इंटरनेट मानक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information under the control of public authorities, in order to promote transparency and accountability in the working of every public authority, and whereas the attached publication of the Bureau of Indian Standards is of particular interest to the public, particularly disadvantaged communities and those engaged in the pursuit of education and knowledge, the attached public safety standard is made available to promote the timely dissemination of this information in an accurate manner to the public. “जान1 का अ+धकार, जी1 का अ+धकार” “प0रा1 को छोड न' 5 तरफ” “The Right to Information, The Right to Live” “Step Out From the Old to the New” Mazdoor Kisan Shakti Sangathan Jawaharlal Nehru IS 13947-5-2 (2004): Low-Voltage Switchgear and Controlgear, Part 5: Control Circuit Devices and Switching Elements, Section 2: Proximity Switches [ETD 7: Low Voltage Switchgear and Controlgear] “!ान $ एक न' भारत का +नम-ण” Satyanarayan Gangaram Pitroda “Invent a New India Using Knowledge” “!ान एक ऐसा खजाना > जो कभी च0राया नहB जा सकता ह” है” ह Bhartṛhari—Nītiśatakam “Knowledge is such a treasure which cannot be stolen” IS 13947 (Part 5/See IEC 60947-5-2(1 2): 2004 999) Indian Standard LOW-VOLTAGE SWITCHGEAR AND CONTROLGEAR SPECIFICATION PART 5 CONTROL CIRCUIT DEVICES AND SWITCHING Section 2 Proximity — ELEMENTS Switches ICS 29.1 30.20; 29.120.99 BUREAU MANAK June 2004 OF BHAVAN, IN DIANSTAND” 9 BAHADUR SHAH NEW DELHI 110002 A RDS ZAFAR MARG Price Group 18 Low-Voltage Switchgear and Controlgear Sectional Committee, ET 07 NATIONAL FOREWORD This Indian Standard (Part 5/See 2) which is identical withIEC6C)947-5-2(1999) ‘Low-voltage switchgear and controlgear — Part 5-2: Control circuit devices and switching elements — Proximity switches’ issued by the International Electrotechnical Commission (lEC) was adopted .by the Bureau of Indian Standards on the recommendations of Low-Voltage Switchgear and Controlgear Sectional Committee and approval of the Electrotechnical Division Council. In the adopted standard, certain conventions are, however, not identical to those used in Indian Standards. Attention is particularly drawn to the following: a) Wherever the words ‘International ‘Indian Standard’; and Standard’ appear referring to this standard, they should be read as b) Comma (,) has been used as a decimal marker, while in Indian Standards, use a point (.) as the decimal marker. the current practice is to Only the English language text has been retained while adopting it in this Indian Standard, and as such the page numbers have been given afresh here since they are not the same as in IEC Publication. CROSS REFERENCES In this adopted Indian Standard, reference appears to certain International Standards for which Indian Standards also exist. The corresponding Indian Standards which are to be substituted in their respective places are listed below along with their degree of equivalence for the editions indicated: International Standard Corresponding Indian Standard Degree of Equivalence IEC 60050 — 441 (1984) .International Electrotechnical Vocabulary (IEV) — Chapter 441 : Switchgear, controlgear and fuses IS 1885 (Part 17) :1979 Electrotechnical vocabulary : Part “17 Switchgear and controlgear Equivalent IEC 60068-2-6(1995) Environmental testing — Part 2 : Tests — Test Fc : Vibration (sinusoidal) IS 9000 (Part 8) :1981 Basic environmental testing procedures for electronic and electrical Items : Part 8 Vibration (sinusoidal) test do IEC 60068-2-14(1984) Environmental testing — Part 2 : Tests — Test N : Change of temperature IS 9000 (Part 14): 1988 Basic environmental testing procedures for electronic and electrical items: Part 14Test N: Change of temperature do IEC 60068-2-27(1987) Environmental testing — Part 2: Tests — Test Ea and guidance: Shock IS 9000 (Part 7fSec 6) : 1988 Basic environmental testing procedures for electronic and electrical items: Part 7 Impact test, Section 6 Test Ee : Bounce do IEC 60068-2-30 (1 980) Environmental testing — Part 2 : Tests — Test Db and guidance : Damp heat, cyclic (12 + 12 hour cycle) IS 9000 (Part 5/See 2) : 1981 Basic environmental testing procedures for electronic and electrical Items: Part 5 Damp heat (cyclic) test, Section 2 12 + 12h cycle do (Continued on third cover) IS tEC 13947 (Part 5/See 60947-5-2 2) :2004 (1 999) Indian Standard LOW-VOLTAGE SWITCHGEAR AND CONTROLGEAR — SPECIFICATION PART 5 CONTROL CIRCUIT Section 1 DEVICES AND SWITCHING 2 Proximity ELEMENTS Switches General The provisions of the General Rules in part 1 (IEC 60947-1) are applicable to this standard, where specifically called for. General Rules clauses and subclauses thus applicable, as well as tables, figures and appendices, are identified by references to part 1, e.g. subclause 7.1.9.3 of part 1 or annex C of part 1. Clauses 1 to 8 contain the general requirements. proximity switches are given in annex A. 1.1 Scope Specific requirements for the various types of and object This part of IEC 60947 applies to inductive and capacitive proximity switches that sense the presence of metallic and/or non-metallic objects, ultrasonic proximity switches that sense the presence of sound reflecting objects, photoelectric proximity switches that sense the presence of objects and non-mechanical magnetic proximity switches that sense the presence of objects with a magnetic field. These proximity switches are self-contained, have semiconductor switching elements(s) and are intended to be connected to circuits, the rated voltage of which does not exceed 250 V 50 Hz/60 Hz a.c. or 300 V d.c. This Standard is not intended to cover proximity switches with analogue outputs. The object of this standard – is to state for proximity switches: definitions; classification; — characteristics; – product information; normal service, — constructional – 1.2 mounting and transport and performance conditions; requirements; tests to verify rated characteristics. Normative references The following normative documents contain provisions which, through constitute provisions of this part of IEC 60947. At the time of publication, were valid. All normative documents are subject to revision, and parties on this part of IEC 60947 are encouraged to investigate the possibility recent editions of the normative documents indicated below. Members of registers of currently valid International Standards. IEC 60050(441):1984, International Switchgear, controlgear and fuses IEC 60068-2-6:1995, Environmental Electrotechnical ‘Vocabulary reference in this text, the editions indicated to agreements based of applying the most IEC and ISO maintain (IEV) – Chapter testing – Part 2: Tests – Test Fc: Vibration (sinusoidal) 441: IS 13947 (Part 5/See 2): IEC 60947-5-2 ( 1999) 2004 IEC 60068-2-14:1984, Environments/ testing – Part 2: Tests – Test N: Change of temperature IEC 60068-2-27:1987, Environmental testing – Part 2: Tests – Test Ea and guidance: Shock IEC 60068-2-30:1980, Environmental heat, cyclic (12 + 12 hour cycle) IEC 60364 (all parts), IEC 60446:1989, testing – Part 2: Tests - Test Db and guidance: Damp E/ectrica/ insta//ations of bui/dings Identification of conductors by colours or numerals IEC 60536:1976, Classification against electric shock IEC 60947-1:1996, of electrical and electronic equipment with regard to protection Low-voltage s witchgear and contro/gear - Part 1: Genera/ ru/es IEC 60947-5-1:1997, Low-voltage s witchgear and corttrolgear – Part 5-1: devices ands witching elements – Electromechanical control circuit devices Control circuit IEC 61”000-4-2:1995, Electromagnetic compatibility (EMC) – Part 4: Testing and measurement techniques – Section 2: Electrostatic discharge immunity test – Basic EMC publication IEC 61000-4-3:1995, Electromagnetic compatibility (EMC) - Part 4: Testing and measurement techniques – Section 3: Radiated, radio-frequency, electromagnetic field immunity test IEC 61000-4-4:1995, Electromagnetic compatibility (EMC) - Part 4: Testing and measurement techniques – Section 4: Electrical fast ‘transient\burst immunity test – Basic EMC publication IEC 61020-5-1:1991, Electromechanical s witches for use in electronic equipment Sectional specification for pushbutton switches – Section 1: Bfank detail specification ISO 630:1995, Structura/ stee/s - Plates, wide flats, bars, sections and profiles - Part 5: Is IEC 2 13947 (Part 5/See 60947-5-2 2): 2004 (1 999) Definitions Clause 2 of part 1 applies with the following Alphabetical additions: index of definitions A Adjuster of a proximity switch ................................................................................. Adjuster of a capacitive proximity switch ............................................................ ..... Adjuster of an ultrasonic proximity switch ........... ..................................................... Ambient light for a photoelectric proximity switch .................................................... Assured operating distance (sa). .................. ................................................ ........... Axial approach ..... ................................................................................................... 2.2.15 2.2.15.1 2.2.15.2 2.4.7 2.3.1.7 2.3.3 B Blind zone .......... .................................................................................................... Break function ........................................................................................................ 2.3.1.3 2.4.1.2 c Capacitive proximity switch ..................................................................................... Currents (~ ............................................................................................................. 2.1.1.2 2.4.5 D Damping material ................................................................................................... Differential travel (/-/) .............................................................................................. 2.2.5 2.3.5 E Effective operating distance (sr) .............................................................................. Embeddable proximity switch .................................................................................. Emitter ................................................................................................................... Excess gain for a photoelectric proximity switch ...................................................... 2.3.1.5 2.2.9 2.2.12 2.4.6 F Free zone ............................................................................................................... Frequency of operating cycle (fl .............................................................................. 2.2.4 2.4.3 I Independent (snap) action ...................................................................................... Inductive proximity switch ..................................... ...................................... ............ 2.4.2 2.1.1.1 L Lateral approach .................................................................................................... 2.3.2 M Make function ......................................................................................................... Make. break. or changeover function ..................... .................................................. Maximum operating distance .................................................................................. Minimum operating distance ................................................................................... Minimum operational current ("/m)............................................................................ 2.4.1.1 2.4.1.3 2.3.1 .2.2 2.3.1 .2.1 2.4.5.2 N No-load supply current (/O) ...................................................................................... Non-damping material ............................................................................................ Non-embeddable proximity switch ........................................................................... Non-mechanical magnetic proximity switch ............................................................. 3 2.4.5.3 2.2.6 2.2.10 2.1.1.5 IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 ( 1999) o OFF-state operating Operation current (/r) ................ .............................................................................. distances (s) ................................. .......................................................... of a proximity switch ............................................................................... 2.4.5.1 2.3.1 2.3 P Parts of proximity switches ................................................................................. .... Photoelectric proximity switch ................................................................................. Proximity switch (IEV 441-14-51) ............................................................................ 2.2 2.1.1.4 2.1.1 R Rated operatit?g distance (sn) ................................................................................. Receiver ................................................................................................................. Reference axis ....................................................................................................... Reflector ...................... ................................................................................. ......... Repeat accuracy (~ .............................................................. ................................. Response time proximity switch .............................................................................. 2.3:1.1 2.2.13 2.2.2 2.2.14 2.3.4 2.4.1.4 s Semiconductor switching element ......................................................... .................. Sensing face ..y ...................... ................................................................................ Sensing range (sol).......................... ...................................... .................................. Sound absorbing material ....................................................................................... Sound reflecting material .............................. .......................................................... Standard target ............. ............. ........................................... .. ................................ Switching element characteristics ........................................................................... Switching element function ................................................................... ......... ......... 2.2.1 2.2.11 2.3.1.2 2.2.8 2.2.7 2.2.3 2.4 2.4.1 T Time Total Turn Turn delay before availability (tv) ............................................................................ beam angle ....................................................................... ............................. off time for a photoelectric proximity switch ..................................................... on time for a photoelectric proximity switch ........................................... .......... 2.4.4 2.3.1.4 2.4.1.6 2.4.1.5 u Ultrasonic proximity switch ........ .............................................................................. Usable operating distance (sU) ................................................................................ 