HID Ballast Wiring Connections

advertisement
PIB - HID Fixture Wiring Instructions
5/6/2014
HID Ballast Wiring Connections
TYPICAL REACTOR WIRING CONNECTIONS
(for HI reactor ballasts with model number –1xx suffix,
such as S0150-02C-111)
HID
LAMP
SOCKET
Black lead from
lamp socket
White lead from
lamp socket
Supply White Lead
STARTER
RED (X1)
LAMP
BLUE (X3)
X3
WHITE (X2)
X3
120v
Supply Black Lead
LAMP
VIN
1. Field wiring connections should only be made by qualified personnel.
2. Turn off supply voltage at breaker before accessing fixture Wiring Compartment.
3. Refer to wiring diagram on ballast label for proper component connections (typical connections illustrated above).
4. For safe operation:
a) Ground all system components (metallic case capacitor, ballast core, fixture housing, etc)
b) Insure all unused leads are individually insulated from ground
c) Wire product in accordance with local and national electric codes
d) Never perform maintenance while fixture is energized
5. Reassemble fixture Wiring Compartment after completing wiring connections.
6. Turn on supply voltage at breaker.
Specifications subject to change without notice.
Howard Lighting Products | 580 Eastview Drive | Laurel, MS 39443
(toll free) 800.956.3456 | (direct) 601.422.0033 | (fax) 601.422.1652
www.HowardLightingProducts.com
PIB - HID Fixture Wiring Instructions
5/6/2014
HID Ballast Wiring Connections
TYPICAL HX (High Reactance) BALLAST CONNECTIONS
(for HI HX-ballasts with model number –5xx suffix, such as M0100-71C-511)
277v
Supply black lead
208v
240v
120v
DRY TYPE
CAPACITOR
BALLAST CAP
BALLAST COM
Black lead from
lamp socket
LAMP
PRI.
COIL
SEC.
COIL
RED (X1)
BLUE (X3)
X3
WHITE (X2)
STARTER
HID
LAMP
SOCKET
Supply white lead
BALLAST COM
White lead from
lamp socket
277v
Supply black lead
BALLAST CAP
BALLAST COM
Supply white lead
Black lead from
lamp socket
LAMP
208v
240v
120v
OIL TYPE
CAPACITOR
PRI.
COIL
SEC.
COIL
RED (X1)
BLUE (X3)
X3
WHITE (X2)
STARTER
HID
LAMP
SOCKET
BALLAST COM
White lead from
lamp socket
1. Field wiring connections should only be made by qualified personnel.
2. Turn off supply voltage at breaker before accessing fixture Wiring Compartment.
3. Refer to wiring diagram on ballast label for proper component connections (typical connections illustrated above).
4. For safe operation:
a) Ground all system components (metallic case capacitor, ballast core, fixture housing, etc)
b) Insure all unused leads are individually insulated from ground
c) Wire product in accordance with local and national electric codes
d) Never perform maintenance while fixture is energized
5. Reassemble fixture Wiring Compartment after completing wiring connections.
6. Turn on supply voltage at breaker.
Note: Fixtures are typically wired to 277v tap unless otherwise specified. To re-configure for an alternate input voltage tap:
1.
Remove BLACK lead from existing ballast input leadwire (typically factory wired to 277v tap)
2.
Insulate the unused ballast lead with electrical tape or wire nut.
3.
Identify the desired ballast input leadwire (120v lead in illustration above).
4.
Strip the desired ballast leadwire and re-connect BLACK lead with supplied wirenut.
Specifications subject to change without notice.
Howard Lighting Products | 580 Eastview Drive | Laurel, MS 39443
(toll free) 800.956.3456 | (direct) 601.422.0033 | (fax) 601.422.1652
www.HowardLightingProducts.com
PIB - HID Fixture Wiring Instructions
5/6/2014
HID Ballast Wiring Connections
TYPICAL CWA BALLAST WIRING CONNECTIONS
(for HI Metal Halide CWA type ballasts with model number –2xx suffix, such as M0400-71C-211)
Black lead from
lamp socket
Supply Black lead
277v
120v
208v
240v
PRI.
COIL
SEC.
COIL
BALLAST
CAP
OIL TYPE
CAPACITOR
Supply White lead
HID
LAMP
SOCKET
BALLAST COM
Black lead from
lamp socket
Black lead from
lamp socket
Supply Black lead
DRY TYPE
CAPACITOR
277v
120v
208v
240v
PRI.
