Firetube Boilers and Accessories

advertisement
America’s Boiler Company
Firetube
Boilers
and
Accessories
Contents
PRODUCT
PAGE
Series 3 Packaged Firetube Boiler..................................................................................................................3
Series 3 Shock Proof Boiler...........................................................................................................................9
Series 3 Packaged Firetube Boiler “Ohio Special”.........................................................................................11
Anticipated Efficiencies.................................................................................................................................13
Wetback vs. Hard Refractory Dryback Design..............................................................................................15
Series 4S 4-Pass Wetback Scotch Boiler.....................................................................................................17
Low Nox Boiler............................................................................................................................................21
Series 4F Forced Draft Firebox Boiler...........................................................................................................23
Series 4F-40 ................................................................................................................................................27
Series 4F-45 ................................................................................................................................................29
Series 4F-50 ................................................................................................................................................31
Series 4F Forced Draft Firetube Boiler “Ohio Special” .................................................................................33
Series 4N Natural Draft Firebox Boiler .........................................................................................................35
Series 4NP Natural Draft Firebox Boiler .......................................................................................................43
C Series Compact Package Boiler ................................................................................................................45
Component Summary Information ..............................................................................................................49
Chemical Feed System ................................................................................................................................52
Bypass and Shot Feed Systems ..................................................................................................................54
Boiler Feedwater System ............................................................................................................................ 56
Condensate Return System ........................................................................................................................ 57
Blowdown Heat Recovery System ...............................................................................................................58
Bottom Blowdown Tank ..............................................................................................................................60
Flash Separator ...........................................................................................................................................62
Bottom Blowdown Separator ......................................................................................................................64
Conductivity Controller ...............................................................................................................................66
Water Softener Systems BS & BP ...............................................................................................................68
Horizontal and Integral Deaerators ..............................................................................................................70
Engineering and Application Data Index ......................................................................................................73
Series 3
Packaged Firetube Boiler
Series 3 - Packaged Firetube Boiler
Save Thousands Of Dollars
Over The Life Of Your Boiler
Long-term energy and maintenance efficiencies are the
focus of Burnham quality engineering. When choosing
a boiler, it’s a good idea to select a product with these
features in order to reduce enormous hidden costs down
the road. Review our wetback versus dryback literature for
cost savings.
Boiler Costs Is Not Jus A First Year Proposition
With any ordinary boiler, expenses such as fuel,
maintenance, and repair costs can escalate as the years
go on. Burnham packaged boilers are designed to diminish
these significant expenditures.
Burnham’s High Life-Cycle Efficiency
While most competitive boilers can give fuel-to-steam
efficiencies of 80% or over—when they’re new—how
consistently can they be expected to maintain this level
of operation? Burnham wetback boiler performance will
not drop due to deteriorating rear refractory, leaking door
baffles and seals, and heat-stressed rear tube sheet
as can happen with some drybacks. Easy access is a
necessity for those with heavy refractory, since they need
frequent and expert maintenance.
The Burnham Wetback Saves
Big Money On Maintenance
Over the life of a dryback, brittle refractory baffling and
rear door gasketing will require continuous monitoring,
maintenance, and replacement, costing thousands upon
thousands of dollars. These built-in maintenance costs can
eventually equal or exceed the original cost of the boiler.
As refractory deteriorates, leaking hot gas causes boiler
efficiency to drop until the condition is noticed and the
repairs can be made. Expensive flue temperature alarms
are offered with some drybacks to monitor this dangerous
and costly potentiality. The rear door itself can become
heat-distorted, requiring an expensive replacement. In
addition, boiler downtime during repairs can mean crippling
losses.
This waste of time and money is eliminated with the
Burnham Wetback. The actively functional water jacket
eliminates the need for: refractory wall, rear door, rear
door inspection and sealing, door swing space, and flue
temperature alarm. These costly maintenance headaches
are gone, while boiler performance is increased. Burnham
has only a small, inexpensive refractory area in the burner
area, for burner mounting. The rear access door liner is a
ceramic fiber insert that contains no refractory.
The furnace and rear turnaround area are cool running, fully
wetbacked radiant heat transfer surfaces. They promote good
internal water circulation and rapid heat absorption. There is no
need for the forced internal circulation pumps often specified to
cool the rear tube-sheets and drybacks.
The Burnham Wetback Is Built To Last
Typical dryback boilers have a common rear tubesheet that
expands and contracts at different rates adjacent to each
tube pass, stressing tube ends and increasing the likelihood
of leaks. Additionally, the heavy refractory used in some
drybacks reflects intense heat to the rear tube ends and tube
sheet, accelerating their deterioration. In attempts to stop
leaking, the rear ends of tubes have sometimes been welded.
Cleaning or tube replacement involves opening both the front
and rear covers and resealing them when the job is done.
Usually, if tubes have been welded at the ends, the welds must
be burned out, the tube sheet repaired (or a new segment
welded in) and the new tubes welded.
These costly expenditures are not an issue with the Burnham
Scotch Marine: separate rear tube sheets from each pass
to expand and contract at its own rate without tube-to-sheet
stress. Tubes are rolled and flared in low-pressure units; and
rolled, flared and beaded in high-pressure units. No welding
of tubes is permitted, nor is it necessary. Any eventual tube
replacement is simply a mechanical operation, no welding
involved. The end result is less cost and less headache.
Series 3 - Ratings and Data
Gross Output
Heating
Surface
Net Rating
Firing Rate
Boiler
Model
Shell
Diam.
BHP
MBH
LBS/
HR
Steam
MBH
Steam
Sq. Ft.
Water,
MBH
Sq.
Ft.
F.S.
Sq.
Ft.
W.S.
Gas,
MBH
Oil,
GPH*
40
48
40
1,339
1,380
1,011
4,211
1,164
200
220
1,674
12/11
50
48
50
1,674
1,725
1,290
5,376
1,456
250
280
2,093
60
48
60
2,009
2,070
1,560
6,499
1,747
300
335
70
54
70
2,343
2,415
1,819
7,580
2,037
350
80
54
80
2,678
2,760
2,079
8,663
2,329
90
54
90
3,013
3,105
2,339
9,747
100
54
100
3,348
3,450
2,599
125
66
125
4,184
4,313
150
66
150
5,021
175
66
175
200
66
250
Furn.
Vol.,
Cu.
Ft.
Water Content
Approx. Wt.
Dry, Lbs.
Lbs.
Steam
Lbs.
Water
15-30
PSI
150
PSI
14.8
1,760
2,185
3,700
4,200
15/14
17.1
2,303
2.701
4,200
4,700
2,500
18/17
19.3
2,765
3,235
4,700
5,200
390
2,930
21/20
27.8
3,285
4,160
5,500
6,200
400
445
3,348
24/23
30.2
3,672
4,641
5,900
6,700
2,620
450
500
3,766
27/25
33.0
4,060
5,143
6,400
7,200
10,830
2,911
500
555
4,185
30/28
35.8
4,523
5,711
6,900
7,700
3,248
13,535
3,638
625
695
5,230
38/25
41.9
5,585
6,673
8,700
9,500
5,175
3,898
16,243
4,366
750
835
6,276
45/42
47.7
6,660
7,947
9,700
10,600
5,858
6,040
4,548
18,950
5,094
875
970
7,333
52/49
53.1
7,758
9,245
10,900
11,600
200
6,695
6,900
5,198
21,658
5,822
1,000
1,110
8,369
60/56
58.8
8,829
10,519
12,300
13,300
78
250
8,369
8,625
6,498
27,074
7,277
1,250
1,360
10,461
75/70
86.6
11,174
13,983
15,400
18,600
300
78
300
10,043
10,350
7,797
32,489
8,733
1,500
1,630
12,500
90/84
99.1
12,315
16,649
18,100
21,400
350
90
350
11,716
12,075
9,096
37,901
10,188
1,750
1,900
14,645
105/98
113.5
15,392
19,340
21,000
23,700
400
90
400
13,390
13,800
10,396
43,317
11,643
2,000
2,175
16,738
120/112
124.7
16,765
22,125
23,200
26,100
500
102
500
16,738
17,250
12,995
54,147
14,555
2,500
2,715
20,923
150/140
152.0
18,515
23,788
27,400
30,600
600
102
600
30,085
20,700
15,594
64,957
17,465
3,000
3,260
25,106
180/168
174.3
22,128
28,381
31,500
35,500
700
102
700
23,433
24,150
18,193
75,805
20,377
3,500
3,805
29,319
210/196
195.8
25,767
33,005
35,700
39,700
800
108
800
26,780
27,600
20,792
86,633
23,287
4,000
4,349
33,475
240/224
302.3
33,945
43,762
43,900
52,900
900
114
900
30,128
33,217
23,500
97,615
N/A
4,500
4,905
37,660
269/252
278
40,893
N/A
47,800
56,600
1000
144
1,000
33,476
34,500
25,990
108,294
N/A
5,000
5,430
41,846
300/280
309
45,437
N/A
51,600
102,200
Note: Dimensions and Data are Not for Construction Purposes and are Subject to Change without Notice
• Large, fully waterbacked furnace tube assures complete combustion and heat absorption without flame impingement.
• Three gas passes extract maximum usable heat from the fuel while maintaining optimum flow for forced draft firing.
• Fully waterbacked reversing chamber effectively
absorbs radiant heat into the water,
keeping tube ends and rear of
boiler cooler than those of
hot-running drybacks.
• Ready access to tubes through rugged front door and rear covers
makes routine cleaning easier and less costly than with drybacks.
• Burner does not have to be disturbed.
• No inner air baffle door to contend with.
• No delicate expensive baffle tiles or door seals to replace.
Front View
• Unlike dryback boilers, securing the doors on a Burnham wetback boiler requires no specialized skills or expensive repair materials. It is a simple process which can be done with in-house personnel and performed with minimal downtime.
Rear View
It All Adds Up To Significant Cost-Performance Advantage.
What do all these features and specifications mean? More
savings for you! Our Packaged Wetback Firetube boilers are
designed for long-term efficiency and economical operation,
making Burnham your cost-performance leader!
• Forced-draft firing with oil (No. 2, 4, 5, or 6),
• Low or high pressure steam or water
The Series 3 matches burner to boiler, providing a fuelefficient, low-maintenance package. Maintenance costs
can be further controlled in your boiler room with optional
accessories. Such options include state-of-the-art annunciator
systems, custom-designed to monitor all boiler and burner
interlocks vital to your specific installation. They provide instant
readouts of both normal and abnormal operating conditions.
These features will pinpoint the cause of unscheduled
shutdowns; reducing maintenance time and skill required.
• Highly efficient three-pass design
• Fully waterbacked primary heating surfaces
• Separate rear tube sheets for longer service life
• Wetback design allows easy front and rear access
gas or combination gas/oil
• No expensive refractory or door replacement as
with some drybacks.
Series 3 — Standard Equipment
Boiler:
Three pass full wetback, packaged firetube type, constructed
in accordance with requirements of the ASME Code Section
IV for 30 psi and 125 psi water or 15 psi steam; Section I
for higher pressure steam. All units are registered with the
National Board.
Boiler tubes are expanded and flared in low pressure boilers;
expanded and beaded in high pressure boilers. Turbulator
baffles are not used in tubes. Separate second and third pass
rear tube sheets allow safe expansion and contraction.
Waterbacked rear turnaround promotes rapid internal
circulation and reduces gas temperatures at entrance to
second pass, reducing tube end stress.
Easy opening hinged, insulated front flue doors with
lightweight closure provide full access to all tubes. A 16inch diameter bolted rear access door with observation port
provides access to the boiler furnace. Rear tube access is
provided by removing light weight gasketed door(s) installed
in the rear smokebox. No elaborate seals are used.
A manhole is furnished as standard on water and low
pressure steam boilers sizes 3-125 and larger; on high
pressure steam boilers sizes 3-70 and larger.
Handhole washouts are provided for easy inspection and
cleaning of waterside surfaces.
All steam boilers provided with a dry pan to ensure dry steam.
A feedwater diffuser is provided on high pressure boilers. All
water boilers are equipped with a dip tube at supply outlet
and diffuser at return inlet.
The round flanged vertical smoke outlet is equipped with a
locking quadrant damper. All boilers are provided with an
enameled steel jacket over 2 inches of fiberglass insulation,
and lifting lugs.
The boiler is mounted on a heavy duty structural steel base
with extended skid and burner platform for protection of the
burner during shipment and rigging.
Standard Trim and Controls:
Steam: 157 pump control/low water cut-off with alarm
contacts–piped with quick opening blowoff valve. Gauge
glass set with hand-operated and try cocks. Steam pressure
gauge—4 1/2 inch dial on sizes 100 hp and smaller, 6
inch dial on larger sizes. L404C manual reset high limit
pressuretrol and appropriate firing rate control when required.
Manual reset probe auxiliary low water cut-off.
ASME side outlet safety valve(s).
Water: 63M manual reset low water cut-off with 30 psi
units, 150 low water cut-off with higher pressure units–piped
with quick opening blowoff valve. Combination pressure/
temperature gauge–3 1/2 inch dial on 100 hp and smaller. On
larger sizes a 6 inch combination pressure/altitude gauge and
5 inch dial temperature gauge. L4006A operating aquastat
and L4006E manual reset high limit aquastat and appropriate
firing rate control when required.
Burner Equipment:
Burner mounts to front head of boiler with no elaborate seals.
Factory packaged units available with forced draft burners for all
commonly used fuels–gas, all grades of oil–No. 2 through No.
6–and combination gas/oil. Choice of pressure or air atomizing
burners for No. 2 oil–air atomizing on heavy oil. Gas burners are
available for either natural or LP gas.
Refer to burner data sheets for standard burner equipment and
operating sequence.
Accessories and Optional Equipment:
Accessories and optional equipment available at extra cost,
including, but not limited to:
• Solid-state annunciators
• Alternate or additional water level controls or low water cut-offs
• Built-in tankless heater coils—low-pressure boilers only
• Motorized or pneumatic feed valves
• Surface skimmers and blowoff valves
• Bottom blowdown valves and drain valves
• Feed stop and check valves
• Sequence draft controls
• Lead/lag sequencing systems
• Boiler Feed systems
• Low NOx burners
• Deaerators
• Water Softeners
• Chemical Feed systems
• Blowdown systems
• Sample Coolers
©2009 Burnham Commercial - Lancaster, PA
Phone: 1-888-791-3790
www.burnhamcommercial.com
ASME side outlet safety valve(s).
Series 3
Shock Proof Boiler
Eliminate any thermal shock concerns with a Series 3-SP Shock Proof hot water boiler package.
Our low pressure, 15 psi steam boiler is equipped with a full capacity coil type
heat exchanger capable of 125 psi maximum water pressure.
Eliminate Thermal Shock…
Eliminate any thermal shock concerns with our Series 3-SP Shock
Proof hot water boiler package. This boiler design uses our reliable
Series 3 that incorporates a high steam space volume that can
easily accommodate the industries largest full capacity coil. The
Series 3 wetback design and low volumetric furnace release
rates allow easy firing and a prolonged boiler life. When properly
commissioned and maintained, your shock -proof packaged boiler
will last for many years.
Shock Proof Benefits
• No steam side water make up, no steam side
accessories are required.
• There is only one initial steam side water treatment required.
Since the steam side is sealed, expensive maintenance hours,
auxiliary equipment and chemicals are eliminated. A clean steam side will make your boiler run more efficiently.
• The hot system water flows only through the tubes of the heat
exchanger eliminating thermal stresses and hot water maintenance issues on the boiler side.
Shock Proof Features
• Specially designed heat exchanger tubes which are highly resistant to corrosion and erosion. • Specially constructed head
• Flanged supply and return
• Coil trim package included, consists of inlet and outlet pressure
gauges, inlet and outlet thermometers and coil side safety valves.
