 1 Demand-controlled ventilation offers significant energy savings by exhausting only the necessary amount of air throughout the day. % of Operation Demand Control Ventilation for Multistory Buildings Constant Volume - Load Shape 100 80 60 40 20 0% 1 2 3 4 Series 2 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Time of Day Note: A standard VFD compatible motor can also function within a Variable Volume system. • Constant Pressure Applications – Apartments, condos, hotels; clothes dryers, residential kitchens and bathrooms. • Constant Airflow Applications – Filtered or other variable resistance systems. The Constant Airflow control is available with Greenheck’s Airflow Measuring Station (AMS) for airflow sampling Air Quality – VOC - Control a Vari-Green motor via changes in volatile organic compounds (VOC’s). VOC’s are gasses that are emitted from humans, building materials, perfumes, foods, and furniture off-gassing. Range is 0-2000 CO2 PPM equivalent. • Institutional facilities – Schools, court house, hospitals; bathrooms, waiting rooms, cafeteria. • Commercial buildings – Office space, conference rooms, bathrooms, break room. Air Quality – Temperature and Humidity - Control Vari-Green motor via changes in temperature, humidity, or both. Range is 15 to 130°F and 0 to 100% relative humidity. • Multifamily structures - Apartments, condos, hotels; bathrooms, utility rooms. • Commercial buildings - Office buildings, office space, conference rooms, utility rooms, bathrooms. 9 Options and Accessories BIRDSCREEN - Galvanized mesh is standard. Optional aluminum or stainless steel rigid wire are also available. HOOD INSULATION - Hood insulation is dual-density to minimize condensation, reduce thermal transfer, and enhance sound absorption at high and low frequencies. LIFTING LUGS - Four heavy gauge steel brackets are available to provide lifting points when raising the fan to the roof. TIE DOWN POINTS - Four heavy gauge steel brackets are available to secure the fan in heavy wind applications. Cables and anchors by others. COATINGS - Additional information on Greenheck coatings can be found in our Performance Coatings for Commercial & Industrial Fans and our Product Application Guide, Performance Coatings for Ventilation Products. A wide variety of coatings and colors are available in two categories: Decorative coatings – Standard colors are available. Protective coatings – Electrostatic applied powder coatings are available to protect against most environments. 10 1 0 DISCONNECT SWITCHES A wide selection of NEMA rated switches are available for positive electrical shutoff and safety, including: dust-tight, rainproof, and corrosion-resistant. Switches may be internally or externally mounted. SPEED CONTROLLERS - Available for use with shaded pole and permanent split capacitor (PSC) open motors on models LD and LDP fans. They provide an economical means of system balancing with direct drive fans. CURB EXTENSIONS - Extensions raise the fan discharge above the roof line and provide an accessible mounting location for dampers. Insect screen bases constructed with a removable fine mesh are recommended for applications where insect entry must be prevented. Curb extensions are not available with LDP and LBP severe duty construction models. DAMPERS - Designed to prevent outside air from entering back into the building when fan is off. Options include gravity and motorized dampers. Damper sizes are shown on each performance data page. ROOF CURBS - Prefabricated roof curbs reduce installation time and costs by ensuring compatibility between the fan, curb and roof opening. All curbs are insulated with fiberglass. A wide variety of roof curbs are available including flanged, pitched and sound-absorbing. CURB SEAL - Rubber seal between fan and curb to ensure proper sealing when attached to a curb. MOTOR STARTERS The fundamental function of a motor starter is to protect the motor from damage that can occur from overheating. With a Greenheck motor starter you will be provided with the best motor protection available. Severe Duty Dimensions LDP - SEVERE DUTY DIMENSIONS C B D E A Model Number A A B C D E Damper Size (square) Roof Opening (square) Weight* Cover Thickness Louver Thickness Curb Cap Thickness 60 65 17 347⁄8 347⁄8 175⁄8 13⁄4 8 101⁄2 375 (432) (886) (886) (448) (44) (203) (267) (170) 70 75 0.25 0.125 0.100 80 LDP (0.045) (0.056) (0.113) 85 19 367⁄8 367⁄8 175⁄8 13⁄4 10 121⁄2 400 aluminum aluminum steel (483) (934) (934) (448) (44) (254) (318) (181) 90 95 100 397⁄8 397⁄8 195⁄8 13⁄4 12 141⁄2 425 22 (559) (1013) (1013) (498) (44) (305) (368) (193) 120 All dimensions are in inches (millimeters). Weight in pounds (kilograms). *Weight shown is the largest cataloged Open Drip Proof motor. LBP - SEVERE DUTY DIMENSIONS B C D E A Model Number 10 14 18 LBP 21 24 30 A 22 397⁄8 503⁄8 181⁄8 13⁄4 Damper Size (square) 12 (559) (1013) (1280) (460) (44) (305) A B C D E Roof Opening (square) 101⁄2 (267) Weight* Louver Thickness Curb Cap Thickness 550 (249) 26 437⁄8 517⁄8 181⁄8 13⁄4 16 101⁄2 550 (660) (1114) (1318) (460) (44) (406) (267) (249) 101⁄2 550 30 477⁄8 577⁄8 245⁄8 13⁄4 18 (267) (249) (762) (1216) (1470) (625) (44) (457) 10 ⁄2 700 (267) (318) 1 Cover Thickness 34 517⁄8 617⁄8 245⁄8 13⁄4 24 101⁄2 800 (864) (1318) (1572) (625) (44) (610) (267) (363) 40 577⁄8 697⁄8 271⁄4 13⁄4 30 101⁄2 950 (1016) (1470) (1775) (692) (44) (762) (267) (431) 0.100 0.125 0.25 (0.045) (0.056) (0.113) aluminum aluminum steel All dimensions are in inches (millimeters). Weight in pounds (kilograms). *Weight shown is the largest cataloged Open Drip Proof motor. 