COIL
SEC.
COIL
BALLAST
CAP
HID
LAMP
SOCKET
Supply White lead
BALLAST COM
Black lead from
lamp socket
1. Field wiring connections should only be made by qualified personnel.
2. Turn off supply voltage at breaker before accessing fixture Wiring Compartment.
3. Refer to wiring diagram on ballast label for proper component connections (typical connections illustrated above).
4. For safe operation:
a) Ground all system components (metallic case capacitor, ballast core, fixture housing, etc)
b) Insure all unused leads are individually insulated from ground
c) Wire product in accordance with local and national electric codes
d) Never perform maintenance while fixture is energized
5. Reassemble fixture Wiring Compartment after completing wiring connections.
6. Turn on supply voltage at breaker.
Note: Fixtures are typically wired to 277v tap unless otherwise specified. To re-configure for an alternate input voltage tap:
1.
Remove BLACK lead from existing ballast input leadwire (typically factory wired to 277v tap)
2.
Insulate the unused ballast lead with electrical tape or wire nut.
3.
Identify the desired ballast input leadwire (120v lead in illustration above).
4.
Strip the desired ballast leadwire and re-connect BLACK lead with supplied wirenut.
Specifications subject to change without notice.
Howard Lighting Products | 580 Eastview Drive | Laurel, MS 39443
(toll free) 800.956.3456 | (direct) 601.422.0033 | (fax) 601.422.1652
www.HowardLightingProducts.com
PIB - HID Fixture Wiring Instructions
5/6/2014
HID Ballast Wiring Connections
TYPICAL CWA BALLAST w/STARTER WIRING CONNECTIONS
(for HI Pulse Start CWA type ballasts with model number –6xx suffix, such as M0400-71C-611)
(also, for HI High Pressure Sodium CWA type ballasts with model number –2xx suffix, such as S0400-71C-211)
BALLAST CAP
BALLAST CAP
OIL TYPE
CAPACITOR
SUPPLY
BLACK LEAD
LAMP
LAMP
277v
120v
208v
240v
PRI.
COIL
SEC.
COIL
BLACK LEAD FROM
LAMP SOCKET
RED (X1)
BLUE (X3)
WHITE (X2)
X3
X3
BALLAST COM
COM
BALLAST
STARTER
HID LAMP
SOCKET
SUPPLY
WHITE LEAD
BALLAST COM
COM
BALLAST
WHITE LEAD FROM
LAMP SOCKET
BALLAST CAP
SUPPLY
BLACK LEAD
BALLAST CAP
DRY TYPE
CAPACITOR
LAMP
LAMP
277v
120v
208v
240v
PRI.
COIL
BALLAST COM
COM
BALLAST
SEC.
COIL
X3
X3
BLACK LEAD FROM
LAMP SOCKET
RED (X1)
BLUE (X3)
WHITE (X2)
STARTER
HID LAMP
SOCKET
SUPPLY
WHITE LEAD
BALLAST COM
COM
BALLAST
WHITE LEAD FROM
LAMP SOCKET
1. Field wiring connections should only be made by qualified personnel.
2. Turn off supply voltage at breaker before accessing fixture Wiring Compartment.
3. Refer to wiring diagram on ballast label for proper component connections (typical connections illustrated above).
4. For safe operation:
a) Ground all system components (metallic case capacitor, ballast core, fixture housing, etc)
b) Insure all unused leads are individually insulated from ground
c) Wire product in accordance with local and national electric codes
d) Never perform maintenance while fixture is energized
5. Reassemble fixture Wiring Compartment after completing wiring connections.
6. Turn on supply voltage at breaker.
Note: Fixtures are typically wired to 277v tap unless otherwise specified. To re-configure for an alternate input voltage tap:
1.
Remove BLACK lead from existing ballast input leadwire (typically factory wired to 277v tap)
2.
Insulate the unused ballast lead with electrical tape or wire nut.
3.
Identify the desired ballast input leadwire (120v lead in illustration above).
4.
Strip the desired ballast leadwire and re-connect BLACK lead with supplied wirenut.
Specifications subject to change without notice.
Howard Lighting Products | 580 Eastview Drive | Laurel, MS 39443
(toll free) 800.956.3456 | (direct) 601.422.0033 | (fax) 601.422.1652
www.HowardLightingProducts.com