UFO-6W Emergency Lighting Fluorescent Battery Pack INSTALLATION INSTRUCTIONS - Auto Select UFO-6W IMPORTANT SAFEGUARDS INSTALLATION INSTRUCTIONS -Auto Select When using electrical equipment, basic safety precautions should always be followed including the following. ! IMPORTANT SAFEGUARDS ! READ AND FOLLOW ALL SAFETY WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE INSTRUCTIONS FOLLOWED, INCLUDING THE FOLLOWING: 1. To prevent high voltage from being present on red & yellow output leads prior to installation, inverter READ AND FOLLOW ALL SAFETY INSTRUCTIONS connector must be open. Do not join inverter connections until installation is complete and AC power is supplied to the emergency ballast. 1. To prevent high voltage from being present on red & yellow output leads prior to installation, 2. This inverter product connector is for use with 16W through (2ft -inverter 4ft) T8 and T12 single or bipin for one or twoand lamp must be open. Do40W not join connector untilpin installation is complete emergency mode operation,toinstant start and rapid start; 40W through 215W (5ft - 8ft) T8 and T12 single AC power is supplied the emergency ballast. pin bipin for oneislamp emergency mode operation, instant and rapid start; and 16W through 31W 2. orThis product for use with 16 W through 40 W (2ft - 4ft)start T8 and T12 single pin or bipin for one U-Bend T8 bipin one or two lampoperation, emergency modestart operation, instant start rapid start or two lamp for emergency mode instant and rapid start; 40 and W through 215fluorescent W (5ft lamp 8ft) fixtures. T8 and T12 single pin or bipin for one lamp emergency mode operation, instant start and 3. Makerapid surestart; all connections in accordance with the National Electrical any local mode regulations. and 16 W are through 31 W U-Bend T8 bipin for one or twoCode lampand emergency 4. To reduce the risk of electrical shock, both normal and emergency power supplies and inverter operation, instant start and rapiddisconnect start flourescent lamp fixure 3. Make of sure connections arebefore in accordance connector the all emergency ballast servicing. with the National Electrical Code and any local 5. This regulations. emergency ballast is for factory or field installation in either the ballast channel or on top of the fixture. 4. To reduce the risk of shock, disconnect normal and emergency power supplies and 6. This product is suitable forelectric damp locations where the both ambient temperature is 0ºC minimum, +50ºC maximum. inverter connector of the emergency ballast before servicing. Product is also suitable for installation in sealed and gasketed fixtures. Product is not suitable for heated air 5. This emergency ballast is for factory or field installation in either the ballast channel or on top of outlets and wet or hazardous locations. the fixture.AC power source is required (120 through 277 VAC, 50/60 Hz). 7. An unswitched 6. This product is suitable for damp locations where the ambient temperature is 0°C minimum, 8. Do not install near gas or electric heater. +50°C maximum. Product is also suitable for installation in sealed and gasketed fixtures. Product 9. Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field replaceable. is not suitable for heated air outlets and wet or hazardous locations. Contact the manufacturer for information on service. 7. An unswitched AC power source is required (120 through 277 VAC, 50/60 Hz). 10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. 8. Do not install near gas or electric heaters. 