• Equipped with a full capacity coil type heat exchanger designed for 125 psi maximum water pressure.
Ratings and Data
Model Number
Output @ Coil Nozzle, MBH,
GPM @ 20°F Delta T/180°F/200°F
3L125SP 3L150SP 3L200SP 3L250SP 3L300SP 3L350SP 3L400SP 3L500SP 3L600SP 3L800SP
4,184
5,021
6,695
8,369
10,043
11,716
13,390
16,738
20,085
26,780
420
503
670
840
1,008
1,180
1,340
1,680
2,015
2,755
Delta P thru coil at above flow rate, PSI
5
5
5
5
5
5
5
5
5
5
Head Flange Size, 150# ANSI
4”
4”
5”
6”
6”
6”
8”
8”
8”
8”
Performance criteria based on 10 psi boiler operating pressure
Flanges orientation may be horizontal, as illustrated, or vertical. Consult factory.
Lancaster, PA 17601
Phone: 888-791-3790
www.burnhamcommercial.com
10
Series 3 Packaged Firetube Boiler — “Ohio Special”
Three pass full wetback, packaged firetube, constructed in
accordance with requirements of the ASME code, section IV
for 15-psi steam; Section 1 for higher pressure steam. All units
are registered with the National Board.
Boiler tubes are expanded and flared in low-pressure boilers;
expanded and beaded in high pressure boilers. Separate
second and third pass rear tube sheets allow safe expansion
and contraction.
Waterbacked rear turnaround promotes rapid internal
circulation and reduces gas temperatures at entrance to
second pass, reducing tube end stress.
Easy opening hinged, insulated front flue doors with bolted
closure provide full access to all tubes. A 16-inch diameter
bolted rear access door with observation port provides access
to the boiler furnace. Removing lightweight gasketed door(s)
installed on the rear smokebox provides rear tube access. No
elaborate seals are used. A manhole is furnished as standard
on all Ohio Special Boilers, 100 through 225 hp. Handhole
washouts are provided for easy inspection and cleaning of
waterside surfaces.
The boiler is mounted on a heavy-duty structural steel base
with extended skid and burner platform for protection of the
burner during shipment and rigging.
Standard Trim and Controls
All steam boilers are provided with a dry pan to ensure
drysteam. A feedwater diffuser is provided on high-pressure
boilers.
157 pump control/low water cut-off with alarm, contactspiped with quick opening blowoff valve. Gauge glass set
with hand operated gauge and tri-cocks. Steam pressure
gauge: 4-1/2 inch dial on 100 HP, 6 inch dial on larger sizes.
L404A operating pressuretrol, L404C manual reset high limit
pressuretrol and appropriate firing rate control when required.
Manual reset probe auxiliary low water cut-off. ASME side
outlet safety valve(s).
The round-flanged vertical smoke outlet is equipped with a
locking quadrant damper. All boilers are provided with an
enameled steel jacket over 2 inches of fiberglass insulation
and lifting lugs.
Ratings and Data
100X
125X
150X
175X
200X
225X
Shell Diameter Ratings
Gross Output - BHP
Gross Output - MBH
Gross Output - LBS/HR
Net Rating - MBH
Net Rating - Sq. Ft.
54
100
3,348
3,450
2,599
10,829
54
125
4,184
4,312
3,249
13,536
54
150
5,021
5,175
3,898
16,244
54
175
5,858
6,037
4,548
18,951
54
200
6,695
6,900
5,198
21,658
54
225
7,532
7,762
5,848
24,366
Safety Valve
Safety Valve
3,450
3,906
4,312
4,882
5,175
5,858
6,037
6,834
6,900
7,811
7,762
8,787
358
383
358
383
358
383
358
383
358
383
358
383
(15 PSIG) - LBS/HR
(150 PSIG) - LBS/HR
Heating Surface - Sq. Ft.
Fireside
Waterside
Firetubes
Number
Diameter - Inches
46
2.5
46
2.5
46
2.5
46
2.5
46
2.5
46
2.5
Furnace
Volume - Cu. Ft.
Diameter - Inches
30.5
25
30.5
25
30.5
25
30.5
25
30.5
25
30.5
25
Firing Rate
100 BTU Gas - MBH
140 MBTU/Gal. Oil - GPH
150 MBTU/Gal. Oil - GPH
4,184
29.9
27.9
5,230
37.4
34.9
6,277
44.8
41.8
7,323
52.3
48.8
8,369
59.8
55.8
9,415
67.2
62.8
11
Dimensions (in inches)
100X
125X
150X
175X
200X
225X
A - Base Width
B - Furnace Center
C - Overall High Pressure Supply Connection
Overall Low Pressure Supply Connection
38
33-5/16
76-5/8
76-5/8
38
33-5/16
76-5/8
76-5/8
38
33-5/16
76-5/8
76-5/8
38
33-5/16
76-5/8
76-5/8
38
33-5/16
76-5/8
76-5/8
38
33-5/16
76-5/8
76-5/8
D - Width over Trim
E - Width over Jacket
F - Base to N.W.L.
G - Overall Length
69-1/4
59-1/4
59-3/4
190-1/2
69-1/4
59-1/4
59-3/4
190-1/2
69-1/4
59-1/4
59-3/4
190-1/2
69-1/4
59-1/4
59-3/4
192-1/2
69-1/4
59-1/4
59-3/4
192-1/2
69-1/4
59-1/4
59-3/4
194-1/2
H - Base Length
J - Front to High Pressure Feed Connection
K - Base Extension
L - Flue Door Clearance
159-3/4
93-1/8
35-3/4
29-1/2
159-3/4
93-1/8
35-3/4
29-1/2
159-3/4
93-1/8
35-3/4
29-1/2
159-3/4
93-1/8
35-3/4
29-1/2
159-3/4
93-1/8
35-3/4
29-1/2
159-3/4
93-1/8
35-3/4
30-3/4
M - Tube Removal Space
N - High Pressure Supply Size
Low Pressure Supply Size
P - Shell Length over Flue Outlet
125
4” flg
8” flg
154-3/4
125
4” flg
8” flg
154-3/4
125
4” flg
8” flg
154-3/4
125
6” flg
8” flg
156-3/4
125
6” flg
8” flg
156-3/4
125
6” flg
8” flg
158-3/4
Q - Front to Supply
R - High Pressure Supply to Manway
Low Pressure Supply to Manway
S - Flue Outlet Flange Diameter
60-1/8
33
33
17
60-1/8
33
33
17
60-1/8
33
33
17
60-1/8
33
33
17
60-1/8
33
33
17
60-1/8
33
33
17
T - Flue Inside Diameter
U - Outside Flange to Center
V - Floor to Flue Outlet Flange
13-3/8
8-1/2
74-3/8
13-3/8
8-1/2
74-3/8
13-3/8
8-1/2
74-3/8
15-1/2
9-1/2
74-3/8
15-1/2
9-1/2
74-3/8
17-1/2
9-1/2
74-3/8
W - Floor to High Pressure Feed Connection
X - Feed Connection Size
43-5/16
1-1/4
43-5/16
1-1/4
43-5/16
1-1/4
43-5/16
1-1/2
43-5/16
1-1/2
43-5/16
1-1/2
5,536
664
5,536
664
5,536
664
5,536
664
5,536
664
5,536
664
7,000
12,450
8,100
13,550
7,050
12,450
8,150
13,550
7,100
12,500
8,200
13,600
7,500
12,950
8,600
14,050
7,650
13,050
8,750
14,150
7,650
13,050
8,750
14,150
Water Content
LBS
Gallons
Approximate Shipping Weight
Low Pressure (Dry) - LBS
Low Pressure (Wet, N.W.L) - LBS
High Pressure (Dry) - LBS
High Pressure (Wet, N.W.L.) - LBS
© 2006 Burnham Commercial - Lancaster, PA
Phone: 1-888-791-3790
www.burnhamcommercial.com
12
Anticipated Efficiencies
Natural Gas
125%
50%
75%
100%
BOILER
SIZE
10 #
125 #
10 #
125 #
10 #
125 #
10 #
125 #
100
125
150
200
82.50
81.00
82.00
82.50
78.50
77.00
78.00
79.00
83.50
82.00
83.00
83.50
80.50
79.00
80.00
80.50
83.50
82.00
83.00
83.50
81.00
79.50
80.50
81.00
83.50
82.00
83.00
83.50
81.00
79.50
80.50
81.50
250
300
350
400
500
600
81.50
82.00
82.50
82.00
82.50
83.00
78.00
78.50
78.50
78.00
79.00
79.50
82.00
82.50
83.00
83.00
84.00
84.00
79.50
80.00
80.50
80.00
81.00
81.00
82.00
82.50
83.00
83.00
84.00
84.50
80.00
80.50
81.00
80.50
81.50
82.00
82.00
82.50
83.00
83.00
84.00
84.50
80.00
80.50
81.00
80.50
81.50
82.00
700
800
1000
83.00
83.50
83.50
79.50
80.00
80.00
84.50
84.50
84.50
81.50
81.50
81.50
84.50
84.50
84.50
82.00
82.00
82.00
84.50
84.50
84.50
82.00
82.00
82.00
#2 Oil
125%
50%
75%
100%
BOILER
SIZE
10 #
125 #
10 #
125 #
10 #
125 #
10 #
125 #
100
125
150
200
85.50
84.00
85.00
86.00
81.50
80.00
81.00
82.00
86.50
85.00
86.00
87.00
83.50
82.00
83.00
84.00
86.50
85.50
86.50
87.00
84.00
82.50
83.50
84.50
86.50
85.50
86.50
87.00
84.00
82.50
83.50
84.50
250
300
350
400
500
600
85.00
85.50
85.50
85.00
86.00
86.00
81.50
81.50
82.00
81.50
82.00
82.50
85.50
86.00
86.50
86.00
87.00
87.50
83.00
83.50
84.00
83.50
84.00
84.50
85.50
86.00
86.50
86.50
87.50
87.50
83.00
83.50
84.50
84.00
85.00
85.00
85.50
86.00
86.50
86.50
87.50
87.50
83.00
83.50
84.50
84.00
85.00
85.00
700
800
1000
86.50
87.00
87.00
82.50
83.00
83.00
87.50
88.00
88.00
84.50
85.00
85.00
88.00
88.00
88.00
85.50
85.50
85.50
88.00
88.00
88.00
85.50
85.50
85.50
13
Thermal Efficiency
The effectiveness of the boiler as a heat exchanger. It is the ability of the boiler to exchange heat through tubes and
furnace, by radiation, conduction and convection, to the transfer medium (water). A few of the factors affecting thermal
efficiency are heating surface, tube number and diameter, furnace tube length and diameter.
Combustion Efficiency
This is a measure of the ability of the burner to effectively and completely burn the fuel, coupled with the thermal
efficiency of the boiler. Burners requiring high amounts of excess air to provide flame stability will be less efficient.
Combustion efficiency does not take into account heat loss to the surrounding air through the boiler jacket and piping.
Fuel to Steam Efficiency
Sometimes referred to as overall efficiency. This is a ratio of heat output to heat input. This includes boiler jacket and
piping losses to the surrounding environment. It is the percent of useable heat in the steam (or hot water) compared to
the heat input supplied by the burner. It is also defined as the combustion efficiency less boiler jacket and piping loss
(radiation and convection losses). Since fuel-to-steam efficiency reflects the portion of actual usable heat supplied to
the system, it is most useful when comparing performance of similar equipment, or when doing fuel savings analysis.
BOILER RATINGS
Ratings may be expressed
in the following units:
BHP = Boiler Horsepower. One BHP is the evaporation of 34.5 lbs of 212°F water per hour into dry saturated steam at the same temperature.
BTUh
BHP =
33,475 BTUh/BHP
BTU = British Thermal Units: that quantity of heat required to raise one (1) lb. of water one (1) degree on the Fahrenheit scale. BTUh = BTU/hr.
MBH =1000 BTUh
PPH = Pounds of steam per hour
MBH
PPH =
0.9703 MBH/PPH
Gross Rating – The full output of a boiler actually available to the heating or process system at the outlet nozzle. The Commercial Steel Boiler Industry catalogs gross output as 80% of input.
Net Ratings – The net connected design load that can be supplied with heat by a boiler of given output, allowing for normal system piping losses and pickup from a cold start. Since steam system piping losses may be expected to be larger than for water systems, and steam boilers require greater heat input from a cold start than water boilers before heat flows to the system, steam net ratings for automatic fired boilers are slightly lower in relation to gross output than water net ratings. Hand fired net water and steam ratings are equal and are lower in relation to gross output in order to provide ample allowance for rapid pickup from a banked fire.
MBH net water = Gross MBH x 0.87
MBH net steam = Gross MBH x 0.776
Square Foot Ratings – Net ratings based on a heat emission rate of 240 BTUh per square foot of radiation for steam, and 150 BTUh per square foot for water.
Square Feet Net Steam =
Steam Net MBH
Square Feet Net Water =
0.24 MBH / sq. ft.
14
Water net MBH
0.15 MBH / sq. ft.
Wetback Design vs. Hard Refractory
Dryback Design
Why is a Wetback design better?
Burnham’s three-pass wetback design has a rear water
wall, which separates the primary heating surface of the
combustion chamber from the rear tube sheet. The water
jacket eliminates the need for a refractory wall and rear
door swing space behind the boiler, as well as costly
refractory maintenance. The rear water wall eliminates the need for gasketing,
which is vulnerable to the temperature generated in the
rear of the turnaround area. A wetback design boiler not
only overcomes these expensive deficiencies, but it has
great overall efficiency and virtually maintenance-free
construction. A Burnham boiler will cost you less over the lifetime
of the boiler because it is better by design! Some Points to Remember:
Wetback Advantages
•
•
•
•
•
•
Wetback boilers have separate tube sheets between all major temperature changes.
The rear access door is constructed of lightweight ceramic fiber
The rear doors require no cool-down period and can be opened immediately
No space consuming area required for the swing door
The split rear flue doors are easily removed
Efficiency is readily maintainable because the design of the boiler promotes complete and even circulation of flue gases
Dryback Disadvantages
•
•
•
•
•
Flue gas temperature differential of 1300F-1600F between the second and third passes creates damaging stresses on the single tube sheet. The cost of rear door refractory replacement (approximately every three years) will drastically increase operating costs, as well as the costs associated with yearly rear door gasket replacement. Opening and resealing the rear door is time consuming and requires a 24-hour cool down period prior to opening The heavy refractory may sag on the davit and must be rigged back into place. Heavy jacks or expensive rigging may be required just to open and close the rear doors
Exposing the refractory to hot flue gases can cause erosion and destroy the baffle; resulting in the uneven circulation of flue gases and lower efficiency
Rear refractory walls radiate unabsorbed heat, leading to external heat loss
15
WHAT IS FUEL-TO-STEAM EFFICIENCY AND IS IT IMPORTANT?
Fuel-to-steam efficiency is very important because it is the only true measure of overall packaged boiler operational
efficiency. True fuel-to-steam efficiency takes into account radiation and convection heat losses, which less reputable
manufacturers may ignore. We suggest purchasing your boiler from a manufacturer who guarantees fuel-to-steam
efficiency in the performance of your entire packaged boiler. Be wary of misleading efficiency terms, such as “thermal
efficiency” or “combustion efficiency”. Contact your local Burnham Commercial sales representative for further definition.
MAINTAINABLE EFFICIENCY VS. ATTAINABLE EFFICIENCY
When looking at efficiency as criteria for purchasing a boiler, especially fuel-to-steam efficiency, the manufacturer’s
design efficiency sets theoretical fuel costs while operation efficiency determines actual fuel costs. There is a difference between attainable efficiency and maintainable efficiency. Correct burner adjustments are the key to maintainable efficiency. It is a compromise between the optimum and the practical. Good burner tuning is achievable only with
a good burner design and a good burner/boiler package. WILL A DRYBACK BOILER COST MORE TO OWN?