2.1 Basic definitions 2.1.1 proximity switch a position switch which is operated [IEV 441-14-51]1) without mechanical 2.1.1.1 inductive proximity switch a proximity switch ‘producing an electromagnetic semiconductor switching element 2.1.1.2 capacitive proximity switch a proximity switch producing an electric switching element 1) see 2.1.1.3 2.3.1.6 IEC 60051)(441). contact field with the moving within field within a sensing a sensing zone part and having zone and having a semiconductor a IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) 2.1.1.3 ultrasonic proximity switch (see figure 2) a proximity switch transmitting and receiving having a semiconductor switching element ultrasound 2.1.1.4 photoelectric proximity switch (see figure 1) a proximity switch which senses objects that either and having a semiconductor switching element waves reflect or interrupt 2.1.1.5 non-mechanical magnetic proximity switch proximity switch which senses the presence of a magnetic swltchlng element and no moving parts in the sensing element 2.2 Parts of a proximity field a sensing visible zone or invisible and light and has a semiconductor switch 2.2.1 semiconductor switching element an element designed to switch the current semiconductor 2.2.2 Reference within of an electric circuit by controlling conductivity of a axis 2.2.2.1 reference axis for inductive, capacitive, non-mechanical magnetic and ultrasonic proximity switches an axis perpendicular to the sensing face and passing through its centre 2.2.2.2 reference axis for types R and D photoelectric proximity switches an axw located midway between the optical axis of the emitter and this of receiver lenses (see figure 1) 2.2.2.3 reference axis for type T photoelectric proximity an axis perpendicular to the centre of the emitter 2.2.3 standard target a specified object sensing distances used for making comparative 2.2.6 non-damping material a material which has negligible measurements on the characteristics influence of the operating of a proximity on the characteristics 5 or switches 2.2.4 free zone a volume around the proximity switch which is kept free from any material the characteristics of the proximity switch 2.2.5 damping material a materi; l which has an influence elements I distances capable switch of a proximity switch and of affecting IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1-999) 2.2.7 sound-reflecting material a material which reflects the ultrasound 2.2.8 sound-absorbing a material with detectable echo material negligible reflecting waves and gives detectable characteristics for 2.2.9 embeddable proximity switch a proximity switch is “embeddable” when any damping sensing face plane without influencing its characteristics d 2.2.10 non-em beddable proximity switch a proximity switch is “non- embeddable” when a specified necessary in order to maintain its characteristics 2.2.11 Sensing echoes ultrasound material waves can which be ,placed free zone around gives around its sensing no the face is face 2.2.11.1 sensing face of an inductive proximity a surface of the proximity switch through switch which the electromagnetic 2.2.11.2 sensing face of a capacitive proximity a surface of the proximity switch through switch which the electric 2.2.11.3 sensing face of an ultrasonic proximity switch a surface of the proximity switch where ultrasound field emerges field emerges is transmitted and received 2.2.11.4 sensing face of a non-mechanical magnetic proximity switch a surface of the proximity switch through which the change in a magnetic 2.2.12 emitter the light source, 2.2.13 receiver the detector, emitter 2.2.14 reflector a specified switches lens and necessary lens and necessary device used to reflect circuitry circuitry field is detected which provide the light beam to monitor the presence light back to the receiver 6 of the light beam from the for type R photoelectric proximity IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 ( 1999) 2:2.15 Adjuster 2.2.15.1 adjuster of a capacitive proximity switch a part of capacitive proximity switch used to set the operating distance. for influence due to target material, transmission medium and installation Its use compensates (mounting) conditions 2.2.15.2 adjuster of an ultrasonic or a photoelectric proximity switch a part of an ultrasonic or a photoelectric proximity switch used to set the operating within the sensing range 2.3 Operation of a proximity 2.3.1 operating distances (s) a distance at which the target the output signal to change distance switch approaching the sensing face along the reference axis causes 2.3.1.1 rated operating distance (sn) the rated operating distance is a conventional quantity used to designate the operating distances. It does not take into account either manufacturing tolerances or variations due to external conditions such as voltage and temperature 2.3.1.2 sensing range (sol) the range within which the operating distance may be adjusted 2.3.1 .2.1 minimum operating distance the lower limit of the specified sensing range of an ultrasonic”or 2.3.1 .2.2 maximum operating distance the upper limit of the specified sensing range of an ultrasonic 2.3.1.3 blind zone the zone between be detected the sensing 2.3.1.4 total beam angle the solid angle around level drops by 3 dB face and the minimum the reference proximity switch or photoelectric proximity switch operating axis of an ultrasonic 7 photoelectric distance, proximity where no object switch, where can the sound IS 13947 IEC (Part 5/See 2) :2004 60947-5-2 (1 999) ~“n’e’’’---m Figure1a - Type T, emitterand receiver- Trough beam photoelectric % Blind zone for reflector --h- ‘ Figure1b - Type R, emitter-receiver-andreflectw- Retroreftactwephotoelectric G::::=EEZI 1. I % Blind zone for reflector -+- Figure1c - Type D, emitter-receiverand object- Oiffusereflectivephotoelectric Figure 1- Sensing range (sol) photoelectric proximity switches (see 7.2.1.3 and 8.4) 2.3.1.5 effective operating distance (sr) the operating distance of an individual voltage and mounting conditions 2.3.1.6 usable operating distance (su) the operating distance of an individual ~roximity proximity 2.3.1.7 assured operating distance (sa) the distance from the sensing face within under specified conditions is assured 2.3.2 lateral approach the approach of the target perpendicular switch, switch, measured measured which the correct to the reference 2.3.3 axial approach the approach of the target with its centre maintained at stated under specified operation conditions of the proximity axis on the reference temperature, axis switch IS IEC 2.3.4 repeat accuracy (1?) the value of variation of the effective operating distance Switching 2.4.1 switching element element (Part 5/See 60947-5-2 (sJ under specified 2.3.5 differential travel (H) the distance between the operating point when the target the release point when the target moves away 2.4 13947 approaches 2) :2004 ( 1999) conditions the proximity switch and characteristics function 2.4.1.1 make function a make function causes load current flow when a target is not detected 2.4.1.2 break function a break ‘function causes load current flow when a target is not detected to flow when a target not to flow when a target 2.4.1.3 make-break, of changeover function a switching element combination which contains 2.4.1.4 response time for a proximity switch the time required for the device switching the sensing zone element to respond 2.4.1.6 turn off time for a photoelectric proximity switch the time required for the switching element to respond with excess gain of 0,5 (see 2.4.6) substantially 2.4.3 frequency of operating cycles (f) number of operating cycles performed independent by a proximity and load current is detected one make function 2.4.1.5 turn on time for a photoelectric proximity switch the time required for the switching element to respond with excess gain of 2 (see 2.4.6) 2.4.2 independent (snap) action a switching element function is detected not to and load current and one break function after the target enters or exits after the target enters the sensing range after the target exits the sensing range from the velocity of the target switch during a specified period of time 2.4.4 time delay before availability (tv) the time delay before availability is the time between the switching on of the supply voltage the instant at which the proximity switch becomes ready to operate correctly 9 to and IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) 2.4.5 Currents (/) 2.4.5.1 off-state current (Ir) the current which flows through the load circuit of the proximity 2.4.5.2 minimum operational current (Im) the current which is necessary to maintain 2.4.5.3 no-load supply current (/.) the current drawn by a three connected to a load ON-state or four-terminal conduction proximity 2.4.6 excess gain for a photoelectric proximity switch the ratio of the light received by the photoelectric operate the photoelectric proximity switch 2.4.7 ambient light for a photoelectric for the purpose of this standard, that originating from the emitter switch in the OFF-state of the switching switch proximity switch proximity switch ambient light is the light received Blind zone from Sen;ing range element its supply to the light by the receiver when required Total beam angle Reference axis i Figure 2- Ultrasonic proximity 10 switch operating distances to other than -1 Maximum operating distance not Table 11st ps.11 digit SENSING 2nd pos.11 digit MEANS 3.1 . I Classification 3rd pos./3 digits of proximity switches 4th pos.11 digit MECHANICAL INSTALLATION 3.2 CONSTRUCTION FORM AND SIZE 3.3 SWITCHING ELEMENT FUNCTION (OUTPUT) 3.4 5th pos.11 digit 6th pos.11 digit 3.5 METHOD OF CONNECTION 3.6 TYPE OF OUTPUT i = induchve 1 = embeddable FORM (1 capital letter) A = NO (make) P = PNP-output 1 = integral leads C = capacitive 2 = non-embeddable A = cylindrical B = NF (break) 3 or 4 terminal d.c. 2 = plug-in U = ultrasonic 3 = either threaded barrel C = changeover N = NPN-output 3 = screw 9 = other D = diffuse reflective photoelectric B = cylindrical smooth barrel M = non-mechanical magnetic C = rectangular with square cross-section R = retroreflective photoelectric D = rectarigular with rectangular cross-section T = through beam photoelectric DIMENSION (make-break) 3 or 4 terminal d.c. P = programmable D = 2 terminal d.c. by user F = 2 terminal a.c S = other U = 2 terminal a.c. or d.c. (2 numbers S = other for diameter or side length Ultrasonic proximity switch example: u 3 A30 A D 2 Ultrasonic Either Cylindrical threaded NO (make) function 2 terminal d.c. Plug in 030 mm IS 13947 IEC 3 (1 999) Classification Proximity table 1. 3.1 switches according the sensing Classification to various by a capital to the mechanical is designated according general characteristics letter designates installation by one digit in the second position. to the construction the construction The two numbers designate side for rectangular types. 3.4 Classification form and size The switching 3.5 element Classification element is designated by a capital function according Classification according The method of connection 4 4.1 one capital types or a length letter placed in the fourth to method is designated letter and placed in the fifth position. of connection by a one-digit number placed in the sixth position. of characteristics The characteristics Operating of a proximity conditions Rated and limiting Rated voltages Currents (4.3) (4.3.1 ) (4.3.2) Rated supply frequency (4.3.3) Frequency cycles Normal switch shall be stated (4.2) values of operating load and abnormal Short-circuit Utilization characteristics categories position. to type of output by a capital (4.3.4) load characteristics (4.3.5) (4.3.6) for the switching element 12 of one function Characteristics Summary letter and two or rectangular. of cylindrical to switching The type of output is designated 3.6 form, e.g. cylindrical the size, e.g. the diameter according in letter in the first position. The construction form and the size are designated by three digits, numbers. This three-digit designation is placed in the third position. The capital as shown means means is designated installation Classification according to sensing according The mechanical 3.3 are classified Classification In this standard 3.2 2) :2004 (Part 5/See 60947-5-2 (4.4). in the following terms. IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) 4.1.1 Operation of an inductive or capacitive proximity switch The output signal is determined by the presence or absence of a designated object in the electromagnetic or electric field which absorbs or alters energy radiated from the sensing face. 4.1.2 Operation of an ultrasonic proximity switch The output signal is determined by the presence or absence of a designated sensing zone which reflects ultrasound energy radiated from the sensing face. 4.1.3 Operation of a photoelectric proximity Operating 4.2.1 Operating The relationship 4.2.1.1 4.2.2 Operating The relationship distance(s) between distances the operating distance and capacitive distances of an ultrasonic the operating switches range values are given in the relevant annexes. proximity distances Sensing switch is shown in figure 4. range (sd) Operating distance(s) Sensing range (sJ For photoelectric proximity is shown in figure 3. in the relevant Sensing 4.2.3.1 that either (sn) are specified distance(s) between of inductive 4.2.2.1 4.2.3 object conditions Rated operating Rated operating in the switch The output signal is determined by the presence or absence of a designated reflects or interrupts visible or invisible light radiated from the emitter. 4.2 object proximity annexes. of a photoelectric switches the operating proximity distances 13 switch are given as the sensing range (sd). IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 ( 1999) Reference axis . . . . . . . .<’+ .......... ...... ..[u I % msx s~ ~~~ sn Standard target 1 . —; sr mm 1. sumax+H I .. I Sr mex +H k ~+H Assured operating armin+H . . . . . ..i“” 1. . . . . . . su min J , ......... ...... i Sa sumin+H Sensing face / I Proximity switch Figure 3- Relationship between operating distances of inductive and capacitive proximity switches (see 4.2.1, 7.2.1.3 and 8.4.1) -. .;....... ..... ----.... 1i.. tieterence axis I smax Effective operating distance -% Minimum operating distance I ~a+H Maximum operating distance Assured operating distance I Standard target ... , % %nm “J ~in+H I p r Figure 4- +d Ultrasonic proximity ‘witch Relationship between operating distancea of ultrasonic switches (see 4.2.2, 7.2.1.3 and 8.4.1) 14 proximity IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1999) 4.3 Rated and limiting 4.3.1 values for the proximity switch and switching element(s) Voltages The proximity 4.3.1.1 switch and its switching Rated operational voltage element(s) are defined by the following rated voltages: (UJ The rated operational voltage NOTE The manufacturer range shall be designated may state a range between the limiting values which include all the tolerances Ue. The relationship between (Ue) (or range) shall not exceed 250 V a.c. or 300 V d.c. Ue and U~ is shown below: , ..... ..EE5E*H4.....-.* u~ L u~~ln- 15-% 4.3.1.2 Rated Uemax+ lo% voltage insulation (Ui) The rated insulation voltage of a proximity switch is the value of voltage voltage tests and creepage distances are referred. For proximity switches insulation voltage. 4.3.1.3 the highest Rated impulse When the rated applies. impulse 4.3.1.4 drop Voltage of U,, this rated operational withstand voltage withstand voltage voltage to which the dielectric shall be considered to be the rated (UimP) is declared by the manufacturer, 4.3.1.3 of part 1 (Ud) The voltage drop is the voltage measured across the active output of the proximity switch when carrying the operational current flows under specified conditions. The values are specified in 7.2.1.15. 4.3.2 Currents The proximity 4.3.2.1 See7.2.1 4.3.2.2 switch and its switching Rated operational current element are defined (/e) .11. Minimum operational current (/m) See 7.2.1.12. 15 by the following currents. IS 13947 (Part 5/See IEC 60947-5-2 4.3.2.3 2): 2004 (1999) OFF-state current (Ir) See 7.2.1.13. 4.3.2.4 No-load supply The no-load supply manufacturer. 4.3.3 current current (/.) of a three- or four-terminal proximity shall be stated by the Rated supply frequency The rated supply frequency 4.3.4 Frequency 4.3.5 Normal 4.3.5.1 shall be 50 Hz and/or 60 Hz. of operating The frequency of operating by the manufacturer. cycles (f) cycles load and abnormal shall be in accordance element with the relevant capacities and behaviour shall comply with the requirements Making A switching and breaking element capacities under abnormal shall comply with the requirements Short-circuit 4.3.6.1 element it is not nacessary to specify separately given in table 5. it is not necessary to specify separately characteristics Rated conditional short-circuit current The rated conditional short-circuit current proximity switch shall withstand satisfactorily Utilization of switching conditions NOTE For a switching element to which a utilization category is assigned, a making and breaking capacity. 4.3.6 or stated given in table 4. NOTE For a switching element to which a utilization category is assigned, a making and breaking capacity. 4.3.5.2 annexes load characteristics Rated making and breaking under normal conditions A switching 4.4 switch categories of a proximity switch is 100 A prospective. the test specified in 8.3.4. for the switching The element The utilization categories as given in table 2 are considered standard. Any other type of application shall be based on agreement, between manufacturer and user, but information given in manufacturer’s catalogue or tender may constitute such an agreement. 16 IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) Table 2 – Utilization Kind of current Catagory Alternating current AC-12 categories for switching elements Typical application Control of resistive loads and solid state loads with optical isolation AC-140 Control of small electromagnetic (closed) current s0,2 A: loads with holding e.g. contactor relays Direct current 5 5.1 Product DC-12 Control of resistive loads and solid state loads with optical isolation DC-13 Control of electromagnets information Nature of information The following information shall be given by the manufacturer. 5.