11. Do not use this product for other than intended use. 9. Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field 12. Servicing should be performed by qualified service personnel. replaceable. Contact the manufacturer for information on service. 10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe CAUTION: Verify that all replacement lamp types marked on the installed luminaire are also identified as suitable for use condition. 11. Do not use this product for other than intended use. with this inverter/charger pack. 12. Servicing should be performed by qualified service personnel. SAVE THESE INSTRUCTIONS CAUTION: Verify that all replacement lamp types marked on the installed luminaire are also identified as suitable for use with this inverter/charger pack. 2 1 REV B C DATE 11.OCT.2010 RECORD EC-091027001 EC-160616002 DESN CHCK MDB JEB SGH JEB SAVE THESE INSTRUCTIONS B 16.JUN.2016 WARNING - This product contains chemicals known to the State of California to cause cancer, birth defects, and/or other reproductive harm. Thoroughly wash hands after installing, cleaning, or otherwise touching this product. B 56B5 EMERGENCY LIGHTING EQUIPMENT CONTAINS NICKEL-CADMIUM RECHARGEABLE BATTERY. MUST BE RECYCLED OR 57B9 EXIT FIXTURE DISPOSED OF PROPERLY. Ni - Cd WARNING – This product contains chemicals known to the State of California to cause cancer, birth defects and/or other NO LISTING 56B5 LISTING 57B9 LISTING INSTALLATION INSTALLATION INSTALLATION WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON RED AND WARNING: PREVENT HIGH VOLTAGE FROM BEING PRESENT RED AND YELLOW WARNING: WARNING: TO TOTO PREVENT PREVENT HIGH HIGH VOLTAGE VOLTAGE FROM FROM BEING BEING PRESENT PRESENT ON ONON RED RED AND AND YELLOW YELLOW YELLOW OUTPUT LEADS PRIOR TO INSTALLATION, INVERTER CONNECTOR OUTPUT LEADS PRIOR INSTALLATION, INVERTER CONNECTOR MUST OPEN. OUTPUT OUTPUT LEADS LEADS PRIOR PRIOR TO TOTO INSTALLATION, INSTALLATION, INVERTER INVERTER CONNECTOR CONNECTOR MUST MUST BE BEBE OPEN. OPEN. DO DODO MUST BE OPEN. DO NOT JOIN INVERTER CONNECTOR UNTIL INSTALLATION IS NOT JOIN INVERTER CONNECTOR UNTIL INSTALLATION IS COMPLETE AND POWER NOT NOT JOIN JOIN INVERTER INVERTER CONNECTOR CONNECTOR UNTIL UNTIL INSTALLATION INSTALLATION IS AND AC POWER IS COMPLETE COMPLETE AND ACAC POWER COMPLETE AND AC POWER IS SUPPLIED TO THE EMERGENCY BALLAST. IS SUPPLIED THE EMERGENCY BALLAST. IS TO THE EMERGENCY BALLAST. IS SUPPLIED SUPPLIED TOTO THE EMERGENCY BALLAST. NOTE: Make sure necessary branch circuit wiring is available. unswitched source of power NOTE: NOTE: Make Make sure sure the thethe necessary necessary branch branch circuit circuit wiring wiring is is available. available. An AnAn unswitched unswitched source source of of power power is is is required. The emergency ballast must from same branch circuit ballast. required. required. The The emergency emergency ballast ballast must must be be be fed fedfed from from the thethe same same branch branch circuit circuit as as as the thethe AC ACAC ballast. ballast. Disconnect power from fixture. Remove ballast channel cover and install emergency ballast 1. 1. 1. Disconnect Disconnect AC ACAC power power from from the thethe fixture. fixture. Remove Remove the thethe ballast ballast channel channel cover cover and and install install the thethe emergency emergency ballast ballast either in the ballast channel (see Illustrations & or 2) or of the fixture* (see Illustration either either in in the the ballast ballast channel channel (see (see Illustrations Illustrations 11 & &12) 2) or on on on top toptop of of the the fixture* fixture* (see (see Illustration Illustration 3). 