The answer is simple…Yes! The high cost of maintenance is the biggest consideration in overall efficiency in a dryback design. Consider this example: an average 300 HP boiler operating under normal conditions with a conservative lifespan of 25 years. Our surveys have shown that during this boiler’s lifetime the rear door refractory would be
replaced about 8 times (roughly every three years). Also, assuming the boiler is opened only once a year for inspection, regasketing of the rear door would occur 25 times.
How much cheaper is the hard refractory backed boiler?
So, somebody is offering a hard refractory backed boiler design for less money than a wetback design! While it may
make your initial capital investment costs look great, what does it do to your pocketbook in the long run? Let’s take a look....
Average cost for replacing rear door hard refractory: $6,000
Average cost of regasketing the rear door: $500
Apply these costs to the average lifespan of the boiler:
$6,000 X 8 = $48,000
$500 X 25 = $12,500
Compare the costs of replacing the rear door gasket of your wetback design:
$30 X 25 = $750
The difference between the hard refractory dry back maintenance and the wetback maintenance is
$60,500 - $750 = $59,750.
Now comes the shocking part...for the same amount of money spent in dryback maintenance:
YOU COULD HAVE PURCHASED
A NEW BURNRHAM WETBACK BOILER!
16
Series 4S
4-Pass Wetback Scotch Boiler
17
4-Pass Wetback Scotch Boiler
America’s Boiler Company
The Burnham Commercial Series 4S four-pass wetback
scotch boiler was designed using our 140+ years of boiler
experience and is sold and serviced through the largest
and most experienced network of sales representatives in
the country. With a complete commercial product offering
and unmatched sales and technical support, it’s no wonder
why we are America’s Boiler Company!
Why Choose the Series 4S?
• The design incorporates positive water flow circulation and maximum heat transfer to maximize ratings.
• The handhole clean-outs are placed for ease of servicing.
• The heavy steel base provides adequate stability along with shipping and rigging protection.
•
•
It is completely packaged and ready for “same day”
installation.
The 5 sq.ft./hp rated design does not use turbulators or welded tube ends.
• The multitude of QC checkpoints and stringent final inspection assures you of a quality product.
• There are no proprietary parts or gaskets on the boiler trim or the burner.
Latest Design Techniques
• All external trim piping is designed and installed in accordance with the ASME
Code and is certified by an
independent inspection agency for compliance.
The Series 4S uses the very latest design techniques
and standards. Its furnace, the workhorse of the boiler,
is designed for low volumetric release rates of no more
than 136,000 btu/hr/cu.ft. The lower the release rates,
the “easier” your boiler works. As your boiler works
easier, less stress is put upon the steel, tube ends,
refractory, etc., resulting in a longer lasting boiler. In
addition to longevity, a larger furnace makes for ease
in firing using any selected burner vendor. The Series
4S is also easily converted to a low NOx product when
needed.
• The fiberglass insulated steel jacket is finish painted with high gloss Burnham blue enamel.
Higher Efficiency
•
The access door is constructed of durable, lightweight vacuum formed ceramic fiber—the door liner weighs less than 40 pounds!
• The front and rear full-sized hinged access doors are standard and secured with non-corrosive brass nuts. • The UL approved packaged burners are trimmed and
wired to assembled gas trains.
The Burnham Series 4S design produces a higher
efficiency due to the larger furnace and higher heat
transfer design. To determine the efficiency of your next
job, contact your local Burnham representative.
4 Pass Wetback Scotch Boiler—To learn more about wetback versus dryback, please refer to our wetback literature
18
Dimensions and Ratings
A
100
125
150
175
200
250
300
350
400
500
600
700
800
68
68
76
76
76
86
86
94
94
104
104
114
114
B
84
85
93
93
93
103
103
111
111
121
121
131
131
C
150
176
169
188
207
207
235
240
263
264
300
282
311
Dimensions are approximate, see detailed drawings for more specific dimensions.
Rating Data
Boiler Size, HP
100
125
150
175
200
250
300
350
400
500
600
700
800
Shell Diameter
62
62
70
70
70
70
78
88
88
98
98
108
108
Gross Output, BHP
100
125
150
175
200
250
300
350
400
500
600
700
800
Gross Output, MBH
3348
4184
5021
5858
6695
8369
10,043
11,716
13,390
16,738
20,085
23.433
26,780
Gross Ouput, Lbs./Hr.
3450
4312.5
5175
6037.5
6900
8625
10,350
12,075
13,800
17,250
20,700
24,150
27,600
Heating Surface, FS Sq. Ft.
Firing Rate - Gas
Gas - MBH
Oil - GPH (140 MBTU/Gal.)
500
625
750
875
1000
1250
1500
1750
2000
2500
3000
3500
4000
4184
29.9
5230
37.4
6277
44.8
7323
52.3
8369
59.8
10,461
74.7
12,553
89.7
14,645
104.6
16,738
119.6
20,922
149.4
25,106
179.3
29,291
2092
33,475
239.1
39
46
58
66
73
93
108
133
149
177
206
219
246
Furnace Volume - Cu. Ft.
Heat Releases Rate
BTU/Hr./Cu. Ft.
Water Content
Flooded - Gal.
NWL - Gal.
Shipping Weight - Lbs.
15/30 psi
125/150 psi
107,618 112,686 108,471 111,565 114,003 112,617 116,193 110,011 112,491 118,528 121,670 133,559 136,013
875
779
1,115
995
1,187
1,019
1,391
1,187
1,606
1,367
1,750
1,487
2,110
1,786
2,661
2,266
3,045
2,601
3,536
2,818
4,256
3,405
4,747
3,932
5,431
4,507
8,000
8,900
9,940
10,400
10,500
11,700
12,000
13,200
13,200
14,400
15,600
19,000
18,300
21,600
22,300
21,600
24,500
27,600
28,900
32,300
33,200
37,100
38,300
45,100
42.500
50,000
19
Series 4S Standard Equipment
Boiler:
Four-pass full wetback firetube type, constructed in
accordance with requirements of the ASME Code, Section
IV for 30 PSI and 125 PSI water or 15 PSI steam; Section I
for higher-pressure steam. All units are registered with the
National Board.
Water: 63M manual reset low water cut-off with 30 PSI
units,
150M low water cut-off with higher-pressure units—piped
with quick opening blowoff valve. Combination pressure/
temperature gauge—3 ½ inch dial on 125 HP and smaller.
On larger sizes a 6-inch combination pressure/altitude
gauge and 5-inch dial temperature gauge. L4006A operating
aquastat and L4006E manual reset high limit aquastat and
appropriate firing rate control when required. ASME side outlet relief valve(s).
Turbulator baffles are not used in tubes. Separate rear tube
sheets allow safe expansion and contraction.
Waterbacked rear turnaround promotes rapid internal
circulation and reduces gas temperatures at the entrance to
the second pass, reducing tube end stress.
Burner Equipment:
Easy opening hinged, insulated front flue doors with light
weight non-refractory closure provide full access to all tubes.
A light weight 16-inch diameter bolted rear access door with
observation port provides access to the boiler furnace. Rear
tube access is provided by removing lightweight gasketed
doors(s) installed on the rear smokebox. No elaborate seals
are used.
Burner mounts directly to the front head of the boiler with no
elaborate seals.
Factory packaged units available with forced draft burners
for all commonly used fuels—gas, all grades of oil—No. 2
through No. 6—a combination gas/oil. Choice of pressure
or air atomizing burners for No. 2 oil—air-atomizing burners
for No. 2 oil—air atomizing on heavy oil. Gas burners are
available for either natural or LP gas.
A manhole is furnished as standard. Handhole washouts
are provided for easy inspection and cleaning of waterside
surfaces.
Refer to burner data sheets for standard burner equipment
and operating sequence.
All steam boilers are provided with a dry pan to ensure dry
steam. A feedwater diffuser is provided on high-pressure
boilers. All water boilers are equipped with a dip tube at
supply outlet and diffuser at return inlet.
Accessories and Optional Equipment:
Accessories and optional equipment available at extra cost,
including, but not limited to:
• Alternate or additional water level controls or low water
cut-offs
• Built-in tankless heater coils—low-pressure boilers only
• Motorized or pneumatic feed valves
• Surface skimmers and blowoff valves
• Bottom blowdown valves and drain valves
• Feed stop and check valves
• Sequence draft controls
• Lead/lag sequencing systems
• Boiler Feed systems
• Low NOx burners
• Deaerators
• Water Softeners
• Chemical Feed systems
• Blowdown systems
• Sample Coolers
The round-flanged vertical smoke outlet is equipped with a
quadrant damper. All boilers are provided with an enameled
steel jacket installed over 2 inches of fiberglass insulation
and lifting lugs.
The boiler is mounted on a heavy-duty structural steel base
with extended skid and burner platform for protection of the
burner during shipment and rigging.
Standard Trim and Controls:
Steam: 157 pump control/low water cut-off with alarm
contacts—piped with quick opening blowoff valve. Gauge
glass set with hand-operated gauge and try cocks. Steam
pressure gauge—4 ½-inch dial on sizes 125 HP and smaller,
6-inch dial on larger sizes. L404A operating pressuretrol,
L404C manual reset high limit pressuretrol and appropriate
firing rate control when required. Manual reset probe
auxiliary low water cut-off.
ASME side outlet safety valve(s).
Lancaster, PA 17601
Phone: 888-791-3790
www.burnhamcommercial.com
20
Low NOx
21
Low NOx
America’s Boiler Company
Combining these three features contribute to an ideal
low NOx package application.
Burnham Commercial has been designing and
producing boilers for 140+ years, and we sell and
service through the largest and most experienced
network of sales representatives in the country. Our
representatives are capable of providing technical
assistance, competent pricing, start-up, and long term
servicing. It’s no wonder we are America’s Boiler
Company!
Our firebox design provides
the largest furnace possible in a firetube, and our
scotch boilers have some of the largest furnaces
available in our market—meaning we can meet all
your Low NOx needs.
Important Design Considerations
Low NOx Needs
Our proven designs use the very latest low
NOx techniques and standards. Our furnace,
the workhorse of the boiler, is designed for low
volumetric heat release. The lower the release rates,
the “easier” your boiler works. As your boiler works
easier, less stress is put upon the steel, tube ends,
refractory, etc., resulting in a longer lasting boiler. In
addition to longevity, a larger boiler makes for ease in
firing using any selected burner vendor.
Being America’s Boiler Company, we know what
burner vendors are looking for in boiler designs when
it comes to reduced NOx combustion levels—large
furnaces, high heat transfer, and low draft losses:
• Large furnaces mean low volumetric release rates. • High heat transfer for the most efficient boiler for your application.
• Less burner motor horsepower so less energy is used to operate your boiler. Smaller furnaces are extremely susceptible to erratic
flame patterns. Deformed flame patterns cause
uneven heat distribution, uneven absorption and
localized hot spots, which can lead to overheating
and over stressing. Our selections give the customer
the choice of any of the major low NOx burner
manufacturers. Because we have so many proven
product design selections to choose from, we can
custom fit any of our products to your boiler room.
Burnham Commercial can offer you firebox, threepass or four-pass wetback scotch. We are
the only manufacturer who can offer
their packages complete with flue gas
recirculation piping, when necessary. That
eliminates extra design responsibility and
field installation costs.
Proven Product Applications
Unlike any other manufacturer, every Burnham Commercial Low NOx package is design application
approved by our own Engineering Department and
our burner vendors’ Engineering and Applications
Design Groups. Our 140+ years successful track
record assures you that our products, and our vendor
selection, are the best available.
Lancaster, PA 17601
Phone: 888-791-3790
www.burnhamcommercial.com
22
Series 4F
Forced Draft Firebox Boiler
23
Series 4F Forced Draft Firebox Boiler
The Versatile Boiler
The Burnham Commercial 4F forced draft steel
firebox boiler is a consistent sales leader in the
heating industry. Its compact and constructive
design saves on installation, operation, and maintenance.
4F Saves on Installation
The 4F is a compact boiler that fits where other
designs of similar capacity cannot. Available for
15 psi steam and 30 or 60 psi water*, the 4F
can serve perfectly as the heart of almost any
system. As a factory assembled, forced-draft fired
boiler, this packaged unit does not require a tall,
expensive vent stack or excessive jobsite time and labor.
4F Saves in Operation
•
The furnace surrounds the flame with highly efficient waterbacked primary heat absorbing surfaces. This large
combustion chamber is easy to fire and accommodates many forced-draft
burners without flame impingement or other critical firing problems.
•
Forced draft firing makes the 4F inherently more efficient than boilers using outmoded atmospheric burners and gives you a feature that atmospheric units cannot offer: the option of burning gas or oil.
•
A dual fired burner allows you to burn the more economical fuel or the most readily available fuel at the flip of a switch and affords you leverage in negotiating fuel prices.
•
The 4F is an economical heat source, whether used singly or in multiples. In fact, 4F’s with modulating burners may be sequenced to operate in a step-fired system more cost effectively than a large number of space saver boilers when ongoing maintenance costs are considered.
4F Saves on Maintenance
• Superior design makes the 4F easy to clean and
maintain — requiring no special tools, materials, or skills.
•
Opening the front flue door allows firetubes to be brushed out quickly, unlike the watertubes used in some boilers which can be virtually impossible to clean.
• Elaborate or expensive proprietary seals are not required to re-close the doors as with some boilers.
• As a wetback boiler, there is no delicate or expensive rear refractory to maintain.
*60-psi water boiler - consult factory for available sizes.
24
Series 4F — Models 63 - 675
Dimensions (in Inches)
4F Boiler Models
63
78
92
107
A - Boiler Width
31
31
31
31
32
39
B - Boiler Length
127
154
180
209
240
277
311
36-3/8 36-3/8 36-3/8 36-3/8 45-1/8 45-1/8 45-1/8
45-1/2 52-1/2 44-1/2
53
61
70
57
65
72-1/2
C - Boiler Height
55-1/4 55-1/4 55-1/4 55-1/4 63-5/8 63-5/8 63-5/8 63-5/8 70-5/8 70-5/8 70-5/8
D - Base Width
33-1/4 33-1/4 33-1/4 33-1/4 38-5/8 38-5/8 38-5/8 38-5/8 47-3/8 47-3/8 47-3/8
E - Base Length
47-1/2 54-1/2
65
72
64
72-1/2 80-1/2 92-1/2 79-1/2 87-1/2
95
345
360
450
45-1/8
52-3/4
52-3/4
563
675
56-1/2 56-1/2
80
80-3/4
93-1/4 104-3/8 122-1/4
70-5/8
82-7/16
82-7/16 85-3/16 85-3/16
47-3/8
53-1/8
53-1/8
57
57
102-1/2
107-1/2
124
135-1/8
153
F - Base Extension
15-1/2 15-1/2 19-1/2 19-1/2 19-1/2 19-1/2 19-1/2 22-1/2 22-1/2 22-1/2 22-1/2
22-1/2
26-3/4
30-3/4
G - Front Smoke Box Height
27-5/16 27-5/16 27-5/16 27-5/16 29-7/16 29-7/16 29-7/16 29-7/16 35-1/8 35-1/8 35-1/8
35-1/8
38-1/2
38-1/2 41-9/16 41-9/16
H - Front Smoke Box Depth
30-3/4 30-3/4
5-1/2
5-1/2
5-1/2
5-1/2
6-1/2
6-1/2
6-1/2
6-1/2
7-1/2
7-1/2
7-1/2
7-1/2
6-1/2
6-1/2
7-1/2
7-1/2
J - Supply Location
13
13
13
13
16
16
16
16
19
19
19
19
28
28
28
28
*K - Supply Size
4
4
4
4
6
6
6
6
6
8
8
8
8
10
10
10
*L - Return Size - Steam
3
3
3
3
4
4
4
4
4
4
4
4
4
4
4
4
6-1/2
6-1/2
6-1/2
6-1/2
7
7
7
7
7
7
7
7
7-3/8
7-3/8
7-3/8
7-3/8
7
7
7
7
10
10
10
10
12
12
12
12
—
—
—
—
—
—
—
—
14
14
18
18
M - Return Location
N - Top Vent Collar Dia.