-1.1 Identification a) The manufacturer’s name or trade mark. b) A type designation or other marking which makes it possible to identify the proximity switch and get the relevant information from the manufacturer or his catalogue (see table 1). c) Reference to this standard if the manufacturer claims compliance. Basic rated values and utilization d) Rated operational voltage(s) (see 4.3.1.1 ). currents e) Utilization category and rated operational rated frequency/frequencies or at direct current, d.c. f) Rated insulation voltage 9) Rated impulse withstand h) IP code (see 7.1.10). i) Pollution degree (see 4.3.1 .2). voltage (see 4.3.1 .3). (see 6.1.3.2). j) Type and maximum ratings of short-circuit protective k) Rated conditional short-circuit current (see 4.3:6.1). 1) Electromagnetic m) Operating compatibility distances n) Repeat accuracy o) Differential at the rated operational device (see 7.2.5). (EMC) (see 7.2.6). (see 7.2.1 .3). (see 7.2.1 .4). travel (see 7.2.1 .5). P) Frequency of operating cycles (see 7.2.1 .6). r) Minimum operational current (see 7.2.1 .12). s) OFF-state t) No-load current (see 7.2.1 .13). supply current (see 4.3.2.4). u) Voltage drop (see 7.2.1.1 5). v) Switching w) Mounting x) Physical element function application, dimensions (see 2.4.1). embedctable or non-embeddable (see 7.3). y) Excess gain (see 7.2.1 .10). 17 (see 2.2.9 and 2.2.10). voltages and IS 13947 (Part 5/See IEC 60947-5-2 5.2 2) :2004 (1 999) Marking 5.2.1 General Marking of data under a) and b) of 5.1.1 is mandatory on the nameplate or marked on the body of the proximity switch in order to permit the complete information to be obtained from the manufacturer. Cylindrical proximity switches of 12 mm or smaller body diameter may provide this marking on the cord or on a tag permanently attached to the cord, located no further than 100 mm from the body of the device. Marking shall be indelible removable in service. and Data under c) to y) when manufacturer’s literature. not included 5.2.2 Terminal Subclause 5.2.3 identification 7.1.7.4 Functional Instruction legible, and on the shall not proximity be placed switch, shall be marked for installation, where operation shall indicate 6 service, mounting service conditions Normal be included in the markings The above documents any. 6.1 normally and marking this is not apparent Proximity switches complying following standard conditions. the recommended and transport with this by the construction of the and maintenance The manufacturer shall specify in his documents or catalogues operation and maintenance of the proximity switch. Normal shall on parts applies. The sensing face proximity switch. 5.3 easily the conditions extent and frequency for installation, of maintenance, if conditions standard shall be capable of operating under the NOTE If the conditions for operation differ from those given in this standard, the user shall state the deviations from the standard conditions and consult the manufacturer on the suitability for use under such conditions. 6.1.1 6.1.1.1 Ambient air-temperature Inductive, proximity capacitive, switches non-mechanical magnetic and ultrasonic These proximity switches shall operate between the ambient temperatures of -25 ‘C to +70 “C. The operating characteristics shall be maintained over the permissible range of ambient temperature. NOTE For ultrasonic proximity switches, due to the temperature, the operating distance may change by 0,17 fact that the per kelvin. speed of sound is dependent upon air ‘). i 18 IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) 6.1.1.2 Photoelectric proximity switch Photoelectric proximity switches shall operate to +55 ‘C. The operating characteristics shall ambient temperature. 6.1.2 between the ambient temperatures be maintained over the permissible of -5 ‘C range of Altitude Subclause 6.1.3 6.1.2 of part 1 applies. Climatic 6.1.3.1 conditions Humidity The relative humidity (RH) of the air shall not exceed 50 % at 70 “C. Higtrer relative are permitted at lower temperatures, e.g. 90 ?4. at +20 “C. humidities NOTE Condensation on the sensing face and the change of humidity may influence the operating distances. Care should be taken of condensation which may occur due to variations in temperature. (50 V. RH at 70 “C equivalent to 100 % RH at 54 ‘C). 6.1.3.2 Pollution degree Unless otherwise stated by the manufacturer, a proximity switch is intended for installation under environmental conditions of pollution degree 3 as defined in 6.1 .3.2 of part 1. However, other pollution degrees may apply depending upon the micro-environment. 6.2 Conditions during transport and storage A special agreement shall be made between the user and the manufacturer if the conditions during transport and storage, e.g. temperature and humidity conditions, differ from those defined in 6.1. 6.3 Mounting Mounting dimensions annex A. 7 Constructional 7.1 7.1.1 and conditions and Constructional shall be according performance to the relevant specification sheet of requirements requirements Materials Materials shall be suitable for the particular comply with the relevant test requirements. Special attention to protect certain application shall be called to flame and humidity insulating materials against humidity. NOTE Requirements 7.1.2 Current-carrying and shall resisting enable the equipment qualities, and to the necessity strength and are under consideration. parts and their connections Current-carrying parts shall have capacity for their intended use. the necessary mechanical to current-carrying IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1999) For electrical connections, no contact pressure shall be transmitted through insulating material other than ceramic or other material with characteristics not less suitable, unless there is sufficient resiliency in the metallic parts to compensate for any possible shrinkage or yielding of the insulation material. 7.1.3 Clearances and creepage-distances When the manufacturer declares a rated impulse withstand voltage, part 1 apply. If no value for UimP has been declared, the requirements 7.1.4 Uim , tables 13 and 15 of of }.2.3 apply. Actuation Proximity switches the characteristics 7.1.5 Vacant 7.1.6 Vacant 7.fl.7 Terminals 7.1.7.1 Constructional Subclause 7.1.7.2 7.1.7.1 7.1.7.3 capacity means may have integral connecting additions. leads; in this case the outer sheath of the leads shall be 2+$1 m long. Connection Subclause target, requirements of part 1 applies with the following switches Proximity connecting of the standard of part 1 applies. Connection Subclause 7.1.7.4 7.1.7.2 or absence of part 1 applies. -Connecting Subclause 7.1.7.3 are tested for operation by the presence of which are specified in 8.3.2.1. 7.1.7.4 identification and marking of part 1 applies with the following Proximity according switches with to table 3. Proximity switches integral with terminal connecting connections leads additions. shall have shall be identified 20 wires according identified with to table 3. colours IS 13947 (Part 5/See 2): IEC 60947-5-2 (1 999) Table 3 – Connection Type I Function 2 terminals a.c. and and wiring identification Wire Wire colour + Brown Blue I Terminal nutnber,~ NO (make) NC (break) 2 terminals d.c. unpolarized NO/NC programmable NO (make) 2 terminals d.c. polarized NC (break) NO (make) + — Brown Blue Black 1 3 4 Brown Blue Black 1 3 2 Brown Blue Black 1 3 4 Brown Blue Black 1 3 2 Brown Blue Black White 1 3 4 2 output L 3 terminals a.c. and NO (make) output a.c Jd.c. .L NC (break) output + 4 terminals d.c. polarized Change over (make/break) 1 4 Brown Blue + NC (break) I + — output 3 terminals d.c. polarized 3 terminals polarized 2004 NO output NC output I 1) It is recommended z) Terminal numbers (except for a.c. proximity switches and proximity switches 8 mm connector) shall be the same as integral connector pin numbers. 1 2 that both wires are of the same colour. I using 3 terminals I The bi-colour of green-and-yellow (green/yellow) shail be used only to identifv the Protective conductor (IEC 60446). To rnaintain-histo~ic integrity of earth secu~ity, the coiour g~een shall not be used for any other purpose than to identify the protective earth conductor. 7.1.8 Vacant 7.1.9 Provisions 7.1.9.1 for protective Constructional Subclause 7.1.9.1 earthing requirements of part 1 applies with the following NOTE 1 For proximity switches having class II insulation, connected to the protective earth terminal (see IEC 60536). NOTE 2 Proximity switches with maximum provision for protective earthing. rated voltages addition. the outside not exceeding metal enclosure is not required either 50 V a.c. or 120 V d.c. need no Consideration must be given to the safety insulation of the supply and its transformer accordance with the installation rules (see IEC 60364). 21 to be (if any) in IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) 7.1.9.2 Protective Subclause 7.1.9.2 7.1.9.3 earth terminal of part 1 applies. Protective earth terminal marking and identification Subclause 7.1.9,.3 of part 1 applies. 7.1.10 Degree of protection Proximity switches, when installed in accordance with the -manufacturer’s instruction shall have minimum IP65 protection, except for photoelectric switches which shall have minimum IP54 protection and shall be verified according to 8.2. NOTE During the test for the degree of protection the operation of the proximity switch is not required. 7.1.11 Requirements for proximity switches with integrally connected cables See annex C. 7.1.12 Class II proximity switches These devices shall not be provided with means for protective earthing (see IEC 60536). For class II proximity 7.2 Performance switches 7.2.1.1 Operating by encapsulation, apply to clean new equipment. conditions General The equipment shall be mounted in accordance with specification sheet (annex A) or by the manufacturer. For the tests of 7.2.1.3 through 7.2.1.2 see annex B. requirements The following requirements 7.2.1 insulated Operating The proximity 7.2.1.6 the load shall be adjusted given in the relevant to provide 0,2 le. limits switch shall operate a) between 85 % and 110 b) between 85 Y. the instructions 9!o satisfactorily of Ue, or Ue ~in and 110 !Yo of Ue ~ax, or c) over the range UB. For d.c., the value of the ripple voltage 7.2.1.3 Operating (pea~ to peak) shall not exceed 0,1 Ue (see 4.3.1 .1). distances The operating distances are measured according to 8.4. The operating distances when the target is moving towards the proximity switch in an axial approach. 22 are stated IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) For inductive and capacitive distances is shown in figure 3. For ultrasonic figure 4. proximity For photoelectric in figure 1. 7.2.1 .3.1 switches, proximity Effective proximity the relationship switches, operating switches, is relationship between the relationship distance The effective operating distance temperature of 23 “C * 5 “C. the between the operating between the distances the operating operating is shown distances in is shown (sr) measured For inductive and capacitive proximity rated operating distance (sn): at the switches rated voltage it shall be between and at an ambient 90 % and 110 % of the o,9sn<srsl,lsn — For ultrasonic proximity switches maximum operating distances: it shall be any distance between the minimum and Smin < Sr < Smax 7.2.1 .3.2 Usable operating distance (su) Usable operating distance is measured over the ambient voltage at 85 YO and 110 Y. of their rated value. — For inductive and ultrasonic effective operating distance proximity (sr): switches, temperature it shall be between range and the supply 90 % and 110 % of the o,9sr<su<l,lsr — For capacitive proximity operating distance (sr): switches, it shall be between 80 9’o and 120 Y. of the effective 0,8srssUSl,2sr 7.2.1 .3.3 Assured operating distance (sa) — For inductive proximity switches, the assured operating distance is between O of the rated operating distance Sn: Y. and 81 Y. ?. and 72 YO o<saso,9xo,9sn For capacitive proximity switches, the assured of the rated operating distance Sn: operating distance proximity switches ()<5a<(),9xo,8sn 7.2.1 .3.4 Sensing range (sJ for photoelectric The sensing range is measured The sensing range is shown: according to 8.4. in figure 1 la for type T: emitter and receiver, in figure 11 b for type R: emitter, receiver and reflector, in figure 1lC for type D: emitter, receiver and object. 23 is between O IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) The sensing range is stated by the manufacturer according to the test method specified in 8.4.2. 7.2.1 .3.5 Sensitivity proximity and operating switches distances for O lx and 5 000 of non-mechanical For non-mechanical magnetic proximity switches, the operating their tolerances shall be declared by the manufacturer. 7.2.1.4 Repeat accuracy lx of ambient-light magnetic sensing characteristics and (1?) The repeat accuracy of the effective operating distance (sJ is measured over an eight hour period at an ambient temperature of between 23 ‘C * 5 “C at a relative humidity of any value in the range of 6.1.3.1 to a tolerance of *5 % and with a specified supply voltage. The difference between operating distance (sr): any two measurements ~< 7.2.1.5 Differential shall not exceed 10 % of the effective 0,1 s, travel (H) The differential travel is given as a percentage of the effective operating distance (sr). The measurement is made in accordance with 8.4.1.3 at an ambient temperature of 23 “C A 5 ‘C and at the rated supply voltage. It shall be less than 20 Y. of the effective operating distance (sr): /+< 0,2 Sr 7.2.1.6 Frequency 7.2.1 .6.1 Inductive, of operating capacitive cycles (f) and ultrasonic proximity The frequency of operating cycles shall be in accordance be measured according to 8.5.1 and 8.5.2. 7.2.1 .6.2 Photoeiect~ic The frequency proximity of operating switchas with the relevant annexes and shall switch cycles (f) is determined ‘= from the formula: bn;~fi where ton is the turn on time; tofl is the turn off time; and shall be stated by the manufacturer; to.and to~, shall be measured 7.2.1.7 according Time delay before availability The time delay before availability to 8.5.3. (tv) (Start-up shall not exceed time) 300 ms. During this time the switching element shall not give any false signal. A false signal is a signal other than zero which appears for longer than 2 ms (see 8.3.3.2.1). NOTE Zero signal means that only OFF-state current flows through the load. 24 I IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) 7.2.1.8 Turn on time (ton) The turn on time and the measuring method shall be stated by the manufacturer. 7.2.1.9 Turn off time (toti) The turn off time and the measuring 7.2.1.10 Excess method shall be stated by the manufacturer. gain, photoelectric proximity switch The excess gain and the measuring method shall be stated by the manufacturer. 7.2.1.11 Rated operational current (IJ The rated operational current shall be: 50 mA d.c. or 200 mA a.c. r.m.s. Greater values may be agreed 7.2.1.12 Minimum The minimum upon between operational operational current current manufacturer (Im) shall be: 2 terminals /m <5 mA d.c. or a.c. r.m. s. 3 or 4 terminals /m <1 mA d.c. and verified 7.2.1.13 according OFF-state and user. to 8.3.3.2.2. current (Ir) The maximum current (/r) which flows through the load circuit of a proximity switch in the OFFstate shall be: /r s 1,5 mA d.c. or 2 terminals /r s 3 mA a.c. r.m.s. /rs 0,5 mA d.c. 3 or 4 terminals and verified 7.2.1.14 according Switching The switching to 8.3.3.2.4. 7.2.1.15 element element Voltage The voltage to 8.3.3.2.3. operation shall be independent according to 8.3.3.2.5 U~ <8 V d.c. or U~ <10 V a.c. r.m.s. 3 or 4 terminals action drop (Ud) drop measured 2 terminals operation Ud <3,5 V d.c. 25 shall be: and shall be verified according IS 13947 (Part 5/See IEC 60947-5-2 7.2.2 Temperature Subclause 2) :2004 (1 999) rise 7.2.2 of part 1 applies with the following additions. The temperature rise limit f-or proximity switches is 50 K. This temperature exterior of enclosure, metailic or non-metallic materials, and for terminals. 7.2.3 Dielectric The proximity switch shall be capable Impulse The minimum switches voltage test voltage of withstanding insulated by encapsulation, generator and breaking a) Making and breaking in 8.3.3.4. see annex B. are: 1,2/50 ps impulse; it is permissible Ability to make and break under normal Making tests specified shall be 1 kV. NOTE For ~roximity devices with sizes below M12 protection components to achieve this requirement. 