11 Severe Duty Curb Installation Options OUTSIDE CURB DIMENSION 1.75 INCH (44 MM) THROAT DIMENSION (ROOF OPENING) 1.75 INCH (44 MM) Concrete CURB HEIGHT 12, 18, OR 24 INCHES 1 INCH (25 MM) INSULATION HILTI KB11, 3/8-16 X 3 ON 12 INCH (305 MM) MAXIMUM CENTERS. MINIMUM TWO PER SIDE. (305, 457, or 610 MM) ROOF OPENING 2.5 INCH (57 MM) EMBEDMENT MINIMUM CONCRETE STRENGTH OF 3000 PSI 1.75 INCH (44 MM) 4 INCH (102 MM) MOUNTING FLANGE TYPICAL 2.25 INCH (57 MM) TYPICAL 4 INCH (102 MM) TYPICAL OUTSIDE FLANGE DIMENSION THROAT DIMENSION AND ROOF OPENING EQUAL OUTSIDE CURB DIMENSION MINUS 3.5 INCHES (89 MM) OUTSIDE CURB DIMENSION 1.75 INCH (44 MM) THROAT DIMENSION (ROOF OPENING) 1.75 INCH (44 MM) Steel CURB HEIGHT 12, 18, OR 24 INCHES CORNER TOP VIEW 1 INCH (25 MM) INSULATION (305, 457, 610 MM) HILTI KWIK-FLEX 12-14 SCREW, NO. 3 POINT. THREE (3) FASTENERS EACH CORNER AND MAXIMUM OF 4.5 INCHES (114 mm) SPACING; ADD ADDITIONAL FASTENERS TO SATISFY. 4 INCH (102 MM) MOUNTING FLANGE TYPICAL ROOF OPENING CORRUGATED ROOF DECK 6 X 3 INCH (152 x 76 mm) STEEL MOUNTING ANGLE (12 GAUGE MINIMUM) ROOF TRUSS 1.75 INCH (44 MM) 2.25 INCH (57 MM) TYPICAL 4 INCH (102 MM) TYPICAL OUTSIDE FLANGE DIMENSION THROAT DIMENSION AND ROOF OPENING EQUAL OUTSIDE CURB DIMENSION MINUS 3.5 INCHES (89 MM) Model Number Code The model number system is designed to completely identify the fan. The correct code letters must be specified to designate belt or direct drive. The remainder of the model number is determined by the size and performance selected from the following pages. LB - 30 - VG/7 Model LD - Fabra Hood Direct Drive LB - Fabra Hood Belt Drive LDP - Louvered Penthouse Direct Drive LBP - Louvered Penthouse Belt Drive Fan Size LD/LDP 60 thru 120 LB/LBP 10 thru 54 12 VG = Vari-Green (Direct Drive only) Motor hp (Belt Drive only) 6 = 1/6 10 = 1 50 = 5 4 = 1/4 15 = 11⁄2 75 = 71⁄2 3 = 1/3 20 = 2 100 = 10 5 = 1/2 30 = 3 150 = 15 7 = 3/4 Motor RPM (Direct Drive only) A = 1725 B = 1140 C = 860 International (see CAPS for Performance) K = 950 RPM J = 1475 RPM 12 LD/LDP 60-75 Direct Drive LD Dimensions Size 60 and 65 0.6 27 131⁄2 (584) 13 ⁄8 Static Pressure Pa (340) (44) 0.5 120 3 13⁄4 RPM Density 0.075 lb/ft3 140 (686) (343) 17 17 (432) (432) 2 (51) 100 80 60 40 Static Pressure in. wg 23 0 23 111⁄2 /L DP LD -6 5 /L DP -6 0 0.2 0.0 0 50 100 150 200 250 300 cfm 23 (584) LD 0.3 0.1 20 LDP Dimensions 0.4 0 (584) 50 100 150 200 250 300 350 400 450 500 3 m /hr (292) Size 70 and 75 14 0.6 RPM Density 0.075 lb/ft3 140 (356) 0.5 17 17 (432) (432) Hood Thickness Cover Thickness Louver Thickness Curb Cap Thickness Damper Size Square Roof Opening Square Weight* LD 60 thru LD 75 24 ga 0.064 (0.029) 8 (203) 101⁄2 (267) Galvanized 37 (17) 100 80 60 40 LDP 60 thru LDP 75 0.064 (0.029) 0.081 (0.036) 0.064 (0.029) 8 (203) 101⁄2 (267) Aluminum 49 (22) Static Pressure in. wg 1 ⁄4 (44) Static Pressure Pa 120 3 LD 0.4 /L DP -7 0 0.3 LD /L DP -7 5 0.2 0.1 20 0.0 0 0 50 100 150 200 250 300 350 400 cfm 0 100 200 300 400 500 600 3 m /hr All dimensions are in inches (millimeters). Weight in pounds (kilograms). *Weight shown is the largest cataloged Open Drip Proof motor. See page 11 for severe duty LDP dimensions. Model Number LD/LDP-60 Motor HP 1/60 Fan RPM 1590* CFM / Static Pressure in Inches wg Watts 51 W LD/LDP-65 1/30 1680* 70 W LD/LDP-70 1/30 1665* 73 W LD/LDP-75 1/25 1620* 79 W CFM 0 0.1 0.125 0.2 0.25 0.3 202 171 164 139 119 97 0.375 0.4 Sones 4.8 4.3 4.3 4.0 3.8 3.6 CFM 274 245 238 208 187 165 129 112 Sones 5.6 5.3 5.2 5.0 5.1 5.1 5.1 5.2 0.45 0.5 CFM 360 324 314 282 257 231 188 171 132 Sones 6.4 6.0 5.9 5.5 5.4 5.3 5.2 5.1 5.0 CFM 400 360 351 317 290 264 222 206 168 122 Sones 5.8 5.2 5.1 4.9 4.7 4.5 4.2 4.1 4.0 3.8 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings include the effects of a birdscreen in the airstream. *Speed (RPM) shown is nominal. Performance is based on actual speed of test. The sound ratings shown are loudness values in fan sones at 5 feet (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sones. 13 LD/LDP 80-95 Direct Drive VG LD Dimensions Size 80 and 85 27 (343) 0.7 Static Pressure Pa 16 13⁄4 19 (44) 4 19 (483) (102) 140 112 84 (483) Static Pressure in. wg 168 (406) RPM Max System Curve Density 0.075 0.8 196 56 THIS SYS TEM CUR VE (711) (686) 0.6 0.5 0.4 TO THE LEF T OF 131⁄2 0.3 0.2 0.1 0 0.0 0 /L DP -8 5 /L DP -8 0 DO 28 LD LD NO TS EL EC T 28 LDP Dimensions 80 160 240 25 121⁄2 (635) 320 400 480 (635) 0 160 320 480 640 800 Size 90 and 95 17 RPM Max System Curve Density 0.075 112 84 CURV E 0.5 0.4 0.3 -9 5 90 0.0 0 DP P- 0.1 0 /L D 0.2 28 LD /L 56 0.6 LD LDP 80 thru LDP 95 0.064 (0.029) 0.081 (0.036) 0.064 (0.029) 10 (254) 121⁄2 (318) Aluminum 63 (29) 140 0.7 YSTE M 168 THIS S (483) 0.8 TO THE LEFT OF (483) 196 NO TS ELE CT (44) 0.9 DO 19 224 Static Pressure in. wg 19 Static Pressure Pa 13⁄4 Weight* 960 3 (432) Hood Thickness Cover Thickness Louver Thickness Curb Cap Thickness Damper Size Square Roof Opening Square 640 m /hr (318) LD 80 thru LD 95 24 ga 0.064 (0.029) 10 (254) 121⁄2 (318) Galvanized 45 (20) 560 CFM 25 200 400 600 800 1000 1200 CFM 0 250 500 750 1000 1250 1500 1750 2000 3 m /hr All dimensions are in inches (millimeters). Weight in pounds (kilograms). *Weight shown is the largest cataloged Open Drip Proof motor. See page 11 for severe duty LDP dimensions. Model Number LD/LDP-80 Motor HP 1/20 VG HP 1/6 Fan RPM 1550* 115 W LD/LDP-85 1/20 1/6 1500* 120 W LD/LDP-90 1/15 1/6 1550* 92 W LD/LDP-95 1/8 1/6 1550* CFM / Static Pressure in Inches wg Watts 160 W CFM 0 0.1 0.125 0.2 0.25 0.3 0.375 0.5 481 426 413 372 342 310 258 165 Sones 8.8 8.2 8.0 7.8 7.6 7.4 7.2 7.5 CFM 576 507 490 440 403 360 291 182 Sones 8.6 8.1 8.0 7.7 7.3 7.1 7.0 7.8 CFM 819 735 714 654 608 562 485 361 0.6 0.625 Sones 8.8 8.6 8.5 8.4 8.3 8.1 7.8 7.9 CFM 1052 965 942 870 825 780 695 552 430 396 Sones 11.8 11.2 11.1 10.8 10.4 10.2 10.0 9.8 10.1 10.2 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings include the effects of a birdscreen in the airstream. *Speed (RPM) shown is nominal. Performance is based on actual speed of test. The sound ratings shown are loudness values in fan sones at 5 feet (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sones. 