P - Rear Vent Collar Dia.
—
—
—
—
Q - Rear Vent Collar Height
38
38
38
38
9
9
9
9
R - Smoke Box Depth
T - Top Vent Collar Height
U - Tube Pull Space
V - Supply Fitting Height
46-1/2 46-1/2 46-1/2 46-1/2
12
12
12
12
—
—
—
—
52
52
52
52
14
14
14
42-1/2 42-1/2 42-1/2 42-1/2 52-1/2 52-1/2 52-1/2 52-1/2 59-1/4 59-1/4 59-1/4
32
39
1-1/2
1-1/2
45-1/2 52-1/2 44-1/2
1-1/2
1-1/2
3-1/4
58-13/16 58-13/16 59-5/8 59-5/8
14
16
59-1/4
66-5/16
81-1/2
16
53
61
70
57
65
72-1/2
80
3-1/4
3-1/4
3-1/4
3-1/4
3-1/4
3-1/4
3-1/4
3-3/8
3-3/8
58
58
58
58
69-3/16
69-3/16
W - Normal Water Line Height 43-3/4 43-3/4 43-3/4 43-3/4 51-1/2 51-1/2 51-1/2 51-1/2
*3” and 4” are IPS female thread, 6” and larger are flanged. 150# bolt pattern. Specifications, Dimensions Data Subject to Change without Notice
25
20
20
66-5/16 69-1/8 69-1/8
94
105
123
3-7/16 3-7/16
72
72
Series 4F — Models 827 - 3075
The Complete Boiler Room Supplier
Dimensions (in Inches)
4F Boiler Models
827
993
1157
1323
1654
1985
2315
2645
A - Boiler Width
64
64
70
70
76
82
82
82
3075
96
B - Boiler Length
106-1/4
129
116-1/2
136
130-1/2
128
148
163
163
C - Boiler Height
151-1/2
95-3/16
95-3/16
106-3/4
106-3/4
122-3/8
142-3/8
142-3/8
142-3/8
D - Base Width
61
61
67
67
73
79
79
79
93
E - Base Length
138-1/4
161
158-1/2
178
172-1/2
170
190
205
213
F - Base Extension
30
30
40
40
40
40
40
40
48
G - Front Smoke Box Height
29-1/8
29-1/8
33-11/16
33-11/16
41-7/8
55-1/8
55-1/8
55-1/8
69-3/4
H - Front Smoke Box Depth
12-3/4
12-3/4
13-1/2
13-1/2
14-1/2
15-1/2
15-1/2
15-1/2
16-1/2
J - Supply Location
22
22
22
22
22
22
22
22
68
*K - Supply Size
8
8
8
8
10
12
12
12
12
*L - Return Size - Steam
4
4
4
6
6
6
6
6
6
Return Size - Water
6
6
6
8
8
8
8
8
8
M - Return Location
10-1/4
10-1/4
11-1/8
11-1/8
11-1/8
11-1/2
11-1/2
11-1/2
10-1/2
N - Rear Smoke Box Depth
19-3/8
19-3/8
19-3/8
19-3/8
21-3/8
23-3/8
23-3/8
23-3/8
23-3/8
20
20
22
22
24
28
28
28
30
66-3/16
66-3/16
76-13/16
76-13/16
90-11/16
106-5/16
106-5/16
106-5/16
110-1/2
R - Top Vent Collar Width
22
22
26
26
28
34
34
34
44
S - Top Vent Collar Depth
16
16
16
16
18
20
20
20
20
T - Top Vent Collar Height
76-1/8
76-1/8
87-3/
87-3/4
102-5/8
120-1/4
120-1/4
120-1/4
123-15/16
108
131
118-1/2
138
132-1/2
130
150
165
165
78-1/4
78-1/4
89-3/4
89-3/4
104-1/2
118-1/2
118-1/2
118-1/2
126
P - Rear Vent Collar Dia.
Q - Rear Vent Collar Height
U - Tube Pull Space
W - Normal Water Line Height
*4” are IPS female thread, 6” and larger are flanged. 150# bolt pattern. Specifications, Dimensions Data Subject to Change without Notice
© 2008 Burnham Commercial - Lancaster, PA
Phone: 1-888-791-3790
www.burnhamcommercial.com
26
Series 4F-40
Forced Draft Firebox Generator
Ratings and Data
63
78
92
107
127
154
180
209
240
277
311
345
360A
450A
563A
675A
Gross Output
MBH
BHP
Lbs. Stm/Hr
527
15.7
543
653
19.5
673
770
23.0
794
896
26.8
923
1,063
31.8
1,096
1,289
38.5
1,328
1,506
45.0
1,553
1,749
52.2
1,803
2,009
60.9
2,070
2,318
69.2
2,389
2,603
77.8
2,683
2,887
86.2
2,975
3,015
90.1
3,108
3,770
112.6
3,885
4,720
141.0
4,864
5,657
169.0
5,832
Net Rating - Steam
MBH
Sq. Ft.
409
1,705
507
2,115
598
2,490
695
2,895
825
3,445
1,000
4,165
1,169
4,870
1,357
5,655
1,559
6,495
1,799
7,495
2,020
8,415
2,240
9,335
2,340 2,926 3,663 4,390
9,750 12,190 15,265 18,295
Net Rating - Water MBH
458
568
670
780
925
1,121
1,310
1,522
1,748
2,017
2,265
2,512
2,623
3,280
4,106
4,922
Firing Rate - Gas MBH
Firing Rate - Light Oil GPH*
Heavy Oil GPH*
659
4.7
—
816
5.8
—
963
6.9
—
1120
8.0
—
1329
9.5
—
1,611
11.5
—
1,883
13.5
—
2,186
15.6
—
2,511
17.9
—
2,898
20.7
—
3,254
23.2
—
3,609
25.8
—
3,769
26.9
25.1
4,713
33.7
31.4
5,900
42.1
39.3
7,071
50.5
47.1
Heating Surface Sq. Ft.
Fireside
Waterside
59
63
73
78
86
92
101
107
120
127
145
154
168
180
194
209
224
240
257
277
289
311
320
345
360
398
450
497
563
622
675
746
Furnace Volume Cu. Ft.
8.8
10.7
12.6
14.6
18.3
21.9
25.3
29.1
34.7
39.7
44.4
49.1
58.9
68.0
89.3
104.7
Heat Release MBH/Cu. Ft.
74.9
76.3
76.4
76.7
72.6
73.6
74.4
75.1
72.4
73.0
73.3
73.5
64.0
69.3
66.1
67.5
65
90
81
112
94
132
110
153
133
168
145
196
172
232
198
268
214
288
245
329
274
369
302
408
470
569
551
666
663
881
788
951
Approx. Dry Weight Lbs.
1,700
1,900
2,100
2,600
2,700
3,100
3,300
3,600
4,200
4,400
5,300
5,600
6,710
8,700
Approx. Full Weight Lbs.
Steam
Water
2,240
2,450
2,570
2,835
3,090
3,195
3,510
3,870
3,800
4,095
4,300
4,735
4,730
5,235
5,250
5,830
5,980
6,595
6,435
7,140
7,575
8,365
8,110 10,615 13,290 14,825 16,970
8,995 11,495 14,255 15,975 18,325
4F - 40 Boiler Models
Water Content Gal.
Steam
Water
Ratings based on 4 square feet of heating surface per boiler horsepower
* Light oil—140,000 BTU/GAL
** Heavy oil,—150,000 BTU/GAL
Instantaneous Hot Water Heating Coils
Rated Capacity — Gallons Heated
40° to 140°F Boiler Water Temp.
108°F
180°F
212°F
GPM
GPH
GPH
3.5
210
325
Coil Number
INA-210
*For Use in the Following Boiler Sizes
Subject to Capacity Limitation of Boiler
All sizes
INA-300
All except 4F-63
5.0
300
466
INA-360
All sizes
6.0
360
560
INA-450
All except 4F-63
7.5
450
700
INA-600
4F-154 and larger, also 4F-107
10.0
600
933
INA-750
4F-154 and larger, also 4F-107
12.5
750
1,165
INA-900
4F-92 and larger
15.0
900
1,400
INA-1125
4F-154 and larger
18.7
1,125
1,750
INA-1350
4F-277 and larger, also 4F-209
22.5
1,350
2,100
INA-1500
4F-345 and larger
25.0
1,500
2,330
*Two coils of any size or combination of sizes may be installed in 4F-1157 and larger
27
9,300 10,400
Series 4F-40 Standard Equipment
Boiler:
Water Trim:
Jacket:
The following trims are shipped loose for field mounting:
3 ½” theraltimeter (on models 4FW63 through 4FW675)
or 5” thermometer and 6” pressure/altitude gauge (on
models 4FW827 and larger) and loose ASME side outlet
relief valve(s).
The boilers are a three pass design constructed and
stamped in accordance with ASME Section IV of the
ASME Code for 15 psig steam or 30 psig water on any
size boiler or 60 psig water on sizes 4FW63 through
4FW993. They are the sealed forced draft firing design
with skid base and floor insulation. The flue outlet is
a top outlet on sizes 4F63 through 4F345 and a rear
outlet on sizes 4F450 and larger. Optional outlets are
available on all sizes. The boiler comes complete with a
gas tight front flue cleanout door, rear observation port
on sizes 4F63 through 4F345, or rear access door and
observation port on sizes 4F450 and larger and lifting
lugs on sizes 4F127 and larger. Optional access doors
and lifting lugs are available for all sizes.
Rectangular type 1” fiberglass insulated jacket on sizes
4F63 through 4F345, 2” fiberglass insulated rectangular
jacket on sizes 4F450 through 4F675 and 2” fiberglass
wrap around jacket on sizes 4F827 and larger.
Steam Trim:
The following trim is shop mounted and wired: MM157
combination pump control and LWCO with alarm
contacts and quick opening blowoff valves, probe
type manual reset auxiliary LWCO, L404A operating
pressuretrol, L404C manual reset high limit pressuretrol
and appropriate firing rate control when required.
The following trims are shop mounted and wired:
probe type LWCO (on 30 psig models 4FW63 through
4FW675) or MM63M manual reset LWCO with quick
opening blowoff valve (on 30 psig models 4FW827 and
larger) or probe type LWCO (on 60 psi models 4FW63
through 4FW675) or MM150M manual reset LWCO
with quick opening blowoff valve (on all 60 psi boilers
on models 4FW827 and larger) or L4006A operating
aquastat, L4006E manual reset high limit aquastat and
appropriate firing rate control when required.
Burner:
As selected for the fuel to be burned, mounted and
wired. Refer to burner data sheets for details of burner
equipment. Burners available for gas, No. 2 oil, No. 4 oil,
No. 5 oil, No. 6 oil, combination gas/No. 2 oil, gas/No. 4 oil, gas/No. 5 oil, gas/No. 6 oil, combination gas/No. 2 oil, gas/No. 4 oil, gas/No. 5 oil, and gas/No. 6 oil.
The following trim is shipped loose for field mounting:
3 ½” steam pressure gauge (on models 4FL63 through
4F675), 6” steam pressure gauge (on models 4F827
and larger), ASME side outlet safety valve(s) and gauge
glass set.
© 2006 Burnham Commercial - Lancaster, PA
Phone: 1-888-791-3790
www.burnhamcommercial.com
28
Series 4F-45
Forced Draft Firebox Generator
Ratings and Data
4F - 45 Boiler Models
63
78
92
107
127
154
180
209
240
277
311
345
360A
450A
563A
675A
Gross Output
MBH
BHP
Lbs. Stm/Hr
469
14
483
579
17.3
597
683
20.4
704
797
23.8
821
944
28.2
973
1,145
34.2
1,180
1,339
40.0
1,380
1,553
46.4
1,601
1,784
53.3
1,839
2,062
61.6
2,125
2,313
69.1
2,384
2,568
76.7
2,646
2,678
80.0
2,760
3,348
100.0
3,450
4,251
127.0
4,380
5,055
151.0
5,210
364
1,515
449
1,870
530
2,210
618
2,575
733
3,055
889
3,705
1,039
4,340
1,205
5,020
1,384
5,765
1,600
6,665
1,795
7,480
1,993
8,305
2,078 2,598 3,299 3,923
8,660 10,825 13,745 16,345
Net Rating - Water MBH
403
504
594
693
821
996
1,165
1,351
1,552
1,794
2,012
2,234
2,350
2,913
3,698
4,398
Firing Rate - Gas MBH
Firing Rate - Light Oil GPH
Heavy Oil GPH
586
4.2
—
724
5.2
—
854
6.1
—
996
7.1
—
1,180
8.4
—
1,431
10.2
—
1,674
12.0
—
1,941
13.9
—
2,230
15.9
—
2,578
18.4
—
2,891
20.7
—
3,210
22.9
—
3,348
23.9
22.3
4,185
29.9
27.9
5,314
38.0
35.4
6,319
45.1
42.1
Heating Surface Sq. Ft.
Fireside
Waterside
59
63
73
78
86
92
101
107
120
127
145
154
168
180
194
209
224
240
257
277
289
311
320
345
360
398
450
497
563
622
675
746
Furnace Volume Cu. Ft.
8.8
10.7
12.6
14.6
18.3
21.9
25.3
29.1
34.7
39.7
44.4
49.1
58.9
68.0
89.3
104.7
Heat Release MBH/Cu. Ft.
66.6
67.7
67.8
68.2
64.5
65.3
66.2
66.7
64.3
64.9
65.1
65.4
56.8
61.5
59.5
60.4
65
90
81
112
94
132
110
153
133
168
145
196
172
232
198
268
214
288
245
329
274
369
302
408
470
569
551
666
663
801
788
951
Approx. Dry Weight Lbs.
1,700
1,900
2,100
2,600
2,700
3,100
3,300
3,600
4,200
4,600
5,300
5,600
6,900
8,700
Approx. Full Weight Lbs.
Steam
Water
2,240
2,450
2,570
2,835
3,090
3,195
3,510
3,870
3,800
4,095
4,300
4,735
4,730
5,235
5,250
5,830
5,980
6,595
6,435
7,140
7,575
8,365
8,110 10,615 13,290 14,825 16,970
8,995 11,495 14,255 15,975 18,325
Net Rating - Steam
MBH
Sq. Ft.
Water Content Gal.
Steam
Water
9,300 10,400
360A-3
450-A
563A-3
675A-3
827
993
1157
1323
1654
1985
2315
Gross Output
MBH
BHP
Lbs. Stm/Hr
2,953
88.2
3,044
3,445
102.9
3,550
4,188
125.1
4,316
4,924
147.1
5,075
6,126
183.0
6,315
7,388
220.7
7,617
8,606
257.1
8,872
9,842
294.0
10,146
12,302
367.5
12,682
14,766
441.1
15,223
17,220
514.4
17,753
Net Rating - Steam
MBH
Sq. Ft.
2,292
9,550
2,673
11,140
3,250
13,540
3,821
15,920
4,754
19,810
5,733
23,890
6,885
28,690
7,873
32,805
9,546
39,775
11,458
47,740
13,363
55,680
Net Rating - Water MBH
2,569
2,997
3,644
4,284
5,330
6,428
7,487
8,563
10,703
12,846
14,981
Firing Rate - Gas MBH
Firing Rate - Light Oil GPH
Heavy Oil GPH
3,691
26.4
24.6
4,306
30.8
28.7
5,235
37.4
34.9
6,155
44.0
41.0
7,658
54.7
51.0
9,235
66.0
61.6
10,758
76.8
71.7
12,303
87.9
82.0
15,378
110.0
102.7
18,458
132.0
123.2
21,525
154.0
143.7
Heating Surface Sq. Ft.
