: : 686013 : CTX+R1610230A CONTAX-R+relays 16A 1NO 230Vac EAN13: 5413656860136 Active Series Relays - Contax R+ Rated switching capacity (A) 16A Contact combination 1NO Coil voltage (V) 230 Vac AC/DC AC Coil DC/AC factor 0.5:1 (115 Vdc) Standard packing 12 Standards NBN EN 60947-4-1, CE Number of modules Drive module 1 Number of modules With section power contact 2 Coil Voltage range (in % from Un) 85-110% Electrical life service Mechanical 2 x 10<SUP>6</SUP> controls Reclosing time when closing <10 ms Operating temperature -20°C / 45°C Connection of the lamps 1.5-10 mm² Possible volt/phase Fuse rating (gL) 20 A Possible volt for non-compensated fluor-lamps 900 VA Switching on voltage NO contact <0.040 s Switching on voltage NC contact <0.020 s Switching off voltage NO or NC contact <0.050 s Possible volt/phase Max volt AC-1- Operating mod 3 kW Possible volt/phase Max volt AC-1- Contactbloc 8.5 kW ge.com/ex/industrialsolutions : 30/09/2016 1/2 : 686013 CONTAX-R+relays 16A 1NO 230Vac Possible volt/phase Max volt AC-1- Max volt AC-5b 1.8 kW Possible volt/phase Max volt AC-7b- Operating mod 0.9 kW Possible volt/phase Max volt AC-3- Contatcbloc 1.5 kW/250V 2.2kW/400V Possible volt/phase Min volt per phase (at 5V) 2W Possible volt- sockets & incandes lamps (40 to 200W) 1800 W Possible volt for compensated fluor-lamps- Serie 1800 VA Possible volt for compensated fluor-lamps- Parallel 500 VA Electrical life service Electrical at full voltage AC-1 3 x 10<SUP>5</SUP> controls Coil power-loss - AC 1.8 VA Coil power-loss - DC 2.1 W Coil pick-up power (AC) 3.4 VA Weight 0.118 kg ETIM 5.0 EC001652 ETIM 6.0 EC001652 More info on website • Function: Relays are electromechanically controlled switches used to control low power loads. • Applications: Switching of lighting, heating, etc. Galvanic insulation of i.e. status signalisation lamps from a (high) power (high voltage) circuit. Galvanic insulation of PLC-inputs or outputs to avoid destruction through excessive voltage. • Features: The switch position is visualised by the position of the front handle. The safety terminals are equipped with captive Pozidriv screws and have IP20 protection degree. Add-on auxiliary contacts available. Because of the advanced product design, no spacers are needed. Increased safety: sealing caps for both coil and terminal are available. ge.com/ex/industrialsolutions : 30/09/2016 2/2