7.2.4.1 the dielectric withstand The characteristics of the impulse source energy: 0,5 J. 7.2.4 for the properties For class II proximity 7.2.3.1 rise applies source impedance: for the manufacturer load and abnormal to specify 500 Q; external load conditions capacities capacities under normal conditions The switching elements shall be capable of making and breaking currents without failure under the conditions stated in table 4, for the relevant utilization categories and the number of operations indicated, under the conditions specified in 8.3.3.5. b) Making and breaking capacities under abnormal conditions The switching elements shall be capable of making and breaking currents without failure under the conditions stated in table 5, for the relevant utilization categories and the number of operations under the conditions specified in 8.3.3.5. 26 IS 13947 (Part IEC 60947-5-2 Table 5/See 2) :2004 (1 999) 4 – Verification o.f making and breaking capacities of switching elements under normal conditions corresponding to the utilization categories 1, ‘Normal Mske ‘) conditions of use Bresk 2, Number and rate of operations for make snd break Utilization I T category Ille AC-12 AC-140 DC-13 1 1 6 1 1 1 1 1 1, = rated operational u, = rated operational / = u = P = TOw = Cos q) Ulue Ille i- Number of operations or To,g5 T0,95 l-- DC-12 Coa q or U/ue 0,9 1 1 0,3 1 Operations per minute ON-time ms 3) 0,9 6050 6 50 1 0,3 6050 6 20 1 1 ms 61350 6 1 1 6 Pm. 4) 6050 6 T0,95 current voltage current to be made or broken voltage before make Ue/, = steady-state power consumption time to reach 95 ‘A of the steady-state current, In milliseconds 1) See 8.3.3.5 2) For tolerances 3) The first 50 operations 4) The value “6 x P results from an empirical to and upper I]mit of P = 50 W. Table on test quantities, see 8.3.2.2 shaft be run at U/Ue = 1,1 with the loads set at U, relationship which is found to represent most d.c, magnetic loads up 5 – Verification of making and breaking abnormal conditions corresponding capacities of switching elements to the utilization categories 1, under Conditions anormalea d’emploi z) Utilization cate-gory Make and breaks) Ul”ue Ille 4) 6 DC-12 1,1 See note 0,7 10 Operations per minute ON-time ms 6 20 5) rated operational current voltage = current to be made or broken = voltage before make /, = U, = rated operational U Number of operations Not applicable DC-13 / Cos p Not applicable AC-12 AC-1-4O Number and rate of operations for make and break NOTES 1) See 8.3.3.5. 2) The abnormal condition is to simulate a blocked open electromagnet. 3) For tolerances 4) An overload conditions, on test quantities, 5) This test is covered by the test performed according to table 4, note 3. protection device see 8.3.2.2. specified by the manufacturer 27 may be used to verify the abnormal IS 13947 IEC (Part 5/See 60947-5-2 7.2.5 2) :2004 (1999) Conditional short-circuit current The switching element shall withstand the stresses conditions specified in 8.3.4. 7.2.6 Electromagnetic compatibility The operating characteristics electromagnetic interferences manufacturer. resulting from short-circuit currents under (EMC) of the proximity switch shall be maintained at all levels of (EMI) up to and including the maximum level stated by the The proximity device to be tested shall have all the essential represents and shall be in a clean and new condition. design details Maintenance cycle is not permitted. 7.2.6.1 or replacement Radiated In accordance 7.2.6.2 electromagnetic field strength Electrostatic discharge be applied test voltage 7.2.6.3 (ESD) immunity test voltage by the contact discharge method to proximity devices with shall be 4 kV. The test voltage shall be applied metallic enclosures. The minimum MHz. with IEC 61000-4-2. The test voltage shall metallic enclosures. The minimum field immunity shall be 3 V/m. band: 80 MHz to 1000 In accordance by the air gap discharge method to proximity devices with non shall be 8 kV. Fast “transient immunity “In accordance with IEC 61000-4-4. The minimum test voltage For process industry shall be 1 kV. and when cables are longer than 2+%1 m the minimum test voltage shall be 2 kV. 7.2.6.4 it with IEC 61000-4-3. The minimumlest Frequency of parts during or after a testing of the type which Surge immunity For proximity devices it is not necessary to test for surge immunity. The operating environment of these devices is considered to be well protected against surge voltages caused by lightning strikes. 28 IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) 7.2.6.5 Immunity Provisionally 7.2.6.6 7.2.7.1 and until further Immunity Provisionally 7.2.7 to conducted to voltage and until further Emission disturbances induced by RF fields study no tests are required. dips study no tests are required. requirements Conditions during measurement The measurement shall be made in the operating mode producing the highest emission in the frequency band being with normal applications (see clause 4). Each measurement shall be performed in defined including grounding conditions investigated which is consistent and reproducible conditions. Descriptions of the tests, test methods and setups are given in the standards listed in table 7. The contents of these standards are not reproduced here, however modifications or additional information needed for the practical application of the tests are given here. Proximity devices which are intended to be powered by public mains supply, therefore within the scope of IEC 61000-3-2 and IEC 61000-3-3, regarding low frequency emission shall also comply with the requirements of these standards. 7.2.7.2 Emission limits Table 7 gives the limit values for proximity devices installed in normal service conditions. Table 7Port Emission limits for proximity devices Limits Frequency range 30 MHz to 230 MHz Standard 40 dB (pV/m) quasi peak, measured at 10 m distance Enclosure 230 MHz to 1 000 MHz 47 dB (pV/m) quasi peak, measured at 10 m distance 0,15 MHz to 0,50 MHz 79 dB (pV) quasi peak 66 dB (pV) average 0,50 MHz to 30 MHz 73 dB (pV) qwesi peak 60 dB (pV) average AC power These limits are given for proximity devices exclusively used (environment 2). W;en they may be used in domestic environment, be included in the instructions for use: CISPR 11 CISPR 11 in industrial the following environment warning shall Warning This is a class A product. In a domestic environment this product may interference in which case the user may be required to take adequate measures. 29 cause radio IS 13947 (Part IEC 60947-5-211 7.3 Physical 5/See 2) :2004 999) dimensions Proximity switches with standardized specification sheet (annex A). NOTE 7.4 physical dimensions are given in the Proximity switches with other dimensions are also covered by this standard. Shock and vibration Shock 7.4.1 In accordance with Six shocks applied IEC 60068-2-27 with the following in each direction along three mutually perpendicular Pulse shape: half-sine Peak acceleration: 30 gn Duration 11 ms 7.4.2 of the pulse: conditions: axes (six separate Frequency IEC 60068-2-6 with the following conditions, along three 1 mm for inductive, capacitive, non-mechanical and ultrasonic proximity switches 0,5 mm for photoelectric proximity magnetic switches Sweep cycle duration: 5 min Duration of endurance at resonant frequency or at 55 Hz: 30 min in each of the three axes (90 min in all). Results mutually 10 Hzto55Hz range: Amplitude: 7.4:3 tests): Vibration In accordance with perpendicular axes: to be obtained After the test, the operating characteristics 8 relevant shall remain as given in clause 4. Tests Unless otherwise (23 t -5) “C. 8.1 8.1.1 stated the tests shall be carried out at an ambient Kinds of tests General Subclause 8.1.1 of part 1 applies. 8.1.2 Type tests Type tests are intended to verify compliance with this standard. This comprises the verification of: a) Temperature rise (8.3.3.3). b) Dielectric properties (8.3.3.4). 30 air temperature of IS 13947 IEC c) Making and breaking conditions (8.3.3.5). d) Performance under conditional e) Constructional f) capacities requirements Degree of protection distances (8.4). h) Operating frequency (8.5). Electromagnetic j) Shock withstandability k) Vibration 8.1.3 Routine short-circuit elements current under abnormal are (8.2). (8.6), (7.4.1). the inspection Sampling Subclause (7.4.2). responsibility and of verification the manufacturer of electrical and are usually the the dielectric test is tests Compliance 8:3 to tests These tests are subject Subclause limited operation. 8.1.4 of part 1 applies 8.1.-5 Special 8.2 normal (8.3.4). The inspection may be supplemented by a dielectric test. When performed, carried out according to 8:3.3.4, the test duration may be reduced to 1 s. 8.1.4 and tests tests mechanical compatibility withstandability Routine switching 2) :2004 ( 1999) (8.2). g) Operating i) of (Part 5/See 60947-5-2 to agreement between with constructional manufacturer and user. requirements 8.2 of part 1 applies where applicable. Performances 8.3.1 Test sequences The type and sequence Sample of tests to be performed on five representative No. 1 Test No. 1- temperature Test No. 2 – mechanical Test No. 3 – dielectric rise (8.3.3.3). properties properties of termina(s (8.2.4 of part 1). (8.3.3.4). Test No. 4 – visual inspection. Sample No. 2 Test No, 1 – degree of protection Test No, 2 – vibration (annex C of part 1). (7.4.2). Test No. 3 – frequency of operating Test No. 4 – operating distances (8.4). Test No. 5- properties (8.3.3.4). dielectric cycles (8.5). 31 samples are as follows: IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 ( 1999) Sample No. 3 Test No. 1 – degree of protection Test No. 2- shock (7.4.1). Test No. 3- frequency (annex C of part 1). of operating cycles (8.5). Test No. 4 – operating distances (8.4). Test No. 5- properties (8.3.3.4). Sample dielectric No. 4 Test-No. 1- making and breaking capacities Test No. 2 – dielectric properties (8.3.3.4). Test No. 3 – operating distances (8.4). Sample (8.3.3.5). No. 5 Test No. 1- electromagnetic Test No. 2 – performance compatibility under short-circuit Test No. 3- dielectric properties (8.3.3.4). Test No. 4- operating distances (8.4). There shall be no failure (8.6). conditions (8.3.4). of any of the above tests. NOTE 1 More than one test sequence or all test sequences may be conducted on one sample at the request of the manufacturer. However, the test shall be conducted in the sequence given above for each sample. NOTE 2 For class II proximity switches insulated by encapsulation, additional samples are required (see annex B). For pri ximity switches with integrally connected cables, additional samples are required (see annex C). 8.3.2 General 8.3.2.1 test conditions General requirements Subc,ause 8.3.2.1 of part 1 applies 8.3.2.1.1 Standard unless otherwise target for inductive specified and capacitive with the following proximity switches The target is square shape having a thickness of 1 mm and made of carbon Fe 360 as defined in ISO 630 and it shall be of the rolled finish. The length (a) of the side of the square — the diameter of the circle inscribed three times the rated operating For a capacitive proximity addition. steel is equal to on the active surface distance Sn whichever of the sensing is greater switch, the target shall be connected 32 (figure to earth. face, or 5). e.g. type IS 13947 (Part 5/See 2) :2004 [EC 60947-5-2 (1 999) 3 \ & Capacitive -a only ..-. a 8.3.2.1.2 = The target is square finish. For dimensions 8.3.2.1.3 = proximityswitch = sensing face = target = opersting distance = dketilon of motion Method of measuring target for ultrasonic Standard Standard .—. + f 1 2 3 4 5 Figure 5- —.— ---- the operating proximity distance (8.3.2.1 and 8.4.1) switch shape, having the thickness of 1 mm and made from see relevant specification sheets in annex A. target for photoelectric proximity metal with rolled switch a) Type R For the purpose of this test, the standard specified by the manufacturer. target is the reflector which is either supplied or is the emitter which is either supplied or b) Type T For the purpose of this test, the standard specified by the manufacturer. target c) Type D 1) 100 mm x 100 mm white paper with 90 0/’ reflectivity, 2) 200 mm x 200 mm white paper with 90 % reflectivity. 8.3.2.1.4 Standard target for non-mechanical For non-mechanical manufacturer. 8.3.2.2 proximity switches the proximity target switch shall be specified by the Test quantities Subclause 8.3.2.2 8.3.2.3 magnetic magnetic Evaluation of part 1 applies except for 8.3.2.2.3. of test result The condition of the proximity applicable to each test. switch after each test shall The proximity switch is deemed to have met the requirements requirements of each test and/or test sequence as applicable. 33 be checked by the verification of this standard if it meets the IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) 8.3.2.4 Test reports Subclause 8.3.2.4 8.3.3 Performance 8.3.3.1 under no load, normal load and abnormal load condition Operation Subclause 8.3.3.1 8.3.3.2 of part 1 applies. Operating Operational 8.3.3.2.1 of part 1 applies. limits voltages are defined under 7.2.1.2. Time delay before availability The test is performed with the proximity switch connected to a test circuit shown in figure 6. The target is placed in a position such that the switching element !s in the ON-state. With rated operational voltage Ue, or with the minimum value of the rated operational voltage when it is given as a range, the load is adjusted to obtain the minimum operational current /m. The time delay before availability and the duration of any false signal are measured by recording the signal across the load with an oscilloscope as the bounce-free “Switch” is closed. for a d.c. switching element. Figure 7a shows the Figure 7 shows typical oscillograms oscillogram when when the switching For inductive 3 s“. the switching element and capacitive element is in ON--state and figure 7b shows the oscillogram is in OFF-state. proximity switches the target shall be positioned The measured time delay before availability, the time accordinq to 7.2.1.7. The duration of the false signal, figures 7: and 7b, shall be according to 7.2.1.7. - at either 1/3 Sn or between t3 and to in figure 7 shall be if any, the time between L and ti on Ue or Ue ~ln T I Switch (bounce-free) Trigger input :’--- 0 :- osc’’’oscope ,, For 3 terminal / d.c. proximity switch ~ ~ _klk+_ Figure 6 – Test circuit ‘“””--””””””signa’inp” for the verification of time delay before availability (see 7.2.1.7 and 8.3.3.2.1) 34 IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 ( 1999) A output signal ON-state Output signal during I to 1 tl I b I I tz tq 4 Time (t) Figure 7a - Switching element is in ON-stste output signal A Output s!gnal during to tl tp tq 4 Time (t) Figure ?b - Switching element is in OFF-stete to = t, t2 t3 t~ = = = = supply is switched beginning of false end of false signal end of time delay maximum time for on signal (if any) (if any) delay (300 ms) to, which means that toand t,are the same time marks. NOTE 1 The false signal (if any) may begin at NOTE 2 In case of no false signal, the time mark t~ can have any position between NOTE 3 The waveform of the false signal (if any) is not defined. Figure 7- Signal output across 35 toand t4. load in figure 6 (see 8.3.3.2.1) Is 13947 (Part 5/See 2) :2004 [EC 60947-5-2 (1 999) 8.3.3.2.2 Minimum operational The test is performed current with the proximity (Im) switch connected Rt to a testcircuit shown in figure 8. : resistive load R2 : resistive load For 3 termmal /“ d.c. proximity switch V : high impedance voltmeter >0,2 MKVV mA : milliammeter D s RI S R2 : switch Meters: r.m.s. for a.c. average for d.c. A Test circuit for the verification of minimum operational current OFF-state current, voltage drop and independent snap action (see 8.3.3.2.2, 8.3.3.2.3, 8.3.3.2.4 and 8.3.3.2.5) Figure 8- The target is placed in a position such that the switching element is in the ON-state. With supply voltage Ue and the switch S being open, the load “Rl is adjusted current /m. The measured value shall not exceed the value specified in 7.2.1.12. The switching 8.3.3.2.3 element OFF-state shall not change current to obtain the state during the test. (/,) With the circuit in figure 8 and the switch S closed, the load R2 is adjusted operational current /e when the supply voltage is the highest Ue. The target position such that the switching element is in the OFF-state. to obtain the rated is then moved in a The (Ir) current shall be measured with supply voltage Ue + 107. or with the maximum value of the supply voltage U~ where it is specified as a range. The (/r) current shall not exceed the value specified in 7.2.1.13. 8.3.3.2.4 Independent (snap) action Independent (snap) action -shall be checked at maximum and minimum operating load currents at both maximum and minimum rated operating voltages. Resistive loads of appropriate value shall be used for each of the four tests. These tests shall be carried out by moving the target from a position where the switching element is in the OFF-state to a position where the switching element is in the ON-state and observing the output on an oscilloscope. The switching element function shall be substantially independent from the velocity of the target and the output shall switch between the ON and the OFF states without oscillating, or holding at any intermediate level. 