Fireside
Waterside
397
429
463
500
563
608
662
715
827
893
993
1,072
1,157
1,250
1,323
1,429
1,654
1,786
1,985
2,143
2,315
2,500
Furnace Volume Cu. Ft.
58.9
68.0
89.3
104.7
115.6
139.2
160.7
186.5
234.0
301.6
348.6
Heat Release MBH/Cu. Ft.
62.7
63.3
58.6
58.8
66.2
66.3
66.9
66.0
65.7
61.2
61.7
Water Content Gal.
Steam
Water
421
519
492
676
602
740
712
875
761
1,003
925
1,220
1,050
1,330
1,227
1,554
1,443
1,826
1,720
2,147
1,979
2,473
Approx. Dry Weight Lbs.
6,900
8,800
9,300
12,400
13,200
14,800
18,300
19,200
23,000
28,000
34,500
Approx. Full Weight Lbs.
Steam
Water
10,405
11,225
12,900
14,430
14,315
15,465
16,930
18,290
18,970
20,325
22,500
24,950
27,040
28,675
29,415
32,140
35,010
38,200
42,320
45,870
50,970
55,085
4F - 45 Boiler Models
Ratings based on 4.5 square feet of heating surface per boiler horsepower
29
Series 4F Standard Equipment
Boiler:
The boilers are a three pass design constructed and
stamped in accordance with ASME Section IV of the
ASME Code for 15 psig steam or 30 psig water on any
size boiler or 60 psig water on sizes 4FW63 through
4FW993. They are the sealed forced draft firing design
with skid base and floor insulation. The flue outlet is
a top outlet on sizes 4F63 through 4F345 and a rear
outlet on sizes 4F450 and larger. Optional outlets are
available on all sizes. The boiler comes complete with a
gas tight front flue cleanout door, rear observation port
on sizes 4F63 through 4F345, or rear access door and
observation port on sizes 4F450 and larger and lifting
lugs on sizes 4F127 and larger. Optional access doors
and lifting lugs are available for all sizes.
Jacket:
Rectangular type 1” fiberglass insulated jacket on sizes
4F63 through 4F345, 2” fiberglass insulated rectangular
jacket on sizes 4F450 through 4F675 and 2” fiberglass
wrap around jacket on sizes 4F827 and larger.
Steam Trim:
The following trim is shop mounted and wired: MM157
combination pump control and LWCO with alarm
contacts and quick opening blowoff valves, probe
type manual reset auxiliary LWCO, L404A operating
pressuretrol, L404C manual reset high limit pressuretrol
and appropriate firing rate control when required.
The following trim is shipped loose for field mounting:
3 ½” steam pressure gauge (on models 4FL63 through
4F675), 6” steam pressure gauge (on models 4F827
and larger), ASME side outlet safety valve(s) and gauge
glass set.
Water Trim:
The following trims are shop mounted and wired:
probe type LWCO (on 30 psig models 4FW63 through
4FW675) or MM63M manual reset LWCO with quick
opening blowoff valve (on 30 psig models 4FW827 and
larger) or probe type LWCO (on 60 psi models 4FW63
through 4FW675) or MM150M manual reset LWCO
with quick opening blowoff valve (on all 60 psi boilers
on models 4FW827 and larger) or L4006A operating
aquastat, L4006E manual reset high limit aquastat and
appropriate firing rate control when required.
The following trims are shipped loose for field mounting:
3 ½” theraltimeter (on models 4FW63 through 4FW675)
or 5” thermometer and 6” pressure/altitude gauge (on
models 4FW827 and larger) and loose ASME side outlet
relief valve(s).
Burner:
As selected for the fuel to be burned, mounted and
wired. Refer to burner data sheets for details of burner
equipment. Burners available for gas, No. 2 oil, No. 4 oil,
No. 5 oil, No. 6 oil, combination gas/No. 2 oil, gas/No. 4 oil, gas/No. 5 oil, gas/No. 6 oil, combination gas/No. 2 oil, gas/No. 4 oil, gas/No. 5 oil, and gas/No. 6 oil.
Instantaneous Hot Water Heating Coils
*For Use in the Following Boiler Sizes
Subject to Capacity Limitation of Boiler
Coil Number
Rated Capacity — Gallons Heated
40° to 140°F Boiler Water Temp.
108°F
180°F
212°F
GPM
GPH
GPH
INA-210
All sizes
3.5
210
325
INA-300
All except 4F-63
5.0
300
466
INA-360
All sizes
6.0
360
560
INA-450
All except 4F-63
7.5
450
700
INA-600
4F-154 and larger, also 4F-107
10.0
600
933
INA-750
4F-154 and larger, also 4F-107
12.5
750
1,165
INA-900
4F-92 and larger
15.0
900
1,400
INA-1125
4F-154 and larger
18.7
1,125
1,750
INA-1350
4F-277 and larger, also 4F-209
22.5
1,350
2,100
INA-1500
4F-345 and larger
25.0
1,500
2,330
*Two coils of any size or combination of sizes may be installed in 4F-1157 and larger
© 2006 Burnham Commercial - Lancaster, PA
Phone: 1-888-791-3790
www.burnhamcommercial.com
30
Series 4F-50
Forced Draft Firebox Generator
Ratings and Data
63
78
92
107
127
154
180
209
240
277
311
345
360A
450A
563A
675A
Gross Output
MBH
BHP
Lbs. Stm/Hr
422
12.6
435
522
15.6
538
616
18.4
635
716
21.4
738
850
25.4
876
1,031
30.8
1,063
1,205
36.0
1,242
1,400
41.8
1,442
1,607
48.0
1,656
1,855
55.4
1,911
2,082
62.2
2,146
2,310
69.0
2,381
2,410
72.0
2,484
3,015
90.0
3,108
3,770
112.6
3,885
4,520
135.0
4,660
Net Rating - Steam
MBH
Sq. Ft.
327
1,365
405
1,690
478
1,990
556
2,315
660
2,750
800
3,335
935
3,895
1,086
4,525
1,247
5,195
1,439
5,995
1,616
6,735
1,793
7,470
1,870
7,790
2,340 2,926 3,508
9,750 12,190 14,615
Net Rating - Water MBH
367
454
536
623
740
897
1,048
1,218
1,398
1,614
1,811
2,010
2,097
2,623
3,280
3,932
Firing Rate - Gas MBH
Firing Rate - Light Oil GPH
Heavy Oil GPH
528
3.8
—
653
4.7
—
770
5.5
—
895
6.4
—
1,063
7.6
—
1,289
9.2
—
1,506
10.8
—
1,750
12.5
—
2,009
14.4
—
2,319
16.6
—
2,603
18.6
—
2,888
20.6
—
3,013
21.5
20.1
3,769
27.0
25.2
4,713
33.6
31.4
5,650
40.4
37.7
Heating Surface Sq. Ft.
Fireside
Waterside
59
63
73
78
86
92
101
107
120
127
145
154
168
180
194
209
224
240
257
277
289
311
320
345
360
398
450
497
563
622
675
746
Furnace Volume Cu. Ft.
8.8
10.7
12.6
14.6
18.3
21.9
25.3
29.1
34.7
39.7
44.4
49.1
58.9
68.0
89.3
104.7
Heat Release MBH/Cu. Ft.
60.0
61.0
61.1
61.3
58.1
58.8
59.5
60.1
57.9
58.4
58.6
58.8
51.2
55.4
52.8
53.9
65
90
81
112
94
132
110
153
133
168
145
196
172
232
198
268
214
288
245
329
274
369
302
408
470
569
537
666
683
801
788
951
Approx. Dry Weight Lbs.
1,700
1,900
2,100
2,600
2,700
3,100
3,300
3,600
4,200
4,400
5,300
5,600
6,700
8,700
Approx. Full Weight Lbs.
Steam
Water
2,240
2,450
2,570
2,835
3,090
3,195
3,510
3,870
3,800
4,095
4,300
4,735
4,730
5,235
5,250
5,830
5,980
6,595
6,435
7,140
7,575
8,365
8,110 10,615 13,290 14,825 16,970
8,995 11,495 14,255 15,975 18,325
4F - 50 Boiler Models
360A-3
450-A
563A-3
675A-3
827
993
1157
1323
1654
1985
2315
2645
3075
Gross Output
MBH
BHP
Lbs. Stm/Hr
2,658
79.4
2,739
3,100
92.6
3,195
3,769
112.6
3,885
4,432
132.4
4,568
5,537
165.0
5,706
6,648
199.0
6,852
7,746
231.0
7,983
8,857
265.0
9,129
11,074
331.0
11,413
13,290
397.0
13,697
15,499
463.00
15,974
17,708
529.0
18,252
20,587
615.0
21,217
Net Rating - Steam
MBH
Sq. Ft.
2,063
8,596
2,406
10,025
2,925
12,188
3,439
14,329
4,299
17,910
5,161
21,505
6,014
25,060
6,877
28,655
8,598
35,825
10,318
42,995
12,033
50,140
13,748
57,285
15,976
66,525
Net Rating - Water MBH
2,312
2,697
3,279
3,856
4,817
5,784
6,739
7,706
9,634
11,562
13,484
15,406
17,911
Firing Rate - Gas MBH
Firing Rate - Light Oil GPH
Heavy Oil GPH
3,323
23.7
22.2
3,875
27.7
25.8
4,711
33.7
31.4
5,540
39.6
36.9
6,921
49.9
46.6
8,310
60.0
56.0
9,683
70.0
65.3
11,071
80.0
74.7
13,843
99.0
92.4
16,613
119.0
110.7
19,374
139.0
129.3
22,135
158.0
148.0
25,734
184.0
172.0
Heating Surface Sq. Ft.
Fireside
Waterside
397
429
463
500
563
608
662
715
827
893
993
1,072
1,157
1,250
1,323
1,429
1,654
1,786
1,985
2,143
2,315
2,500
2,645
2,857
3,075
3,321
Furnace Volume Cu. Ft.
58.9
68.0
89.3
104.7
115.6
139.2
160.7
186.5
234.0
301.6
348.6
383.8
505.6
Heat Release MBH/Cu. Ft.
56.4
57.0
52.8
52.9
59.9
59.7
60.3
59.4
59.2
55.1
55.6
63.5
50.9
Water Content Gal.
Steam
Water
421
519
492
676
602
740
712
875
761
1,003
925
1,220
1,050
1,330
1,227
1,554
1,443
1,826
1,720
2,147
1,979
2,473
2,173
2,718
2,814
3,665
Approx. Dry Weight Lbs.
6,900
8,800
11,000
12,400
14,800
18,300
19,200
19,800
23,000
28,000
34,500
38,200
49,000
Approx. Full Weight Lbs.
Steam
Water
10,450
11,225
12,900
14,430
14,315
15,465
16,930
18,290
18,970
20,325
22,500
24,950
27,040
29,375
29,415
32,140
35,010
38,200
42,320
45,870
50,970
55,085
56,290
60,820
72,430
79,510
4F - 50 Boiler Models
Water Content Gal.
Steam
Water
Ratings based on 5 square feet of heating surface per boiler horsepower
31
9,300 10,400
Series 4F Standard Equipment
Boiler:
The boilers are a three pass design constructed and
stamped in accordance with ASME Section IV of the
ASME Code for 15 psig steam or 30 psig water on any
size boiler or 60 psig water on sizes 4FW63 through
4FW993. They are the sealed forced draft firing design
with skid base and floor insulation. The flue outlet is
a top outlet on sizes 4F63 through 4F345 and a rear
outlet on sizes 4F450 and larger. Optional outlets are
available on all sizes. The boiler comes complete with a
gas tight front flue cleanout door, rear observation port
on sizes 4F63 through 4F345, or rear access door and
observation port on sizes 4F450 and larger and lifting
lugs on sizes 4F127 and larger. Optional access doors
and lifting lugs are available for all sizes.
Jacket:
Rectangular type 1” fiberglass insulated jacket on sizes
4F63 through 4F345, 2” fiberglass insulated rectangular
jacket on sizes 4F450 through 4F675 and 2” fiberglass
wrap around jacket on sizes 4F827 and larger.
Steam Trim:
The following trim is shop mounted and wired: MM157
combination pump control and LWCO with alarm
contacts and quick opening blowoff valves, probe
type manual reset auxiliary LWCO, L404A operating
pressuretrol, L404C manual reset high limit pressuretrol
and appropriate firing rate control when required.
The following trim is shipped loose for field mounting:
3 ½” steam pressure gauge (on models 4FL63 through
4F675), 6” steam pressure gauge (on models 4F827
and larger), ASME side outlet safety valve(s) and gauge
glass set.
Water Trim:
The following trims are shop mounted and wired:
probe type LWCO (on 30 psig models 4FW63 through
4FW675) or MM63M manual reset LWCO with quick
opening blowoff valve (on 30 psig models 4FW827 and
larger) or probe type LWCO (on 60 psi models 4FW63
through 4FW675) or MM150M manual reset LWCO
with quick opening blowoff valve (on all 60 psi boilers
on models 4FW827 and larger) or L4006A operating
aquastat, L4006E manual reset high limit aquastat and
appropriate firing rate control when required.
The following trims are shipped loose for field mounting:
3 ½” theraltimeter (on models 4FW63 through 4FW675)
or 5” thermometer and 6” pressure/altitude gauge (on
models 4FW827 and larger) and loose ASME side outlet
relief valve(s).
Burner:
As selected for the fuel to be burned, mounted and
wired. Refer to burner data sheets for details of burner
equipment. Burners available for gas, No. 2 oil, No. 4 oil,
No. 5 oil, No. 6 oil, combination gas/No. 2 oil, gas/No. 4 oil, gas/No. 5 oil, gas/No. 6 oil, combination gas/No. 2 oil, gas/No. 4 oil, gas/No. 5 oil, and gas/No. 6 oil.
Instantaneous Hot Water Heating Coils
Coil Number
*For Use in the Following Boiler Sizes
Subject to Capacity Limitation of Boiler
Rated Capacity — Gallons Heated
40° to 140°F Boiler Water Temp.
108°F
180°F
212°F
GPM
GPH
GPH
INA-210
All sizes
3.5
210
325
INA-300
All except 4F-63
5.0
300
466
INA-360
All sizes
6.0
360
560
INA-450
All except 4F-63
7.5
450
700
INA-600
4F-154 and larger, also 4F-107
10.0
600
933
INA-750
4F-154 and larger, also 4F-107
12.5
750
1,165
INA-900
4F-92 and larger
15.0
900
1,400
INA-1125
4F-154 and larger
18.7
1,125
1,750
INA-1350
4F-277 and larger, also 4F-209
22.5
1,350
2,100
INA-1500
4F-345 and larger
25.0
1,500
2,330
*Two coils of any size or combination of sizes may be installed in 4F-1157 and larger
© 2006 Burnham Commercial - Lancaster, PA
Phone: 1-888-791-3790
www.burnhamcommercial.com
32
Series 4F Forced Draft Firetube Boiler
“Ohio Special”
Series 4F Ohio Special Boiler Features:
• Three pass full wetback, packaged firetube type,
constructed in accordance with requirements of the ASME Boiler and Pressure Vessel Code, Section IV
for 15-psi steam. All units are registered with the National Board.
• Sealed forced draft firing design.
• Boiler tubes are expanded and flared. Separate
second and third pass rear tube sheets allow safe expansion and contraction.
• Waterback rear turnaround promotes rapid internal circulation and reduces gas temperatures at entrance to second pass, reducing tube and stress.
