chapter 3 cascaded multilevel inverters

advertisement
56
CHAPTER 3
CASCADED MULTILEVEL INVERTERS
3.1
INTRODUCTION
To implement STATCOM at meaningful Mega Volt Ampere
(MVA) level, a high power VSC is needed. But semiconductor devices are
limited to operate in high current and voltage ratings and hence it is
difficult to connect a semiconductor switch directly to medium voltage
networks (2.3-6.9 kV). One solution to this problem is to use multilevel
VSC to increase the output voltage. Multi Level Inverters (MLI) contains
several power semiconductors and capacitor voltage sources (Tolbert et al.
1999). Output voltages of MLIs include the additions of the capacitor
voltages due to the commutation of the switches (Lai and Peng et al. 1996).
(a) Two levels, (b) Three levels and (c) n levels
Figure 3.1
One phase leg of an inverter
57
Figure 3.1 shows a schematic diagram of one phase leg of
inverters with several numbers of levels. The power semiconductor is
represented by an ideal switch. A 2-level inverter, as shown in
Figure 3.1 (a), generates an output voltage of 2-levels with respect to the
negative terminal of the capacitor, while the 3-level inverter shown in
Figure 3.1 (b) generates three voltages, and so on. Thus, the output
voltages of multilevel inverters have several levels and they can reach high
voltages with ‘n’ number of levels (Tolbert et al. 1999).
MLIs have been receiving increasing attention in recent years
because they have many attractive features when compared to the
conventional bipolar inverters (Peng and Lai 1997, Peng 2001).
The features are:
The output voltage distortion is very low due to multiple levels
in the output voltages
The rate of change of voltage dv/dt of switches is low since the
switches endure reduced voltage and due to the lower voltage
swing of each switching cycle
The switches can operate at a lower switching frequency
The
common-mode
voltages
can
be
eliminated
using
sophisticated modulation methods (Rodriguez et al. 2004)
The voltage stress on each switch is decreased due to series
connection of the switches
The rated voltage and total power of the inverter could be safely
increased
58
The THD and filters are reduced due to more output levels
Low acoustic noise and Electro Magnetic Interference (EMI)
can be obtained
The MLI based STATCOM can be directly connected to the
grid without the bulky step-up transformer, resulting in cost and
weight reduction
The MLIs can also respond within 1 ms much faster than the
conventional PWM converters and Advanced Static Var
Compensators (ASVCs) do (Kumar et al. 2010)
The unwanted effects caused by the line frequency converter
transformer such as saturation and DC magnetization can also
be eliminated
A voltage level of three is considered to be the smallest number
in multilevel converter topologies. By switching the main power
semiconductor devices even at the line frequency, a sinusoidal output
voltage waveform with fast system response with a sufficiently high
number of voltage levels can be obtained. This naturally minimizes the
entire system losses and the output filter requirement. In addition, by
adding more H-bridge converters, the amount of var can be simply
increased without redesign of the power stage, and build-in redundancy
against individual H-bridge converter failure can be realized (Peng et al.
1996). Moreover, a three-phase Cascaded Multilevel Converter (CMC)
topology generates different output voltage waveforms and offers the
potential for AC system phase-balancing. This feature is impossible in
other VSC topologies utilizing a common DC link (Alhadidi et al. 2003,
59
Garica and Garica 2000, Lehn et al. 2002). A great combination of the
STATCOM concept and the CMC topology is a promising controller in the
modern FACTS technology (Rodriguez et al. 2002).
3.2
TOPOLOGIES OF MULTILEVEL INVERTERS
Traditional magnetic transformer coupled multipulse VSC has
been a well-known method and has been implemented in 18 and 48 pulse
converters
for
battery
energy
storage
and
STATic
CONdenser
(STATCON) applications, respectively (Walker 1990). These converters
typically synthesize the staircase voltage wave by varying transformer
turns ratio with complicated zigzag connections (Lai and Peng 1996).
Problems of the magnetic transformer coupling method are bulky, heavy,
and lossy. The capacitor voltage synthesis method is thus preferred when
compared to the magnetic coupling method. There are three major
capacitor-voltage synthesis-based multilevel converters, listed as follows:
Diode-clamped multilevel converter
Flying-capacitor multilevel converter
Cascaded converters with separated DC sources
3.2.1
Diode-Clamped Multilevel Converter
The Diode Clamped Multi Level Inverter (DCMLI) also called
the Neutral-Point Clamped (NPC) inverter was presented in 1980
(Bhagwat and Stefanovic 1983). Because the NPC inverter effectively
doubles the device voltage level without requiring precise voltage
matching, this circuit topology prevailed in 1980s. Figure 3.2 shows the
power circuit of one phase leg of a 5-level Diode-Clamped Multilevel
60
Converter (DCMC) or NPCMC. In this topology, semiconductor devices
are connected in series and DC link is divided into smaller capacitors and
connects to switches by clamp diodes. The clamp diode connections are
used to block the current and their numbers in each leg is selected in such a
way so as to have the same block voltages. To generate M voltage levels,
M-1 capacitors are needed on the dc bus (Hosseini Aghdam et al. 2008).
The ground point shown in the Figure 3.2 is the common reference point
and is connected to the middle of DC link. For example, in a 5-level
inverter shown in Figure 3.2, DC bus voltage consists of four capacitors:
C1, C2, C3 and C4. For a DC link voltage of Vdc, the capacitors voltages will
be Vdc/4.
Figure 3.2
Power circuit of one phase leg of a 5-level DCMLI
Table 3.1 shows the phase
voltage levels and their
corresponding switch states. Since all the devices are switched at the
fundamental frequency, the efficiency is high. In Table 3.1, state 1
represents that the switch is ON, and state 0 represents that the switch is
61
OFF. In each phase leg, a set of four adjacent switches is switched ON at
any given time.
Table 3.1
Diode-Clamped 5-level converter voltage levels
and their switch states
Output
Switch state
S1
S2
S3
S4
S5
S6
S7
S8
Vdc/2
1
1
1
1
0
0
0
0
Vdc/4
1
1
1
1
1
0
0
0
0
0
0
1
1
1
1
0
0
-Vdc/4
0
0
0
1
1
1
1
0
-Vdc/2
0
0
0
0
1
1
1
1
Since in DCMLI topology switches should withstand the DC
link voltage, this topology uses high voltage power electronic switches.
DCMLI generates high and steep voltage steps which may affect the life
time of the load; therefore, filters are needed to reduce the ripple in the
inverter output voltage. However these filters are usually heavy and
expensive. In this topology excessive clamping diodes are required.
Real power flow control for the individual is difficult. The main drawback
of DCMLI is the unbalanced DC link capacitor. It restricts the application
of DCMLI to 5 or less number of levels.
3.2.2
Flying-Capacitor Multilevel Converter
The Capacitor-Clamped Multi Level Inverter (CCMLI) or
Flying Capacitor Multi Level Inverter (FCMLI) emerged in the 1990s.
