Installation and
Maintenance
Manual
1.2 Alternate Information Sources. If additional questions
arise relative to these luminaires that this document or your supplier
cannot answer, please refer them to:
Holophane
Field Service Department
P.O. Box 3004
Newark, OH 43058-3004
(866) 759-1577
2
INSTALLATION
2.1 Tools and Materials Required.
Flat Screwdriver
Adjustable Wrench
2.2 Luminaire Installation.
2.2.1 Mount the housing assembly to the mounting arm (2” nominal
pipe). For installation of photocontrol option see section 2.4. Level
the assembly across the top of the housing and tighten the two
slipfitter bracket bolts (18-22 ft. lbs.). See Figure 1.
FAILURE TO FOLLOW THESE WARNINGS
MAY RESULT IN DEATH, INJURY OR
SIGNIFICANT PROPERTY DAMAGE.
Figure 1
GR482
1
INTRODUCTION
GR1021A
1.1 Equipment Description
The HMSP® Series luminaire has been listed to applicable U.S. &
Canadian safety standards by Underwriters Laboratories Inc. They
are suitable for use in wet locations, and ambient temperatures up to
40 degrees Celsius.
•
•
•
The luminaire design allows permanent installation of the
reflector and housing while still providing easy maintenance and
repair of internal components.
The lamp and optical glass are directly accessible through the
bottom of the reflector.
The ballast assembly can be detached for repair by removing
four screws and unplugging two electrical connectors.
2.2.2 Route the electrical supply wires from the end of the mounting
arm through the notch in wall of the wiring chamber, and connect to
the terminal block or fusible disconnect.
NOTE
Fusible Disconnect Option: With factory installed fusible disconnect
for 120 volt, 240 and 277 volt line-to-neutral system, fuse only the line
side and connect line side incoming lead to the fusible disconnect.
Then attach the white lead to the incoming neutral lead using the
supplied wire nut. For 208 volt and 240 volt line-to-line and 480 volt,
fuse both line sides and connect both incoming leads to the fusible
disconnect.
Fuse Kit Accessory: When in-line fusing is specified, see fuse kit
instruction sheet.
IM-170-C
WARNING
DO NOT FUSE THE GROUNDING CONDUCTOR. FAILURE
TO FOLLOW THIS WARNING MAY RESULT IN INJURY OR
DEATH.
Figure 3
2.2.3 Make electrical connections to the ballast assembly by joining
color-coded plugs and connectors.
2.2.4 Attach the cover (ballast assembly) to the housing using the
four screws. Tighten evenly and securely.
CAUTION
BE CERTAIN THAT NO WIRING IS PINCHED BETWEEN
THE COVER AND HOUSING.
2.2.5 Install the correct lamp and energize the luminaire to check for
proper operation.
ASYMMETRIC DISTRIBUTION
2.3 Optics Orientation
The HMSP® Series luminaire produces either Type I Long & Narrow,
Asymmetric or Type V Square light patterns. Care must be taken in
orienting the light pattern.
GR1247
Figure 4
2.3.1 Locate the orientation label located on the reflector. See
Figure 2, 3 and 4.
2.3.2 Loosen the three reflector screws only enough to allow the
reflector to rotate.
2.3.3 Rotate the reflector to the correct orientation relative to layout
requirements and tighten the three screws to 70-80 in-lbs.
WARNING
RETIGHTEN THE THREE REFLECTOR SCREWS TO THE
TORQUE INDICATED. FAILURE TO FOLLOW THIS
WARNING MAY RESULT IN INJURY OR DEATH.
Figure 2
TYPE V SQUARE DISTRIBUTION
GR1022A
2.4 Photocontrol Option
The photocontrol receptacle is shipped partially assembled to the
housing assembly. If equipped with the photocontrol option, perform
the following:
2.4.1 Loosen one of the conduit nuts securing the photocontrol
receptacle to the electrical housing.
2.4.2 Rotate the photocontrol receptacle assembly to the position
TYPE I LONG & NARROW DISTRIBUTION
GR1186
where the receptacle will point straight up after the luminaire is
installed.
2.4.3 Securely tighten the nuts to prevent rotation by the wind or
vibration.
2.4.4 Loosen the nut securing the receptacle to the elbow and
rotate the receptacle to point the arrow marked “N” in a direction that
is generally North but not pointing directly toward a nearby luminaire.
Securely retighten the nut.
2.4.5 Install a twist-lock type photocontrol into the receptacle.
3
MAINTENANCE
3.1 Relamping and Cleaning.
3.1.1 Disconnect electrical power to the luminaire.
3.1.2 Wipe off the exterior of the luminaire to remove dirt or debris.
3.1.3 Remove the lamp and dispose of it in a safe and legal
manner.
3.1.4 Install the correct lamp type and wattage into the lamp socket.
3.1.5 Wipe the inside of the reflector with a soft, dry cloth. The
refractor may be washed with water and detergent, if needed.
IM-170-C
3.2 Electrical Component Replacement
4 Limited Warranty and Limitation of Liability
3.3
The Holophane limited warranty and limitation of liability is published
in the "Terms and Conditions" section of the current Holophane
buyer's guide, and is available from your local Holophane sales
representative.
Electrical components mounted on the ballast assembly can
be replaced as follows: (refer to Figure 5)
Figure 5
®
Acuity Lighting Group, Inc.
214 Oakwood Ave., Newark, OH 43055
IM-170-C 1/07 ©2002 Acuity Brands Inc.
Visit our web site at www.holophane.com
Printed in USA
GR260A
3.4
3.5
Disconnect electrical power to the luminaire.
Wipe off the exterior of the luminaire to remove dirt or debris
that could enter when the assembly is removed.
3.6 Remove the screws that secure the cover (ballast assembly)
assembly to the housing and tip the cover up. Unplug the electrical
connectors. Move the assembly to a horizontal work surface for
repair.
3.7 Tag electrical leads for use when installing the new
components and note the color-coded plugs and connectors.
3.8 Break electrical connections or cut wires as necessary.
3.9 Remove the attaching hardware and retain for reuse.
3.10 Remove the electrical component.
3.11 Place the new component into position assuring that the
locating bosses properly position it.
3.12 Install the attaching hardware. Tighten the fasteners securely.
3.13 Make electrical connections in accordance with wire tags and
proper wiring practices.
3.14 Check the interior of the housing and ballast assembly for
evidence of damage or potentially hazardous conditions.
3.15 Set the ballast assembly on the housing assembly and make
the electrical connections by joining the proper color-coded plugs and
connectors.
3.16 Attach the cover (ballast assembly) to the housing using the
four screws. Tighten evenly and securely. Be certain that no wiring is
pinched between the cover and housing.
3.17 Connect electrical power to the luminaire and check for proper
operation.
IM-170-C