14 LD/LDP 100-120 Direct Drive VG LD Dimensions LD/LDP-100 131⁄2 1.1 (686) (343) 1.0 (559) (559) 4 (102) 110 0.7 0.6 0.5 0.4 0.3 55 0.2 0.1 LDP Dimensions TO 22 0.8 0 0.0 0 11 SE LE CT (44) 22 165 Static Pressure in. wg (591) 25 17 Static Pressure Pa 231⁄4 TH EL EF TO FT HIS SYS TEM CUR VE 0.9 220 40 N OT (800) 13⁄4 RPM Max System Curve Density 0.075 27 311⁄2 86 0 DO 200 400 600 800 28 14 (711) 1000 1200 0 (711) 540 1080 1620 2160 2700 3 191⁄4 LD/LDP-120 (489) RPM Max System Curve Density 0.075 1.2 1.0 TO TH EL EFT OF THI SS YST EM 0.6 0.4 60 NO T 0.2 25 120 0.8 17 LD 100 thru LD 120 LDP 100 thru LDP 120 24 ga 0.064 (0.029) 0.081 (0.036) 0.064 (0.029) 0.064 (0.029) 12 (305) 12 (305) 141⁄2 (368) 141⁄2 (368) Aluminum Galvanized 82 (37) 57 (26) 180 CUR V E 240 SE LE CT 22 (559) Static Pressure in. wg 22 (559) Static Pressure Pa 13⁄4 (44) Weight* 1600 m /hr (356) Hood Thickness Cover Thickness Louver Thickness Curb Cap Thickness Damper Size Square Roof Opening Square 1400 CFM 28 11 40 86 0 DO 0 0.0 0 200 400 600 800 1000 1200 1400 1600 1800 2000 CFM 0 680 1360 2040 2720 3 m /hr All dimensions are in inches (millimeters). Weight in pounds (kilograms). *Weight shown is the largest cataloged Open Drip Proof motor. See page 11 for severe duty LDP dimensions. Model Number Motor HP VG HP Fan RPM LD/LDP-100-C 1/8 1/4 860 LD/LDP-100-B 1/6 1/4 1140 LD/LDP-100-A 1/4 1/4 1725 LD/LDP-120-C 1/8 1/4 860 LD/LDP-120-B 1/6 1/4 1140 LD/LDP-120-A 1/4 1/2 1725 CFM BHP Sones CFM BHP Sones CFM BHP Sones 0 766 0.022 6.3 1016 0.051 12.0 1538 0.18 16.2 0.125 568 0.029 5.3 879 0.065 11.0 1457 0.21 14.8 0.2 407 0.028 5.1 780 0.068 10.6 1399 0.22 14.4 CFM BHP Sones CFM BHP Sones CFM BHP Sones 921 0.03 6.6 1221 0.071 11.9 1848 0.25 21 702 0.041 5.3 1072 0.086 10.9 1762 0.28 19.6 536 0.043 5.1 960 0.094 10.3 1693 0.29 19.4 CFM / Static Pressure in Inches wg 0.25 0.375 0.5 0.625 0.75 0.875 0.9 709 0.068 10.4 1360 0.22 14.2 493 0.066 10.4 1256 0.23 14.3 1142 0.24 14.2 1024 0.24 14.8 891 0.23 15.3 724 0.23 15.9 678 0.22 16.1 886 0.096 10.0 1652 0.29 19.3 664 0.099 9.2 1540 0.31 18.6 1412 0.33 18.4 1286 0.34 18.2 1142 0.35 18.2 979 0.34 18.3 940 0.33 18.3 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness values in fan sones at 5 feet (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sones. 15 LB/LBP 10 Belt Drive LB Dimensions 1.4 (711) 1.2 22 (44) (559) (559) (85) 100 50 0 LBP Dimensions (711) SY ST EM OF TH IS LE FT 0.4 0.2 22 0.0 0 T NO 10 SE 67 83 60 3 0 200 0 400 600 800 1000 1200 1400 1600 500 1000 1500 2000 2500 3 m /hr (356) (432) (559) 00 (978) 17 13⁄4 34 13 cfm 381⁄2 14 15 E 0.6 DO 28 67 TH 22 17 T 1 ⁄4 150 0.8 LE C 3 31⁄4 1.0 TO Static Pressure Pa (432) 200 Static Pressure in. wg (438) 250 RPM HP Density 0.075 lb/ft3 p p 300 17 (44) 3h 4h (991) CU RV E 17 ⁄4 1 1/ 1/ 39 28 22 (559) Hood Thickness Cover Thickness Louver Thickness Curb Cap Thickness Damper Size Square Roof Opening Square Weight* LB-10 22 ga 0.064 (0.029) 12 (305) 141⁄2 (368) Galvanized 56 (25) LBP-10 0.064 (0.029) 0.081 (0.036) 0.064 (0.029) 12 (305) 141⁄2 (368) Aluminum 99 (45) All dimensions are in inches (millimeters). Weight in pounds (kilograms). *Weight shown is the largest cataloged Open Drip Proof motor. See page 11 for severe duty LBP dimensions. Model Number Motor HP Fan RPM 600 712 937 1049 LB/LBP-10-4 1/4 1162 1274 1386 1499 1611 1689 LB/LBP-10-3 1/3 1767 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 0 539 0.013 3.0 639 0.021 3.6 841 0.048 5.1 942 0.067 5.9 1043 0.091 6.9 1144 0.12 8.0 1244 0.15 9.2 1346 0.19 10.0 1446 0.24 11.2 1516 0.28 12.2 1587 0.32 13.5 0.125 351 0.014 1.6 500 0.024 2.3 746 0.053 4.3 855 0.073 5.3 963 0.097 6.3 1070 0.13 7.5 1177 0.16 8.8 1283 0.2 9.8 1388 0.25 10.9 1461 0.29 11.9 1533 0.33 13.0 0.25 CFM / Static Pressure in Inches wg 0.375 0.5 0.625 0.75 0.875 1 1.125 MAX. BHP AT A GIVEN RPM - (rpm/2476)3 MAXIMUM FRPM = 1767 TIP SPEED = rpm x 2.913 MAX. MOTOR FRAME SIZE = 56 623 0.054 3.6 759 0.076 4.7 887 0.103 5.9 1004 0.13 7.1 1114 0.17 8.4 1224 0.21 9.5 1331 0.26 10.7 1406 0.3 11.6 1480 0.34 12.6 625 0.075 4.2 780 0.103 5.4 917 0.14 6.8 1047 0.18 8.2 1168 0.22 9.3 1280 0.27 10.4 1356 0.31 11.3 1432 0.35 12.2 618 0.099 4.7 818 0.14 6.3 953 0.18 7.9 1093 0.22 8.8 1220 0.28 10.1 1304 0.32 11.0 1385 0.36 11.9 861 0.17 7.3 1006 0.22 8.3 1142 0.28 9.5 1237 0.32 10.6 1327 0.36 11.7 910 0.22 7.8 1064 0.28 9.0 1158 0.32 9.9 1254 0.36 11.0 970 0.27 8.5 1087 0.32 9.5 1182 0.36 10.5 980 0.31 8.9 1112 0.36 10.1 997 0.36 9.5 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness values in fan sones at 5 feet (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sones. 