Figure 3.3 shows a 5-level Flying Capacitor Multilevel Converter (FCMC)
62
topology
or
Capacitor
Clamped
Multilevel
Converter
(CCMC).
The voltage level in the FCMC is similar to that of the DCMC. In this
topology the connecting points of the semiconductor devices connected in
series are clamped by extra capacitors. The series connections of clamped
capacitors are necessary to block the current and their numbers in each leg
are selected in such a way that all the capacitors store the same energy.
In this way large and heavy capacitors will not be needed. The output
voltage is symmetric with respect to the neutral point. There is no
interconnection in the three interior loops between balancing capacitors Ca,
Cb and Cc to the DC link sources for each phase, like the DCMC topology.
Table 3.2 shows a possible switch combination of the voltage levels and
their corresponding switch states.
Figure 3.3
Power circuit of one phase leg of a 5-level FCMC
63
Table 3.2
Flying Capacitor 5-level voltage levels and
their corresponding switch states
Output
Switch state
S1
S2
S3
S4
S5
S6
S7
S8
Vdc/2
1
1
1
1
0
0
0
0
Vdc/4
1
1
1
0
1
0
0
0
0
1
1
0
0
1
1
0
0
-Vdc/4
1
0
0
0
1
1
1
0
-Vdc/2
0
0
0
0
1
1
1
1
In FCMC there is more than one combination that can produce
output voltages. This feature of FCMC makes it more flexible than the
DCMC. By nature of this topology, however, the CMC is impossible to
apply in intertie or back-to-back applications, such as Unified Power Flow
Controller (UPFC). Connecting separate DC sources between two
converters in a back-to-back arrangement is not possible because a short
circuit will be introduced when back-to-back converters are not switching
simultaneously. For back-to-back intertie system for UPFC, DCMLI is
most suitable because other two types may require more switching per
cycle and more sophisticated control to balance the voltage.
3.2.3
Cascaded-Multilevel Converters with Separated DC Sources
The Cascade Multilevel Inverter (CMI) was first proposed in
1975 (Ooi et al. 1999, Patil et al. 1999). Separate DC sourced full-bridge
cells are placed in series to synthesize a staircase AC output voltage.
This structure uses cascaded inverters with Separate DC Sources (SDCSs).
This topology includes several H Bridge cells, i.e., Full Bridge Inverters
64
(FBI) connected in series as shown in Figure 3.4 (a). A desired voltage is
synthesized from several independent sources of DC voltages obtained
from batteries, capacitors, fuel cells or solar cells (Mathur and Seyezhai
2008). CMC configuration is increasingly used at high power area due to
its direct high voltage output with no need of a transformer (Sirisukprasert
2004).
Figure 3.4(a)
Figure 3.4(b)
Single phase leg structure of a CMC with SDCS
Individual H-Bridge cell of a CMC
65
The number of output phase voltage levels in a CMC is defined
by M=2s+1; where s is the number of DC sources and M is the output
phase voltage level. By controlling the conducting angles at different
converter levels minimum THD can be obtained. Compared to DCMC and
FCMC, CMC is easy to design and assemble because of the uniform circuit
structure of the converter units. The voltage level of the inverter can be
increased in multiples of two by changing the number of FBI i.e., adding
additional bridge inverter cells to each phase limb.
The proposed structure of the single phase 5-level CMC consists
of eight semiconductor switching devices and two SDCS connected to a
single phase FBI/H-bridge inverter as shown in Figure 3.5.
(a) Mode 1
(c) Mode 3
Figure 3.5
(b) Mode 2
(d) Mode 4
Switching modes of 5-level CMC
66
Table 3.3
CMC 5-level voltage levels and their corresponding
switch states
Switch state
Output
S1
S2
S3
S4
S5
S6
S7
S8
+Vdc
1
0
0
1
1
1
0
0
-Vdc
0
1
1
0
0
0
1
1
0
0
0
0
0
0
0
0
0
+2Vdc
1
0
0
1
1
0
0
1
-2Vdc
0
1
1
0
0
1
1
0
Each inverter level can generate five different voltage outputs,
+2Vdc, +Vdc, 0, and -Vdc, -2Vdc by connecting the DC source to the AC
output by different combinations of the four switches as shown in
Table 3.3. Switches S1, S2, S3, S4, S5, S6, S7 and S8 are switched in different
modes of switching sequences to generate output voltages across AB of the
H-bridge module. Table 3.3 shows one possible switching state to produce
a 5-level output voltage (Marchesoni and Tenca 2002).
3.2.4
Comparison of Power Component Requirements among
Multilevel Converters
Among the three types of multilevel converters (DCMC, FCMC
and CMC) the CMC is easy to design and assemble. The voltage synthesis
in a FCMC has more flexibility than a DCMC. From comparison as shown
in Table 3.4, it shows that the CMC type is more advantageous when
compared to other types where additional diodes and capacitors are
required (Peng et al. 1998). The CMC uses the least number of power
components, but requires separate isolated power sources for each inverter
67
cell. This would normally entail using a large isolation transformer. But for
this only requirement, a CMC is superior to other types and hence it is best
suited for high power applications. Table 3.4 compares the main power
component requirements per phase leg among these three multilevel VSCs,
where M is the number of voltage levels.
Table 3.4
Comparison among multilevel converters based on power
component requirements for phase leg
Flying
Cascaded
capacitors
multilevel
(FCMC)
(CMC)
2(M-1)
2(M-1)
2(M-1)
2(M-1)
2(M-1)
2(M-1)
(M-1)(M-2)
0
0
(M-1)
(M-1)
(M-1)/2
0
(M-1)(M-2)/2
M2+2M-3
(M2+7M-8)/2
Converter
Diode clamped
configuration
(DCMC)
No of switching
devices
No of Diodes
No of clamping
diodes
DC bus
capacitors
Balancing or
clamping
0
capacitors
Total
(7/2)(M-1)
In Table 3.4, the number of main switches and main diodes
needed by each converter to achieve the same number of voltage levels is
the same. But DCMC needs extra clamping diodes, FCMC needs extra
balancing capacitors and CMC needs extra DC bus capacitors. So the total
devices for each converter are different (Tolbert et al. 2002). Even though
68
the CMC needs more capacitors when compared to those needed in the
DCMC, this is not considered to be a disadvantage in STATCOM
applications.
An Ultra CAPacitor (UCAP) bank or a Superconducting
Magnetic Energy Storage (SMES) module for example, can be individually
integrated with each H-bridge converter to enable real power compensation
capability in a STATCOM system. Since each inverter can be seen as a
module with similar circuit topology, control structure and modulation,
incase of a fault in one of these modules, it is possible to replace it quickly
and easily. It is possible to bypass the faulty module without stopping the
load, bringing a continuous overall availability, using an appropriate
control strategy. The reduction in number of devices used in a 5-level
CMLI when compared to conventional inverters is shown in Table 3.5.
