Motor Cabinet Sizing –NEC Article 430 Motor control cabinets are composed of the following items 1. A housing for all the devices 2. Feeder Conduit and Conductors 3. Main Circuit Breaker – Ground Fault / Short Circuit Protection 4. Main Power distribution bus for the motor control devices 5. Individual plug in bays for motor control devices, containing: a. Motor Branch Circuit – Ground Fault / Short Circuit Protection b. Motor Control Devices c. Motor Branch Circuit conductors Figure 1 - Motor Control Cabinet The photo to the left is a typical motor control cabinet and can be seen in person in room B103. The purpose of this document will be to size the items listed above. You will be designing and selecting a.) b.) c.) d.) e.) f.) g.) h.) i.) j.) k.) Feeder Wire Size Feeder Conduit Size (EMT) Main Circuit Breaker Size Branch Circuit Breaker Size Branch Circuit Wire Size Branch Circuit Grounding Conductor Branch Circuit Conduit (LFMC) Magnetic Starter Size Overload Size Switch Enclosure Size Feeder Grounding Conductor Size NOTES: For this project Minimum conduit size = ½” Minimum Conductor size = 12 AWG Motor Cabinet Sizing –NEC Article 430 Page 1 Figure 2 NEC Table NEC Article 430 - The NEC table on the left is your road map to Article 430. This table should be used to help you navigate around the article as needed. Examples: 1. Feeder – 430.24, 430.25, 430.26 2. Motor Circuit Conductor – Part II 3. Motor Overload Protection – Part III This table should be your starting point for determining all the related code sections to the ten items listed on the previous page. As with other articles, references in Article 430 will take you outside of article 430. Be sure and follow all the references in determining proper values to utilize. NEMA Sizes - The National Electrical Manufacturers Association (NEMA) has set a series of standard motor switch and starter sizes. This allows different manufacturers parts to be easily substituted for existing installations. That list follows below. NEMA MAGNETIC STARTER SIZES NEMA MAG 208V 230V 460V 575V STARTER MAX MAX MAX MAX SIZE HP HP HP HP 0 3 3 5 5 1 7.5 7.5 10 10 2 10 15 25 25 3 25 30 50 50 4 40 50 100 100 5 75 100 200 200 6 150 200 400 400 NEMA Switch Sizes 30 60 100 200 400 600 1000 Motor Cabinet Sizing –NEC Article 430 Page 2 Excel Motor Sizing Worksheet Students will be provided with a motor sizing worksheet to assist in the process of designing the motor control center. The worksheet is shown on the next page with descriptions of each item. An example motor branch circuit is shown along with descriptions of each box. MOTOR BLOCK 240V DC DESCRIPTION 1.15 S.F. /THWN CU N.E.C. FEEDER THWN COPPER FEEDER SERVICE FULL LOAD AMPS 19 DC MOTOR MOTOR #1 MOTOR # 2 MOTOR # 3 MOTOR # 4 MOTOR # 5 Percent 25 10 15 5 5 1 89 2 111 20 N.E.C. BRANCH 3 COPPER WIRE SIZE 1 21 134 22 TIME DELAY FUSE SIZE 24 MAG. STARTER O.L. PROTECTION GROUNDING CONDUCTOR Copper Size x # wires Copper * # wires Ground Size 2-#12 Field Wires Total Area needed Conduit Area CONDUIT SIZE 175 23 SWITCH SIZE EMT Table 25 0 4 5 6 400 7 3 8 111.3 9 6 10 0.1158 2 0.2316 0.0507 0.0266 0.3089 0.3490 11 12 13 14 15 16 17 From conduit table 1" 18 Liquidtite Metal (sum above 3) 1. Motor Horsepower is in the box above 2. Motor Full Load amps from Tables 430.247 to 430.251(B) 3. Minimum conductor amperage per Part II 4. Wire size in AWG or kcmils 5. Motor branch circuit short circuit / ground fault amperage calculated per Part IV 6. Motor branch circuit short circuit / ground fault protection using Value 5 and calculated per Part IV 7. NEMA Switch size using chart on previous page 8. NEMA Magnetic Starter size using chart on previous page 9. Motor Overload protection calculated per Part III 10. Motor Grounding conductor calculated per Article 250, and table 250.122 Motor Cabinet Sizing –NEC Article 430 Page 3 11. Area of the selected branch circuit conductor in square inches from Chapter 9, Table 5 12. Number of branch circuit conductors (typically 2) 13. Number of wires times the branch circuit area calculated in item 11 above. 14. Ground wire area, again from Chapter 9, Table 5 15. The area required for 2 each, 12 AWG conductors for the field wiring. 16. Sum of items 13, 14 & 15. This is the total area required. 17. Using Chapter 9, Table 4, the minimum conduit size is selected for both the LFMC and EMT. This number is the square inches available for the conduit you selected. Since there are over 2 wires in the conduit, you should use the 40% fill column. 18. Trade Size designation (in inches) for the selected conduit. 19. Motor Feeder amps as calculated per Part II 20. same value as 19 21. Feeder Conductor size selected in accordance per Part II 22. Time Delay Fuse or Circuit Breaker amperage as calculated in accordance per Part V 23. Standard Time Delay Fuse or Circuit Breaker size selected using value 22 and in accordance per Part V 24. NEMA Switch Size, same method as Item 7 25. Conduit sizing work area, the same method as with items 11 – 18 above, There are only three wires in this conduit, the field wires are not included in the feeder conduit. Figure 3 - Motor Controller Bus Access Points Motor Cabinet Sizing –NEC Article 430 Page 4 Figure 4 - Motor Controller Bus Connections Figure 5 - Motor Controller Motor Cabinet Sizing –NEC Article 430 Page 5 Figure 6 - Motor Control Devices In Figure 6, motor control devices are shown. 1. Branch Circuit Short Circuit / Ground Fault Protection 2. Motor Starter 3. Motor Overloads and Branch Circuit conductor connections 4. Control Transformer Primary and Secondary Over Current Protection 5. Control Transformer Motor Cabinet Sizing –NEC Article 430 Page 6