3).3). Select appropriate wiring diagram to connect emergency ballast to the ballast and lamp. Make sure 2. 2. 2. Select Select the thethe appropriate appropriate wiring wiring diagram diagram to to connect connect the thethe emergency emergency ballast ballast to to the the AC ACAC ballast ballast and and lamp. lamp. Make Make sure sure all connections in accordance with National Electrical Code and local regulations. all all connections connections are areare in in accordance accordance with with the thethe National National Electrical Electrical Code Code and and any anyany local local regulations. regulations. ILLUSTRATION ILLUSTRATION ILLUSTRATION 11 1 ILLUSTRATION ILLUSTRATION 22 ILLUSTRATION 2 ILLUSTRATION ILLUSTRATION ILLUSTRATION 33 3 installation on top of the fixture, bundle covers be required by state or local codes. These covers available from *For *For*For installation installation on on top top of of the the fixture, fixture, wire wirewire bundle bundle covers covers may maymay be be required required by by state state or or local local codes. codes. These These covers covers are areare available available from from the the the manufacturer asaccessory an accessory kit and must be ordered separately. local distributor or the factory for complete infomation. manufacturer manufacturer as as an an accessory kit kit and and must must be be ordered ordered separately. separately. Call CallCall your youryour local local distributor distributor or or the the factory factory for for complete complete infomation. infomation. Install switch through ballast channel cover oftroffer a troffer or through side ofstrip a strip fixture. Drill 3. 3. 3. Install Install the thethe test testtest switch switch through through the thethe ballast ballast channel channel cover cover of of aa troffer or or through through the thethe side side of of aa strip fixture. fixture. Drill Drill aa a 1/2" hole and install switch shown (see Illustration & 2). Refer to the wiring diagrams section and wire 1/2" 1/2" hole hole and and install install the thethe switch switch as as as shown shown (see (see Illustration Illustration 11 & &12). 2). Refer Refer to to the the wiring wiring diagrams diagrams section section and and wire wire switch it removes power from unswitched to the emergency ballast. the thethe test testtest switch switch so so so itit removes removes AC ACAC power power from from the thethe unswitched unswitched hot hothot line lineline to to the the emergency emergency ballast. ballast. Refer to Illustration 4 and install charging indicator light that it will visible after fixture is installed. 4. 4. 4. Refer Refer to to Illustration Illustration 44 and and install install the thethe charging charging indicator indicator light light so so so that that itit will will be be be visible visible after after the thethe fixture fixture is is installed. installed. NOTE: After installing charging indicator light and switch, mark each with appropriate label. NOTE: NOTE: After After installing installing the thethe charging charging indicator indicator light light and and test testtest switch, switch, mark mark each each with with the thethe appropriate appropriate label. label. IfIf If a detached charging indicator light is used, connect matching wire colors and install shown aa detached detached charging charging indicator indicator light light is is used, used, connect connect by by by matching matching wire wire colors colors and and install install as as as shown shown in Illustration in in Illustration Illustration 4. 