36 IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) 8.3.3.2.5 Voltage drop (Ud) The voltage drop is measured across the active outputs of the proximity switch when the switching element is in the ON-state and carrying the rated operational current (/e) at 23 ‘C + 5 ‘C ambient temperature and at the lowest rated frequency. This measurement is performed with the circuit in figure 8 and the switch S closed. The load Rz is adjusted to obtain the rated operational current (/e) with the supply voltage Ue. The voltage drop U,-Jis measured: . at Ue+l OO\’ and Ue–150h, or Ue ~aX +1070 and Uemin–15Yo, — or UB ~aX and UB min The measured 8.3.3.3 voltage drop shall not exceed Temperature the values specified in 7.2.1.15. rise The proximity switch, installed in free air, is supplied with its rated operational voltage (~e) (or the highest operational voltage of its voltage range), and connected to a load corresponding to its rated operational current (Ie) until the thermal equilibrium is reached. The temperature rise, measured on the terminals enclosure shall not exceed 50 K (see 7.2.2). when The length of conductor shall be 2+$1 m. 8.3.3.4 Dielectric connected to each terminal applicable, and on any point properties The test for verifying dielectric properties shall be made: — in accordance with 8.3.3.4 of part 1 if the manufacturer impulse withstand voltage Uim~ (see 4.3.1 .3); has declared — in accordance with 8.3.3.4.1 has been declared. of this standard For class II proximity 8.3.3.4.1 of the Application switches and 8.3.3.4.2 insulated and 8.3.3.4.3 by encapsulation, a value for the rated if no value of Uimp see annex B. of the test voltage This test is to be carried out under circumstances approaching actual service conditions e.g. with conductors attached. The external surface of all insulating parts likely to be touched in service shall be made conducting by being closely covered by a metal foil. The proximity switch shall be capable of withstanding the test voltage type test, and 1 s for routine test with the following conditions: live parts of the switching between earthed; – between live parts of the switching element and surfaces of the proximity touched in service, conducting or made conducting by metal foil; switch – between if any. to electrically and parts of the proximity for 1 min for a - live parts belonging element applied separated 37 switching switch intended elements, to be likely to be IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) 8.3.3.4.2 Value of the test voltage A sinusoidal voltage The test voltages of power frequency is applied according are given in table 6. Table Rated 8.3.3.4.3 There Results insulation 6 Dielectric voltage DC AC v v test voltage (r.#s.) v 75 50 500 150 125 1 250 300 250 1 500 to be obtained shall be no unintentional N“OTE 1 ExceptIon suppressing means. to 8.3.3.4.1. is an intentional disruptive disruptive discharge discharge during the test designed for the purpose, e.g. transient overvoltage NOTE 2 The term “disruptive discharge” relates to a phenomenon associated with the failure of insulation under electrical stress, in which the discharge completely bridges the insulation under test, reducing the voltage between the electrodes to.zero or nearly to zero. NOTE 3 The term “sparkover” is used when a disruptive discharge occurs in a gaseous or liquid dielectric. NOTE 4 The term “flashover” gaseous or Ilquid medium. NOTE 5 is used when a dwruptwe 8.3.3.4.4 Impulse The test is performed — the proximity voltage withstand according device is not powered test shall be applied: a) between all terminals b) between terminals c) between supply. each output connected intended produces permanent of a dielectric in a together in a liquid or additional requirement: and earth; to the power supply; and each terminal — three positive and three negative intervals of not less than 5 s. strength; during the test; to be connected terminal loss of dielectric test to 7.2.3.1 with the following the impulse NOTE occurs over the surface The term “puncture” is used when a disruptive discharge occurs through a solid dielectric. NOTE 6 A disruptive discharge in a solid dielectric gaseous dielectric, the loss may be only temporary. – discharge pulses shall intended be applied The impulse voltage withstand test is designed as a type test. 38 to be connected between each to the power two points at IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) 8.3.3.5 Making and breaking capacities Tests for verification of making and breaking test requirements stated in 8.3.2.1. 8.3.3.5.1 capacities shall be made according to the general Test circuits The load impedance shall be placed on the load side of the device as shown circuit voltage with the test current flowing shall not be less than Ue. in figure 9. The Ue Ue 1 T 0 H#:;;hedevi’e Ix/e 2 termmal a.c. or 2 termmal d.c. a) Figure 9- Test circuit for the verification Making 8.3.3.5.2 The load circuitry 8.3.3.5.3 and breaking shall be adjusted Making The load circuitry 8.3.3.5.4 b) and breaking shall be adjusted Results capacities of making 8.3.4.1 Performance Test circuit and breaking capability (see 8.3.3.5) under normal conditions to give the values shown in table 4. capacities under abnormal conditions to give the values shown in table 5. to be obtained After the test, the effective operating distance remain within the limits given in 7.2.1.3.1. 8.3.4 3 termmal d.c. under short-circuit of the proximity current switch shall be measured and conditions and test procedure The proximity switch “PSi’ in new condition shall be mounted as in service, in free connected to the test circuit with the same size wire as used in service, see figure 10. air, and The short-circuit protective device “SCPD” shall be of the type and rating stated by the manufacturer. This “SCPD” shall be omitted if the proximity switch is integrally protected against short circuits. 39 Is 13947 (Part 5/See IEC 60947-5-2 2) :2004 (1 999) The target is placed in a position such that the switching element is in the ON-state; RI k selected so that the current flowing through the proximity switch is equal to its rated operational current. The supply S shall be adjusted to 100 A prospective short-circuit current. The “SC’i switch, parallel with RI load, is intended to cause the short circuit. The open circuit voltage shall be 1,1 times the rated operational voltage or the maximum value of the voltage range. The test shall be performed three times by randomly closing the “SC” switch. The test current is maintained until the SCPD or the internal short-circuit protection in the proximity switch has operated. The interval between each of the three tests shall be not less than 3 min. The actual time between tests shall be stated in the test report. After each test, the “SCPD” shall be replaced or reset. SCPD I CL ,,, 1 -U--p’l I L-—l Ps under test supply s / I SC switch Prospective short-c!rcult current 100 A a) 2 termmal a.c. or 2 termmal d.c. SCPD RI - e supply . a Ps under test I SC switch Prospective short-circuit current 100 A b) 3 terminal d.c. Figure 108.3.4.2 Results Short-circuit Testing 8.4.1 8.4.1.1 of operating Inductive, Test A proximity (see 8.3.4.2) to be obtained After the test, the operating distance within the limits given in 7.2.1.3.1. 8.4 testing capacitive, of the proximity switch -shall be measured and remain distances non-mechanical magnetic and ultrasonic according to the relevant proximity switches conditions switch in new condition is mounted annex and the target is moved, not faster than 1 mm/s, towards and away from the sensing face of the proximity switch in an axial direction. The operating distances are measured as shown in figures 3 and 4. 40 I IS ~ 3947 (Part IEC 60947-5:2 Effective 8.4.1.2 operating distance 5/See 2) :2004 (1 999) (s,) The effective operating distance is measured at the rated voltage or at any voltage within the voltage range and at 23 “C & 5 ‘C ambient air temperature. The measured value shall be within the limits given in 7.2.1.3.1. 8.4.1.3 Differential travel (H) The differential travel is defined as a percentage measurement is made at the ambient temperature target away shall from 8.4.1.4 Usable Usable with be the moved supply the proximity switch. The measured operating operating the towards proximity distance distance voltage towards the proximity 8.4.1.5 Repeat accuracy switch value within shall the (sr) range be according and then be moved to 7.2.1.5. (su) is measured at of the effective operating distance (s,). The of 23 “C k 5 “C at rated supply voltage. The over the –25 “C to +70 ‘C ambient temperature range and 110 Y. of its rated value. The target shall be moved The measured value shall be within the limits given in 7.2.1.3.2. 85 switch. Y. (R) The repeat accuracy of the effective operating distance (s,) is measured over an 8 h period with an enclosure temperature within 23 “C & 5 “-C and with supply voltage Ue.& 5 0/0 or at any voltage *5 ‘Z within the rated operational voltage range. The target shall be moved towards the proximity switch. The measured value shall be within the limits given in 7.2.1.4. 8.4.2 8.4.2.1 Photoelectric Testing proximity of the sensing This test is performed photoelectric proximity clean air conditions, at and at an ambient light 8.4.2.2 Source switches range (sd) at rated voltage or at any voltage within the voltage range with new -switches, except when specified as verification after another test, in any ambient temperature between 23 “C ~ 5 “C, both in darkness (O lx) of 5000 lx obtained as per 8.4.2.2. of ambient light a) Either: 24 x 36 (35 mm) slide projector, with glass condensing lens of focal length 80 mm, with anticaloric (heat) filter removed, with tungsten halogen lamp, colour temperature between 3000 K and 3200 K (by varying supply voltage) and delivering 5 000 lx measured with Iuxmeter and obtained by varying the distance between the light source and the Iuxmeter. b) Or: Xenon lamp delivering 5000 lx measured with distance between the light source and the Iuxmeter. 41 Iuxmeter and obtained by varying the K 13947 (Part 5/See 2) :2004 IEC 60947-5-2 ( 1999) 8.4.2.3 Type T The receiver is moved, not faster than 1 mm per second emitter and the maximum and minimum operating distances a) without ambient b) with ambient in an axial direction, are measured: the light (O lx); light (5 000 lx). The light source is positioned at an angle of 5° * 1° to the reference receiver (see figure 11a, type T). 8.4.2.4 towards axis and is aimed at the Type R The reflector, per 8.3.2.la) is moved, not faster than 1 mm per second in an axial direction, towards the photoelectric proximity switch and the sensing range is measured. a) without ambient b) with ambient light (O Ix); light (5 000 lx). The light source is positioned at an angle of 5° * 10 to the reference photoelectric proximity switch (see figure 11 b, type R). 8.4.2.5 at the Type D There are two standard targets: — target per 8.3.2.1.3 (cl) for operating distances not exceeding — target per 8.3.2.1.3 (c2) for operating distances above 400 mm. 400 mm; The target is moved, not faster than 1 mm/s in an axial direction, proximity switch and the sensing distance is measured: a) without ambient b) with ambient Results The sensing towards the photoelectric light (O lx); tight (5 000 lx). The light source is positioned at an angle of 15° + 10 to the reference photoelectric proximity switch (see figure 1lc, type D). 8.4.2.6 axis and is aimed axis and is aimed at the to be obtained range shall be as stated by the manufacturer 42 (see 7.2.1 .3.4). IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 ( 1999) m < <“j, , Emitter Receiver .. I _ 1 Figure Ila - Type T, emitter end receiver Luxmeter and receiver : % - 0 Reflector Figure 11b - Type R, emitter-receiver end reflector Luxmeter ! . ., and receiver : Target (see 8.3.2.1 .3) Figure llc - Type D, emitter-receiver end object Figure 11- Testing of the seneing 43 range (see 8.4) Is 13947 (Part 5/See 2) :2004 IEC 60947-5-2 ( 1999) -i @-’--Method 2 Method 1 line / ofCentre target 1 = proximity switch 2 = target 3 = disc in non-magnetic and non-conducting material NOTE To avoid angular influence from one target to another, the disc shall be constructed to include at least 10 targets, if the rated operating distance (sn) is less than 10 mm, or 6 targets for higher operating distances. Figure 8.5 12- Testing When method 8.5.1 Methode for meaeuring the operating frequency mechanical magnetic proximity switches for the frequency the proximity described, Method a) Inductive, of operating of inductive, capacitive (if applicable) I and non- cycles switch frequency of operating cycles exceeds the limit of the measuring the manufacturer shall state the method of measurement. for measuring capacitive the frequency and non-mechanical of operating cycles magnetic proximity I switches As shown in figure 12, the targets are fixed on the front (method 1) or sides (method 2) of teeth on a rotating disc, the spaces between the teeth being 2a, in such a manner that they can pass in front of the sensing face of the proximity switch at a distance equal to half of the rated operating distance. Each target shall have the same dimensions as those specified in 8.3.2.1. The output signal of the proximity switch is measured with the speed of rotation of the disc increasing from O. The targets of the rotating switches are tested. disc shall be connected to earth when capacitive proximity An illustration of the output signal of proximity switches is given in figure 14. With the speed increasing, the durations t, and t2 decrease. For direct current proximity switches, the rated value of the operating frequency is obtained when t, or t2 correspond to 50 ~s, or when the characteristics of the output signal, in the “ON” or “OFF” states, reaches the values specified in the relevant annexes. For alternating current proximity switches, the rated value of the operating frequency obtained when either t, or t2 corresponds to one-half period of the supply frequency (fb). 44 is IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 ( 1999) b) Ultrasonic proximity switch As shown in figure 13 the targets teeth on a rotating disc. are fixed on the front (method 1) or sides (method 2) of The spaces between the teeth being 3a in such a manner that they can pass in front of the sensing face at the minimum operating distance and the proximity switch shall be adjusted to thi-tolerating distance. I W 1 2 S min. . Yr ‘ ‘,< (3>’ I, .,-=’ L- @-”-Method 2 Method 1 Centre line / of target 1 = proximity switch 2 = target 3 = disc in non-magnetic and non-conducting material NOTE 1 targets, To avoid angular influence from one target to another, the disc shall be constructed NOTE 2 Method 2 is only applicable Figure 13- Methods output signal to narrow-beam for meaauring angled proximity switches, the operating f, ultrasonic frequency proximity switch t I .— Figure 14- to include at least 10 Output t, t~ . signal of direct current of operating 45 .-a t, * Time (t) proximity switch during the measurement frequency f IS 13947 (Part 5/See IEC 60947-5-2 The operating 2): 2004 (1 999) frequency f is determined from the following f=~ 8.5.2 Results 8.5.3.1 t,+ tp to be obtained The values obtained 8.5.3 formula: shall be not less than those given in the relevant Photoelectric proximity Measurement annexes. switches means As shown in figure 15, a rotating disc with one or more targets is fixed parallel to the sensing face of the proximity switch at a distance less than 10 cm, and in such a way that the reference axis of the proximity switch passes through the centre of the target. 