Table 3.5
Comparison of number of devices required per phase
Devices used
Conventional
per phase
Inverters
Main power
CMLI
8
5
Diodes
20
8
Capacitors
4
2
switches
For the more than three level configuration used in high voltage
var compensation application like STATCOM, the DCMC voltageimbalance problem cannot be overcome by utilizing control techniques
only (Peng and Lai 1997). Either oversized capacitors or complex balance
circuits are absolutely required. This makes the DCMC unsuccessful in
69
such applications. Similarly in the FCMC topology, an unacceptable
amount of capacitance is required for high voltage levels. In the 7-level
FCMC converter, 15 clamping capacitors plus six DC-link capacitors are
required per phase to achieve the same voltage rating achieved by utilizing
three capacitors in the CMC topology. This requirement makes the system
less cost-effective and they also induce a severe voltage-imbalance
problem in the transient period and at the steady state.
3.2.5
Proposed Asymmetric Cascaded Multilevel Converter
An Asymmetric CMC (ACMC) consists of unequal capacitor
voltages. Instead of using an identical DC link for every H-bridge
converter, different DC links can be used to synthesize a greater number of
output voltage levels without any additional complexity to the existing
topology. A MLI with k partial inverters connected in series is shown in
Figure 3.6. Each cell is supplied by an unequal DC voltage source.
To determine the voltage levels among different DC links, a binary system
can be effectively used, i.e., 1Vdc, 2Vdc, 4Vdc… 2(N-1) Vdc, where N is the
number of H-bridge converters in one phase leg.
The proposed work focuses on ACMC with two unequal DC
sources in each phase to generate seven level equal step multilevel outputs.
This structure is favorable for high power applications since it provides
higher voltage at higher modulation frequencies with a low switching
(carrier) frequency. It means low switching loss for the same THD. It also
improves the reliability by reducing the number of DC sources. However
increased rating of the switches is required for ACMC to withstand the
whole DC bus.
70
Figure 3.6
3.3
Asymmetric cascaded-multilevel converter
MODULATION STRATEGIES
The function of a modulation strategy is to force the inverter
voltages/currents to follow the reference voltages/currents. The modulation
strategies for inverters can be divided into two categories: The voltage
modulation strategies and the current modulation strategies. The output
voltages of the inverter will follow the reference voltages. In the
applications of multilevel inverters, the voltage-mode control systems are
much more popular than the current-mode control systems. The reason is
that the current-mode control systems usually require very high switching
frequencies for smoothing currents.
Most multilevel inverters are used in high-voltage and highpower applications where the power semiconductor switches cannot switch
at very high frequencies. With the voltage-mode control, contrarily, the
inverter can switch at lower frequencies, even at line-frequency for the
cases of multilevel inverters. Hence in this chapter, only the modulation
strategies for the voltage-mode control will be investigated. Depending on
71
their
switching
frequency,
modulation
techniques
for
multilevel
applications can be classified into the following main groups:
1.
Fundamental Frequency Switching (FFS), where each inverter
has only one commutation per cycle.
Selective
Harmonic
Elimination
(SHE)
(Mathur
and
Seyezhai 2008)
2.
High Frequency Switching (HFS), where each inverter has
several commutations per cycle.
Space Vector PWM (SV-PWM) technique
Carrier-Based PWM technique (Leon et al. 1998)
Sinusoidal PWM (Multicarrier PWM)
In all these methods a reference signal is compared to a carrier
signal and output state is selected based on which signal is higher at any
moment. In selection of carrier and reference signals there are some points
which are mentioned below:
Carrier signal is usually a symmetric triangular wave, but a saw
tooth wave can be used either. An important fact is that the symmetric
signal generates fewer harmonics. The reference signal can be continuous
or sampled but synchronous with carrier signal. The second method usually
generates fewer harmonics. Since now-a-days digital controllers are used,
this method is preferred (Veenstra and Rufer 2000).
72
Advantages of FFS
Eliminates low order harmonics in order to reduce the distortion
in the output voltage (Tolbert et al. 1999, Rodrigue et al. 2007).
Disadvantages of FFS
It has no significant effect on higher order harmonics (Zhang
and Fahmi 2003, Chiasson et al. 2003)
Complex calculations are involved in calculating the switching
angles and transferring to a digital system
Results in unbalanced power distribution
With a multi-pulse transformer, this power imbalance can lead
to a distorted input current
Switching losses are high
Different absorbed active power due to different voltage levels
aggravates the DC link voltage imbalance
Advantages of Space Vector PWM Strategy
Enhanced output voltage
Reduction of harmonics
Considerable reduction in THD (Kumar et al. 2008)
73
Disadvantages of Space Vector PWM Strategies
Implementation of space vectors require DSP
High Cost and Complexity involved in implementation
3.3.1
Carrier based PWM
Among various PWM control techniques, the most popular one
is the Multi Carrier PWM (MCPWM) which shifts the harmonics to high
frequencies by using high frequency carriers (Visser et al. 2002).
As electronic devices have limited switching frequencies, high switching
carriers are limited by this constraint (McGrath and Holmes 2000).
Carrier based technique is based on the comparison of a specific sinusoidal
reference signal with high frequency modulator carrier signals as shown in
Figure 3.7 which are usually selected triangular and modified in phase or
vertical positions to reduce the output voltage harmonic content. These
methods have been used widely for switching of multilevel inverters due to
their simplicity, flexibility and reduced computational requirements
compared to FFS and SVM (Ainsworth et al. 2003). The main advantage of
PWM converters is the possibility of controlling the converter gain and
consequently the converter output voltage (Hanson et al. 2002). In the most
popular PWM method, the width of each pulse is varied in proportion to
the amplitude of a sine waveform.
This triangular carrier signal reduces noises in the system ripple
current, harmonics distortion acoustic noise. The comparison of this signal
with a triangular generates the system output (Figure 3.7). Whenever the
reference sinusoidal signal is greater than the triangular wave; the VSI is
fired to switch a positive output and vice-versa for a negative output. It can
74
be seen that the fundamental component of the resulting output voltage is
equal to the reference sinusoid (Liang and Nwankpa 1999).
The number of switching per cycle is a constant predictable
value with the voltage controlled PWM and is determined by the ratio of
triangle-wave modulation frequency to system frequency, or frequency
modulation ratio, mf. The triangular or carrier waveform has a certain
switching frequency, which establishes the frequency at which the
converter switches. The frequency of the carrier waveform determines the
fundamental frequency of the output voltage.
mf
f carrier
f control
(3.1)
By varying the amplitude of the control waveform from zero to
the amplitude of the carrier waveform the pulse width can be varied from
0 to 1800. The amplitude modulation ratio ma defines the ratio between the
control and carrier waveforms:
ma
A control
A carrier
Number of ON or OFF
switchings per cycle
(3.2)
TriangularWave
Frequency
System Frequency
(3.3)
The shortest switching time will always occur at the peaks of the
reference sinusoid. The closer the modulation index is to one, the shorter
this switching time will be, assuming over modulation does not occur
(Michael et al. 1998).