• Easy opening, insulated front flue doors with bolted closure provide full access to all tubes. A 16-inch diameter bolted rear access door with observation port
provides access to the boiler furnace.
• Handhole washouts are provided for easy inspection and cleaning of waterside surfaces.
• The round horizontal smoke outlet is standard. Vertical smokebox outlet and quadrant dampers are optional.
• All steam boilers provided with a dry pan to ensure
dry steam.
• All boilers are provided with an enameled steel jacket over 2 inches of fiberglass insulation and lifting lugs.
• The boiler is mounted on a heavy-duty steel base with extended skid and burner platform for protection of the burner during shipment and rigging.
33
Standard Trim and Controls
• Steam pressure gauge — 3 ½
• 157 combination pump control
• L404 operating pressuretrol
• LWCO with alarm contacts
• Gauge glass set
• L404C manual reset high limit pressuretrol and appropriate firing rate control when required. Manual reset probe auxiliary LWCO.
Dimensions (in Inches)
Ratings and Data
• quick opening blowoff valves
4F360-OS Boiler Model
4F360-OS Boiler Model
4F360-OS
Gross Output
MBH
BHP
Lb. Stm./Hr.
3,015
90.1
3,108
Net Rating - Steam
MBH
Sq. Ft.
2,340
9,750
107-1/2
Net Rating - Water
MBH
2,623
F - Base Extension
26-3/4
Firing Rate
G - Front Smoke Box Height
36-3/4
H - Front Smoke Box Depth
6-1/2
Gas - MBH
Oil - GPH
Light Oil (140,000 BTU/Gal.)
Heavy Oil (150,000 BTU/Gal.)
A - Boiler Width
52-1/4
B - Boiler Length
80-3/4
C - Boiler Height
82-3/8
D - Base Width
53-1/8
E - Base Length
J - Supply Location
26
K - Supply Size - Flanged
8
L - Return Size - Threaded
M - Return Location
4
7-3/8
N - Smoke Box Depth - Rear Vent
8
P - Vent Collar Diameter
14
Q - Rear Vent Collar Height
R - Smoke Box Depth - Top Vent
T - Top Vent Collar Height
U - Tube Pull Space
3,769
—
26.9
25.1
Heating Surface - Sq. Ft.
Fireside
Waterside
358
396
Furnace Volume
Cu. Ft.
58.9
Heat Release
MBH/Cu. Ft.
64
Water Content - Gal.
Steam
Flooded
470
569
58-3/4
Approx. Dry Weight - Lbs.
16
Approx. Full Weight - Lbs.
66-1/4
6,710
Steam
Flooded
10,615
11,495
81
V - Supply Fitting Height
3-1/2
W - Normal Water Line Height
69-1/4
34
© 2006 Burnham Commercial - Lancaster, PA
Phone: 1-888-791-3790
www.burnhamcommercial.com
Series 4N
Natural Draft Firebox Boiler
35
Series 4N Natural Draft Firebox Boiler
Ratings for Oil, Gas or Stoker Firing
4N Boiler Models
63
78
92
107
127
154
180
209
240
277
311
345
397
Gross Output
MBH
BHP
Lbs.Stm./Hr.
245
7.3
253
299
8.9
308
348
10.4
359
403
12.0
415
522
15.6
538
626
18.7
645
724
21.6
746
870
26.0
897
996
29.8
1,027
1,142
34.1
1,177
1,278
38.2
1,317
1,414
42.2
1,457
21,60
65
2,226
Net Rating Steam
MBH
Sq. Ft.
190
790
232
970
270
1,125
313
1,305
405
1,690
486
2,025
562
2,340
675
2,815
773
3,220
887
3,695
992
4,235
1,098
4,570
1,667
6,990
Net Rating Water
MBH
213
260
303
351
454
545
630
757
867
994
1,112
1,230
1,878
Firing Rate - Gas MBH
Light Oil (140,000 BTU/Gal.)
Heavy Oil (150,000 BTU/Gal.)
306
2.2
—
374
2.7
—
435
3.1
—
504
3.6
—
653
4.7
—
783
5.6
—
905
6.5
—
1,088
7.8
—
1,245
8.9
—
1,428
10.2
—
1,598
11.4
—
1,768
12.6
—
2,700
19.3
18.0
Coal (Stoker)
Lbs./Hr.
25
31
36
41
54
64
74
89
102
117
131
145
222
Heating Surface
Sq. Ft.
Fireside
Waterside
45
47
55
57
64
67
74
77
96
100
115
120
133
139
153
160
183
193
210
221
235
247
260
274
397
429
Furnace Volume
Cu. Ft. *
8.8
10.7
12.6
14.6
18.3
21.9
25.3
29.1
34.7
39.7
44.4
49.1
58.9
Heat Release
MBH/Cu. Ft.
34.8
35.0
34.5
34.5
35.7
35.8
35.8
37.4
35.9
36.0
36.0
36.0
45.8
67
92
83
114
96
134
113
156
133
168
149
200
171
231
197
267
209
283
239
323
267
362
295
401
421
520
1,500
1,700
1,900
2,200
2,500
2,800
3,100
3,400
3,900
4,300
4,900
5,200
6,500
Water
2,055
2,265
2,390
2,650
2,700
3,020
3,140
3,500
3,605
3,895
4,040
4,465
4,525
5,025
5,040
5,620
5,635
6,250
6,285
6,985
7,120
7,910
7,650
8,535
10,005
10,830
463
563
662
827
993
1157
1323
1654
1985
2315
2645
3075
Gross Output
MBH
BHP
Lbs.Stm./Hr.
2,519
75
2,596
3,063
92
3,156
3,601
108
3,712
4,499
134
4,636
5,402
161
5,567
6,294
188
6,484
7,197
215
7,417
8,998
269
9,273
10,798
323
11,129
12,594
376
12,979
14,389
430
14,829
16,738
500
17,250
Net Rating Steam
MBH
Sq. Ft.
1,956
8,150
2,378
9,910
2,796
11,650
3,493
14,555
4,194
17,475
4,887
20,360
5,588
23,280
6,986
29,110
8,384
34,930
9,778
40,740
11,172
46,550
12,989
54,120
Net Rating Water
MBH
2,190
2,663
3,131
3,912
4,697
5,473
6,258
7,824
9,390
10,951
12,512
14,554
3,149
22.5
21.0
3,829
27.3
25.5
4,501
32.1
30.0
5,624
40.2
37.5
6,753
48.2
45.0
7,868
56.2
52.5
8,996
64.3
60.0
11,248
80.3
75.0
13,498
96.4
90.0
15,743
112.5
104.9
17,986
128.5
120.0
20,923
149.5
139.5
Water Content Gals.
Steam
Water
Approx. Dry Weight Lbs.
Lbs.
Approx. Weight FullSteam
4N Boiler Models
Firing Rate - Gas MBH
Light Oil (140,000 BTU/Gal.)
Heavy Oil (150,000 BTU/Gal.)
Coal (Stoker)
Lbs./Hr.
258
314
369
461
554
646
738
923
1,108
1,292
1,476
1,717
Heating Surface
Sq. Ft.
Fireside
Waterside
463
500
563
608
662
715
827
893
993
1,072
1,157
1,250
1,323
1,429
1,654
1,786
1,985
2,143
2,315
2,500
2,645
2,857
3,075
3,321
Furnace Volume
Cu. Ft. *
68.0
89.3
104.7
115.6
139.2
160.7
186.5
234.0
301.6
348.6
383.8
505.6
Heat Release
MBH/Cu. Ft.
46.3
42.9
43.0
48.7
48.5
49.0
48.2
48.1
44.8
45.2
46.9
41.4
492
607
602
740
712
875
761
1,003
925
1,220
1,050
1,330
1,227
1,554
1,443
1,826
1,720
2,147
1,979
2,473
2,173
2,718
2,814
3,665
Approx. Dry Weight Lbs.
8,000
8,500
10,100
12,300
13,300
16,600
18,600
21,700
26,500
32,800
37,500
48,200
Approx. Weight Full Lbs.
Steam
Water
12,100
13,055
13,515
14,665
16,030
17,390
18,630
20,645
21,005
23,455
25,340
27,675
28,815
31,540
33,710
36,900
40,815
44,370
49,270
53,385
55,590
60,120
71,630
78,710
Water Content Gals.
Steam
Water
All models have 3 inch diameter tubes—except 3075 has 2-1/2 inch tubes
* = deos not include base volume
36
Series 4N — Models 63 - 662
Dimensions (Inches)
4N Boiler Models
A - Boiler Width
B - Boiler Length
63
78
92
107
127
154
180
209
240
277
311
345
397
463
30-1/4 30-1/4 30-1/4 30-1/4 35-7/8 35-7/8 35-7/8 35-7/8 44-5/8 44-5/8 44-5/8 44-5/8 52-1/4 52-1/4
30
37
43-1/2 50-1/2 42-1/2
51
59
68
55
63
70-1/2
78
563
662
56
56
76-3/4 89-1/4 100-3/8 118-1/4
C - Boiler Height
52-1/8 52-1/8 52-1/8 52-1/8 60-1/2 60-1/2 60-1/2 60-1/2 67-1/2 67-1/2 67-1/2 67-1/2 79-1/4 79-1/4
82
82
D - Base Width
29-3/4 29-3/4 29-3/4 29-3/4 35-1/8 35-1/8 35-1/8 35-1/8 43-7/8 43-7/8 43-7/8 43-7/8 50-1/8 50-1/8
54
54
E - Base Length
30-1/2 37-1/2
*F - Base Height
15
15
44
51
43
15
15
18
51-1/2 59-1/2 68-1/2 55-1/2 63-1/2
18
18
18
18
18
71
18
78-1/2 78-1/8 90-5/8 101-3/4 119-5/8
18
18
18
18
18
G - Front Smoke Box Height
22-3/4 22-3/4 22-3/4 22-3/4 24-7/8 24-7/8 24-7/8 24-7/8 30-5/8 30-5/8 30-5/8 30-5/8 33-5/8 33-5/8 36-3/4 36-3/4
H - Front Smoke Box Depth
6-1/2
6-1/2
6-1/2
6-1/2
7-1/2
7-1/2
7-1/2
7-1/2
8-1/2
8-1/2
8-1/2
8-1/4
8-1/4
8-1/4
9-3/4
9-3/4
12
12
12
12
15
15
15
15
18
18
18
18
26
26
26
26
4
4
4
4
6
6
6
6
6
8
8
8
8
10
10
10
J - Supply Location
**K - Supply Size
L - Return Size
3
3
3
3
4
4
4
4
4
4
4
4
4
4
4
4
M - Return Location
3-1/2
3-1/2
3-1/2
3-1/2
4
4
4
4
4
4
4
4
4-3/8
4-3/8
4-3/8
4-3/8
N - Smoke Box Depth - Top
Rear
8
8
8
8
9
9
9
9
10
10
10
10
16-1/2 16-1/2 16-1/2 16-1/2 20-1/2 20-1/2 20-1/2 20-1/2 22-1/2 22-1/2 22-1/2 22-1/2
16
16
16
16
16
16
16
16
20
24
26
28
P - Vent Collar Diameter
Q - Rear Vent Collar Height
14
14
14
14
33-7/8 33-7/8 33-7/8 33-7/8
18
18
18
18
20
20
20
20
40
40
40
40
46
46
46
46
51-1/2 51-1/2 52-3/8 52-3/8
35-1/4 35-1/4 42-1/2 42-1/2
R - Smoke Box Collar
Width Top Vent
—
—
—
—
—
—
—
—
—
—
—
—
S - Smoke Box Collar
Depth Top Vent
—
—
—
—
—
—
—
—
—
—
—
—
10
13
T - Top Vent Collar Height
U - Tube Pull Space
41-7/8 41-7/8 41-7/8 41-7/8 49-1/8 49-1/8 49-1/8 49-1/8
57
57
57
57
64
64
61
70
57
65
72-1/2
80
81
94
105
23
3-3/8
3-3/8
3-3/8
3-3/8
3-3/8
3-3/8
3-3/8
3-1/2
3-1/2
3-5/8
3-5/8
55
55
55
55
69
69
39
45-1/2 52-1/2 44-1/2
V - Supply Fitting Height
1-5/8
1-5/8
W - Normal Water Line Height
40-3/4 40-3/4 40-3/4 40-3/4 48-1/2 48-1/2 48-1/2 48-1/2
1-5/8
*Oil, Gas, Stoker Only - See note below rating table for hand-fired boilers.
**4” is IPS female thread, 6” and larger are flanged
Specifications, dimensions data subject to change without notice.
3-3/8
13
53
32
1-5/8
12
37
66-3/16 66-3/16
66-7/8 66-7/8
4N —
Models
827
- 3075
TheSeries
Complete
Boiler
Room
Supplier
The
Complete
Boiler
Room
Supplier
Dimensions (Inches)
4N Boiler Models
827
993
1157
1323
1654
1985
2315
2645
3075
A - Boiler Width
64
64
70
70
76
82
82
82
96
B - Boiler Length
106-1/4
129
116-1/2
136
130-1/2
128
148
162
163
*C - Boiler Height
91
91
102-1/2
102-1/2
118-1/8
138-1/8
138-1/8
138-1/8
148
D - Base Width
61-1/2
61-1/2
67-1/2
67-1/2
73-1/2
79-1/2
79-1/2
79-1/2
93-1/2
E - Base Length
107-1/4
130
117-1/2
137
131-1/2
129
149
164
164
F - Base Height
18
18
18
18
18
18
18
18
18
G - Front Smoke Box Door Height
29-5/16
29-5/16
35-7/16
35-7/16
40-3/8
52-1/8
52-1/8
52-1/8
65-7/8
H - Front Smoke Box Depth
12-3/4
12-3/4
13-3/4
13-3/4
14-3/4
15-3/4
15-3/4
15-3/4
16-1/2
J - Supply Location
22
22
22
22
22
22
22
22
68
**K - Supply Size
8
8
8
8
10
12
12
12
12
**L - Return Size - Steam
4
4
4
6
6
6
6
6
6
**L - Return Size - Water
6
6
6
8
8
8
8
8
8
M - Return Location
N - Smoke Box Depth Rear
P - Rear Vent Collar Diameter
6
6
6-7/8
6-7/8
6-7/8
7-1/4
7-1/4
7-1/4
7
20-3/4
20-3/4
22-3/4
22-3/4
22-3/4
24-3/4
24-3/4
24-3/4
26
28
32
32
35
38
44
44
44
46
71-1/2
71-1/2
81-1/2
81-1/2
94-5/8
110-5/8
110-5/8
110-5/8
119
R - Top Vent Collar Width
48
48
51
51
55
72
72
72
84
S - Top Vent Collar Depth
14
17
16
19
16
18
18
18
22
T - Top Vent Collar Height
Q - Rear Vent Collar Height
87-3/4
87-3/4
99-1/4
99-1/4
113-7/8
132-7/8
132-7/8
132-7/8
142
U - Tube Pull Space
108
131
118-1/2
138
132-1/2
130
150
165
165
W - Normal Water Line Height
74
74
85-1/2
85-1/2
100-1/4
114-1/4
114-1/4
114-1/4
122-1/2
*Oil, Gas, Stoker Only - See note below rating table for hand-fired boilers.
**4” is IPS female thread, 6” and larger are flanged
Specifications, dimensions data subject to change without notice.