4 1 2 3 4 Receiver Disc Emitter Reference 1 2 3 4 sensor Figure 15 – Measurement For types T and R, the effective For type D, the surface standard target. If the operating distance means for turn-on rotating target ton shall and turn-off time t.ff be made the tests, then the manufacturer A recorder (for example, a memory oscilloscope) the proximity switch and by the reference sensor Measurement time Emitter-receiver Disc Target Reference sensor beam shall be fully broken by the rotating of the affects 1 2 3 4 Emitter-receiver Disc Reflector Reference sensor A reference sensor having a switching frequency under test (E UT) is also put around the disc. 8.5.3.2 Type D (diffuse reflective) Type R (retro-reflective) Type T (through beam) of turn-on target. of the same material as the shall state the test distance. at least ten times higher than the equipment can draw simultaneously (see figures 16 and 17). curves delivered by time (f,.) The positional relationship between the reference sensor and the EUT shall be adjusted while rcoving the disc slowly so that the output of the reference sensor changes its state simultaneously with the output of the EUT. 46 IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) To measure tOn,the disc speed is adjusted so that the EUT is operated . the maximum operating frequency stated by the manufacturer. at approximately The turn-on time fOn is the maximum observed delay between the output sensor and the change of state of the EUT output (see figure 16). of the half of reference State B Reference sensor output State A 1 Target detected Equipment under test output Delay K Q No target detected NOTE The diagram refers to logic?; states A and B. A and B will differ according to the type of proximity switch . Figure 8.5.3.3 M-easurement 01 turn-off 16 – Turn-on time ton measurement time (tOff] The positional relationship between the reference sensor and the EUT shall be adjusted while moving the disc slowly so that the output of the reference sensor changes its state simultaneously with the output of the EUT. To measure tOff,the disc speed is adjusted so that the EUT is operated the maximum operating frequency stated by the manufacturer. at approximately half of The turn-off time tOffis the maximum observed delay between the noted output of the reference sensor and the change of state of the EUT output (see figure 17). State B Reference sensor output State A Target detected + — + Delay Equipment under test output No target detected NOTE The diagram refers to logical states A and B. A and B will differ according to the type of proximity switch Figure 17- Turn-off time tOffmeasurement 47 IS 13947 (Part 5/See 2): (1999) IEC 60947-5-2 8.52.4 Results 2004 to be obtained 0{ operating The frequency cycles f determined less than that given by the manufacturer. by the formula given in 7.2. i.6.2 shall be not I Verification 8.6 of the electromagnetic compatibility The tests shall be performed under the following conditions: — the proximity device mounted in free air shall be connected the rated operational current (/e) and supplied with its rated maximum voltage of its voltage range) (Ue); — the connecting leads shall be 2+81 m. For proximity type of cable used shall be specified devices by the manufacturer to a load corresponding to operational voltage (or the not having and recorded integral cables, the in the test report. The test shall be performed: a) with the target set at a position such that the switching element is in the OFF-state; b) with the target~et such that the switching element is in the ON-state; c) for inductive or 3 Sn. at a position and capacitive For the test according to 7.2.6.3 proximity the following devices, additional — cylindrical proximity devices shall be mounted clamped between the locknuts of the device plane; the target mounting shall be positioned conditions in a non-embeddea shall be connected apply: Inanner. A metal washer to the reference ground — rectangular proximity devices shall be mounted in a non-embedded plate which shall be connected to the reference ground plane; manner on a flat metal — the method of connection to the reference ground plane shall be in accordance manufacturer’s instructions, if given, and sha~ be stated in the test report. Performance at 1/3 sn with the criteria During the tests the state of the switching element shall not change for more than 1 ms for d.c. devices and one half wave of supply frequency for a.c. devices. 8.6.1 Electromagnetic The test is performed 8.6.2 Electrostatic field immunity according discharge to IEC 61000-4-3 and 7.2.6.1. immunity The test is performed according to IEC 61000-4-2 and to 7.2.6.2 and shall be repeated 10 times at each measuring point, with a minimum time interval of 1 s between pulses. 8.6.3 Fast transient immunity The test is performed according to IEC 61000-4-4, placed in the capacitive coupling clamp. 8.6.4 Emission and to 7.2.6.3, with all the connecting requirements The test is performed according to CISPR 11 group 1, class A, and 7.2.7. 48 leads IS 13947 (Part 5/See 21:2004 IEC 60947-5-2 (1 999) 8.7 Test results and test report The test results shall be documented in a comprehensive test report. The test report shall present the objective, the results and all relevant information of the tests. The test report shall define the proximity device under test, including the cable layout and the necessary auxitiary equipment. Any deviation from the test plan shall be mentioned. Where a range of proximity devices are made according to the same principle and design, and using the same type of components, tests may be performed on representative samples. Furthermore based on first results, the testing laboratory may limit the tested frequency range for radiation or conduction tests and shall include in the report the frequency range used. 49 IS IEC 13947 (Part 5/See 60947-5-2 2) :2004 ( 1999) Annex A (normative) Specification sheets MODEL INDUCTIVE CYLINDRICAL WITH A.1 (1A) 1A PROXIMITY THREADED SWITCHES BARREL Dimensions The dimensions and thread sizes shown in figure A.1 (1A) shall be according to table A.1 (1A). leads shall be Within the dimensional limits of C/l and /2 all rigid parts of the connecting included. The diameter of unthreaded port~on d, shall not exceed the minor diameter of the thread. For type 11 embeddable, the thread can b~ omitted and the diameter reduced to d2 on a length not exceeding /3 = 1 mm. For type 12 the thread can be omitted and the diameter reduced to dz on a length not exceeding /3 = 2 Sn. Across flats (AF) s Target Figure A.1 (1A) - Dimensions Table A.1 (1A) – Dimensions I Ssnsing mssns: inductive (1) 1 embeddsbls I I Dimensions 2 nonembeddsble Body Type Nuts m d3* +0,1 5 msx. 13 4 15 80 17 4 20 50 100 24 4 26 50 100 36 5 42 d, /1 12 Thresd size min. msx. 40 60 40 11A08 12A08 11A12 12A12 M12x 11A18 12A16 M18X1 11A30 12A30 “ d3min. in millimetres M8x1 M30 X 1 1,5 =l,13AF 50 AF IS 13947 IEC A.2 (1A) Rated operating (Part 5/See 60947-5-2 2) :2004 (1 999) distances The rated operating distance, for embeddable and non-embeddable proximity switches, shall be according to table A.2 (1A). The rated operating distance is a conventional quantity, it does not take into account either manufacturing tolerances or variations due to external conditions such as voltage and temperature (s-ee 2.3.1.1 and 7.2.1.3.1). Table A.2 (1A) – Rated operating distances in millimetres I Type 11- Embeddable Form and size A.3 (1A) Form and size Rated operating distance Rated operating distance A08 1 A08 2 A12 2 A12 4 A18 5 A18 8 A30 10 A30 15 Installation Embeddable A.2 (1A) a. Type 11- Non-embeddable I proximity (mounting) switches, Non-embeddable proximity figure A.2 (1A) b. when installed switches when in damping installed material in damping y///////////////////// shall be according material shall be according y///////////////////// ! II >3xd1 t Free zone or non-dampmg material (e.g. a non-metalllc material) a) Embedded in metal b) Not embedded in metal Figure A.2 (1A) - Installation 51 (mounting) to figure to IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1999) A.4 (1A) Frequency of operating Minimum requirements cycles (f) in operating Switching Form and size Installation A12 A18 A30 element function: – A or B Type of output Por A08 cycles per second N D 1 500 300 2 300 200 1 400 200 2 200 100 1 200 100 2 100 50 1 70 50 2 50 30 F 5 NOTE The frequency of operating cycles are only stated for the most common types. For all other possible types (according to table 1 Classification) the frequency of operating cycles shall be stated by the manufacturer. 52 IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 ( 1999) MODEL INDUCTIVE CYLINDRICAL WITH A.1 (IB) 16 PROXIMITY SMOOTH SWITCH BARREL Dimensions The dimensions shown in figure A.1 (IB) shall be according to table A.1 (lB). Within dimensional limits of d, and /2, all rigid parts of the connecting leads shall be included. No part of the proximity switch within the length /2 shall exceed the diameter the d,. Sensingface l— \ .-. —.- ----- -.-. —.-. —.- .-. —.—.- _.— —___ ----- .-. —.- .- ._. - -. —.- ----- ------ dl #-[ i u t / Target /3 /1 s“ I Figure A.1 (IB) - Dimensions Table A.1 (IB) – Dimensions Sensing means: inductiva (1) 1 Em beddable type IIB04 IIB06 A.2 (IB) Rated operating in millimetres Dimensions d, 11 /2 13 min. max. max. 4 25 50 0,5 6,5 40 60 1 distances The rated operating distance shall be according to table A.2 (l B). The rated operating distance is a conventional quantity. It does not take into account either manufacturing tolerances or variations due to external conditions such as voltage and temperature (see 2.3.1.1 and 7.2.1.3). 53 IS I 3947 IEC (Part 5/See 2) :2004 60947-5-2 (1 999) Table A.2 (IB) – Rated operating distance in millimetres Type 11 - Embeddsble A.3 (IB) Installation The proximity Type Rated operating distance B04 0,8 B06 1 (mounting) switch when installed in damping material Figure A.2 (lB) - Installation A.4 (IB) Frequency of operating Minimum requirements Form and size I Mechanical cycles shall be according in damping (f) in operating installation 1 B06 NOTE 1 I 1 material cycles per second Type of output N D 300 600 I Same as A.4 (1A), 54 - Switching element function: A or B Por B04 to figure A.2 (lB). 500 I 250 IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) MODEL INDUCTIVE RECTANGULAR WITH A.1 (IC) SQUARE IC PROXIMITY SWITCHES CROSS-SECTION Dimensions em bendable, 26 mm x 26 mm. Overall and mounting A.1,1 (IC) Type 11C26 inductive, dimensions shall be according to figure A.1 (lC). The rigid part of the cable assembly is included in the overall dimensions. The cable entry shall allow the passage and ensure the anchorage as well as the tightness of a-cable with an external diameter of 7 mm to 10 mm. I ConnectIon to internal terminals Only one sensing face which may occupy any of the three sides Cable entry I 26 I ,-,- 195 1 75 --i < Y 04,2 pi o+ (2x) 26 95 max. L-----J Figure A.1 (IC) – Dimensions 55 in millimetres IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1999) 35 mm x 35 mm. Overall and moqnting A,l.2 (IC) Type 12C35 inductive, non-embeddable, dimensions shall be according to figure A.1.2 (lC). The rigid part of the cable assembly is included in the overall dimensions. Onlyonesensingfacewhich mayoccupyanyof thefive-sides / _AJ .._._, ._. __ -.--. — -----.-. —.— .-. —.-----—. A < @ 5,3 ..—. z f - 1 I I - 18 20 15 Cable entfy 60 * m 78 . 100 max. . Figure A.1:2 (IC) - Dimensions in millimetres embeddable A.1.3 (IC) Type 12C30 inductive, non-embeddable and type 11C30 inductive 30 mm x 30 mm. Overall and mounting dimensions shall be according to figure A.1.3 (lC). The rigid part of the cable assembly is not included in the overall dimensions. e Only one sensing face which may occupy any of the five sides \ ! .. ........ . Sensing face Cable entry ------------ J 30 .—.—. . 12 min. @ 4,3 3 II —.- .— -.-. ,-. — .- .- .-.: ‘Q .—. —.- .—---- ------ ------ --- ;+ 3 26 - 41 ‘ 5,3 0 95 max. Figure A.1.3 (IC) - Dimensions in millimetres 56 21 30 IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) A.1.4 (IC) Type 12C40 inductive, non-embeddable – Type IIC40 inductive embeddable 40 mm x 40 mm. Overall and mounting dimensions shall be according to figure A.1.4 (lC). The rigid part of the cable assembly is not included in the overall dimensions. P Only one sensing face which may occupy any of the five sides .. . . . . ... Sensing face q Cable entry ------.—---- 40 .-. ...—. 16 min. --;-. —.— .— -------------..=..-. — ‘-1 ~+~ -.— .IQ .... ‘ -t-i-, , 1 I r------ .— 05’3 3 -H-793 30 4~ -&-------------@- 25 - 60 45 Figure A.1.4 (IC) - Dimensions A.2 (IC) Rated operating in millimetres distance The rated operating distance shall be according to table A.2 (lC). The rated operating distance is a conventional quantity, it does not take into account either manufacturing tolerances or variations due to external conditions such as voltage and temperature (see 2.3.1.1 and 7.2.1.3). Table A.2 (IC) - Rated operating Type A.3 (IC) Installation Rated operating distance 11C26 embeddable C35 non-embeddable 10 15 11C40 embeddable 12C40 non embeddable 15 20 11C30 embeddable 12C30 non-embeddable 10 15 (mounting) A.3.1 (IC) Figure distance in millimetres Type IIC proximity switch installed in damping material is shown in figure A.2 ([C). A.2 (IC) a shows the proximity switch with front sensing face. Figure A.2 (IC) b shows the proximity switch with side sensing face installed. 57 IS 13947 (Part 5/See 2) : 2004 IEC 60947-5-2 (1999) n o 1 Sensing face b) Figure A.2 (lC) - Installation A.3.2 (IC) Type 12C proximity L of a IIC proximity switch installed in damping switch in damping material material as shown in figure Sensing face a) Angle mounting /, b) Channel mounting Sensing face \ Sensing face d) Not embedded in damping material c) Embedded in damping material Figure A.3 (IC) – Installation of 12C35 in damping 58 material A.3 (lC). IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) A.4 (IC) Frequency of operating Minimum requirements cycles (f) in operating cycles per second Switching-element Form and size Instsllaticm Por N D 40 1 40 C35 2 100 50 C30 1 70 50 1 50 50 and NOTE function: A or B Type of output C26 C40 - ‘Same as A.4 (1A). 59 F 5 is 13947 (Part 5/See 2): IEC 60947-5-2 ( 1999) 2004 MODEL INDUCTIVE WITH A.1 (ID) ID RECTANGULAR PROXIMITY SWITCHES RECTANGULAR CROSS-SECTION Dimensions Type 12D non-embeddable proximity switches shall have overall and mounting dimensions according to figure A.1 (ID) and table A.1 (ID). Parts of the cable assembly are not included in the overall dimensions. ........... ,, E ‘[ i ‘i _ 40 *1,5 Sensing face Cable entry _.-;---i “ 16 min. 4 /2 lL Cableentry Al.+_.--_...+. ~ 1 I I bl I I-=--l Figure A.1 (ID) - Dimensions Table A.1 (ID) - Dimensions I in millimetres max. Type /1 msx. /2 = b2 12D60 120 45 50 12D80 135 65 80 60 b, IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1999) A.2 (ID) Rated operating distance The rated operating distance for non-embeddable proximity switches -shall be according to table A.2 (ID). The rated operating distance is a conventional quantity, if does not take into account either manufacturing tolerances or variations due to external conditions such as voltage and temperature (see 2.3.1.1 and 7.2.1 .3). Table A.2 (ID) - Rated operating Type I distances Rated operating distance 1.2D60 non-embeddable 25 I 12DLt0 non-em beddable A.3 (ID) Installation The installation figure A.2 (ID). in mi’llimetres I 40 (mounting) of the 12D60 and 12D80 proximity switches in damping material is shown I Free zone or non-dampmgmaterial (for instance a non-metalhcmaterial) Figure A.2 (ID) - Installation A.4 (ID) Frequency of operating Minimum requirements cycles of 12D in damping (f) in operating material cycles per second - Switchrng element function: A or B Form snd size NOTE Installation Type of output Por N D D60 2 25 15 D80 2 10 10 Same as A.4 (1A). 61 F 5 in IS 13947 (Part 5/See 2): IEC 60947-5-2 (1 999) 2004 MODEL CAPACITIVE CYLINDRICAL WITH A.1 (CA) CA PROXIMITY THREADED SWITCHES BARREL Dimensions The dimensions are thread sizes shown in figure A.1 (CA) shall be according to table A.1 (CA). Within the dimensional limits of d, and /2, all rigid parts of the connecting leads shall be included. The diameter of unthreaded portion d2 shall not exceed the minor diameter of the thread. The thread can be omitted and the diameter reduced to d2 on a length not exceeding /3 <2 x Sn. Across flats (AF) Sensing face \ /\ Target Sn I Figure A.1 (CA) - Dimensions Table -Al (CA) - Dimensions in millimetres Dimensions Sensing meens: capacitive (C) Nuts Body Type CA18 CA30 “ d, 1, I* Thresd size min. max. M18x 1 50 100 50 100 M30 X 1,5 m d3* +0,15 max. 24 4 28 36 5 42 AF d3 min. = 1,13AF 62 m IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) A.2 (CA) Rated operating The rated operating in clause A.3 (CA). distance distance (sn) is adjusted by the manufacturer under mounting conditions stated The rated operating distance shall be set according to table A.2 (CA). The rated operating distance is a conventional quantity, it does not take into account either manufacturing tolerances or variations due to external conditions such as voltage, temperature, humidity and mounting conditions. Table A.2 (CA) – Rated operating distances Type A.3 (CA) Installation in millimetres Rated operating distance CA18 5 CA30 10 (mounting) Ta nl Capacitive proximityswitch II = Figure A.2 (CA) - Installation A.4 (CA) Frequency Minimum requirements: of operating (mounting) cycles (f) 10 operating cycles per second for type A18 and type A30. 63 IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) MODEL CAPACITIVE WITH CB PROXIMITY SMOOTH (.Under consideration.) 