75
Figure 3.7
SPWM modulation
The modulation index can be reduced by increasing the
capacitor voltage, thereby increasing the minimum switching time
(Phoivos D. Ziogas 1981, Jeevananthan et al. 2004, Enjeti et al. 1988).
Modulation index
1
capacitor voltage steady state
(3.4)
With CMC, the maximum modulation index for linear operation
can be high under fundamental frequency mode. For a Multilevel inverter
say a M-level inverter, (M-1) carrier waves are compared with a controlled
sinusoidal modulating signal. The cross over points is used to determine
the switching instants. For a 5-level inverter, a modulating signal and
4 carrier waves are required for each phase of the inverter (Joos et al.
1998).
The widely used MCPWM methods are Phase Shifted (PS),
Phase Disposition (PD), Phase Opposition Disposition (POD) and
Alternative Phase Opposite Disposition (APOD). The methods used for
76
diode-clamped inverter application (PD, POD and APOD) are derived from
the disposition of carriers. If all carriers are selected with the same phase,
the method is known as PD method. A sinusoidal reference waveform is
compared with vertically shifted carrier waveforms.
Figure 3.8
Multilevel SPWM with PS method
in a 7-level inverter
In POD method, the carriers above the zero line of reference
voltage are out of phase and with the carriers below this line is by 180°.
Compared to the PD method, this method has better results with reference
to harmonic performances in lower modulation indices. In POD method,
there is no harmonic at the carrier frequency.
The third group is known as APOD method. Each carrier of this
method is phase shifted by 180° from its adjacent one. POD and APOD
77
methods are exactly the same for a 3-level Inverter. The major difference
in APOD is the presence of the larger amount of third order harmonics.
But the third order harmonics is not considered because it gets cancelled in
line voltages. This method results in a better THD for line voltages when
compared with the POD method.
Figure 3.8 shows PS method in a 7-level CMC. With the two
multilevel SPWM, the dominant lower order harmonics are pushed to
around (M-1)fsw, where fsw is the switching frequency of power
semiconductor devices. In other words, equivalent switching frequency of
the inverter is (M-1) fsw.
In the PS method which is being widely used in cascaded
topologies, all triangular carrier signals have the same amplitude and
frequency but they are phase shifted by 90° to each other so that the output
voltage of every H-bridge is time shifted which leads to the equivalent
switching frequency of the summed output voltage being increased, then
the output harmonic content is reduced without increasing the switching
frequency (Liang et al. 1999).
In the PS method the harmonics of the resultant STATCOM
output voltage only appear as sidebands centered around the frequency of
2Nfs (where N is the No. of H bridge inverters and fs is the frequency of
triangular carrier signals) and its multiples so that the voltage across the
DC capacitor of each inverter is the same. Hence the resultant STATCOM
output voltage has very high equivalent switching frequency even if the
switching frequency of the individual switches is not so high. It is
generally accepted that PS method results in lower distortion factors in the
inverter output voltage for all modulation indices (Calais et al. 2001).
78
PS multicarrier PWM method provides equal switching stress
and power handling for all the cascaded units. The multilevel cascaded
topology with PS carrier reduces effective switching delay due to PWM
and ripple magnitude in the current error. The H-bridge inverters share the
same modulating sinusoidal signal. Frequency ratio of the carrier and
modulating sinusoidal signal is
Kc = fc/fs
(3.5)
The period of triangular carrier
c=
2 /Kc
(3.6)
For ‘n’ number of modules in cascaded inverters, the triangular
carrier is phase shifted by
sh =
c/2n
= 2 /2nKc
(3.7)
The output voltage equivalent frequency ratio is
Keff = 2nKc
(3.8)
If n=3, the equivalent switching frequency of the output voltage
is 6fs.
With regard to modulation, the most popular SPWM control
technique for the NPCMLI and the FCMLI is the PD method. The most
popular SPWM control technique for the CCMLI is the PS method.
However, examining the frequency spectrum of the output phase voltage of
the three types of multilevel inverters, the same value of THD can be
obtained when SPWM multi-carrier with PD carriers and SPWM with PS
carriers are used.
79
3.4
POWER FLOW SOLUTIONS
Most researchers and industries use Newton-Raphson method of
iterative solution (Saadat 1992, Juan 2006, Hieu Le Nguyen 1997, Ghadir
Radman 2007). While traditional power flow program do not include
FACTS controllers, papers have been published dealing with power flow
problem considering FACTS controllers (Ge 1999, Chung 2005, Zhang
2003). Undoubtedly, an important part of power system study is power
flow, thus for power flow control of a system, it is very important to
include this new proposed CMC based controller in power flow equations.
A power flow study will provide extensive information about
the system’s state, weaknesses and possible expansion opportunities.
The most important information given by the power flow is the voltage and
phase angle at each node. Real and reactive power may also be obtained,
though the accuracy of the output depends on the system status.
Power flow solutions base themselves on system constraints and
assumptions, the single-phase representation of the voltage, phase angle,
and power are shown below :
N
Pi
Yin Vi Vn cos
in
n
-
i
(3.9)
Yin Vi Vn sin
in
n
-
i
(3.10)
n 1
N
Qi
n 1
These polar forms of the power flow equations provide the real
and reactive net calculated values. On a theoretical basis, the equation
would work according to the conservation of energy. Since there are losses
in the systems that need to be taken into account, the theoretical equations
will have a disparity of Pi and Qi. The power flow calculation hence
80
depends on the quantities Vi, Vn, Pi, and Qi. The power flow hence,
depends on three types of nodes or buses: The load bus, in which the real
and reactive parts are known. Second is the generation or voltage control
bus, in which the voltage magnitude is maintained at a constant
predetermined value. The last bus, the reference voltage angle bus is
known as the slack bus.
N
N
Pt
N
Pgi
t 1
Plt
t 1
N
N
Qt
t 1
N
Qgi
t 1
(3.11)
0
t 1
Q lt
(3.12)
0
t 1
A complexity arises in trying to simultaneously solve the
equations. Since the functions for real power Pi and reactive power Qi are
dependent on non linear functions of the state variables voltage Vi and
phase angle
i,
iteration methods are employed to solve for both sides of
Equation (3.11) to try to solve for the two remaining constants. Various
methods can be used to speed up the iteration process and make it converge
within a certain error margin (Chattopadhyay et al. 1994). The NewtonRaphson (N-R) method is one of the fastest iterative methods (Fuerte
Esquivel et al. 2000). This method begins with an initial approximation and
generally converges at a zero of a given system of nonlinear equations
(Chong Han et al. 2008, Blaabjerg et al. 2004).
3.4.1
Switching
Angle
Calculation
using
Newton-Raphson
Method
Selection of switching angles can be done either by using the
SHE method or THD minimization method (Lehn and Iravani 1998).
SHE method is preferred when the number of levels is low.