16 LB/LBP 14 Belt Drive LB Dimensions 3 250 OF TH IS EF T EL 0 0.0 0 TH TO 0 300 48 (813) N 600 900 1200 1500 1800 2100 2400 2700 cfm 40 16 2 O T 0.2 DO 32 43 50 LBP Dimensions 70 (660) 0.4 (102) 5 (660) 100 82 (44) 26 0.6 RPM HP Density 0.075 lb/ft3 hp 65 26 2 7 4 13⁄4 150 hp 0.8 1/ 11 (457) 200 hp 13 18 4 99 Static Pressure Pa (445) 1/ 1.0 S YS TEM C 1/ (991) SE LE CT (889) Static Pressure in. wg 17 ⁄2 1 URV E 1.2 39 35 0 1000 2000 (1016) 3000 4000 3 m /hr (406) 17 (432) 13⁄4 26 26 (44) (660) (660) Hood Thickness Cover Thickness Louver Thickness Curb Cap Thickness Damper Size Square Roof Opening Square Weight* LB-14 22 ga 0.064 (0.029) 16 (406) 181⁄2 (470) Galvanized 81 (37) LBP-14 0.064 (0.029) 0.081 (0.036) 0.064 (0.029) 16 (406) 181⁄2 (470) Aluminum 116 (53) All dimensions are in inches (millimeters). Weight in pounds (kilograms). *Weight shown is the largest cataloged Open Drip Proof motor. See page 11 for severe duty LBP dimensions. Model Number Motor HP Fan RPM 480 564 731 LB/LBP-14-4 1/4 815 899 982 1066 1118 LB/LBP-14-3 1/3 1170 1257 LB/LBP-14-5 1/2 1343 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 0 903 0.022 4.1 1061 0.035 4.7 1375 0.077 5.9 1533 0.11 6.7 1690 0.14 7.5 1847 0.19 8.5 2004 0.24 9.8 2102 0.27 10.7 2200 0.31 11.5 2364 0.39 12.9 2525 0.47 14.4 0.125 614 0.025 3.2 848 0.041 4.2 1231 0.086 5.6 1402 0.12 6.4 1574 0.15 7.3 1743 0.2 8.4 1912 0.25 9.7 2016 0.28 10.6 2120 0.32 11.3 2290 0.4 12.7 2456 0.49 14.1 0.25 CFM / Static Pressure in Inches wg 0.375 0.5 0.625 0.75 0.875 1 1.125 MAX. BHP AT A GIVEN RPM - (rpm/1639)3 MAXIMUM FRPM = 1343 TIP SPEED = rpm x 3.829 MAX. MOTOR FRAME SIZE = 56 1024 0.089 5.1 1241 0.12 5.9 1439 0.16 6.9 1629 0.21 8 1807 0.26 9.4 1913 0.3 10.3 2019 0.34 11.1 2197 0.42 12.5 2372 0.51 13.8 1013 0.12 5.4 1264 0.17 6.4 1482 0.21 7.5 1681 0.27 8.9 1801 0.31 9.8 1920 0.36 10.6 2112 0.44 12.1 2289 0.53 13.5 946 0.15 5.7 1297 0.21 7 1534 0.28 8.4 1672 0.32 9.3 1797 0.36 10.1 2002 0.44 11.6 2199 0.54 13.1 1351 0.27 7.8 1512 0.32 8.7 1657 0.36 9.5 1887 0.45 11.1 2092 0.55 12.6 1257 0.3 8.1 1487 0.36 9.0 1748 0.45 10.5 1979 0.55 12.2 1585 0.44 10.1 1848 0.55 11.6 1692 0.54 11.1 1386 0.51 10.4 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness values in fan sones at 5 feet (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sones. 17 LB/LBP 18 Belt Drive LB Dimensions 2.5 (445) (762) 200 (114) 3 1/ 1.0 1/ 2 hp 4 LBP Dimensions 19 (914) DO hp 14 60 12 61 10 62 3 66 4 46 N 5 1000 2000 3000 4000 5000 6000 cfm 46 36 0.0 0 2 RPM HP Density 0.075 lb/ft3 hp 86 OT 0 1/ hp hp 0.5 2 1 OT HE LEF TO F TH IS S 30 1/ TT 30 (762) 1.5 SE 13⁄4 (44) Static Pressure in. wg 4 ⁄2 1 hp (533) 400 hp 4 21 1 3/ Static Pressure Pa 2.0 LE C (1016) (991) YST EM C 17 ⁄2 1 URV E 600 39 40 0 2 4 (1168) 6 8 10 3 m /hr X 1000 (483) 241⁄2 (622) 13⁄4 30 30 (44) (762) (762) LB-18 22 ga 0.064 (0.029) 18 (457) 201⁄2 (521) Galvanized 135 (61) Hood Thickness Cover Thickness Louver Thickness Curb Cap Thickness Damper Size Square Roof Opening Square Weight* LBP-18 0.064 (0.029) 0.081 (0.036) 0.064 (0.029) 18 (457) 201⁄2 (521) Aluminum 179 (81) All dimensions are in inches (millimeters). Weight in pounds (kilograms). *Weight shown is the largest cataloged Open Drip Proof motor. See page 11 for severe duty LBP dimensions. Model Number Motor HP Fan RPM 465 LB/LBP-18-4 1/4 562 755 LB/LBP-18-3 1/3 826 888 LB/LBP-18-5 1/2 949 LB/LBP-18-7 3/4 1085 LB/LBP-18-10 1 1141 1286 LB/LBP-18-15 1 1⁄2 1375 LB/LBP-18-20 2 1460 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 0 1753 0.056 3.6 2119 0.099 4.9 2847 0.24 8.7 3115 0.31 10.2 3348 0.39 11.7 3578 0.48 13.4 4091 0.71 16.8 4302 0.83 18.0 4849 1.19 21 5185 1.45 24 5505 1.73 26 0.125 1422 0.064 2.7 1871 0.108 4.1 2671 0.25 7.9 2957 0.33 9.5 3203 0.4 11.0 3442 0.49 13.0 3972 0.73 16.2 4189 0.84 17.3 4749 1.2 20 5091 1.47 23 5417 1.76 25 0.25 1522 0.114 3.4 2474 0.27 7.4 2778 0.34 8.9 3039 0.42 10.4 3292 0.51 12.0 3847 0.75 15.5 4073 0.86 16.7 4648 1.22 19.8 4997 1.49 22 5328 1.78 24 CFM / Static Pressure in Inches wg 0.5 0.75 1 1.25 1.5 1.75 2 MAX. BHP AT A GIVEN RPM - (rpm/1157)3 MAXIMUM FRPM = 1460 TIP SPEED = rpm x 4.843 MAX. MOTOR FRAME SIZE = 145T 1925 0.27 6.5 2324 0.36 8.0 2638 0.45 9.4 2936 0.54 11.0 3575 0.79 14.6 3814 0.91 15.9 4423 1.27 19.2 4790 1.54 21 5138 1.83 23 2110 0.44 8.7 2498 0.55 10.3 3218 0.82 13.4 3493 0.94 14.8 4183 1.32 18.5 4576 1.59 21 4936 1.88 23 2822 0.82 12.9 3140 0.96 14.1 3880 1.35 17.8 4311 1.63 20 4714 1.93 22 2674 0.93 13.8 3568 1.37 17.4 4025 1.66 19.9 4446 1.98 22 3208 1.35 17.1 3719 1.67 19.6 4176 2 22 3382 1.65 19.5 3874 2 22 3538 1.97 22 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness values in fan sones at 5 feet (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sones. 18 LB/LBP 21 Belt Drive LB Dimensions 2.0 E HIS S TO 00 FT 12 LEF 53 10 CT TO T 6 HE 90 LE 9 SE OT 2 N 5 DO 46 19 0.0 0 1000 2000 3000 4000 5000 6000 7000 8000 cfm 46 36 61 LBP Dimensions (914) 75 Static Pressure in. wg hp hp Static Pressure Pa 4 4 hp 0.5 100 0 hp hp 3/ hp 1/ (762) 6 (152) 1.0 3 30 1/ 30 (762) 200 2 13⁄4 300 1/ 23 (584) 1.5 RPM HP Density 0.075 lb/ft3 2 2 400 (44) YST EM CUR V 1/ (584) hp (1092) (1295) 1 23 1 51 43 0 2 4 6 8 10 12 3 (1168) m /hr X 1000 (483) 241⁄2 (622) 13⁄4 30 30 (44) (762) (762) Hood Thickness Cover Thickness Louver Thickness Curb Cap Thickness Damper Size Square Roof Opening Square Weight* LB-21 22 ga 0.064 (0.029) 18 (457) 201⁄2 (521) Galvanized 145 (66) LBP-21 0.064 (0.029) 0.081 (0.036) 0.064 (0.029) 18 (457) 201⁄2 (521) Aluminum 191 (86) All dimensions are in inches (millimeters). Weight in pounds (kilograms). *Weight shown is the largest cataloged Open Drip Proof motor. See page 11 for severe duty LBP dimensions. Model Number Motor HP Fan RPM 465 LB/LBP-21-4 1/4 595 LB/LBP-21-3 1/3 651 699 LB/LBP-21-5 1/2 747 801 LB/LBP-21-7 3/4 855 LB/LBP-21-10 1 899 1010 LB/LBP-21-15 11⁄2 1077 LB/LBP-21-20 2 1200 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 0 2820 0.12 6.6 3609 0.24 8.8 3948 0.32 10.1 4239 0.39 11.6 4531 0.48 13.4 4858 0.59 15.5 5186 0.72 16.7 5452 0.83 17.1 6126 1.18 20 6532 1.43 22 7278 1.98 26 0.25 1732 0.13 5.2 2938 0.28 7.8 3371 0.36 8.8 3724 0.44 9.9 4056 0.53 11.2 4424 0.65 12.9 4790 0.79 14.4 5087 0.91 15.4 5826 1.26 18.9 6260 1.52 21 7034 2.07 25 0.375 2457 0.28 6.9 2970 0.36 8.2 3362 0.45 9.3 3741 0.54 10.4 4157 0.66 11.8 4553 0.8 13.3 4858 0.93 14.5 5614 1.3 18.1 6068 1.56 20 6890 2.12 25 CFM / Static Pressure in Inches wg 0.5 0.625 0.75 1 1.25 1.5 1.75 MAX. BHP AT A GIVEN RPM - (rpm/910)3 MAXIMUM FRPM = 1200 TIP SPEED = rpm x 5.596 MAX. MOTOR FRAME SIZE = 145T 2354 0.34 6.9 2954 0.45 8.6 3390 0.55 9.8 3833 0.67 11.3 4261 0.81 12.8 4602 0.94 13.9 5415 1.32 17.3 5877 1.59 19.4 6712 2.18 24 1964 0.38 7.1 2909 0.53 9.1 3491 0.68 10.8 3954 0.82 12.1 4313 0.95 13.4 5183 1.34 16.6 5691 1.61 18.8 6542 2.2 23 2937 0.64 10.1 3608 0.82 11.5 4019 0.96 12.7 4926 1.35 16.2 5451 1.62 18.2 6375 2.22 23 2894 0.86 11.7 4386 1.36 15.0 4965 1.65 17.3 5954 2.25 22 3369 1.24 14.0 4395 1.63 16.4 5517 2.28 21 5013 2.26 20 4122 2.11 18.5 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness values in fan sones at 5 feet (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sones. 