38
Series 4N Ratings
• 15 psi steam, 30 psi water
• Compact, efficient three-pass firebox design
• Applications firing solid fuel, gas or oil
• Ample firebox assures non-critical combustion,
high efficiency
Ratings for Hand Firing
4N Boiler Models
63
78
92
107
127
154
180
209
240
277
311
345
158
660
1,055
192
800
1,280
225
935
1,500
259
1,080
1,725
337
1,405
2,245
404
1,685
2,695
468
1,950
3,120
538
2,240
3,590
649
2,700
4,330
744
3,100
4,960
831
3,460
5,540
922
3,840
6,150
Fireside
Waterside
45
47
55
57
64
67
74
77
96
100
115
120
133
139
153
160
183
193
210
221
235
247
260
274
Grate Area
Sq. Ft.
4.0
5.1
6.1
7.2
7.2
8.8
10.3
12.0
12.6
12.6
13.4
14.5
Furnace Volume
Cu. Ft.
8.8
10.7
12.6
14.6
18.3
21.9
25.3
29.1
34.7
39.7
44.4
49.1
Heat Release
MBH/Cu. Ft.
39.9
40.1
39.2
39.2
40.5
41.0
41.1
42.9
41.2
41.3
41.0
41.0
Water Content - Gals.
Steam
Water
67
92
83
114
96
134
113
156
133
168
149
200
171
231
197
267
209
283
239
323
267
362
295
401
1,900
2,200
2,500
2,900
3,200
3,700
4,100
4,600
5,150
5,550
6,250
6,650
Steam
Water
2,455
2,665
2,900
3,160
3,310
3,630
3,860
4,220
4,325
4,615
4,920
5,905
5,555
6,055
6,240
6,820
6,895
7,510
7,545
8,245
8,460
9,250
9,100
9,985
397
463
563
662
827
993
1157
1323
1654
1985
2315
2645
Net Rating - Steam or Water
Net Rating - Steam
Net Rating - Water
MBH
Sq. Ft.
Sq. Ft.
1,408
5,865
9,391
1,724
7,185
11,500
2,188
9,115
14,595
2,572
10,715
17,155
3,214
13,390
21,435
3,859
16,080
25,740
4,496
18,730
29,990
5,141
21,420
34,290
6,427
26,780
42,870
7,713
32,135
51,445
8,996
37,485
60,005
10,278
42,825
68,555
Heating Surface - Sq. Ft.
Fireside
Waterside
397
429
463
500
563
608
662
715
827
893
993
1,072
1,157
1,250
1,323
1,429
1,654
1,786
1,985
2,143
2,315
2,500
2,645
2,857
Grate Area
Sq. Ft.
16.4
18.1
20.5
22.5
25.6
28.4
30.9
33.2
37.4
41.2
44.7
48.0
Furnace Volume
Cu. Ft.
58.9
68.0
89.3
104.7
115.6
139.2
160.7
186.5
234.0
301.6
348.6
383.8
Heat Release
MBH/Cu. Ft.
52.3
53.0
49.1
49.2
55.6
55.5
56.0
55.1
55.0
51.2
51.6
53.6
Water Content - Gals.
Steam
Water
421
520
492
607
602
740
712
875
761
1,003
925
1,220
1,050
1,330
1,227
1,554
1,443
1,826
1,720
2,147
1,979
2,473
2,173
2,718
8,150
9,800
10,550
12,350
14,850
16,150
19,700
21,900
25,450
30,600
37,250
42,300
11,645
12,470
13,910
14,865
15,565
16,715
18,280
19,640
21,190
23,200
23,845
26,295
28,480
30,715
32,132
34,860
37,450
40,640
44,935
48,490
53,740
57,855
60,400
64,920
Net Rating - Steam or Water
Net Rating - Steam
Net Rating - Water
MBH
Sq. Ft.
Sq. Ft.
Heating Surface - Sq. Ft.
Approx. Dry Weight - Lbs.
Approx. Full Weight - Lbs.
4N Boiler Models
Approx. Dry Weight - Lbs.
Approx. Full Weight - Lbs.
Steam
Water
Grates for hand firing are not supplied by Burnham Commercial
Select boiler on net rating to match building heat loss or installed radiation.
See additional note regarding heat value of coal on back page
39
Series 4NThe
— Biomass/Wood
Complete BoilerRatings
Room Supplier
Model 4NP-68
Gross Ratings
Boiler Model
MBH
HP
Steam
Lbs./Hr.
Firing Rate
Lbs./Hr.
Fireside Heating Surface
Sq. Ft.
Furnace
Volume
Cu. Ft.
Water Content-Gallons
Water
Steam
Dry Weight
Lbs.
4NP625-68
3,077
92
3,171
653
625
148.5
941
764
16,211
4NP925-68
4,554
136
4,693
967
925
186.6
1,195
1,006
19,675
4NP1250-68
6,153
184
6,342
1,306
1,250
238.0
1,486
1,888
24,562
4NP1538-68
7,571
226
7,803
1,607
1,538
315.7
1,789
1,450
27,390
4NP1850-68
9,107
272
9,386
1,934
1,850
407.7
2,118
1,681
32,595
4NP2153-68
10,599
317
10,923
2,250
2,153
471.9
2,609
2,056
39,030
4NP2500-68
12,307
368
12,684
2,613
2,500
521.3
2,820
2,209
40,190
4NP3075-68
15,138
452
15,601
3,214
3,075
500.4
3,406
2,586
46,370
4NP3690-68
18,165
543
18,721
3,857
3,690
574.1
3,842
2,901
55,000
4NP4305-68
21,193
633
21,842
4,499
4,305
716.2
4,465
3,381
61,996
Model 4NL/W-68
Gross Ratings
Boiler Model
Firing Rate
Lbs./Hr.
Fireside Heating
Surface
Sq. Ft.
MBH
HP
Steam
Lbs./Hr.
4NL/W63-68
222
6.6
228
47
47
4NL/W78-68
271
8.1
279
57
55
Furnace
Volume
Cu. Ft.
Water Content-Gallons
Water
Steam
8.8
2,265
2,055
10.7
2,650
2,390
4NL/W92-68
315
9.4
325
67
64
12.6
3,020
2,700
4NL/W107-68
364
10.9
375
77
74
14.6
3,500
3,140
4NL/W127-68
473
14.1
487
100
96
18.3
2,895
3,605
4NL/W154-68
566
16.9
583
120
115
21.9
4,465
4,040
4NL/W180-68
655
19.6
675
139
133
25.3
5,025
4,525
4NL/W209-68
753
22.5
776
160
153
29.1
5,620
5,040
4NL/W240-68
901
26.9
928
191
183
34.7
6,250
5,635
4NL/W277-68
1,034
30.9
1,065
219
210
39.7
6,985
6,285
4NL/W311-68
1,157
34.6
1,192
246
235
44.4
7,910
7,120
4NL/W345-68
1,280
38.2
1,319
272
260
49.1
8,535
7,650
4NL/W397-68
1,954
58.4
2,014
415
397
58.9
10,830
10,005
4NL/W463-68
2,279
68.1
2,349
484
463
68.0
13,055
12,100
4NL/W563-68
2,772
82.8
2,856
588
563
89.3
14,665
13,515
4NL/W662-68
3,259
97.4
3,359
692
662
104.7
17,390
16,030
4NL/W827-68
4,071
121.6
4,196
864
827
115.6
20,645
18,630
4NL/W993-68
4,888
146.0
5,038
1,038
993
139.2
23,455
21,005
4NL/W1157-68
5,696
170.1
5,870
1,209
1,157
160.7
27,675
25,340
4NL/W1323-68
6,513
194.6
6,712
1,383
1,323
186.5
31,540
28,815
4NL/W1654-68
8,142
243.2
8,392
1,729
1,654
234.0
36,900
33,710
4NL/W1985-68
9,772
291.9
10,071
2,075
1,985
301.6
44,370
40,815
4NL/W2315-68
11,396
340.4
11,745
2,420
2,315
348.6
53,385
49,270
4NL/W2645-68
13,021
389.0
13,419
2,764
2,645
383.8
60,120
55,590
4NL/W3075-68
10,215
305.1
10,528
2,169
2,075
505.6
78,710
71,630
NOTES:
1. Boiler model suffix “68” indicates 6.8 SQ.FT.F.S.H.S./HP
2. Firing rate based on biomass/wood fuel at 6000 BTU/LB and 78.5% operating efficiency
3. Furnace volume is measured from the bottom of the boiler mudleg
40
Series 4N Natural Draft Firebox Boiler
Hand Fired Boilers — Rating Adjustment for
Heating Value of Coal
Jacket: Wrap-around type, with fiberglass
insulation—installed.
Hand fired ratings are based on coal having a heat value
of 13,000 btu per pound. For coal of lesser heat value
per pound, multiply the net load by the factor shown in
the table before selecting boiler size:
Heat Value of Coal - BTU/Lb.
12,500
12,000
11,500
11,000
10,500
10,000
9,500
9,000
Factor
1.04
1.08
1.13
1.18
1.24
1.30
1.37
1.44
Steam Trim: Steam pressure gauge (3-1/2 inch 63A
through 662A; 6 inch 827 and larger), gauge glass set
for mounting on boiler with 63A through 345A, cast iron
water column with gauge glass set and tricocks 397A
and larger, and ASME safety valve(s). Trim not installed.
Water Trim: Theraltimeter (3-1/2 inch) 63A through
662A, pressure/altitude gauge (6 inch) and thermometer,
(6 inch) 827 and larger, ASME relief vavle(s). Trim not
installed.
Additional Equipment
Oil & Gas Fired Boilers - Burner opening in front head
(base refractory or combustion equipment is not supplied
by Burnham Commercial).
Standard Equipment
Boiler: Three-pass boiler constructed and stamped in
accordance with Section IV of the ASME Boiler and
Pressure Vessel Code for 15 psi steam and 30 psi
water with separate base, rear smoke outlet (top outlet
available when specified), gas tight front flue cleanout
door, rear observation port 63A through 345A, rear
access door with observation port 397A and larger,
lifting lugs 127A and larger.
Stoker Fired Boilers - Firedoor(s) in front head; hinged
flue door, all sizes; ashpit door in base (Stoker not
supplied by Burnham Commercial).
Hand Fired Boilers - Same as stoker fired (Grate sets
not supplied by Burnham Commercial).
Instantaneous Hot Water Heating Coils
Rated Capacity—Gallons Heated
40° to 140°F
Boiler Water Temp.
Coil Number
*For Use in the Following Boiler Sizes
Subject to Capacity Limitation of Boiler
108°F
GPM
180°F
GPH
212°F
GPH
INA-210
All sizes
3.5
210
325
INA-300
All except 4N-63A
5.0
300
466
INA-360
All sizes
6.0
360
560
INA-450
All except 4N-63A
7.5
450
700
INA-600
4N-154A and larger, also 4N-107A
10.0
600
933
INA-750
4N-154A and larger, also 4N-107A
12.5
750
1165
INA-900
4N-92A and larger
15.0
900
1400
INA-1125
4N-154A and larger
18.7
1125
1750
INA-1350
4N-277AS and larger, also 4N-209A
22.5
1350
2100
INA-1500
4N-345A and larger
25.0
1500
2330
*Two coils of any size or combination of sizes may be installed in 4N-1157 and larger
41
Series 4N Natural Draft Firebox Boiler
Lancaster, PA 17601
Phone: 888-791-3790
www.burnhamcommercial.com
42
Series 4NP Natural Draft Firebox Boiler
4NP Boiler Models
625
925
1250
1538
A - Boiler Length
141
152
164
165
169
177
192
191
214
243
B - Boiler Supply Height
95
103
113
127
145
151
151
151
151
151
C - Base Length at Mudleg
125
136
142
143
143
151
166
161
184
213
D - Boiler Width at Mudleg
62
68
74
80
86
92
92
104
104
110
1850
2153
2500
3075
3690
4305
E - Firebox Width
48
54
60
66
72
78
78
90
90
96
F - Firebox Length
112
123
129
130
130
138
153
148
171
200
G - Firebox Height
40
42
46
54
66
66
66
54
54
54
H - Supply Location
65
71
75
75
77
79
87
86
98
112
J - Supply Nozzle Size (300lb. Flg.)
4
6
6
6
8
8
8
8
10
10
K - Return Connection Location
31-1/2
31-1/2
31-1/2
31-1/2
31-1/2
31-1/2
31-1/2
31-1/2
31-1/2
31-1/2
M - Return Connection Size
1-1/2
1-1/2
1-1/2
2
2
2-1/2
3
3
3
3
N - Front Smokebox Depth
10
10
12
12
14
14
14
16
16
16
P - Tube Removal Space
117
128
132
133
131
139
154
147
170
199
39
45
Q - Rear Flue Outlet Diameter
27
32
45
45
48
48
48
51
R - Base to Flue Centerline
67-3/4
73-1/4
81-15/16 91-5/8
109-9/16
112-9/16
112-9/16
107-7/16
107-7/16
107-7/16
S - Normal Water Line
92-5/16 104-1/4
76-1/2
83-7/8
121-1/4
125-13/16
125-13/16
122-3/8
122-3/8
122-3/8
AA - Width Over Columns
81
87
93
99
105
111
111
123
123
123
BB - Front and Rear Column Location
17
17
17
17
17
17
17
17
17
17
CC - Middle Column Location
46
54
54
55
55
61
69
64
78
85
Approximate Dry Weight (Lbs.)
16,211
19,675
24,562
27,390
32,595
39,030
40,190
46,370
55,000
61,996
Approximate Weight, Full (Lbs.)
22,575
28,055
34,458
39,469
46,598
56,156
58,591
67,911
79,165
90,160
All specifications, dimensions and data subject to change without notice. Dimensions shown are measured in inches.
43
The Complete
Complete Boiler
Boiler Room
Room Supplier
Supplier
The
Series 4NP
GROSS RATINGS
NET RATINGS
MAX. FIRING RATE - SINGLE
FUEL
HEATING
SURFACE
SQ. FT.
FURNACE
VOLUME.
CU. FT.
WATER
CONTENT
GALLONS
(STEAM)
148.5
764
BOILER
MODEL
MBH
HP
LBS.
STM./
HR.
STEAM
MBH
SQ. FT.
STEAM
GAS
MBH
#2
OIL
GPH
#6
OIL
GPH
#LBS/
HR.