81
THD minimization method is preferred when the number of levels is high,
so that solving of complex transcendental nonlinear equations can be
avoided (Chen and Spooner 2003). In the cascaded converter, the
capacitance requirement is as follows:
I Lrms
2 f Vdc
Cdc cascade =
(3.13)
The inverter output voltage V av is the sum of three H-bridge
output voltages in one leg, i.e.
Vav VH1 VH 2 VH 3
(3.14)
The voltage V av can be varied by varying the output of each
FBI level which can be obtained by switching the devices. The harmonic
content of V av can be obtained from the Fourier series analysis as
Vav
ao
a h cos( h t )
h 1
bh sin( h t )
(3.15)
h 1
With odd harmonics, a o = o and a n = o
Vav
(3.16)
b h sin( h t ) for h 1,3,5...
h 1
For ‘n’ level, the Fourier series of the quarter-wave symmetric
parallel connected multi-level waveform is given as
Vav
4 Vdc
( 2 K 1)
2n 1
cos 2 k 1
K 1
i 1
i
sin 2k 1 t
(3.17)
82
Fundamental rms voltage
Va
4Vdc
2
2n 1
cos
(3.18)
i
i 1
Harmonic rms voltage
n
2 1
4Vdc
cos [ 2k 1 i ]
2(2k 1) i 1
for k 1,2,3...... for i 1,2, N 1) / 2
V2k 1
(3.19)
Amplitude modulation index
m
Va
Va (max)
1
7
7
cos( i )
(3.20)
i 1
Va is the amplitude command of the inverter output voltage and
Va(max) is the maximum obtainable amplitude of the phase voltage when all
switching angles
i
are equal to zero. For releasing SPWM, a higher
frequency triangular wave is compared with the sinusoidal reference wave
of desired frequency (McGrath and Holmes 2000).
The value of individual capacitance Ci required is given as
Ci
qi
Vci
T/4
2I cos tdt
(3.21)
i(t )
mI
2 E Vci
(3.22)
83
where qi is the deviation in the charge on the capacitor, Vci is
the average capacitor voltage,
i is
the switching timing angle of FBI unit.
Using amplitude modulation index m and Va in NR numerical
technique, switching angles are obtained as shown in Table 3.6 (Jiang and
Lipo 2005).
Table 3.6
Switching angles for various modulation indexes
Modulation
Switching timing angles (rad)
index (m)
1
2
3
4
5
6
7
0.45
0.357
0.903
0.804
1.158
1.227
1.424
1.603
0.51
0.445
0.697
0.612
0.902
1.091
1.174
1.208
0.64
0.207
0.558
0.393
0.849
0.807
0.910
1.167
0.78
0.069
0.243
0.206
0.641
0.651
0.818
0.852
0.81
0.107
0.172
0.181
0.273
0.341
0.506
0.828
When m is varied, the inverter either absorbs or generates
reactive power from the power system network. For low m, the inverter
voltage will be greater than the bus voltage and vice versa. For high m, the
modulation angles are less. These values are used for calculating
capacitance values. The total capacitance required for a 3-phase M level
converter is:
C=3
ci
(3.23)
84
3.5
PROPOSED MODULATION STRATEGY
VSC produce harmonics due to switching operation of power
electronic devices (Acha et al. 2001, Singh et al. 1999). The harmonics in
the output voltage of power electronic converters can be reduced using
PWM switching techniques (Mohan et al. 1995). PWM methods reduce the
harmonics by shifting frequency spectrum to the vicinity of high frequency
band of carrier signal (Yuvarajan and Abdollah Khoei 2002). The SPWM
technique, however, inhibits poor performance with regard to maximum
attainable voltage and power (Quek and Yuvarajan 1995). A novel PWM
technique called Inverted-Sine Carrier PWM (ISCPWM) is proposed for
harmonic reduction of the output voltage of ac-dc converters. The proposed
control scheme based on ISCPWM can maximize the output voltage for
each modulation index.
3.5.1
Inverted Sine Carrier PWM Strategy
The ISCPWM method uses a sinusoidal reference signal and an
inverted sine carrier as shown in Figure 3.9 which has better spectral
quality and higher output limit as compared to the conventional SPWM,
without any pulse dropping. The ISCPWM strategy reduces the THD
without losses and also enhances the fundamental output voltage
particularly at lower ma. Although solutions have been already applied
before, this proposed work is focused on adapting and improving this type
of solution to ISCPWM in STATCOM applications.
In this method the control signals have been generated by
comparing sinusoidal reference signal with a high frequency inverted sine
carrier. The carrier frequencies are selected in such a manner that the
number of switching in each band is equal. The proposed modulation
85
technique maximizes the output voltage and gives a low THD. A PI
controller is employed to enhance the performance of the asymmetric MLI
using the proposed modulation strategy.
For the ISCPWM pulse pattern, the switching angles may be
computed in the same way as PWM scheme. The equations of inverted sine
wave are given by Equations (3.24) and (3.25) for its odd and even cycles
respectively.
Figure 3.9
Generation of pulses using ISPWM
y = 1- sin {Mf x -
/ 2 (i-1)}
(3.24)
y = 1- sin {Mf x -
/ 2 (i-2)}
(3.25)
The switching angles for ISCPWM scheme can be obtained
from Equations (3.26) and (3.27)
Ma sinqi+ sin( Mf q i -
/ 2 (i-1) = 1, i = 1,3,5...
(3.26)
Ma sinqi+ sin( Mf q i -
/ 2 (i-2) = 1, i = 2,4,6...
(3.27)
86
ISCPWM technique is classified into two types based upon the
frequency of carrier waves
Unipolar ISCPWM (UISCPWM)-
employ carriers of same
frequency
Variable Frequency ISCPWM (VFISCPWM)- employ carriers
of variable frequency
In the gating pulse generation of the proposed ISCPWM scheme
shown in Figure 3.9, the triangular carrier waveform of PWM is replaced
by an inverter sine waveform.
3.5.2
Proposed Variable Frequency ISPWM Technique
The proposed control strategy replaces the conventional fixed
frequency carrier waveform by variable frequency inverted sine wave.
In unipolar (fixed) ISPWM the switching scheme includes three triangular
carrier signals. The signals are time shifted by Ts/3, where Ts is the period
of these carrier signals. The 3 H-Bridges share the same modulating
sinusoidal signal V(t) and -V(t). The harmonics of the output voltage
appear as sidebands centered around the frequency of 2Nfs and its
multiples, provided that the voltage Vdc of each inverter is the same.
The current harmonics caused by DC capacitor voltage ripple is neglected.
The output voltage has very high equivalent switching frequency even if
the switching frequency of the individual switches is not so high.
The ISPWM has a better spectral quality and a higher fundamental voltage
compared to the triangular based PWM. But the main drawback in the
conventional fixed frequency ISCPWM is the marginal boost in the
magnitude of lower order harmonics and unbalanced switch utilization.
87
This is overcome by employing variable frequency inverted sine carrier
signals. The VFISPWM scheme is more favorable than the conventional
ISPWM technique for use in asymmetric multilevel inverter.