64 SWITCHES BARREL IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) MODEL CAPACITIVE RECTANGULAR WITH A.1 (CC) CC SQUARE PRO-XIMITY SWITCHES CROSS-SECTION Dimensions Overall and mounting dimensions of type C30 shall be according to figure A.1 (CC) a and type C40 shall be according to figure A.1 (CC) b. Apart from these dimensions, the design of the proximity switch is not restricted. The mountina dimensions are included within the dimensions of the housing, but the cable entry dimensions~re not. Only one sensing face wh!ch may occupy any of the fwe sides t 4 -.. ‘F 30 12 min. ___ —.:---.,_ ._. .— .-. :. ___ ,_____ ._ ._. _ . ._. _ . _ :Q-~~ 3 ++-. Ill 04,3 21 26 30 T 5,3 41 - 95 max. Figure A.1 (CC) a - Dimensions, P Only one sensing face which may occupy any of the five sides . type C30 in millimetres . . .. ....... Sensing face $ Cable entry 40 16 min. ‘-------: J I 40 45 60 Figure A.1 (CC) b - Dimensions, 65 type C40 in millimetres IS 13947 (Part 5/See 21:2004 IEC 60947-5-2 (1 999) A.2 (CC) Rated operating The rated operating in clause A.2 (CC). distance distances (sn) is adjusted by the manufacturer under mounting conditions stated The rated operating distance shall be according to table A.2 (CC). The rated operating distance is a conventional quantity, it does not take into account either manufacturing tolerances or variations due to external conditions such as installation (mounting), voltage, humidity and temperature. Table A.2 (CC) – Rated operational Rated operating Type A.3 (CC) Installation distance in millimetres CC30 10 CC40 15 (mounting) Figure A.2 (CC) - Installation A.4 (CC) Frequency Minimum requirements: distance of operating 10 operating (mounting) cycles (f) cycles per second for type C30 and type C40. 66 IS 13947 IEC MODEL CAPACITIVE A.1 (CD) 2) :2004 (1 999) CD RECTANGULAR WITH (Part 5/See 60947-5-2 PROXIMITY RECTANGULAR SWITCHES CROSS-SECTION Dimensions Type D80 proximity switches shall have overall and mounting dimensions according A.1 (CD). Parts of the cable assembly are not included in the overall dimensions. to figure Target —T————~ .% I ~ ,, ...........................: 1: 40*1,5 .& Sensing face I I 1 I I Cable ent 4 16 min 11 0, “&---- ”-”i”-”-”-’-&”- 80 - .–; 65 .-. -.-. i.-._._._ +._ - “+”-”-”-”:”-”-”-”- +“- Figure A.1 (CD) - Dimensions A.2 (CD) Rated operating distance _.l. _._.. Cable entry ! 05,3 Cable entry in.millimetres (sn) The rated operating in clause A.2 (CD). distance is adjusted .by the manufacturer The rated operating distance shall be: Sn = 40 mm. The rated operating distance is a conventional manufacturing tolerances or variations due (mounting), voltage, humidity and temperature. under mounting conditions stated quantity, it does not take into account either to external conditions such as installation 67 IS IEC I 3947 (Part 60947-5-2 A.3 (CD) 5/See 2) :2004 (1999) Installation (mounting) The proximity switch shall be mounted on damping material. The dimensions of the damping material shall be at least three times the outside dimensions of the capacitive proximity switch. Damping material in opposite of the sensing tace shall not be closer than 3 x Sn. t!%% Damping material (earthed metal) Figure A.2 (CD) - Installation (mounting) A.4 (CD) Frequency of operating cycles (t) Minimum requirement: 10 operating cycles per second. 68 IS 13947 (Part 5/See 2) :2004 IEC 60947’5-2 (1 999) MODEL THREADED BARREL ULTRASONIC PROXIMITY A.1 (UA) UA CYLINDRICAL SWITCHES Dimensions The dimensions and thread size shown in figure A.1 (UA) shall be according to table A.1 (UA). Within the dimensional limits of d, and /2, all rigid parts of the connecting leads shall be included. The diameter .dz may exceed the diameter of the thread according to extended sensing ranges. The diameter C/dof the unthreaded part shall not exceed the minor diameter of the thread. Sen /, - Figure A.1 (UA) - Dimensions Table A.1 (UA) - Dimensions I in millimetres Dimensions Nuts AF 24 m d3* +0,1 5 msx. T 4 U3A30..A M30 x 1,5 M30 50 150 0 36 5 U3A30.. B M30 x 1,5 tv130 50 150 0 36 5 U3A30.. E M30 X 1,5 70 max. 50 150 35 36 5142 1 M42 35 150 0 50 6 35 50 6 U3A42.. D M42 U3A42,. E I M42 x 1 “ d~min. X I 70 max. I 50 I 150 = 1,13AF 69 I 28 I I I I 42 42 57 57 1s 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 9991 A.2 (UA) Sensing range The operating distances max. and min. for ultrasonic proximity switches shall be according to table A.2 (UA). These distances are conventional quantities, they do not take into account variations due to external conditions such as temperature, altitude and humidity. Table A.2 (UA) –“Requirements Sensing range for sensing range in millimetres from to Target size mm A 60 300 loxlo 0 300 800 20 x 20 I 500 IDI E 800 A.3 (UA) Installation According to the instructions A.4 (UA) Frequency 2000 6000 I loox 100 loox 100 (mounting) of the manufacturer. of operating Shall be stated by the manufacturer per minute. cycles (f” either in operating 70 cycles per second or in operating cycles IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) MODEL ULTRASONIC RECTANGULAR WITH A.1 (UC) SQUARE UC PROXIMITY SWITCHES CROSS-SECTION Dimensions Overall and mounting dimensions shall be according to figure A.1 (UC). Apart from these dimensions, the design of the proximity switch is not restricted. Within the overall dimensions of the housing, the mounting dimensions are included but the cable entry dimensions are not included. c Only one sensing face which may occupy anyof the five sides .. / Sensing face “’”””””’ Cable entry 40 16 mln 2 ‘------- _.— — -.— — ‘“-ql-‘-----:, 6------ 25 * ---------& ‘-’--uI -- 60 . 120 max. .Figure A.1 (UC) - Dimensions Sensing 40 . 45 I A.2 (UC) 30 of type U3C40 range The maximum and minimum operating distances for ultrasonic proximity switches shall be according to table A.1 (UC). These distances are conventional quantities, they do nol take into account variations due to external conditions such as. temperature, altitude and humidity. 71 IS IEC 13947 (Part 5/See 60947-5-2 2) :2004 (1 999) Tableau A.1 (UC) - Requirements Sensing range for sensing to from range in millimetres Target eize mm A 60 300 c 300 1 000 A.3 (UC) Installation According to the instructions A.4 (UC) Frequency lox 10 20 x 20 (mounting) of the manufacturer. of operating Shall be s~ated by the manufacturer per minute. cycles (f) either in operating 72 cycles per second or in operating cycles IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) MODEL ULTRASONIC WITH A.1 (UD) UD RECTANGULAR PROXIMITY RECTANGULAR SWITCHES CROSS-SECTION Dimensions proximity switches shall have overall and mounting dimensions Type U3D80 ultrasonic according to figure A.1 (UD). Parts of the cable assembly are not included in the overall dimensions. 40’15Lm-#6mn F=’1 Ka’ “q”-”- ”-’:”- ”-”-”-c )“- 00 65 – .-r . -.-..- .<. _.-. ___ ___ - +------{ ------( p-- -“+--”-”- Cable entry [ Cable enhy 32,5 0 5,3* 0,3 40 H- Figure A.1 (UD) - Dimensions A.2 (UD) Sensing - - of type U3D80 in millimetres range The operating distances shall be according to conventional quantities, they do not take into account as temperature, altitude and humidity. 73 table A.2 (UD). These variations due to external distances conditions are such IS IEC 13947 (Part 5/See 60947-5-2 2) :2004 (1 999) Table A.2 (UD) – Requirements Sensing from range to A 60 300 c 300 1 000 E 800 6000 A.3 (UD) Installation According to the instructions A.4 (UD) Frequency Shall be stated per minute. for sensing range in miilimetres Targst size mm lox 10 20 x 20 Ioox loo (mounting) of the manufacturer. of operating by the manufacturer cycles (f) either in operating 74 cycles per second or in operating cycles IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) Annex B (normative) Class II proximity switches insulated Requirements 6.1 and by encapsulation - tests General This annex specifies constructional requirements and tests for class II proximity switches parts of devices in which insulation of class 11, according to IEC 60536, is achieved encapsulation. All parts insulation 6.2 which are not encapsulated shall concerning clea~ances and creepage follow the distances. requirements specified for double Definitions The following definitions apply to this annex. * B.2.1 encapsulation process by which all components, conductors and ends of Integral cables are encased Insulating compound by suitable means such as embedding or potting in an B.2.1.1 embedding process of completely encasing electrical device(s) by pouring a compound over it (them) in a mould, and removing the encased device(s) from the mould after solidification of the compound — B.2. I.2 potting embedding process in which the mould remains attached to the encased B.2.2 compound thermosetting, thermoplastic, catalytically cured and elastomeric and/or additives, after solidification electrical device(s) materials with or without fillers B.2.3 temperature range of the compound the ambient temperature range as stated in 6.1.1 of IEC 60947-1 6.5 Marking Proximity switches according to this annex shall be marked with the following symbol c1 D This symbol is 60417 -2-IEC-5172. 75 IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) B.7 Constructional 6.7.1 Choice requirements of compound The compound tests in B.8. 6.7.2 and functional shall be chosen Adhesion so that the encapsulated proximity switches comply with the of the compound The adhesion of the compound shall be sufficient to prevent the ingress of moisture between the compound and all encapsulated parts and to prevent movement of the encapsulated portion of the cable if any. Compliance shall be verified by the tests of B.8.1 .2.5 and B.8 1.2.2. Compound Figure B.7.3 Dielectric Subclause 6.1 - Encapsulated device properties 7.2.3 applies with the following changes: the test voltage When Uimp is declared by the manufacturer, of the maximum rated operational voltage in the first column IEC 60947-1 for the stated overvoltage category. When Uim is not declared by the manufacturer, table 6 of rhis standard plus 1 000 V. B.8 B.8.1 the test voltage Tests Kind of tests B.8.1.1 Subclause General 8.1.1 of IEC 60947-1 shall be the next higher category of table H.1 or H.2 of annex H of applies. 76 shall be the voltage stated in IS 13947 IEC B.8.1.2 (Part .5/See 60947-5-2 2) :2004 (1999) Type tests The following order. B.8.1 .2.1 sequence Dielectric of six tests shall be applied to each of three samples in the specified tests in new conditions Subclause 8.3.3.4 of IEC 60947-1 applies with the exception that the values of voltage shall be applied between the stripped joined ends of the cable or the shorted terminals and any point of the surface (or metallic foil on the surface) of the encapsulated device (see figure Bl). No breakdown B.8.1 .2.2 of the insulation Cable tests (if applicable) Proximity switches annex C. B.8.1 .2.3 provided Rapid change Test Na shall be performed with integrally of temperature in accordance - TA and T~ are the minimum – transition — number – shall occur. exposure of cycles: 1) of test with IEC 60068-2-14 and the maximum temperatures with the following values: stated in B.2.3; 3 h. damage shall be observed.1) Impact test as follows (see figure B.2). is placed on a rigid support. Three impacts of 0,5 J shall be applied near the centre axis (for cylindrical shape) of the encapsulated device. The impacts with requirements 5; time tl: The test is performed The sample cables shall comply 2 min to 3 rein; time t2: After the test, no visible B.8.1 .2.4 connected are obtained by dropping of the largest surface or the longest a steel ball 0,25 kg from a height of 0,20 m. Smail cracks of the Moulding compounds, if any (see figure B.1 ) are acceptable and B.8.1 .2.5. They-shall not impair the results of the final test of B.8.1 .2.6. 77 after tests B.8.1 .2.3, B.8.1 .2.4 IS 13947 (Part IEC 60947-5-2 5/See 2) :2004 (1 999) -(3---’S’ba”ba” , h t I I / Sample under test /////// ////A%//z%z//%w// /4 L Figure B.2 - Test device The support is considered than 0,1 mm. sufficiently After the test, no visible damage B.8.1 .2.5 55 “c; number 6. of cycles: The test report shall state which variant After the test, no visible damage Following in 8.3.3.4.1 Dielectric test and Subclause 1) is less variant with the following 1 or variant values: 2. shall be observed.1) test after stresses B.8. 1.2.5, 8.3.3.4.2 Routine with IEC 60068-2-30 is applied: the with dielectric the test properties voltage The results to be obtained shall be as stated current shall not exceed 2 mA at 1,1 Ui. B.8.1.3 energy shall be observed.1) in accordance upper temperature: B.8.1 .2.6 under the impact Damp heat, cyclic test The test Db shall be performed – rigid if its displacement shall being be checked applied in 8.3.3.4.3 by respecting tests specified for 1 min. with the addition that the leakage tests 8.1.3 applies but the dielectric test is mandatory. Small cracks of the moulding compounds, if any (see figure B.1) are acceptable and B.8. 1.2.5. They shall not impair the results of the final test of 9.8.1.2.6, 78 after tests B.8.1 .2.3, B.8.1 .2.4 IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) Annex C (normative) Additional for proximity switches connected cables requirements with integrally C.1 General This annex gives additional requirements applying cables for electrical connection to other equipment proximity switches with integrally and/or to the powsr source. The cable integrally connected to such proximity switches is not corrsidered user. This annex states the constructional and performance requirements cable anchorage and the cable entrance seal. C.2 connected replaceable by the for the cable, the Definitions The following definitions apply to this annex: C.2.1 cable connected proximity switch proximity switch having integrally connected and/or to the power source leads for electrical C.2.2 cable entrance sealing means sealing means between cable and device enclosure cable abrasion and which may provide required sealing Constructional C.7.1 Constructional C.7.1.1 temperate damage to the requirements requirements switch rating and shall be provided environmental with flexible cable of appropriate voltage, current and condition. The length of cable provided may be specified in the relevant product standard. C.7.1.2 Cable anchorage The cable anchorage electrical connections Movement connection C.7.1.3 performance so as to prevent from Cable material The pr~ximity NOTE and to other equipment providing the required protection of enclosure and cable anchorage C.2.3 cable anchorage means to relieve mechanical stress from the cable termination electrical connection between the device and the cable C.7 connection shall be such that a force being applied integral to the device. of the cable in to or out of the proximity or internal parts of the device. Cable entrance sealing to the cable is not transmitted switch shall not cause damage to to the cable means A sealing means shall be provided at the cable entrance to the proximity switch suitable degree of protection specified for the proximity switch (see annex C of IEC 60947-1). NOTE The sealing means may be inherent in the device encapsulation. 79 for the IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) C.7.2 Performance requirements The cable and the cable given in clause C.8. C.8 entrance sealing means shall be capable of withstanding the tests Tests The purpose of these tests is to ensure integrity of the cable anchorage during transit handling and installation. Once installed, the proximity switch and cable should be fixed relative to each other. C.8.1 Type tests The following sequence specified order. C.8.1.1 of four tests shall be performed on a representative sample in the entry, applied to the Pull test The cable shall be subjected to a steady pull along the axis of the cable insulating jacket of the cable for a duration of 1 min. The pull force shall be 160 N for the cable diameter greater than or equal to 8 mm. The pull force for cable diameters of less than 8 mm shall be of the value (in N) of 20 times the external cable diameter (in mm). C.8.1.2 Torque test The cable shall be subjected to a torque of 0,1 Nm or limited to the value giving an angle of torque of 360°. The torque shall be applied to the cable, clockwise for 1 min and then counterclockwise for 1 rein, at a distance of 100 mm from the proximity switch entrance. C.8.1.3 Push test The push force shall be applied entrance. along the axis of the cable as close The force is increased slowly to 20 N. The force shall be applied with a 1 min pause between applications. After the tests, no visible damage the cable shall be observed. C.8.1.4 of the cable entrance sealing as possible to the cable for 1 min for each time and means and no displacement of Bend test The cable shall be loaded and bent in the following a) Suspend a 3 kg mass by attaching axis of the cable entrance vertical. b) Tilt the proximity 1 min. it to the cable 1 m from the cable entrance for c) Tilt the proximity switch 90” in the opposite direction relative to vertical so as to cause opposite 90° bend in the cable, maintaining the position for a duration of 1 min. an Results 90° to cause a 90° bend in the cable, maintaining and with the that position C.8.2 switch manner: to be obtained There shall be no damage to the cable, cable sealing means, cable entrance or electrical connecting means of the proximity switch. This will be verified by visual examination and verification of compliance with the stated 1P designation. 