TH , Ltd. Heat technology Heat-Economy 3-1/THP-P

advertisement
Heat technology
3-1/THP-P-1
TH , Ltd.
Heat-Economy
THP-P
Automatic steam low pressure boiler burning
gas and liquid fuel with output of 125, 250,
400, 600, 800 and 1200 kW as a standard
product.
Fuel
Natural gas, town gas, liquid gas, fuel oil, light
fuel oil (LFO), heavy fuel oil (HFO).
Type of construction
Three pass with flame tube, cooled returned
chamber, two bundles of fire tubes and a flue
gases collector.
Operating overpressure
Maximum operating overpressure 0,05 MPa.
Safety valves pre-adjusted at 0,07 MPa.
Operating steam temperature
Saturated steam temperature at maximum
operating overpressure is 111.4 °C.
Basic accessories of boiler THP-P
• Steam valve;
• Two-point control of feeding;
• Emergency pressure switch;
• Two control pressure switch;
• Pressure gauge;
• One direct water gauge;
• One safety valve;
• One independent instrument controlling
water level on water line;
• Blow-down valve;
• Burner connecting flange.
Technical data
Boiler
type
Burner
thermal
output
Boiler
therma
output
Boiler
steam
output
Head loss
on flue
gases side
Water
capacity
full
kW
kW
kg/h
Pa
m
167
THP 125 P
290
THP 260 P
445
THP 400 P
667
THP 600 P
889
THP 800 P
1318
THP 1200 P
1800
THP 1500 P
Right of changes reserved
150
260
400
600
800
1200
1560
230
400
600
900
1200
1850
2400
3
110
260
350
440
520
560
670
Water content
up tonormal
water line
3
Operating
weight
2
m
0,79
1,16
1,42
2,35
2,58
2,99
5,76
Heating
surface
m
0,54
0,86
1,12
1,95
2,14
2,56
4,00
3,8
6,4
8,4
14,5
19,3
29,1
43,0
kg
1560
2010
2895
4435
4780
6433
9410
Boiler body
Boiler body consists of cylindrical shaped shell, two bottoms, flame tube with cooled turned chamber
and two bundles of fire tubes that create a convection heating surface. The front turned chamber is
located in boiler cover. The gas-proof boiler cover consists of tilting door with flange for burner fixing.
The door is covered by fire resistant insulation with integrated observation window. The door is tilted
to the armature part installed on boiler sidewall. On the customer request can be boiler delivered in
left, or right variety. The boiler body is completely insulated by double insulation with metal casing.
The boiler insulation parts are supplied separately in disposable package for easier boiler
transportation.
All heating surfaces are easily accessible for cleaning after boiler opening. This assures permanent
high boiler efficiency even in case of long-term liquid fuel firing.
Boiler efficiency and flue gases temperature
Efficiency at nominal output is 91%. Flue gases temperature at nominal output is 190 - 205 °C.
TH , Ltd.
Heat-Economy
THP-P
Heat technology
3-1/THP-P-2
Main boiler dimensions
Boiler type
THP 125 P
THP 260 P
THP 400 P
THP 600 P
THP 800 P
THP 1200 P
THP 1500 P
Boiler type
Body
length
A
mm
1635
1820
1935
2465
2715
3010
4142
Burner
axis
offset
K
mm
THP 125 P
127
THP 260 P
180
THP 400 P
220
THP 600 P
220
THP 800 P
276
THP 1200 P
THP 1500 P
Right of changes reserved
Body
width
B
mm
1200
1300
1450
1700
1700
1850
2000
Burner
axis
L
mm
440
615
637
670
670
855
918
Body
Height of
height
feeding
C
D
mm
mm
1305
850
1355
960
1580
1050
1795
1100
1795
1100
2067
1395
2321
1566
Max.
boiler
width
M
mm
1490
1590
1740
1990
1990
2075
2582
Frame
length
N
mm
1228
1540
1642
2344
2594
2700
1958
Frame
width
P
mm
1100
1208
1350
1600
1600
1750
1616
Steam
Safety
valve
F
mm
300
350
400
430
430
430
1155
Feeding
Steam
Safety
valve
Feeding
d1
DN/PN
65/16
100/16
125/16
150/16
150/16
200/16
200/16
d2
DN/PN
50/16
65/16
80/16
100/16
100/16
125/16
2x100/16
d3
G“
1
1
1
1
1
1
1½
E
mm
540
625
740
860
860
1000
1292
BOILER SCHEME FOR BOILERS THP 125 P – 1200 P
G
mm
555
560
555
655
655
490
1638
Discharge and
blow-off
H
mm
80
100
80
70
70
100
200
Discharge
sludge blowoff
d4
G“
1
1
1
1
1
1
1
Exhaust
J
mm
850
940
1100
1200
1200
1200
363
Flue gases
outlet
d5
mm
130
200
250
250
315
355
450
THP-P
BOILER SCHEME 1500 P
TH , Ltd.
Heat-Economy
Heat technology
3-1/THP-P-3
Download