Based on the discussions in the previous sections, there are
several well known SPWM strategies for CMCs. Compared to the
conventional triangular carrier based PWM, the Inverted Sine Carrier
PWM (ISCPWM) has a better spectral quality and a higher fundamental
output voltage without any pulse drop. In the fixed frequency carrier based
PWM the switch utilization in multilevel inverters gets affected and results
in unbalanced switch utilization. In order to balance the switching duty
among the various levels in inverters, a variable frequency carrier based
PWM called as VFISPWM has been suggested. This novel method
combines the advantage of inverted sine and multi frequency carrier
signals. The VFISPWM provides an enhanced fundamental voltage, lower
THD and minimizes the switch utilization among the various levels in
inverters.
3.6
IMPLEMENTATION OF ASYMMETRIC MULTILEVEL
INVERTER
A detailed study of the technique used, as shown in Figure 3.10
is carried out for THD measurement. In order to verify the operation
behavior and examine the harmonic content of the ACMC applying
PD SPWM, the circuit is simulated using Matlab / Simulink for different
modulation factors and normalized carrier values. Furthermore, a PI
controller is used to control the MLI using the proposed PWM technique.
PD based unipolar ISPWM strategy is employed for pulse generation.
In the conventional PWM method, triangular wave is used as a carrier but
they are replaced by inverted sine carrier waves modulation strategy.
88
Figure 3.10 Asymmetric cascaded 7- level inverter
The first H-Bridge H1 in Figure 3.10 consists of a separate DC
source Vdc1, and the second H-Bridge H2 consists of a DC source Vdc2.
The output of H-Bridge-1 is v1 (t) and the output of H-Bridge-2 is v2 (t).
Hence the total output voltage is given by v(t) = v1(t) + v2(t). By alternately
opening and closing the switches S1,S4 and S2,S3 of H-Bridge-1
appropriately, output of H1 v1(t) can be made equal to +Vdc, 0 or -Vdc.
Similarly the output voltage of H-Bridge-2 v2(t) can be made equal to
-Vdc/2, 0 or +Vdc/2 by opening and closing the switches of H2. Hence v(t)
takes values -3/2Vdc, -Vdc, -1/2Vdc, 0, +1/2Vdc, +Vdc, +3/2Vdc.
An inverted sine wave of high switching frequency is taken as a
carrier wave and is compared with that of the reference sine wave.
The pulses are generated whenever the amplitude of the reference sine
wave is greater than that of the inverted sine carrier wave. The output
voltage waveform comprising of 7-levels is obtained by modulating the
inverted sine carriers. By employing this new modulation technique the
fundamental voltage can be improved throughout the working range.
For switching of these topologies, various modulation strategies have been
89
already reported in section 3.3. Among them the carrier-based PWM
method uses several triangular carrier signals, keeping only one modulating
sinusoidal signal.
Table 3.7 shows the switching sequence for a 7-level ACMC
shown in Figure 3.10. The carriers will have the same frequency and the
same peak to peak amplitude and are disposed so that the bands they
occupy are contiguous. The zero reference is placed in the middle of the
carrier set. The modulating signal is a sinusoid of frequency 50 Hz.
Table 3.7
Switching sequence for 7-level ACMC
Switches in
Reverse diode in
Conduction
conduction
S1, S4, S8
S7
During
S4, S5, S8
S3
Positive
S1, S4, S5, S8
-
S4, S5, S8
S3
S1, S4, S8
S7
S2, S3, S7
S8
S3, S6, S7
S4
S2, S3, S6, S7
-
S3, S6, S7
S4
S2, S3, S7
S8
Half Cycle
During
Negative
Half Cycle
At every instant each carrier is compared with the modulating
signal. Each comparison gives the value one if the modulating signal is
greater than the triangular carrier, zero otherwise. The results are added to
90
give the voltage level, which is required at the output terminal of the
inverter.
3.6.1
Performance Evaluation of CMC Employing Conventional
PWM
In CMC employing conventional PWM technique as shown in
Figure 3.11, triangular carrier waves are modulated with reference sine
wave for pulse generation (Jochim 1992). The pulses are generated
whenever the amplitude of the reference sine wave is greater than that of
the triangular carrier wave. Simulation circuit for the generation of
triangular wave is shown in Figure 3.12. The carrier and reference sine
waveforms for conventional PWM technique are shown in Figures 3.13
and 3.14 respectively. The generated carrier waves of frequency 4000 Hz
are modulated with reference sine wave of frequency 50 Hz for pulse
generation.
Figure 3.11 Simulation circuit of conventional cascaded MLI
91
Figure 3.12 Simulation circuit for the generation of triangular wave
Figure 3.13 Triangular carrier waves
200
150
100
50
0
-50
-100
-150
0
0.001
0.002
0.003
0.004
0.005
Time(seconds )
0.006
0.007
0.008
0.009
0.01
Figure 3.14 Triangular carrier and reference sine waveforms
for conventional PWM
92
300
200
100
0
-100
-200
-300
0
0.002
0.004
0.006
0.008
0.01
Time(sec)
0.012
0.014
0.016
0.018
0.02
Figure 3.15 Output voltage of CMC (Conventional PWM)
Figure 3.16 FFT window for output voltage (Conventional PWM)
The obtained pulses are then applied to conventional 7-level
CMC and the obtained output voltage waveform of value 265.6 V is shown
in Figure 3.15. With the optimum frequency of 4000 Hz, in conventional
PWM method the obtained THD value is 30.99% as shown in Figure 3.16.
3.6.2
Performance Evaluation of CMC Employing Unipolar
ISCPWM
The proposed unipolar control strategy replaces the triangular
based carrier waveform by inverted sine wave. The application of unipolar
93
PWM to inverted sine carrier results in the reduction of carrier frequencies
or its multiples. So, the advantage of inverted sine and unipolar PWM are
combined to improve the performance of the CMC. The ISCPWM method
uses the sine wave as a reference signal while the carrier signal is an
inverted high frequency sine carrier that helps to maximize the output
voltage for a given modulation index.
Figure 3.17 Simulation circuit for the generation of unipolar inverted
sine carrier waves
Time (secs)
Figure 3.18 Waves employed for generating inverted sine waves
94
Figure 3.17 shows the simulation circuit for the generation of
inverter sinewaves. Figure 3.18 and Figure 3.19 shows the waves
employed for the generation of unipolar (fixed) ISCPWM signals. Inverted
sine waves of frequency 4000 Hz is generated using the simulation circuit
shown in Figure 3.17. This circuit involves the generation of six inverted
sine waves (Figure 3.20) each of amplitude 50 V among which three
inverted sine waves are compared with positive half of reference sine wave
of amplitude 150 V for pulse generation.
