AS-Interface Z Plug 2

advertisement
Technichal Description
AS-Interface Z Plug
Article No. AI010
Content
1.
2.
3.
4.
General.................................................................................................................1
Block Diagram.......................................................................................................2
Use of the Z Plug..................................................................................................2
Technical Data......................................................................................................4
4.1 AS-Interface....................................................................................................4
4.2 M12 pin out.....................................................................................................5
4.3 Undervoltage detection....................................................................................5
4.4 Mechanical and Environmental Data..................................................................5
5. Standards.............................................................................................................6
1. General
The AS-Interface Z Plug AI010 is a slave of the fieldbus system AS-Interface. It serves
as network extension utility for networks with up to 200m length without repeaters.
Previously only 100m network lengths were possible. Its profile is S-B.A.*.E (2 inputs
and 2 outputs).
The AS-Interface Z Plug AI010 can furthermore be used as indicator for undervoltage
detection. If the AS-Interface supply voltage is within the specified level both inputs D2
and D3 are set. If the supply voltage drops below the lower limit of the specified
voltage range the inputs are reset accordingly. Thus a reliable undervoltage detection
for the network can be established.
Rev. 2, 25.10.2006
Page 1 of 6
ICS Industrial Communication Solutions GmbH  D-88069 Tettnang  Germany  All rights reserved. Changes without prior notice
Technical Description
AS-Interface Z Plug
Article No. AI010
2. Block Diagram
Block Diagram of the AS-Interface Z Plug
3. Use of the Z Plug
The AS-Interface Z Plug AI010 can be utilised to extend AS-Interface networks beyond
the limit of 100m. With it's help it is possible to double network length to up to 200m
without repeaters.
In standard networks, where signal quality is below average due to full load or use of
non standard network cable it may be possible to reduce telegram error rates with the
insertion of the Z Plug.
Furthermore the Z Plug has an integrated undervoltage detection circuit that signals a
voltage within the specification or below specification via 2 input bits of an AS-Interface
slave that is integrated in the Z Plug.
Use to extend network length
If the AS-Interface Z Plug AI010 is to be used to extend network length, the following
installation rule has to be observed:
•
The Z Plug is to be installed at the point in the network that has the longest distance
to the AS-Interface power supply unit.
It is not necessary to hit this point exactly, a deviation of ±10m is tolerable. Only one Z
Plug per network shall be installed.
Page 2 of 6
Rev. 2, 25.10.2006
ICS Industrial Communication Solutions GmbH  D-88069 Tettnang  Germany  All rights reserved. Changes without prior notice
Technichal Description
AS-Interface Z Plug
Article No. AI010
If repeaters are used, one Z Plug per network segment is needed, if it is longer than
100m. Due to longer signal delay times in networks with more than 100m length it is
not possible to install two repeaters in series.
The possibility to extend AS-Interface networks as described above also exists for
networks where AS-Interface Safety at Work products are installed.
The properties of AS-Interface networks without and with Z Plug are summarised in the
following table:
criterion
without Z Plug
with Z Plug
62
62
possible network structures
star, ring, line, line with taps,
tree
star, ring, line, line with
taps, tree
max. distance Master-Slave
without (with) repeaters
100m (300m with two
repeaters in series)
200m (400m with one
repeater)
100m (500m)
200m (600m)
max. number of slaves
max. distance Slave-Slave
without (with) repeaters
use for AS-Interface signal quality improvement
If in networks with up to 100m length the telegram error rate is higher than tolerable
and if this high telegram error rate is due to a high load of the network and/or a non
standard cable in use then the installation of a Z Plug may improve the network
communication significantly. This is also true for networks where Safety at Work
products are connected.
The same installation rules as above apply.
use for undervoltage detection
At the most distant point in the network the probability is highest that the voltage drop
along the line is such that the supply voltage level drops below the lower specified limit.
This is particularly the case in networks with a length of up to 200m. The AS-Interface
Z Plug AI010, therefore, is equipped with an undervoltage detection circuit that signals
a supply voltage below the specified limit by resetting the slave inputs D2 and D3. The
detection circuit is designed in such a way that even short undervoltage dips (e.g. in
case a high power actuator changes it's state or slip rings have intermittent contact
problems) are detected and indicated clearly.
Two undervoltage detection voltages are selectable: 26,0V and 22,5V. They are
selected via the slave output D1.
Input D3 is reset in case the undervoltage dip detected has a duration of more than
5ms. Additionally the input D2 is reset if the duration of the undervoltage situation is
Rev. 2, 25.10.2006
Page 3 of 6
ICS Industrial Communication Solutions GmbH  D-88069 Tettnang  Germany  All rights reserved. Changes without prior notice
Technical Description
AS-Interface Z Plug
Article No. AI010
longer than 50ms. If an input has been resetted it will stay in that state for at least
100ms even if the undervoltage dip was shorter.
If the voltage drops below 20V for a longer period of time the integrated AS-Interface
IC will perform a reset; in this case the undervoltage signalisation cannot longer be
maintained.
4. Technical Data
4.1 AS-Interface
AS-Interface Profile:
reverse voltage protection:
Display "Power":
Display "Fault":
AS-Interface operating voltage range:
max. current consumption:
power on delay time:
AS-Interface Specification:
AS-Interface IC
AS-Interface certificate:
1)
S-B.A.*.E (2 inputs and 2 outputs)
yes
----approx. 20...31,6 V 1)
≤ 18 mA
<1s
V2.11, V3.0
ASI-SW
will be applied for
Readdressing the unit is possible in the voltage range 26.5 ... 31.6V only.
The use of the data bits is shown in the following table:
Input Data Image (IDI):
Info (Interface 3) Bit 4 (DI3)
Bit 3 (DI2)
Bit 2 (DI1)
Bit 1 (DI0)
0
U-voltg. >5ms
U-voltg. >50ms
---
---
1
voltage ok
voltage ok
---
---
Bit 3 (DO2)
Bit 2 (DO1)
Bit 1 (DO0)
Output Data Image (ODI):
Info (Interface 3) Bit 4 (DO3)
0
---
---
Uswitch < 26,0V ---
1
---
---
Uswitch < 22,5V ---
Page 4 of 6
Rev. 2, 25.10.2006
ICS Industrial Communication Solutions GmbH  D-88069 Tettnang  Germany  All rights reserved. Changes without prior notice
Technichal Description
AS-Interface Z Plug
Article No. AI010
4.2 M12 pin out
Pin 1:
Pin 3:
A+
A-
For the installation of the Z-Plug on the AS-Interface flat cable an accessory flat cable
connector (ICS Art. No. ZS006) is available.
4.3 Undervoltage detection
switching point:
26,0V ±0,2V or 22,5 ±0,3V (selectable)
switching point over temperature
range:
26,0V ±0,5V oder 22,5V ±0,5V
minimum duration of undervoltage dip:
5ms or 50ms resp.
minimum duration of undervoltage signal: 100ms
4.4 Mechanical and Environmental Data
ambient operating temperature range:
protection rating:
max. vibration level (temporarily):
max. shock:
-25 ... 70 °C
IP67
1,5mm Amplitude (10..55Hz)
10g
All dimensions in mm
Rev. 2, 25.10.2006
Page 5 of 6
ICS Industrial Communication Solutions GmbH  D-88069 Tettnang  Germany  All rights reserved. Changes without prior notice
Technical Description
AS-Interface Z Plug
Article No. AI010
M12 plug according to type JM (IEC 61076-2-101)
5. Standards
IEC 62026-2:2000
This product is designed and manufactured for industrial applications and is not
suitable for sale to the general public.