Programmable Timers 14505526 1 i---‘-7‘ : i J R3 3 3 9 Copyright 0 1988 Honeywell Inc. l All Rights Reserved 74-5032 Temperature Limits: -4 to 131F (-20 to 55C) Programmable Timers provide automatic, timed operation of HVAC and lighting equipment. Closely spaced timing intervals operate equipment only as needed. Timers have either a synchronous clock motor or a regulated quartz oscillator for accurate timing. Timers are flush mounted on panel door or mounted on an accessory rail inside the panel. Trippers: 24-hour model - 4 pair 7-day model - 9 pair Approvals: UL Listed CSA Certified Dimensions In Inches (Millimeters): /i‘, Accessory rail mounted standard; optional flush mounting (panel door) available. ,/& The program spacing (slots) in the outer rim allows interval settings of 15 minutes (24-hour Timer) or 1 hour (7-day Timer). However. tripper thickness requires a minimum interval setting of 30 minutes or 3 hours for the 24-hour or 7-day Timer, rcspcctively. (7) Cl819 ,- Surface mounted on accessory mounting rail Flush mounting (optional) otor C The 7-day Programmable Timer dials are subdivided into the seven days of the week, and AM and PM, for each day in onehour increments. The 24-hour model dials are subdivided into AM and PM in 15-minute increments, The switching time from ON to OFF or OFF to ON is determined by the location on the dial edge of the on/off trippers. The on/off indicator (upper right from dial) allows visual checking of the automatic tripping status as well as manually tripping the timer contacts. Optional standby battery (quartz models only) maintains correct programming time for up to 50 hours in case of power failure. tage: 120V ac, 60 Hz DPDT, makes Terminals 4 to 3 when off, Terminals 4 to 5 when on and Terminals 7 to 6 when off, Terminals 7 to 8 when on. Material: Gold plated silver Rating: 10A, 250V ac resistive In a typical application, the Programmable Timer starts a fan system for day operation (e.g., ON at 7:00 AM) and then later returns the fan to the night mode (e.g., OFF at 6:00 PM). The second switch will control the EP relay to keep the damper shut during night operation. Wire Size: No. 14 AWG maximum 74-5032 2 Copyright 0 1988 Honeywell Inc. * All Rights Reserved Programming Setting The Timers are programmed as follows: To set the Timer, remove clear plastic dust cover and turn knob in center (minute hand) clockwise to the correct time and day of the week (7-day models). Remove clear plastic dust cover. Insert a green tripper, labeled 1, into the slot of the outer rim at each time the equipment is to turn ON. Insert a red tripper, labeled 0, into the slot of the outer rim at each time the equipment is to turn OFF. NOTE: Always use red and green trippers in pairs. Replace dust cover. N imer gears only turn the center knob clockwise. Do NOT turn outer rim by hand. NOTE: For proper Timer operation, the arrow on the dial between one and two o’clock must point to the correct time and to the day of the week (7-day models) on the outer rim. When changing from Daylight Savings Time to Standard Time, it may be easier to remove power from Timer motor for one hour (7-day models) than to reset the time. 24-HOUR MODEL-PROGRAM EVERY 15 MIN. TIMER INPUT VOLTAGE I - - - - CONTROLLED _ C5525 Programmable Timers Wiring. 7 - D A Y MODEL-PROGRAM EVERY HOUR Timer Programming. Copyright 0 1988 Honeywell Inc. Q All Rights Reserved 74-5032 Commercial Buildings Group Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis, MN 55408-0524 74-5032 MLF TAB: IV. C. 2. Commercial Buildings Group Honeywell Limited-Honeywell Limit&e 740 Ellesmere Road Scarborough, Ontario M1P 2V9 Rev. 1-88 Printed in USA Helping You Control Your World