Time (secs)
Figure 3.19
Unipolar inverted sine carrier waves
Figure 3.20 Inverted sine carrier waves (7-level)
95
Time (secs)
Figure 3.21 Reference and inverted sine waveforms
for unipolar ISPWM
300
200
100
0
-10 0
-20 0
-30 0
0
0 .0 02
0.0 04
0.0 06
0.0 08
0 .01
Tim e(sec)
0.012
0 .014
0 .016
0 .018
0.02
Figure 3.22 Output voltage of conventional 7-level CMC
employing unipolar ISCPWM
Figure 3.21 shows the inverted sine carrier waveforms along
with the reference sine waveform for unipolar ISPWM.
96
Figure 3.23 FT window for output voltage (Unipolar ISPWM)
With the proposed Unipolar ISCPWM technique, the obtained
fundamental component and THD values are shown in Figure 3.22 and
Figure 3.23 respectively. Table 3.8 gives a comparision of voltage output
levels and THD values of both conventional and unipolar ISCPWM
inverters.
Table 3.8
Comparison of unipolar ISCPWM with conventional
PWM
PWM
Technique
Conventional PWM
Unipolar ISPWM
Fundamental
Output Voltage
(in volts)
266.6
Total Harmonic
Distortion
(%)
30.97
278
21.82
On implementing Unipolar ISPWM technique for conventional
CMC, THD is reduced considerably by a factor of around 9%.
Hence Unipolar ISCPWM technique is extended for the proposed ACMC,
in order to overcome the disadvantages of conventional CMC.
The generated pulses are then applied to asymmetric cascaded MLI.
97
Output voltage waveform of single phase and 3 phase 7-level ACMC
employing Unipolar ISCPWM technique is shown in Figure 3.24 and
Voltage amplitude
Figure 3.25 respectively.
Time (secs)
Voltage amplitude
Figure 3.24 Output voltage waveform of single phase 7-level ACMC
Time (secs)
Figure 3.25 Output voltage waveform of three phase 7-level ACMC
(Unipolar ISCPWM)
98
3.6.3
Performance Evaluation of CMC Employing VFISCPWM
The proposed control strategy replaces the conventional fixed
frequency carrier waveform by variable frequency inverted sine wave.
Simulation circuit for Variable Frequency Inverted Sine Carrier (VFISC)
generation is shown in Figure 3.26. Pulses for the asymmetric cascaded
MLI are generated by modulating carrier waves with reference to sine
wave of frequency 50 Hz. The obtained pulses from VFISPWM strategy
are then applied to the ACMC. The proposed PWM strategy is also
extended for a three phase asymmetric cascaded MLI by introducing a
phase displacement of 120° between each phase.
Figure 3.26 Simulation circuit for the generation of variable
frequency inverted sine carrier waves
99
Time (secs)
Figure 3.27 Carrier and inverted sine waveforms
for VFISCPWM technique
Time (secs)
Figure 3.28 Variable frequency inverted sine carrier waves
The variable frequency inverted sine carrier waves shown in
Figure 3.28 is compared with sine waveforms as shown in Figure 3.27.
Voltage amplitude
100
Time (secs)
Figure 3.29 Output voltage waveform of single phase 7-level ACMC
Voltage amplitude
employing VFISCPWM
Time (secs)
Figure 3.30 Output voltage waveform of three phase 7-level ACMC
employing VFISCPWM
Output voltage waveforms of single phase and three phase
7-level ACMC employing VFISCPWM technique are shown in
Figure 3.29 and Figure 3.30 respectively.
Voltage amplitude
101
Time (secs)
Figure 3.31 Output voltages waveform of three phase 7-level ACMC
Figure 3.32 FFT window for output voltage (Unipolar ISPWM)
102
The three individual single phase output voltage waveforms of a
three phase 7-level ACMC is shown in Figure 3.31. On implementing
VFISPWM technique for asymmetric cascaded MLI, THD is reduced by a
factor of around 2% as shown in Figure 3.33 when compared to unipolar
ISCPWM strategy as shown in Figure 3.32. The VFISPWM provides an
enhanced fundamental voltage, THD and minimizes the switch utilization
among the various levels in inverters. In this method the control signals
have been generated by comparing sinusoidal reference signal with a high
frequency inverted sine carrier. The carrier frequencies are selected in such
a manner that the number of switching in each band is equal.
Figure 3.33 FFT Window for output voltage (VFISPWM)
The proposed modulation technique for the proposed inverter
topology maximizes the output voltage and gives a low THD of 5.80%.
The FFT window for the output voltage waveform of ACMC employing
fixed frequency ISCPWM is shown in Figure 3.32 and that of ACMC
employing VFISPWM is shown in Figure 3.33.
103
Table 3.9 gives the comparison of THD values obtained for
unipolar ISPWM and VFISPWM control strategies.
Table 3.9
Comparison of THD values - VFISPWM
with unipolar ISPWM technique
PWM
Technique
Total Harmonic
Distortion
(%)
Unipolar ISPWM
7.01
Variable freqency ISPWM
5.80
Some inferences made from the above waveforms are
VFISCPWM technique provides better spectral quality and
reduced THD when compared to Unipolar ISCPWM technique
ISPWM technique provides better spectral quality and a higher
fundamental component when compared to conventional PWM
technique
Harmonics of carrier frequencies and its multiples are not
produced in ISPWM technique
With ISPWM technique the THD is also reduced compared to
conventional PWM technique
The THD decreases with increase in switching frequency and
the fundamental component of voltage increases with increase in switching
104
frequency and is higher for inverted sine carrier when compared to the
conventional triangular carrier.
3.7
NEURAL NETWORK CONTROL OF ACMC
The SPWM technique, however, exhibits poor performance with
regard to maximum attainable voltage and power. The fundamental
amplitude in the SPWM output waveform is smaller than the rectangular
waveform. Among various PWM control techniques the most popular one
is the Multi Carrier PWM (MCPWM) which shifts the harmonics to high
frequencies by using high frequency carriers. But electronic devices have
limited switching frequencies. Hence high switching carriers are limited by
the power electronic devices having limited switching frequencies.
Harmonic Elimination Method (HEM) can be applied for ACMCs to
eliminate harmonics with the use of low switching frequency devices
(Kumar et al. 2008). However this method requires complex calculations of
switching angles.
To overcome this constraint, a HEM based on Artificial Neural
Network (ANN) is proposed to control the ACMC. The proposed work is
based on Multi-Layer Perceptron (MLP) method. The performance is
evaluated with a 7-level ACMC ANN controller.
A multiport system in ANN as shown in Figure 3.34 consists of
a triggering system which consists of eight switches S1-S8. The outputs of
these switches rely upon the output of the neural network connected to it.
The output of this multiport system is given to the H-bridge inverter.
The sum of the voltages of the two driver circuits gives the output voltage
at the scope.
105
Figure 3.34 Multiport system
Figure 3.35 ACMC simulation circuit using ANN controller
Figure 3.35 shows the ACMC simulation circuit of a 7-level
ACMC using ANN controller based on Matlab / Simulink.