19 LB/LBP 24 Belt Drive LB Dimensions 1.6 (1156) (1295) 1 350 1.4 1 (521) 34 (44) (864) (864) 63⁄4 150 100 (171) 4 1/ 3 hp 0.4 0.2 0 0.0 0 T NO 1000 2 RPM HP Density 0.075 lb/ft3 hp 91 0 79 9 68 8 57 7 46 6 S 35 5 2000 3000 4000 5000 6000 7000 8000 9000 cfm 491⁄2 (1016) hp hp 0.6 50 LBP Dimensions 20 hp EF TO 1/ DO 40 4 2 hp TH EL 34 0.8 3/ 1/ 1.0 EL 13⁄4 200 1.2 TO (597) 250 2 EC T 23 ⁄2 1 Static Pressure in. wg Static Pressure Pa 300 1/ hp YS TEM 20 ⁄2 FT HIS S 45 ⁄2 1 CU RVE 51 1 0 2 4 6 8 10 12 14 3 m /hr X 1000 (1257) (508) 231⁄2 (597) 13⁄4 34 34 (44) (864) (864) Hood Thickness Cover Thickness Louver Thickness Curb Cap Thickness Damper Size Square Roof Opening Square Weight* LB-24 22 ga 0.064 (0.029) 24 (610) 261⁄2 (673) Galvanized 188 (85) LBP-24 0.064 (0.029) 0.081 (0.036) 0.064 (0.029) 24 (610) 261⁄2 (673) Aluminum 239 (108) All dimensions are in inches (millimeters). Weight in pounds (kilograms). *Weight shown is the largest cataloged Open Drip Proof motor. See page 11 for severe duty LBP dimensions. Model Number Motor HP Fan RPM 355 LB/LBP-24-4 1/4 409 462 LB/LBP-24-3 1/3 508 LB/LBP-24-5 1/2 582 625 LB/LBP-24-7 3/4 667 LB/LBP-24-10 1 734 LB/LBP-24-15 11⁄2 787 868 LB/LBP-24-20 2 910 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 0 3419 0.11 5.8 3938 0.17 6.3 4449 0.24 7.4 4892 0.32 8.5 5604 0.48 10.7 6018 0.59 12.4 6423 0.72 14.1 7068 0.96 17.0 7578 1.18 19.6 8358 1.58 24 8763 1.82 27 0.25 2715 0.19 5.1 3451 0.28 6.3 4043 0.36 7.4 4917 0.54 9.4 5381 0.66 11.0 5828 0.8 12.7 6531 1.05 15.3 7080 1.29 17.4 7907 1.7 21 8333 1.95 24 0.375 CFM / Static Pressure in Inches wg 0.5 0.625 0.75 0.875 1 1.25 1.375 MAX. BHP AT A GIVEN RPM - (rpm/710)3 MAXIMUM FRPM = 910 TIP SPEED = rpm x 6.414 MAX. MOTOR FRAME SIZE = 184T 2491 0.25 5.3 3433 0.36 6.8 4441 0.55 8.9 4988 0.68 10.3 5505 0.82 12.0 6252 1.08 14.6 6820 1.32 16.5 7675 1.74 20 8114 2 23 3899 0.55 8.4 4497 0.68 10.0 5062 0.83 11.5 5912 1.1 13.9 6560 1.35 15.9 7440 1.78 19.4 7889 2.04 21 3929 0.66 9.5 4589 0.83 11.1 5503 1.1 13.5 6190 1.36 15.4 7192 1.81 18.9 7664 2.07 21 3984 0.79 10.9 5073 1.1 13.2 5799 1.36 15.0 6855 1.82 18.3 7377 2.09 20 4555 1.07 12.9 5398 1.36 14.8 6505 1.83 17.9 7056 2.1 19.8 4909 1.32 14.1 6141 1.82 17.6 6713 2.1 19.5 5285 1.76 16.0 5995 2.08 18.4 5537 2.03 17.2 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness values in fan sones at 5 feet (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sones. 20 LB/LBP 30 Belt Drive LB Dimensions 2.0 hp SY STE M HIS FT TO TH CT TO SE LE 6 40 (1016) 10 12 14 16 5 10 15 20 25 3 (673) 40 8 m /hr X 1000 261⁄2 (1016) 5 0 4 (584) 13⁄4 83 4 3 2 1 2 0 (1473) (44) 71 59 47 35 23 T cfm X 1000 58 46 0.0 0 NO RPM HP Density 0.075 lb/ft3 23 DO 0 hp Static Pressure in. wg 2 1/ Static Pressure Pa 1 hp 0.5 100 LBP Dimensions hp (1016) 3 1/ (1016) hp (44) (216) 2 1/ 40 1.0 4 3/ 40 200 hp 81⁄2 13⁄4 300 1.5 1 (676) hp 26 ⁄8 5 2 400 EL EF (749) (1168) CU RVE 3 (1270) (1600) hp 291⁄2 5 63 50 Hood Thickness Cover Thickness Louver Thickness Curb Cap Thickness Damper Size Square Roof Opening Square Weight* LB-30 22 ga 0.064 (0.029) 30 (762) 321⁄2 (826) Galvanized 249 (113) LBP-30 0.064 (0.029) 0.081 (0.036) 0.064 (0.029) 30 (762) 321⁄2 (826) Aluminum 318 (144) All dimensions are in inches (millimeters). Weight in pounds (kilograms). *Weight shown is the largest cataloged Open Drip Proof motor. See page 11 for severe duty LBP dimensions. Model Number Motor HP Fan RPM 230 LB/LBP-30-3 1/3 366 394 LB/LBP-30-5 1/2 421 LB/LBP-30-7 3/4 483 LB/LBP-30-10 1 529 567 LB/LBP-30-15 11⁄2 605 LB/LBP-30-20 2 667 LB/LBP-30-30 3 703 LB/LBP-30-50 5 835 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 0 3910 0.076 8.0 6221 0.31 8.7 6697 0.38 9.0 7156 0.47 9.7 8210 0.7 12.0 8992 0.92 13.8 9638 1.14 15.3 10284 1.38 16.8 11338 1.85 19.8 11950 2.17 22 14194 3.63 27 0.25 4729 0.37 5.9 5354 0.45 6.5 5939 0.54 7.4 7196 0.8 10.7 8079 1.04 12.9 8797 1.27 14.2 9507 1.53 15.7 10639 2.02 18.6 11287 2.34 20 13635 3.84 26 0.375 CFM / Static Pressure in Inches wg 0.5 0.625 0.75 1 1.25 1.5 1.75 MAX. BHP AT A GIVEN RPM - (rpm/512)3 MAXIMUM FRPM = 835 TIP SPEED = rpm x 7.985 MAX. MOTOR FRAME SIZE = 184T 4290 0.44 6.0 5076 0.55 6.7 6567 0.83 9.7 7559 1.07 12.1 8334 1.31 13.6 9073 1.57 15.2 10257 2.07 17.9 10935 2.41 19.5 13356 3.95 25 5777 0.83 8.8 6946 1.1 11.4 7786 1.34 13.0 8605 1.61 14.6 9863 2.12 17.5 10562 2.46 19.1 13062 4.03 25 6162 1.09 10.3 7174 1.36 12.3 8068 1.64 14.1 9419 2.16 17.1 10184 2.51 18.7 12747 4.09 24 6410 1.33 11.2 7434 1.64 13.3 8933 2.19 16.6 9722 2.54 18.3 12432 4.14 24 7737 2.17 14.9 8701 2.57 17.0 11728 4.24 23 7032 2.41 14.2 10951 4.33 22 9965 4.29 21 8478 4.06 18.2 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness values in fan sones at 5 feet (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sones. 