4. 4. a readily visible location, attach label “CAUTION–This Unit Has More Than One Power Connection 5. 5. 5. In In aIn a readily readily visible visible location, location, attach attach the thethe label label “CAUTION–This “CAUTION–This Unit Unit Has Has More More Than Than One One Power Power Connection Connection Point. Reduce The Risk Electric Shock, Disconnect Both The Branch Circuit-Breakers Fuses And Point. Point. To To To Reduce Reduce The The Risk Risk Of Of Of Electric Electric Shock, Shock, Disconnect Disconnect Both Both The The Branch Branch Circuit-Breakers Circuit-Breakers Or Or Or Fuses Fuses And And Emergency Power Supplies Before Servicing.” Emergency Emergency Power Power Supplies Supplies Before Before Servicing.” Servicing.” ILLUSTRATION 4 ILLUSTRATION 4 TROFFER STYLE FIXTURE STRIP STYLE FIXTURE Fixture Fixture Charging Indicator Light Charging Indicator Light Violet (+) Violet (+) Brown (–) 1/2" White Bushing 5/8" Black Bushing 1/2" Punch Brown (–) 1/2" White Bushing 5/8" Black Bushing NOTE: After installing the charging indicator light and test switch, mark each with the appropriate label. 6. After installation is complete, supply AC power to the emergency ballast and join the inverter connector. 7. A short-term discharge test may be conducted after the emergency ballast has been charging for one hour. Charge for 24 hours before conducting a long-term discharge test. Refer to OPERATION. OPERATION When AC power is applied, the charging indicator light is illuminated, indicating the battery is being charged. When power fails, the emergency ballast automatically switches to emergency power, operating one or two lamps at reduced illumination. When AC power is restored, the emergency ballast returns to the charging mode and delays AC ballast operation for approximately three seconds to prevent false-tripping of AC ballast (end-of-lamp-life) shutdown circuits. This emergency ballast will operate the rated lamp load for a minimum of 90 minutes. MAINTENANCE Although no routine maintenance is required to keep the emergency ballast functional, it should be checked periodically to ensure that it is working. The following schedule is recommended: 1. Visually inspect the charging indicator light monthly. It should be illuminated. 2. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds. Either one or two lamps should operate at reduced illumination. 3. Conduct a 90-minute discharge test once a year. Either one or two lamps should operate at reduced illumination for at least 90 minutes. REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL WIRING DIAGRAMS The following diagrams are typical schematics only. May be used with other ballasts. Consult the factory for other wiring diagrams. Emergency Ballast and AC Ballast must be fed from the SAME BRANCH CIRCUIT. BROWN CONNECTOR OPEN BROWN CONNECTOR CLOSED IMPORTANT TEXT: REFER TO TABLE 1 REGARDING BROWN CONNECTOR Table 1 LAMP (DIAMETER) BROWN BROWN T8,T12 JUMPER WIRE BROWN BASE TYPE BROWN (1”, 1½”) Single or Bipin WATTAGE (Length) 16 - 40 W (2'-4') 40 - 215 W (5' -8') NO. of LAMPS (EMERGENCYMODE) BROWN CONNECTOR 1 CLOSED 2 OPEN 1 OPEN EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS. WIRING DIAGRAM for 1-LAMP emergency operation FIG A ONE (1) LAMP RAPID START BALLAST FIG B WALL SWITCH HOT WHT/RED B L K RED INVERTER CONNECTOR TEST SWITCH WHITE VIOLET (+) CHARGING INDICATOR B L K BROWN (-) BLACK WHITE WHT/BLK COMMON BROWN E M E R G E N C Y B A L L A S T BROWN RED