106
Figure 3.36 ACMC simulation circuit using conventional
SPWM controller
Figure 3.37 Output voltage of the 7-level ACMC
using ANN controller
Figure 3.36 shows the ACMC simulation circuit using
conventional SPWM controller based on Matlab / Simulink. The output
voltage of ACMC is shown in Figure 3.37 using the simulation circuit
shown in Figure 3.35.
107
Table 3.10 gives the switching sequence of a 7-level ACMC
with ANN.
Table 3.10
Switching sequence
INPUT
SWITCHING
VOLTAGE
LEVELS
0
1
0
0
0
0
0
0
0
0
12
2
1
0
0
1
0
1
0
1
24
3
0
0
0
0
1
0
0
1
36
4
1
0
0
1
1
0
0
1
24
5
0
0
0
0
1
0
0
1
12
6
1
0
0
1
0
1
0
1
0
7
0
0
0
0
0
0
0
0
-12
8
0
1
1
0
0
0
1
1
-24
9
0
0
0
0
0
1
1
0
-36
10
0
1
1
0
0
1
1
0
-24
11
0
0
0
0
0
1
1
0
-12
12
0
1
1
0
0
0
1
1
S1 S2 S3 S4 S5 S6 S7 S8
The H-Bridge enables the voltage to be applied across a load in
either direction. The switching table shows the instances at which the
switches S1-S8 are triggered when various voltages are applied. Such a
continuous switching by giving high (1) and low (0) input signals gives rise
to a multilevel output.
Table 3.11 displays the comparison of THD values obtained for
HEM and SPWM control techniques.
108
Table 3.11
3.8
Comparison of HEM with conventional SPWM
Modulation strategy
THD (%)
Conventional SPWM
18.43
Neural implementation of HEM
9.11
FPGA BASED HARDWARE IMPLEMENTATION
In the proposed system, Field Programmable Gate Array
(FPGA) based gate signal generation is used. Complex control algorithms
required by MLIs can be implemented in FPGA but not in real time using
standard low cost microcontrollers or DSP. FPGA allows simultaneous
execution of all control procedures, enabling high performance in repetitive
and massive computation, high computation speed and dynamic response.
However microcontrollers and DSP controllers cannot satisfy the demand.
Figure 3.38 Block diagram of Spartan 3E-Xilinx (Xc3s500-Fg320)
109
Figure 3.39 FPGA kit programmed with Xilinx ISE tool
Figure 3.40 FPGA kit (Spartan 3E-[Xc3s500-Fg320])
and two stage cascaded inverter
The proposed modulator has been implemented in FPGA-Xilinx
Spartan 3E (Figure 3.38) and tested with the prototype inverter.
The experimental verification of multilevel modulation and control is
110
obtained through the laboratory model of a single phase, 5-level inverter
based STATCOM. A FPGA based digital processor is used for the
modulation of a multilevel inverter.
The proposed work presents the design, implementation and test
of a novel real-time controller for a 5-level multilevel converter based on a
FPGA. The main advantages of FPGAs are that they provide higher
performances in repetitive and massive computations. Multilevel
converters, moreover, often require complex control algorithms which
cannot
be
implemented
in
real-time
using
standard
low
cost
microcontrollers or DSP, but can be successfully implemented using
hardware description languages and FPGA. FPGA includes on-chip PWM
controllers
making
implementation
easy.
Hence
the
real
time
implementation of the proposed inverter using FPGA is carried out in the
proposed work. The hardware implementation of a two stage CMC
(Figure 3.40) in FPGA kit programmed with Xilinx ISE tool is shown in
Figure 3.39.
Xilinx Spartan 3E FPGA IC is used for controlling the width of
the pulses from PWM generator, by fixing either the frequency or the
voltage so that the MOSFET’s are turned ON and OFF in the desired
sequence.
Ability to re-program in the field to fix bugs
Small size and increased speed
Offer easy, fast and flexible design and implementation
111
The inherent parallelism of the logic resources on an FPGA
allows for considerable computational output even at a low
MHz clock rates
3.8.1
Generation of gating pulses for the proposed PWM
The gating signals for the 5-level inverter employing the
ISPWM technique is generated using FPGA processor as shown in
Figure 3.41 and tested with the proto-type inverter. Figure 3.42 shows the
VLSI Simulation: Model SIM PWM Pulses. The performance evaluation
of an ISPWM multilevel inverter is done using Matlab/Simulink
environment and minimized THD is determined.
Figure 3.41 Generation of PWM pulses from FPGA
112
Figure 3.42 VLSI simulation : model SIM PWM pulses
The Spartan 3E (Xc3s500-Fg320) is programmed through
Xilinx ISE tool via PC through IMPACT port. With this programme, the
inverter is switched ON and then the waveforms are obtained as shown in
Figure 3.43.
Figure 3.43 5-level output voltage waveform for ISCPWM inverter
113
As per the program in the Spartan 3E-(Xc3s500-Fg320), it
creates the gate signals for the MOSFETs used in the two stage cascaded
inverter. If the gate pulses are given, the respective output is obtained as
shown in the Figure 3.43.
After verifying the design by simulation, synthesis is carried
out. Finally placement, routing and timing optimizations are performed.
The additional advantage in the ISCPWM is that it does not require any
mode changing as required in conventional PWM. Regrettably, the
ISCPWM causes marginal increase in the lower order harmonics, but
except third harmonics all other harmonics are at an acceptable level. It is
worth noting that for three-phase applications, the heightened third
harmonics need not be bothered.
Figure 3.44 Generated pulses using ISPWM technique in CRO
114
Figure 3.45 Cascaded 7-level inverter output waveform in CRO
The hardware implementation of ISCPWM technique for a
7-level CMC done using microcontrollers and the waveforms of the
generated pulses and voltage output measured using a CRO are shown in
Figures 3.44 and 3.55 respectively.
3.9
CONCLUSION
For transmission and distribution voltage levels, the multilevel
VSC offers various advantages over its counterparts. Among the various
multilevel converter topologies, the CMC is the most promising alternative
for the STATCOM application. Analytical, simulated and experimental
results show the superiority of the proposed system. Using MLI, the
switching frequency increases while the ripple magnitude reduces.
The proposed modulation and control scheme is validated through the
experimental results that are obtained using the prototype model of a single
phase, 5-level inverter. To achieve the same number of output voltage
levels, the CMC requires the least total number of components. With its
115
modular structure, the CMC can flexibly expand the output power
capability that corresponds to the requirements of the connected power
system
networks.
Additionally,
its
modularity
is
favorable
to
manufacturing. Moreover, redundancy can be easily applied in the CMC to
enhance reliability for the entire system. This chapter mainly focused on
the ISPWM technique for CMC. Based on the proposed CMC model, the
ISPWM technique was first presented for the 5-level and then for the
7-level CMC and its performance and stability were verified by both
computer simulations and experiments. The experimental results are very
consistent with the simulation results. Moreover, the results demonstrate
the accuracy of the model and the superior performance of the ISPWM
control technique.
Download