21 LB/LBP 36 Belt Drive LB Dimensions 2.0 5 (1600) ST 49 TH EL 6 58 EF T OF 8 hp TO 4 LE CT 40 SE 3 31 T NO 1 0 22 2 4 6 8 10 12 14 16 18 20 cfm X 1000 63 (1314) 0.0 0 67 2 1/ 0 LBP Dimensions 26 TH IS 1 0.5 100 DO 513⁄4 SY hp Static Pressure Pa 2 (1168) hp (1168) hp (44) (248) 2 1/ 46 1.0 4 3/ 46 200 hp 93⁄4 13⁄4 300 1 325⁄8 (829) 1.5 hp (686) 3 400 RPM HP Density 0.075 lb/ft3 EM CU RVE 27 Static Pressure in. wg 60 (1524) hp 63 0 10 20 30 3 (1600) m /hr X 1000 (660) 343⁄8 (873) 13⁄4 46 46 (44) (1168) (1168) Hood Thickness Cover Thickness Louver Thickness Curb Cap Thickness Damper Size Square Roof Opening Square Weight* LB-36 0.064 (0.029) 0.064 (0.029) 36 (914) 381⁄2 (978) Galvanized 338 (153) LBP-36 0.064 (0.029) 0.081 (0.036) 0.064 (0.029) 36 (914) 381⁄2 (978) Aluminum 444 (201) All dimensions are in inches (millimeters). Weight in pounds (kilograms). *Weight shown is the largest cataloged Open Drip Proof motor. See page 11 for severe duty LBP dimensions. Model Number Motor HP Fan RPM 220 LB/LBP-36-5 1/2 315 LB/LBP-36-7 3/4 360 LB/LBP-36-10 1 397 426 LB/LBP-36-15 11⁄2 454 LB/LBP-36-20 2 499 536 LB/LBP-36-30 3 572 614 LB/LBP-36-50 5 678 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 0 6204 0.16 4.9 8884 0.47 8.2 10153 0.7 10.6 11196 0.94 13.7 12014 1.16 14.8 12804 1.41 16.0 14073 1.87 18.2 15116 2.31 20 16132 2.81 22 17316 3.48 25 19121 4.69 30 0.25 6937 0.55 6.3 8570 0.81 8.9 9816 1.08 12.1 10765 1.32 14.0 11668 1.58 15.4 13064 2.06 17.6 14196 2.52 19.7 15287 3.04 22 16540 3.72 24 18419 4.95 29 0.375 CFM / Static Pressure in Inches wg 0.5 0.625 0.75 0.875 1 1.25 1.5 MAX. BHP AT A GIVEN RPM - (rpm/384)3 MAXIMUM FRPM = 678 TIP SPEED = rpm x 9.425 MAX. MOTOR FRAME SIZE = 184T 7487 0.83 7.9 8911 1.1 10.6 9964 1.35 12.7 10949 1.63 14.5 12442 2.13 17.2 13646 2.61 19.3 14790 3.14 21 16087 3.84 24 18041 5.08 29 7775 1.1 9.4 9056 1.37 11.6 10127 1.65 13.7 11760 2.17 16.6 13037 2.67 18.7 14229 3.21 21 15598 3.93 24 17621 5.21 29 7716 1.34 10.1 9209 1.66 12.5 11004 2.2 16.1 12361 2.7 18.4 13649 3.26 20 15066 3.99 23 17165 5.3 28 7552 1.57 11.0 10173 2.2 15.1 11652 2.73 17.8 12989 3.29 19.9 14504 4.05 23 16683 5.37 27 8773 2.12 13.9 10837 2.72 16.7 12313 3.32 19.0 13890 4.08 22 16192 5.44 27 9559 2.65 15.8 11534 3.31 18.1 13262 4.1 21 15636 5.47 26 11584 4.04 19.2 14494 5.52 24 12970 5.45 22 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness values in fan sones at 5 feet (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sones. 22 LB/LBP 42 Belt Drive LB Dimensions 1.6 75 5 (1905) 1 ⁄4 52 (44) 52 (1321) (1321) (292) 100 1 1.0 1 3/ 4 2 0.4 DO LBP Dimensions 29 (1473) hp 2 NO 51 5 45 0 38 5 T 32 0 SE 25 5 19 0 4 6 8 10 12 14 16 18 20 22 24 cfm X 1000 701⁄2 58 TE hp 1/ 0.0 0 hp hp E 0.6 0.2 0 1/ 2 0.8 hp hp TH 111⁄2 3 200 2 1.2 LE CT 373⁄8 (949) Static Pressure in. wg Static Pressure Pa 300 HIS SY S (851) RPM HP Density 0.075 lb/ft3 hp MC 3 UR VE 1.4 FT OF T (1794) LE 33 ⁄2 1 TO 70 ⁄8 5 0 10 20 (1791) 30 40 3 m /hr X 1000 (737) 381⁄4 (972) 13⁄4 52 52 (44) (1321) (1321) Hood Thickness Cover Thickness Louver Thickness Curb Cap Thickness Damper Size Square Roof Opening Square Weight* LB-42 0.064 (0.029) 0.064 (0.029) 42 (1067) 441⁄2 (1130) Galvanized 396 (180) LBP-42 0.064 (0.029) 0.081 (0.036) 0.064 (0.029) 42 (1067) 441⁄2 (1130) Aluminum 530 (240) All dimensions are in inches (millimeters). Weight in pounds (kilograms). *Weight shown is the largest cataloged Open Drip Proof motor. See page 11 for severe duty LBP dimensions. Model Number Motor HP Fan RPM 190 LB/LBP-42-5 1/2 247 LB/LBP-42-7 3/4 283 LB/LBP-42-10 1 311 334 LB/LBP-42-15 11⁄2 356 LB/LBP-42-20 2 392 420 LB/LBP-42-30 3 448 482 LB/LBP-42-50 5 515 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 0 8328 0.21 5.2 10827 0.47 6.9 12405 0.71 8.3 13632 0.94 9.8 14640 1.17 11.5 15605 1.41 13.2 17183 1.89 16.1 18410 2.32 18.6 19637 2.82 22 21128 3.51 23 22574 4.28 25 0.125 6455 0.25 4.3 9583 0.53 6.0 11362 0.78 7.6 12718 1.02 9.3 13812 1.25 11.0 14828 1.5 12.7 16477 1.98 15.5 17751 2.42 18.0 19020 2.93 21 20554 3.63 23 22037 4.41 24 0.25 7772 0.55 5.5 9965 0.83 7.1 11521 1.08 8.7 12766 1.33 10.4 13887 1.58 12.1 15667 2.08 14.9 17030 2.52 17.3 18378 3.04 20 19980 3.74 22 21500 4.53 24 CFM / Static Pressure in Inches wg 0.375 0.5 0.625 0.75 0.875 1 1.25 MAX. BHP AT A GIVEN RPM - (rpm/301)3 MAXIMUM FRPM = 515 TIP SPEED = rpm x 11.061 MAX. MOTOR FRAME SIZE = 184T 7932 0.81 6.5 10057 1.1 8.3 11480 1.37 9.8 12733 1.64 11.5 14715 2.16 14.3 16205 2.62 16.6 17605 3.14 19.4 19281 3.86 22 20887 4.65 24 9795 1.35 9.2 11417 1.66 10.8 13626 2.21 13.7 15201 2.68 16.1 16740 3.22 18.8 18562 3.97 21 20214 4.77 23 9401 1.59 10.3 12382 2.21 13.2 14135 2.72 15.4 15786 3.28 18.1 17683 4.04 20 19480 4.87 22 10481 2.13 12.9 12945 2.72 15.3 14735 3.3 17.5 16796 4.1 19.3 18651 4.94 21 11013 2.61 15.2 13494 3.28 17.6 15798 4.11 18.7 17822 5.01 21 14692 4.09 18.5 16871 5.01 20 14331 4.88 19.3 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness values in fan sones at 5 feet (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sones. 23 LB/LBP 48 Belt Drive LB Dimensions (2210) 300 1.2 (1041) 58 58 (1473) (1473) (295) 100 4 0.6 1 hp 1/ 2 0.4 50 0.2 0 0.0 0 hp hp hp hp DO LBP Dimensions 32 (1626) (813) 0 36 6 31 2 25 8 20 4 N 15 4 8 0 12 16 20 24 28 cfm X 1000 761⁄2 64 42 TH EL 3/ EF TO FT HIS S 2 RPM HP Density 0.075 lb/ft3 hp TO 1 ⁄4 (44) 2 1/ O 3 150 1 0.8 SE LE CT 11 ⁄8 5 200 hp 1.0 T Static Pressure Pa 411⁄2 (1054) Static Pressure in. wg 3 250 5 YST EM C 41 (1788) URV E 1.4 87 703⁄8 0 10 20 (1943) 403⁄8 (1026) 13⁄4 58 58 (44) (1473) (1473) 30 40 3 m /hr X 1000 Hood Thickness Cover Thickness Louver Thickness Curb Cap Thickness Damper Size Square Roof Opening Square Weight* LB-48 0.064 (0.029) 0.064 (0.029) 48 (1219) 501⁄2 (1283) Galvanized 430 (195) LBP-48 0.064 (0.029) 0.081 (0.036) 0.064 (0.029) 48 (1219) 501⁄2 (1283) Aluminum 579 (263) All dimensions are in inches (millimeters). Weight in pounds (kilograms). *Weight shown is the largest cataloged Open