YELLOW YEL/BLK BLU/WHT BLUE LAMP BLUE BLUE BLACK WHITE B L K 1 LAMP RAPID START BALLAST WHT/RED RED INVERTER CONNECTOR WHITE VIOLET (+) CHARGING INDICATOR BROWN (-) BLACK WHITE WHT/BLK COMMON BROWN E M E R G E N C Y FIG D B A L L A S T RED INVERTER CONNECTOR CHARGING INDICATOR E M E R G E N C Y WHITE VIOLET (+) BROWN (-) BLACK WHITE WHT/BLK COMMON YELLOW YEL/BLK LAMP 1 (EMERGENCY) BLUE BLU/WHT BLUE BLUE 2 LAMP RAPID START BALLAST BROWN RED RED WHT/RED INVERTER CONNECTOR TEST SWITCH CHARGING INDICATOR B L K LAMP 2 B A L L A S T YELLOW YEL/BLK BLU/WHT BLUE WHT/RED RED INVERTER CONNECTOR WHITE VIOLET (+) CHARGING INDICATOR BROWN (-) BLACK WHITE WHT/BLK COMMON FIG F LAMP 1 (EMERGENCY) BLUE BLUE E M E R G E N C Y 3 LAMP RAPID START BALLAST BROWN BLU/WHT YELLOW YELLOW VIOLET (+) BROWN (-) WHITE WHT/BLK E M E R G E N C Y BROWN B A L L A S T WARNING: Refer to Table 1 before connecting BROWN RED YELLOW YEL/BLK BLU/WHT LAMP 1(EMERGENCY) BLUE BLUE 2 LAMP INSTANT START BALLAST BLUE LAMP 2 RED WHT/RED B L K TEST SWITCH B L K BLU/WHT INVERTER CONNECTOR CHARGING INDICATOR WHITE VIOLET (+) BROWN (-) BLACK COMMON LAMP 3 RED WHITE WHT/BLK E M E R G E N C Y BROWN B A L L A S T WARNING: Refer to Table 1 before connecting BROWN RED YELLOW YEL/BLK BLU/WHT LAMP 1(EMERGENCY) BLUE RED RED BLUE BLACK WHITE FIG H 3 LAMP INSTANT START BALLAST BLUE BLUE LAMP 2 LAMP 3 RED FOUR (4) LAMP INSTANT START BALLAST B A L L A S T YELLOW YEL/BLK BLU/WHT BLUE LAMP 1 (EMERGENCY) YELLOW RED 4 LAMP RAPID START BALLAST BLU/WHT BLU/WHT LAMP 2 TEST SWITCH INVERTER CONNECTOR CHARGING INDICATOR BRN BRN RED WHITE VIOLET (+) BROWN (-) BLACK COMMON LAMP 3 BLUE BLUE WHT/RED B L K B L K YELLOW RED HOT WHITE WHT/BLK E M E R G E N C Y BROWN B A L L A S T WARNING: Refer to Table 1 before connecting BROWN RED YELLOW YEL/BLK BLU/WHT BLUE LAMP 1 (EMERGENCY) BLACK WHITE LAMP 4 YELLOW BLUE BLUE 4 LAMP INSTANT START BALLAST RED LAMP 2 LAMP 3 YELLOW RED LAMP 4 TWO (2) LAMP RAPID START STEP DIMMING BALLAST COMMON WHT/RED INVERTER CONNECTOR CHARGING INDICATOR TEST SWITCH HOT 1 LAMP INSTANT START BALLAST THREE (3) LAMP INSTANT START BALLAST HOT LAMP 2 WARNING: Refer to Table 1 before connecting BROWN RED BLACK WHITE FIG I LAMP RED BLUE WALL SWITCH HOT B L K WARNING: Refer to Table 1 before connecting BROWN RED YELLOW YEL/BLK BLU/WHT BLUE BLACK WHITE WALL SWITCH TEST SWITCH RED WHITE BLACK COMMON YELLOW YELLOW FOUR (4) LAMP RAPID START BALLAST B L K WHITE WHT/BLK B A L L A S T TWO (2) LAMP INSTANT START BALLAST B L K WARNING: Refer to Table 1 before connecting BROWN RED BLACK WHITE FIG G BROWN (-) BROWN E M E R G E N C Y WALL SWITCH WHT/RED B L K VIOLET (+) BLACK HOT WALL SWITCH TEST SWITCH RED WHITE BLACK WHITE THREE (3) LAMP RAPID START BALLAST HOT B L K CHARGING INDICATOR COMMON WARNING: Refer to Table 1 before connecting BROWN RED BLACK WHITE FIG E INVERTER CONNECTOR WALL SWITCH HOT B L K WHT/RED TEST SWITCH WALL SWITCH TEST SWITCH WALL SWITCH B L K RED RED FIG C TWO (2) LAMP RAPID START BALLAST B L K ONE (1) LAMP INSTANT START BALLAST HOT WARNING: Refer to Table 1 before connecting BLK RED WHITE VIOLET (+) BROWN (-) WHITE BLACK BLK E M E R G E N C Y BROWN B A L L A S T WARNING: Refer to Table 1 before connecting BROWN RED YELLOW YEL/BLK BLU/WHT BLUE LAMP 1 (EMERGENCY) BLUE BLUE WHT/BLK S1 S2 WHITE BLACK BLACK 2 LAMP RAPID START STEP DIMMING BALLAST RED RED YELLOW YELLOW LAMP 2 THE WHITE/BLACK LEAD MUST CONNECT TO THE WHITE LEAD OF THE STEP-DIMMING BALLAST ASSOCIATED WITH THE EMERGENCY BALLAST ONLY. CONNECTIONS TO OTHER BALLASTS OR FIXTURES COULD RESULT IN ABNORMAL