80 IS 13947 (Part 5R3ec 2) :2004 IEC 60947-5-2 (1 999) Annex D (normative) Integral D.1 Plug-in following coupled proximity figures. connectors switches They shall shall for plug-in proximity incorporate provide a minimum an integral switches connector protection rating in accordance of IP65 when with the correctly with their mating connector. 0“0’% # n b I H 5,5 i“,z Note 2 — 7,2.~z — NOTE 1 Pin identification NOTE 2 switches. For a provisional NOTE 3 Protective — Sealing face numbering is riot necessary. period the use of 1/2” UNF is permissible as an alternative to M12 on a.c. proximity earth pin shall be omitted for class II proximity switches. Figure D.1 - M12 0 3-pin integral connector 81 for a.c. proximity switches IS I 3947 IEC (Part 5/See 60947-5-2 2): 2004 (1999) — NOTE .—. .— Sealing face The central pin may be omitted when not necessary. Figure D.2 - M12 0 5-pin integral connector for d.c. proximity switches ilk 2+:’ , -dFigure D.3 -8 M 5 *0,05 ml — 1,75 .;,1 6 min. — Sealing face mm 0 3-pin integral connector 82 for d.c. proximity switches IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) 3+;’ 2+;’ 01 * 0,03 --i t---t 1,75 .:,1 IE @l@4;,llAl -+ t---+l u 5 +0,05 --’ LJ= — 6 min. — Sealing face Figure D.4 - 8 mm 0 4-pin integral connector for d.c. proximity switches 83 IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 ( 1999) —8”’”1 i-’5*0’-lI ,,,65+0,10 n .’V?P xl W*R:4O+31O I /.J /,/l 8 c‘d ,5*0,4 ,,2_g ~ L NOTE 3 Sealingface NOTE 1 Pin identification numbering is not necessary. NOTE 2 For a provisional proximity switches. NOTE 3 period, the use of l/2”-20UNF-2A is permissible as an alternative The protective earth pin shall be omitted for class II proximity switches. Figure D.5 - Ml 20 4-pin integrel connector for a.=. proximity switches 84 to Ml 2 on a.c. IS 13947 IEC ‘8”’” 77 -1,78+0,25 4P 4 1 ---@ —————— — 010,5 0 -0,3 !- ~c /’ ‘?’730+0,15 o — 1,65+~’10 ‘2 .- I I A — 2) :2004 (1 999) 1 /-Ezl 5 PLC (Part 5/See 60947-5-2 R4,40+$10 M12’,OX1 la 00,76+0,03 -1 .O1O 2,55 o’ M 41 Pin identification NOTE 2 For a provisional proximity switches. NOTE 3 numbering period, NOTE 3 d is not necessary, the use of l/2”-20UNF-2A is permissible as an alternate The protective earth pin shall be omitted for clase II proximity switchee. Figure D.6 - Ml 20 L I---7Q,2 Sealingface NOTE 1 2,54*0,25 5-pin integrel connector for a.c. proximity switches 85 to M12 on a.c. IS 13947 (Part 5/See 2): IEC 60947-5-2 (1 999) 2004 —8 min. — — 3 max. - 1,7S*0,25 g,lo 10 97,60 [ ~ !-55+:’0 Sealingface --l NOTE 1 Pin identification NOTE 2 For a provisional proximity switches. NOTE 3 numbering is not necessary. period, the use of l/2’’-2OUN2A2A is permissible as an alternative The protective earth pin shall be omitted for class II proximity switches. Figure D.7 - Ml 20 6-pin integral connector 86 for a.c. proximity switchee to Ml 2 on a.c IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 ( 1999) Annex E (normative) Additional E.1 requirements for proximity switches in strong magnetic fields General The provisions E.1.2 of this section of IEC 60947-5 apply unless specified otherwise in this annex. Scope and object This annex is applicable for proximity example electric weld fields (normally switches which operate within strong magnetic fields, for alternating) or electrolytic fields (normally constant). The object of this annex is to state the performance switches which operate in strong magnetic fields. E.2 suitable for use and the test conditions for proximity Definitions E.2.5 magnetic field the magnetic field induction in the meaning of this standard is defined (flux density). The value is stated in teslas [V. s/m2] by the value of the magnetic E.2.5.1 alternating magnetic field a magnetic field with alternating direction of the magnetic induction with a fundamental frequency f of 45 Hz to 65 Hz where the reference value is the peak value of the magnetic induction E.2.5.2 constant magnetic field a magnetic field with a temporal constant value of the magnetic induction, where the reference value is the mean value of the magnetic induction. A total ripple content of *5 YO is allowed E.2.5.3 Immunity E.2.5.3.1 immunity to an alternating magnetic field a proximity switch is immune to an alternating magnetic field when the state of the output is not changed by the influence of the alternating magnetic field under specified conditions E.2.5.3.2 immunity to a constant magnetic field a proximity switch is immune to a constant magnetic field if the change – due to the influence of the constant magnetic field – of the effective operating distance (sr) is not higher than the value specified 87 Is 13947 (Part 5/See 21:2004 IEC 60947-5-2 (1 999) E.3 Classification According E.3.7 to table 1 with the following Classification according Immunity to an alternating E.3.7.1 The immunity to an alternating eighth position. E.3.7.2 Immunity E.3.7.3 to the type of the influencing Immunity magnetic magnetic to a constant The immunity to a constant eighth position. addition: magnetic to an alternating E.7 Construction E.7.2.I.6 E.7.2.1 .6.1 Inductive The frequency of according to 8:5. E.7.5 of operating Immunity The following values a) alternating magnetic Magnetic magnetic Magnetic E.7.5.1 E.7.5.1.1 by a capital letter Y, placed in the field is designated letter Z, placed in the magnetic field by a capital requirements proximity shall be switches stated by the manufacturer, and measured switch in accordance field shall be applied: field maximum O to 0,1 T, peak value; induction: b) constant cycles to a magnetic in the cycles and capacitive operating letter X, placed field and to a constant and performance Frequency by a capital field field is designated The immunity to both types of magnetic eighth position. field field field is designed magnetic magnetic field induction: O to 0,1 T, mean value. Performance In an alternating The state of with E.8.9.1. the output shall E.7.5.1.2 In a constant Subclause switches. 7.2.1 .3.1 applies, The effective the magnetic operating field. Test is made according magnetic not magnetic field change when tested field with the following distance proximity addition (sr) shall not deviate to E.8.9.2. 88 for inductive and capacitive proximity mo~e than *3O ‘Yo over the state range of . ..........——__. —. —-—._....——.. -. .... . . .. . .,., _____ _ ,. .. ...... . ... IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) E.8 Tests E.8.9 Verification E.8.9.1 Immunity E.8.9.1.1 NOTE The of immunity to an alternating Inspection and test sequence Other test configurahons test shall magnetic field (see figure E.1 ) may be set up. be performed as follows: the magnetic a) The sensor (1) for measuring interior of the air-core inductor (4). field shall be arranged in the centre of the inductor (4) shall be energized with alternating current (A), until the b) The air-core oscilloscope (3) shows a peak value of the magnetic induction of 0,1 T. This value /ref of the current shall be noted. NOTE To adjust the value /,ef, it is allowed to use a phase control up to 30°. c) The sensor (1) is removed and the proximity switch (1) shall be arranged in the air-core inductor, so that the reference axis of the proximity switch is identical with the axis of the air-core inductor (4) and the sensing face of the proximity switch is at the mid point (U2) of the air-core inductor. Tests should perpendicular be performed with the orientations to the magnetic field. d) The air-core inductor (4) shall be energized t (s) = 3/f, but not less than 0,1 s. e) The test according proximity switches with the value /ref for an approximate in line and time to d) shall be performed; – with the target located at 3 x Sn from the sensing – with the target located at 1/3 x Sn from the sensing E.8.9.1.2 of the face; face. Results to be obtained The state of the output shall not change by switching on and switching off /ref or during the time /ref current flows in the air-core inductor. After the test, the effective NOTE operating For sensing face diameters distance (s,) shall remain in accordance with 7.2.1.3.1. larger than 18 mm, the target in the off condition may be removed. 89 _________ . . . ... _. . ..-——. _- ———__ IS 13947 (Part ‘5/See 2) :2004 IEC 60947-5-2 (1 999) 5 I : \ 1 Sensor 2 3 4 5 A I D L Figure E.1 - Examples E.8.9.2 Immunity E.8:9.2.1 NOTE Inspection Measuring instrument for the magnetic induction Oscilloscope (to indicate the peak value) Air-core inductor (the number of windings is not stated) AC ammeter Alternating current Proximity switch Interior diameter of the air-core inductor 2100 mm Length of the air-core inductor 2100 mm of test configuration to a constant magnetic and test sequence for verification of the immunity to an alternating field field (see figure E.2) Other test configurations may be set up. The test shall be performed as follows. a) The sensor (1) for measuring the magnetic air gap between the iron cores (3). induction shall be arranged in the centre of the coils (4) shall be energized with direct current (A) until the measuring b) The inductance instrument for the magnetic induction (2) shows the magnetic induction of 0,1 T. The value /ref of the current shall be noted. c) The sensor (1) is removed and the proximity switch (1) shall be arranged in the middle of the air gap between the iron cores (3) and so thatthe sensing face is in line with the outsides of the iron cores (3). 90 . .. . 1S 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (l-999) d) The effective operating distance sr shall be measured by axis approach the direct current A being adjusted to each of the following values: o lref 0,2 /ref 0,4 Iref 0,6 l,e~ 0,8 /ref of -the target with 1,0 /ref E.8.9.2.2 Results to be obtained In the whole range of the direct current A, the deviation of the effective operating distance Sr shall be within *3-0 Y. of the value measured at O /ref. 1 2 3 Sensor Measuring instrument for the magnetic induction Iron core of the magnetic inductor (inner diameter of iron core = 100 mm) 4 Inductance coils 5 DC ammeter A Direct current I Proximity switch AS Air gap between core (3) >2 x proximity switch diameter with a minimum of 40 mm. NOTE For test purposes, the rest of the switch. the parts of the proximity switch affected Figure E.2 - Example by the magnetic of test configuration for verification in a constant magnetic field 91 field may be separated of the immunity from IS 13947 (Part 5/See 2) :2004 IEC 60947-5-2 (1 999) Annex F (informative) Symbols for proximity m switches General symbol v Inductive proximity switch 4-terminal d.c. PNP output, NO NC E >------L+ ) -n- I @ > -m-’ 3 >.. - 0 : L. - L+ 1----- > -n- - L- Ultrasonic proximity switch 2-terminal d.c. NC Retroflective photoelectric proximity switch 3-terminal d.c. NPN output, NO .*. m m c .&i. >.. Capacitive proximity switch 2-terminal d.c. NO .L+ ). . . . . L1/L+ u R ) I -B-’ @ o >------L- m’ > -n- “ NIL- Ttirough beam photoelectric proximity switch 3-terminal d.c. NPN output, NC - ‘L+ - L- Non-mechanical magnetic proximity switch 3-terminal d.c. PNP output, NO Diffuse reflective photoelectric proximity switch 3-terminal d.c. NPN output, NC f I I D ) ~> @ ~>--- NOTE E ‘>----”-L+ 1 >------L+ M -D-, ) -0-, o ”-” L- )------L- It is permitted to have different orientations of the symbols provided that all information required is retaim Figure F.1 - Examples of symbols 92 for proximity awitchea (Continued frornsecond cover) International Standard Corresponding Indian Standard Degree of Equivalence IEC 60112(1979) Method for determining the comparative and the proof tracking indices of solid insulating materials under moist conditions IS 2824: 1975 Method for determining the comparative tracking index of solid insulating materials under moist conditions (first revision) Equivalent IEC 60364 (all parts) Electrical of buildings SP 30:1985 Not Equivalent installations National electrical code IEC 60947-5-1 (2000) Low-voltage switchgear and controlgear — Part 5-1 : Control circuit devices and switching elements — Electromechanical control circuit devices IS 13947 (Part 5/See 1) :2003 Specification for low-voltage switchgear and controlgear : Part 5 Control circuit devices and switching elements, Section 1 Electromechanical control circuit devices (first ;evision) Identical IEC 61000-4-2 (1995) Electromagnetic compatibility (EMC) — Part 4 : Testing and measurement techniques — Section 2 : Electrostatic discharge immunity test — Basic EMC publication IS 14700 (Part 4/See 2) : 1999 Electromagnetic compatibility (EMC) : Part 4 Testing and measurement techniques, Section 2 Electrostatic discharge immunity test — Basic EMC publication do IEC 61000-4-4 (1995) Electromagnetic compatibility (EMC) — Part 4 Testing and measurement techniques — Section 4 : Electrical fast transient/burst immunity test — Basic EMC publication IS 14700 (Part 4/See 4) : 1999 Electromagnetic compatibility (EMC) : Part 4 Testing and measurement techniques, Section 4 Electrical fast transie-nt/burst immunity test — Basic EMC publication do Amendment No. 1 to the above International this standard. Standard issued on June 1999 has already been incorporated in The Technical Committee responsible for the preparation of this standard has reviewed the provisions of the following International Standards and decided that these are acceptable for use in conjunction with this standard: Title /nfernationa/ Standard IEC 60446(1 989) Identification of conductors by colours or numerals IEC 60536(1 976) Classification of electrical and electronic against electric shock IEC 61000-4-3 (1995) Electromagnetic compatibility (EMC) — Part 4: Testing and measurement electromagnetic field techniques — Section 3 : Radiated, radio-frequency, immunity test tEC 61020-5-1 (1991) Electromechanical switches for use in electronic equipment — Part 5: Sectional specification for pushbutton switches — Section 1 : Blank detail specification ISO 630:1995 Structural equipment with regard to protection steels — Plates, wide flats, bars, sections and profiles For the purpose of deciding whether a particular requirement of this standard is complied with, the final value, observed or calculated, expressing the result of ‘a test or analysis, shall be rounded off in accordance with IS 2:1960 ‘Rules for rounding off numerical values (revised)’. The number of significant places retained in the rounded off value should be the same as that of the specified value in this standard. Bureau of Indian Standards BIS is a statutory institution established under the Bureau of /ndian Standards Act, 1986 to promote harmonious development of the activities of standardization, marking and quality certification of goods and attending to connected matters in the country. Copyright BIS has the copyright of all its publications, No part of these publications may be reproduced in any form without the prior permission in writing of BIS. This does not preclude the free use, in the course of implementing the standard, of necessary details, such as symbols and sizes, type or grade designations. Enquiries relating to copyright be addressed to the Director (Publications), BIS. Review of Indian Standards Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards should ascedain that they are in possession .of the latest amendments or edition by referring to the latest issue of ‘BI.S Catalogue’ and ‘Standards: Monthly Additions’. This Indian Standard has been developed Amendments Amend No. from Doc : No. ET 07 (51 45). Issued Since Publication Text Affected Date of Issue BUREAU OF INDIAN STANDARDS Headquarters : Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002 Telephones :23230131,23233375,2323 9402 Telegrams : Manaksanstha (Common to all oflices) Regional Offices : Telephone Central : Manak Bhavan, 9 Bahadur Shah Zafar Mar~ NEW DELHI 110002 Eastern : 1/14 C.I.T. Scheme Vll M, V. 1. P. Road, Kankurgachi KOLKATA 700054 Northern : SCO 335-336, Sector 34-A, CHANDIGARH Southern : C.I.T. Campus, IV Cross Road, CHENNAI Western : Manakalaya, E9 MlDC, Marol, Andheri (East) . . MUMBAI 400093 r2323 7617 123233841 23378499,23378561 { 23378626,23379120 160022 603843 { 609285 600113 { Branches 22541216,22541442 22542519,22542315 (2832 9295,28327858 128327891,28327892 : AHMEDABAD. 13ANGALORE. BHOPAL. BHUBANESHWAR. COtMBATORE. FARIDABAD. GHAZIABAD. GUWAHATI. HYDERABAD. JAIPUR. KANPUR. LUCKNOW. NAGPUR. NALAGARH. PATNA. PUNE. RAJKOT. THIRUVANANTHAPURAM. VISAKHAPATNAM. Pnnted at Prabhat Offset Press, New Delhi-2