Drip Proof motor. See page 11 for severe duty LBP dimensions. Model Number Motor HP Fan RPM 150 LB/LBP-48-5 1/2 175 199 LB/LBP-48-7 3/4 226 LB/LBP-48-10 1 249 LB/LBP-48-15 1 ⁄2 267 1 285 LB/LBP-48-20 2 314 LB/LBP-48-30 3 359 381 LB/LBP-48-50 5 420 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 0 9666 0.21 6.1 11277 0.34 6.9 12824 0.5 7.6 14563 0.73 8.5 16046 0.98 9.5 17205 1.2 10.6 18365 1.46 12.3 20234 1.96 15.4 23134 2.93 18.4 24552 3.5 20 27065 4.69 23 0.125 6546 0.24 5.4 8948 0.38 5.6 10846 0.56 6.8 12863 0.81 8.2 14530 1.07 9.4 15823 1.31 10.4 17103 1.58 11.7 19141 2.1 14.5 22214 3.1 17.8 23685 3.68 19.6 26278 4.89 23 0.25 CFM / Static Pressure in Inches wg 0.375 0.5 0.625 0.75 0.875 0.9 1 MAX. BHP AT A GIVEN RPM - (rpm/241)3 MAXIMUM FRPM = 420 TIP SPEED = rpm x 12.632 MAX. MOTOR FRAME SIZE = 213T 7629 0.54 7.0 10741 0.83 7.5 12787 1.1 9.2 14222 1.35 10.2 15612 1.63 11.1 17779 2.17 13.4 21041 3.21 17.2 22620 3.81 19.1 25383 5.05 23 10092 1.08 8.3 12151 1.36 9.2 13896 1.66 10.5 16397 2.2 12.5 19878 3.25 16.5 21512 3.87 18.6 24354 5.15 23 11357 1.61 9.6 14665 2.22 12.2 18650 3.29 15.9 20378 3.92 17.9 23363 5.21 22 11934 2.1 11.5 17134 3.31 15.5 19104 3.95 17.4 22317 5.25 22 15069 3.25 14.8 17564 3.95 17.1 21159 5.29 21 11596 2.84 13.4 15491 3.86 16.2 19839 5.31 21 15076 3.85 16.0 19534 5.3 21 18029 5.23 20 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness values in fan sones at 5 feet (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sones. 24 LB/LBP 54 Belt Drive LB Dimensions LBP Dimensions 35 (1778) SY STE H IS FT TO EF TH EL 3 0.0 0 NO 9 18 5 4 13 0 10 15 10 20 (1108) 64 64 (1626) 25 30 35 40 30 40 50 60 3 435⁄8 (1626) 20 m /hr X 1000 (889) 13⁄4 8 29 TO SE LE CT 0.2 0 (2121) (44) 1 34 cfm X 1000 831⁄2 70 40 23 T Static Pressure in. wg Static Pressure Pa hp hp 0.4 DO 0 hp 1 50 0.6 2 (1626) 100 1/ (1626) (318) 0.8 1 64 150 hp (44) 121⁄2 64 200 1.0 2 (1153) 2 hp 45 ⁄8 RPM HP Density 0.075 lb/ft3 1/ 3 250 3 13⁄4 1.2 7 (965) 300 hp (2019) (2210) 5 38 MC UR VE 1.4 87 791⁄2 Hood Thickness Cover Thickness Louver Thickness Curb Cap Thickness Damper Size Square Roof Opening Square Weight* LB-54 0.064 (0.029) 0.064 (0.029) 54 (1372) 561⁄2 (1435) Galvanized 596 (270) LBP-54 0.064 (0.029) 0.081 (0.036) 0.064 (0.029) 54 (1372) 561⁄2 (1435) Aluminum 780 (354) All dimensions are in inches (millimeters). Weight in pounds (kilograms). *Weight shown is the largest cataloged Open Drip Proof motor. See page 11 for severe duty LBP dimensions. Model Number Motor HP Fan RPM 130 LB/LBP-54-10 1 155 206 LB/LBP-54-15 11⁄2 235 LB/LBP-54-20 2 258 277 LB/LBP-54-30 3 296 323 LB/LBP-54-50 5 350 376 LB/LBP-54-75 71⁄2 401 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 0 12159 0.25 4.6 14497 0.42 5.8 19267 0.99 8.7 21980 1.47 11.2 24131 1.95 12.1 25908 2.41 14.1 27685 2.94 17.6 30210 3.82 19.3 32736 4.87 18.9 35167 6.03 22 37506 7.32 25 0.125 11186 0.48 4.9 17356 1.1 8.5 20319 1.6 11.2 22628 2.09 12.5 24517 2.57 13.4 26383 3.11 15.5 29017 4.01 17.8 31634 5.06 19.5 34142 6.25 23 36544 7.54 26 0.25 CFM / Static Pressure in Inches wg 0.375 0.5 0.625 0.75 0.875 1 1.125 MAX. BHP AT A GIVEN RPM - (rpm/198)3 MAXIMUM FRPM = 401 TIP SPEED = rpm x 14.137 MAX. MOTOR FRAME SIZE = 215T 13895 1.12 8.7 17983 1.66 11.3 20831 2.18 13.0 22962 2.68 14.1 25030 3.25 15.2 27789 4.17 17.3 30514 5.25 20 33111 6.45 23 35583 7.77 26 14194 1.6 11.7 17904 2.21 13.3 20554 2.72 14.4 23122 3.31 16.0 26305 4.27 18.4 29312 5.39 21 32039 6.62 24 34583 7.96 27 17326 2.65 13.7 20394 3.34 15.1 24165 4.31 18.3 27766 5.46 22 30716 6.72 25 33500 8.11 28 16072 3.1 13.1 21535 4.29 16.8 25487 5.5 21 29030 6.79 26 32150 8.19 29 17215 4.01 14.7 22974 5.43 19.0 26889 6.82 24 30332 8.24 29 18944 5.13 17.8 24483 6.71 22 28324 8.29 27 20824 6.4 21 26018 8.13 26 22767 7.81 24 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness values in fan sones at 5 feet (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sones. 25 Specifications Direct Drive Specifications Belt Drive Specifications The LD and LDP exhaust fans shall be direct drive type. The fan wheel shall be centrifugal backward inclined, constructed of aluminum and shall include a wheel cone carefully matched to the fan’s venturi for precise running tolerances. Wheels shall be statically and dynamically balanced. The fan shall be constructed of heavy gauge steel or aluminum with a rigid internal support structure and a birdscreen. The LB and LBP exhaust fans shall be belt drive type. The fan wheel shall be centrifugal backward inclined, constructed of aluminum and shall include a wheel cone carefully matched to the fan’s venturi for precise running tolerances. Motors shall be mounted on vibration isolators. Motors shall be readily accessible for maintenance. A disconnect switch shall be factory installed and wired from the fan motor to a junction box within the motor compartment. A conduit chase shall be provided through the curb cap to the motor compartment for ease of electrical wiring. All fans shall bear the AMCA Certified Ratings Seal for Sound and Air Performance. Each fan shall bear a permanently affixed manufacturer’s engraved aluminum nameplate containing the model number and individual serial number for future identification. Fans shall be models LD or LDP as manufactured by Greenheck Fan Corporation in Schofield, Wisconsin, USA. Wheels shall be statically and dynamically balanced. The fan shall be constructed of heavy gauge steel or aluminum with a rigid internal support structure and birdscreen. Motors shall be heavy duty ball bearing type, carefully matched to the fan load, and furnished at the specified voltage, phase and enclosure. Drive frame assembly shall be constructed of heavy gauge steel. Motors and drives shall