OPERATION AND CAUSE PRODUCT DAMAGE. WIRING DIAGRAMS FOR 2-LAMP EMERGENCY OPERATION (2´- 4´, 16- 40 W LAMPS ONLY) Two-lamp emergency operation is not possible with all ballasts. Consult the factory for any ballast other than those shown. FIG J FIG K TWO (2) LAMP RAPID START BALLAST TWO (2) LAMP INSTANT START BALLAST WALL SWITCH WALL SWITCH HOT WHT/RED B L K TEST SWITCH B L K INVERTER CONNECTOR CHARGING INDICATOR RED E M E R G E N C Y WHITE VIOLET (+) BROWN (-) BLACK COMMON WHITE WHT/BLK BROWN B A L L A S T TEST SWITCH BLUE BLUE BLU/WHT BLUE RED RED 2 LAMP RAPID START BALLAST B L K LAMP 2 TEST SWITCH B L K CHARGING INDICATOR RED E M E R G E N C Y WHITE VIOLET (+) BROWN (-) BLACK COMMON WHITE WHT/BLK BROWN B A L L A S T RED YELLOW YEL/BLK TEST SWITCH LAMP 1(EMERGENCY) BLUE BLUE BLU/WHT BLUE BLU/WHT BLU/WHT 3 LAMP RAPID START BALLAST YELLOW YELLOW WHT/RED B L K B L K LAMP 2 (EMERGENCY) WHT/RED B L K RED INVERTER CONNECTOR CHARGING INDICATOR E M E R G E N C Y WHITE VIOLET (+) BROWN (-) BLACK COMMON BROWN RED YELLOW YEL/BLK BLU/WHT BLUE WARNING: Do NOT connect brown connector LAMP 1 RED BLUE BLUE LAMP 2 2 LAMP INSTANT START BALLAST WHITE WHT/BLK VIOLET (+) CHARGING INDICATOR BROWN (-) BLACK WHITE WHT/BLK LAMP 3 E M E R G E N C Y BROWN B A L L A S T WARNING: Do NOT connect brown connector BROWN YELLOW RED YEL/BLK BLU/WHT BLUE LAMP 1 (EMERGENCY) BLUE BLACK WHITE RED RED FIG O BLUE 3 LAMP INSTANT START BALLAST BLUE LAMP 2 (EMERGENCY) LAMP 3 RED FOUR (4) LAMP INSTANT START BALLAST HOT WARNING: Do NOT connect brown connector BROWN RED YELLOW YEL/BLK WHITE WALL SWITCH BROWN B A L L A S T RED INVERTER CONNECTOR COMMON WALL SWITCH TEST SWITCH BLACK WHITE WHT/BLK HOT FIG N FOUR (4) LAMP RAPID START BALLAST B L K BROWN (-) BROWN B A L L A S T FIG M THREE (3) LAMP INSTANT START BALLAST WARNING: Do NOT connect brown connector BROWN BLACK WHITE HOT VIOLET (+) CHARGING INDICATOR E M E R G E N C Y WALL SWITCH WHT/RED INVERTER CONNECTOR WHITE BLACK WHITE WALL SWITCH B L K RED INVERTER CONNECTOR COMMON YELLOW YELLOW THREE (3) LAMP RAPID START BALLAST HOT WHT/RED B L K LAMP 1 BLACK WHITE FIG L HOT WARNING: Do NOT connect brown connector BROWN YELLOW YEL/BLK RED LAMP 1 (EMERGENCY) BLU/WHT BLUE BLACK WHITE TEST SWITCH YELLOW YELLOW RED RED 4 LAMP RAPID START BALLAST BLU/WHT BLU/WHT WHT/RED B L K B L K LAMP 2 (EMERGENCY) RED INVERTER CONNECTOR WHITE VIOLET (+) CHARGING INDICATOR BROWN (-) BLACK WHITE WHT/BLK COMMON LAMP 3 BRN BRN BLUE BLUE E M E R G E N C Y BROWN B A L L A S T BROWN RED YELLOW YEL/BLK BLU/WHT BLUE WARNING: Do NOT connect brown connector LAMP 1 (EMERGENCY) YELLOW BLUE BLACK WHITE BLUE 4 LAMP INSTANT START BALLAST RED LAMP 2 (EMERGENCY) LAMP 3 YELLOW RED LAMP 4 LAMP 4 WIRING DIAGRAMS for EMERGENCY ONLY Fixtures FIG P HOT (CAP) B L K TEST SWITCH B L K FIG Q ONE (1) LAMP WITHOUT AC BALLAST (16W-215W) INVERTER CONNECTOR CHARGING INDICATOR WHT/RED RED WHITE VIOLET (+) BROWN (-) BLACK COMMON (CAP) WHITE WHT/BLK E M E R G E N C Y BROWN B A L L A S T BLU/WHT BLUE HOT WARNING: Refer to Table 1 before connecting BROWN RED YELLOW YEL/BLK (CAP) B L K LAMP TEST SWITCH (CAP) B L K (CAP) TWO (2) LAMPS WITHOUT AC BALLAST (16W-40W) INVERTER CONNECTOR CHARGING INDICATOR WHT/RED RED WHITE VIOLET (+) BROWN (-) BLACK COMMON (CAP) WHITE WHT/BLK E M E R G E N C Y BROWN B A L L A S T WARNING: Do NOT connect brown connector BROWN RED YELLOW YEL/BLK BLU/WHT BLUE LAMP 1 (CAP) (CAP) 09/16 © Copyright Hubbell Lighting, Inc.• 701 Millennium Bvld • Greenville, SC 29607 • (864) 678-1000 • FAX(864) 678-1415 • www.dual-lite.com 93063952 LAMP 2