be mounted on vibration isolators. Motors and drives shall be readily accessible for maintenance. Precision ground and polished fan shafts shall be mounted in permanently sealed, lubricated pillow block ball bearings. Bearings shall be selected for a minimum L10 life in excess of 100,000 hours (L50 average of 500,000 hours) at maximum cataloged operating speed. Drives shall be sized for a minimum of 150% of driven horsepower. Pulleys shall be of the cast type, keyed and securely attached to the wheel and motor shafts. Motor pulleys shall be adjustable for final system balancing. A disconnect switch shall be factory installed and wired from the fan motor to a junction box installed within the motor compartment. A conduit chase shall be provided through the base to the motor compartment for ease of electrical wiring. All fans shall bear the AMCA Certified Ratings Seal for Sound and Air Performance. Each fan shall bear a permanently affixed manufacturer’s engraved aluminum nameplate containing the model number and individual serial number for future identification. Fans shall be models LB or LBP as manufactured by Greenheck Fan Corporation in Schofield, Wisconsin, USA. 26 Specifications Vari-Green® Vari-Green Control - Remote Dial Remote Dial shall be a Vari-Green control specifically designed to provide 0-10 volt DC signal to Greenheck’s Vari-Green Motor. Vari-Green Control - Two Speed Vari-Green® Motor Motor to be an electronic commutation (EC) motor specifically designed for fan applications. AC induction type motors are not acceptable. Examples of unacceptable motors are: Shaded Pole, Permanent Split Capacitor (PSC), Split Phase, Capacitor Start and 3 phase induction type motors. Motors shall be permanently lubricated with heavy-duty ball bearings to match the fan load and prewired to the specific voltage and phase. Internal motor circuitry shall convert AC power supplied to the fan to DC power to operate the motor. Motor shall be speed controllable down to 20% of full speed (80% turndown). Speed shall be controlled by either a potentiometer dial mounted on the motor or by a 0-10 VDC signal. Motor shall be a minimum of 85% efficient at all speeds. Two-speed control shall be a Vari-Green Control specifically designed to allow the Vari-Green Motor to operate at two discrete speeds. Two speed control shall include two dials that may be set at any point between 0 and 10 volts DC and an integral transformer capable of reducing 115/208-240 volt AC power to 24 volt AC power. Vari-Green Control – Constant Pressure Control to be a packaged constant pressure control designed to regulate fan speed based on demand. Control shall include a Proportional Integral Derivative (PID) feedback loop and shall have all components prewired to labeled terminal strips for easy wiring. Fan shall be direct drive including an electronic commutation (EC) Vari-Green Motor. Control package shall be Vari-Green Constant Pressure or Airflow Control. Control with integral pressure transducer shall be a NEMA-4 rated enclosure with built in pressure transducer. The proper pressure/airflow tap for the application shall be supplied. Control with remote pressure transducer shall be a NEMA-4 rated enclosure for both the controller and remote transducer. The proper pressure/airflow tap for the application shall be supplied. LEED information Greenheck became one of the first manufacturers in the Air Movement and Control industry to join the LEED/ green movement when they joined the United States Green Building Council (USGBC) in 2005. Greenheck has been actively researching qualification requirements for our products to meet LEED credits and prerequisites. The Vari-Green motor significantly helps qualification efforts for the Energy and Atmosphere credits and prerequisites; specifically credit one, Optimize Energy Performance and prerequisite two, Minimum Energy Performance. 27 Extraordinary Service Enjoy Greenheck’s extraordinary service, before, during and after the sale. Greenheck offers added value to our wide selection of top performing, energy-efficient products by providing several unique Greenheck service programs. • Our Quick Delivery Program ensures shipment of our in-stock products within 24 hours of placing your order. Our Quick Build made-to-order products can be produced in 1-3-5-10-15 or 25-day production cycles, depending upon their complexity. • Greenheck’s free Computer Aided Product Selection program (CAPS), rated by many as the best in the industry, helps you conveniently and efficiently select the right products for the challenge at hand. • Greenheck has been Green for a long time! Our energy-saving products and ongoing corporate commitment to sustainability can help you qualify for LEED credits. • Our 3D service allows you to download, at no charge, easy-to-use AutoDesk™ Revit™ 3D drawings for many of our ventilation products. Find out more about these special Greenheck services at greenheck.com Building Value in Air Greenheck delivers value to mechanical engineers by helping them solve virtually any air quality challenges their clients face with a comprehensive selection of top quality, innovative airrelated equipment. We offer extra value to contractors by providing easy-to-install, competitively priced, reliable products that arrive on time. And building owners and occupants value the energy efficiency, low maintenance and quiet dependable operation they experience long after the construction project ends. Our Commitment As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties. P.O. Box 410 • Schofield, WI 54476-0410 • Phone (715) 359-6171 • greenheck.com Prepared to Support Green Building Efforts 00.F&V.1001 R6 4-2016 IW Copyright © 2016 Greenheck Fan Corp.