COAL*
FIRE
SIDE
4NP625-62
3,348
100
3,450
2,598
10,825
4,185
30.3
27.9
328*
625
4NP925-62
5,021
150
5,175
3,896
16,233
6,276
45.5
41.8
492*
925
186.6
1,006
4NP1250-62
6,695
200
6,900
5,195
21,646
8,369
60.6
55.8
656*
1,250
238.0
1,188
4NP1538-62
8,369
250
8,625
6,494
27,058
10,461
75.8
69.7
820*
1,538
315.7
1,450
4NP1850-62
10,043
300
10,350
7,793
32,471
12,554
91.0
83.7
984*
1,850
407.7
1,681
4NP2153-62
11,716
350
12,075
9,092
37,883
14,645
106.1
97.6
1148*
2,153
471.9
2,056
4NP2500-62
13,390
400
13,800
10,391
43,296
16,738
121.3
111.6
1312*
2,500
521.3
2,209
4NP3075-62
16,738
500
17,250
12,989
54,121
20,923
151.6
139.5
1,640*
3,075
500.42
2,586
4NP3690-62
20,085
600
20,700
15,586
64,942
25,106
181.9
167.4
1,968*
3,690
574.05
2,901
4NP4305-62
23,433
700
24,150
18,184
75,767
29,291
212.3
195.3
2,296*
4,305
716.22
3,381
4NP625-50
4,184
125
4,312
3,247
13,529
5,230
37.9
34.9
282**
625
148.5
764
4NP925-50
6,193
185
6,383
4,806
20,025
7,741
56.1
51.6
417**
925
186.6
1,006
4NP1250-50
8,369
250
8,625
6,494
27,058
10,461
75.8
69.7
563**
1,250
238.0
1,188
4NP1538-50
10,043
300
10,350
7,793
32,471
12,554
91.0
83.7
676**
1,538
315.7
1.450
4NP1850-50
12,386
370
12,765
9,612
40,050
15,483
112.2
103.2
834**
1,850
407.7
1,681
4NP2153-50
14,394
430
14,835
11,170
46,542
17,993
130.4
119.9
969**
2,153
471.9
2,056
4NP2500-50
16,738
500
17,250
12,989
54,121
20,923
151.6
139.5
1,127**
2,500
521.3
2,209
4NP3075-50
20,085
600
20,700
15,586
64,942
25,106
181.9
167.4
1,352**
3,075
500.42
2,586
4NP3690-50
23,433
700
24,150
18,184
75,767
29,291
212.3
195.3
1,577**
3,690
574.05
2,901
4NP4305-50
28,454
850
29,325
22,080
92,001
35,568
257.7
237.1
1915**
4,305
716.22
3,381
NOTES:
1. Boiler model suffix “62” indicates 6.15 sq. ft. F.S.H.S. /HP and “50” indicates 5 sq. ft. F.S.H.S./HP
2. Firing rate based on:
Natural gas @ 1000 BTU/cu. ft. and 80% heat transfer efficiency
#2 oil @ 138 MBH/gal. and 80% heat transfer efficiency
#6 oil @ 150 MBH/gal. and 80% heat transfer efficiency
* 100% coal input @ 13,000 BTU/pound and 78.5% heat transfer efficiency (6.15 rating)
** Coal input @ 13,000 BTU/pound limited to 70% of input in order to develop 5 sq. ft. rating.
3. Furnace volume is measured from the bottom of the boiler mud leg (no deduction for bridgewall)
4. Approximate dry weight includes H columns and base casing.
Lancaster, PA 17601
888-791-3790
www.burnhamcommercial.com
44
C Series
Compact Package Boiler
45
C Series Compact Packaged Boiler
America’s Boiler Company
FRONT
REAR
The Burnham Commercial C Series compact packaged
boiler was designed using our 140+ years of boiler
experience and is sold and serviced through the largest
and most experienced network of sales representatives in
the country. With a complete commercial product offering
and unmatched sales and technical support, it’s no wonder
why we are America’s Boiler Company!
Packaged Boilers That Can Actually Fit
Through A Door!
The C Series Firetube boiler is fully packaged and
designed to provide maximum cost and energy efficiency.
The C Series boiler fits through any standard 36” x 80”
doorway, eliminating the need for any costly building
alterations or difficult site assemblies. This convenient size
allows for easier and less expensive retrofit or upgrade of
an existing boiler room.
and extra heavy tube sheets assure the continued airtight
conditions necessary for efficient combustion. Opening the
front flue door allows convenient access to the firetubes. By
brushing out all of the firetubes, the original efficiency of the
boiler is restored in a matter of minutes. All tube ends are
rolled in accordance with the ASME code and are inspected
for hydraulic tightness by an independent insurance
inspector, prior to shipping.
These installation, operation and maintenance features add
up to real savings for you. Factory testing assures you that
the boiler will deliver clean, quiet and reliable heat from the
day it’s installed.
A forced-draft unit, the C Series avoids the expense of a tall
stack and is much more economical to operate and install
than atmospheric-fired boilers. The forced draft creates a
more controlled combustion, and a more thorough mixture
of fuel and air is acheived resulting in optimum efficiency.
Other design features help maintain this durability and
economy over the years. While the original efficiency of
some other boilers can decrease when outer wrappers
develop air leaks and tubes cannot be cleaned thoroughly,
the C Series overcomes these problems. Built to ASME
standards, its outer shell of heavy welded steel boilerplate
46
Efficiencies and Features
C Series Anticipated Efficiencies
NATURAL GAS
25%
50%
75%
100%
Boiler HP
10 psig
180°F Water
10 psig
180°F Water
10 psig
180°F Water
10 psig
180°F Water
20
83.2
85.3
83.5
85.3
83.2
84.8
82.6
84.1
30
83.7
85.7
83.8
85.4
83.4
84.9
82.7
84.1
40
83.9
85.8
83.9
85.5
83.4
84.9
82.7
84.1
50
84.1
86.0
84.1
85.7
83.7
85.1
83.0
84.4
60
84.3
86.1
84.3
85.9
84.0
85.4
83.4
84.8
70
84.4
86.1
84.3
85.8
83.9
85.3
83.3
84.7
80
84.4
86.2
84.3
85.9
83.9
85.4
83.3
84.7
90
84.6
86.3
84.6
86.1
84.3
85.7
83.8
85.2
100
84.7
86.4
84.8
86.3
84.6
86.0
84.2
85.6
#2 OIL
25%
50%
75%
100%
Boiler HP
10 psig
180°F Water
10 psig
180°F Water
10 psig
180°F Water
10 psig
180°F Water
20
86.0
88.2
86.2
87.9
86.0
87.5
85.4
86.9
30
86.7
88.6
86.7
88.3
86.4
87.8
85.8
87.2
40
86.8
88.7
86.8
88.3
86.4
87.9
85.9
87.3
50
87.2
89.0
87.1
88.6
86.8
88.2
86.3
87.7
60
87.4
89.2
87.4
88.9
87.1
88.6
86.7
88.1
70
87.5
89.2
87.3
88.9
87.1
88.5
86.6
88.0
80
87.5
89.3
87.4
88.9
87.1
88.5
86.7
88.0
90
87.8
89.5
87.8
89.3
87.6
89.0
87.2
88.6
100
88.0
89.7
88.0
89.6
87.9
89.3
87.6
89.0
C Series Features
Boiler:
an enameled steel jacket installed over fiberglass insulation.
The boiler is mounted on a heavy-duty structural steel base
with extended skid and burner platform for protection of the
burner during shipment and rigging.
Three-pass firetube type, constructed with heavy steel, in accordance with requirements of the ASME Code. All units are
registered with the National Board.
Water cooled sidewalls in the rear turnaround promote rapid
internal circulation and reduce gas temperatures at the entrance to the second pass, reducing tube end stress. All tube
ends are rolled and flared.
Standard Trim and Controls:
Steam: 157 pump control/low water cut-off with alarm con-
tacts—piped with quick opening blowoff valve. Gauge glass
set with hand-operated gauge and try cocks. Steam pressure
gauge—4 ½-inch dial. L404A operating pressuretrol, L404C
manual reset high limit pressuretrol and appropriate firing rate
control when required. Manual reset probe auxiliary
low water cut-off.
ASME side outlet safety valve(s).
Easy-opening insulated front and rear flue doors with light
weight non-refractory closure provide full access to all tubes.
No elaborate seals are used. The C Series oversized furnace
easily accommodates any burner.
Washouts are provided for easy inspection and cleaning of
waterside surfaces.
All steam boilers are provided with a dry pan to ensure dry
steam. A feedwater diffuser is provided on steam boilers. All
water boilers are equipped with a dip tube at supply outlet and
diffuser at return inlet.
The round vertical smoke outlet has room for an optional
quadrant damper. All boilers are provided with lifting holes and
47
Water: 63M manual reset low water cut-off—piped with quick
opening blowoff valve. Combination pressure/temperature
gauge—3 ½ inch dial. L4006A operating aquastat and L4006E
manual reset high limit aquastat and appropriate firing rate
control when required. ASME side outlet relief valve(s).
C-Series Ratings & Dimensions
C Series Ratings
BHP
A
B
C
Gross
Output
MBH
Gross
Output
Lbs/Hr
Net Rating
Water
MBH
Net Rating
Steam
MBH
Sq Ft Net
Steam
Firing Rate
MBH - Gas
Firing Rate
GPH #2 Oil
20
30
66-3/8
75-5/8
670
690
582
520
2,166
816
5.7
30
30
66-3/8
82-5/8
1,004
1,035
873
780
3,249
1,225
8.5
40
34-1/2
73-7/8
90-1/8
1,339
1,380
1,164
1,040
4,332
1,633
11.4
50
34-1/2
75-3/8
100-5/8
1,674
1,725
1,455
1,299
5,415
2,041
14.2
60
34-1/2
75-3/8
113-1/8
2,009
2,070
1,747
1,559
6,497
2,449
17.1
70
34-1/2
78-1/2
114-5/8
2,009
2,415
2,038
1,819
7,580
2,858
19.9
80
34-1/2
78-1/2
125-1/8
2,678
2,760
2,329
2,079
8,663
3,266
22.8
90
34-1/2
78-1/2
135-1/8
3,013
3,105
2,620
2,339
9,746
3,674
25.6
100
34-1/2
78-1/2
145-1/8
3,348
3,450
2,911
2,599
10,829
4,082
28.5
C
A
OVER SKID
OVERALL
WIDTH
PLAN VIEW
B
MAX.
HEIGHT
FRONT VIEW
SIDE VIEW
©2005 Burnham Commercial
Lancaster, PA 17603
Phone: 888-791-3790
www.burnhamcommercial.com
48
Component Summary Information
A boiler is not only a significant plant expenditure, but it is the most important element of any mechanical heating/process
system. The continued reliability of the boiler is heavily dependent upon the quality and chemistry of the water within
the system. Burnham Commercial features a complete line of boiler room accessory products designed to match the
performance needs of your Burnham Commercial boiler. Proper use and installation of this equipment can significantly
improve system efficiency and boiler longevity.
Burnham Deaerator Systems are designed to protect your Burnham boiler and steam
system from the corrosion caused by the presence of non-condensable gases. A solution of
oxygen in water is very corrosive to metals widely used in stem systems. Use of deaerator
systems pay for themselves in fewer downtime hours, less chemical additives and reduced
maintenance to the entire steam system.
Burnham Water Softener Systems are designed to produce conditioned water to reduce the minerals which produce detrimental scale formation on the heat transfer surfaces in the boiler. Use of a
water softener reduces the need for other chemical scale control additives.
Burnham Chemical Feed Systems enable treatment of boiler feedwater with chemicals
that protect against boiler scaling and corrosion. Amount and type of chemical treatment
will vary depending upon the individual application.
Burnham Boiler Feedwater Systems are designed to efficiently store and return hot
condensate in combination with make-up water to automatically meet boiler water demands.
Use of boiler feedwater systems can account for significant fuel savings and lower total
chemical treatment costs.
Burnham Condensate Return Systems are complete systems designed to increase
the energy/water saving circuit for steam heating or process systems and minimize
difficulties from boiler encrustation by recycling previously-treated system water.
Burnham Blow Down Systems are designed to eliminate mineral build-up from
dissolved solids that would cause scale and boiler corrosion. They are available in
two basic types: Bottom Blow Down designed for forceful removal of bottom residue
and Surface Blow Down/Heat Recovery which is an ongoing process that removes
dissolved solids from the top level of water in the boiler while providing a heat recovery
function as well.
49
Typical Steam System Layout
Condensate Return
System
Water Softener
System
Boiler Feedwater
System
Boiler
Surge System
Surface Blow
Down/Heat
Recovery
System
Chemical
Feed System
Deaerator System
Bottom Blow
Down
50
Boiler Accessories
51
Chemical Feed System
Continuous Run & On-Off Boiler
Feedwater Pump Applications
• Equipment to dose chemicals to treat boiler feedwater.
• Introduces chemicals to the boiler or boiler feedwater piping.
• Vertical 50 gallon polyethylene tank on stand with
lid (other size tanks and tank materials available).
• 5/8” piston pump, adjustable from 0 to 6.2 gallons
per hour (GPH) (other size and capacity of piston and diaphragm pumps available).
• Piston pump to 1000 psig (various stainless steel heads available as an option).
• Modular configuration to meet customer
requirements includes: tank with lid on stand, piston pump, factor suction piping and agitator
Continuous Run only: control panel and make-up water meter.
• Can be custom configured to meet customer • Agitator: angle or clamp mounted, 1/4 HP TENV, requirements.
115/1/60 volt motor standard (50 hertz and many other motor options available).
• More than one pump may be mounted under a • Pump control via make-up water meter signal to 50 gallon tank.
• 1/4 HP, totally enclosed non-ventilated (TENV), 115/1/60 volt motor standard (50 hertz and many other motor options available).
• Factory suction piping includes: strainer and safety relief valve.
panel-mounted timer.
• Continuous Run - NEMA 12 control panel
includes: mixer and pump switches, motor relays, fuses, terminal strip and timer.
• On-Off - Control panel and water meter available as options.
52
Chemical Feed System
(Continuous Run & On-off Boiler Feedwater Pump Applications)
Specifications
Dimensions
Capacity in Gallons
Wall
A
B
C
D
Part Number
Tank and Lid only
30
1/8”
18
30
12
49
103
030
55
1/8”
22
34
17
60
305
050
100
1/4”
28
42
18
70
310
0100
150
1/4”
31
47
18
75
315
0150
200
1/4”
36
48
20
77
320
0200
275
1/4”
42
48
20
77
327
0275
360
1/4”
48
48
20
77
336
0360
500
5/16”
54
60
20
89
350
0500
© 2006 Burnham Commercial - Lancaster, PA
Phone: 1-888-791-3790
www.burnhamcommercial.com
53
Bypass and Shot Feed Systems
For applications requiring bulk feeding of chemicals to a pressure system
Bypass Chemical Feeders
• Bypass chemical feeders include: tank, gauge glass, control and sample valves and funnel.
Shot Feeders
funnel.
• Used in applications where a continuous supply of chemical is needed in a closed loop or low
makeup system.
• Flow adjustments of chemicals are made manually with the flow regulator.
• Shot feeders include: tank, sample valve and • Used to add a slug of chemicals into a low makeup or closed loop systems.
• Shot feeders are constructed of steel and have a rated working pressure of 125 psig.
54
Bypass and Shot Feed Systems
Bypass Feeder
Item
Description
Qty.
1
Tank
1
2
Funnel
1
3
Petcocks
2
4
1” Pipe Nipple
2
5
1” Valve
2
6
Gauge Valve
2
7
Sight Glass
1
8
Glass Guards
9
1” x 3/8” Reducer Bushing
Dimensions in Inches
Tank Size
(gallons)
A
(Dia.)
B
(Lht.)
2
1
6
10
1
1-1/2
6
12
10
3’8” Pipe Nipple
3
2
8
10
11
3’8” Union
1
2-1/2
8
12
12
Flow Control Valve
1
5
10
15
13
3/8” valve
1
10
10
29
14
32
18
28
14
1/2” Coupling
3
18
15
1” Coupling
2
25
NOTE: 5 gallon and larger feeders have 12" legs. All dimensions are approximate
3/4 Gallon
Item
Description
Qty.
1
Tank
1
2
Funnel
1
3
1/2” Pipe Nipple
4
4
1” x 1/2” Reducer Bushing
1
5
Petcocks
2
6
1/2” Valve
2
7
1/2” Tee
1
8
1/2” Coupling
4
1 - 25 Gallon
Dimensions in Inches
Item
Tank Size
(gallons)
A
(Dia.)
B
(Lht.)
1
6
10
1-1/2
6
12
2
8
10
2-1/2
8
12
5
10
15
10
10
29
18
14
32
25
18
28
NOTE:
1. All dimensions are approximate
2. All dimensions are in inches
55
Description
Qty.
1
Tank
1
2
Funnel
1
3
1” Pipe Nipple
3
4
Petcocks
2
5
1” Valve
2
6
1/2” Coupling
3
7
1” Coupling
2
© 2006 Burnham Commercial - Lancaster, PA
Phone: 1-888-791-3790
www.burnhamcommercial.com
Boiler Feedwater Systems
Boiler Feedwater System Features
• Complete system including: vessel, pump(s), stand, trim, and control panel
BHFS
• Acts as a reservoir for condensate return,
make-up water, and boiler feedwater
• Horizontal, stand-mounted, atmospheric configuration. Vessel unbolts from stand for ease of replacement and installations
• Dished head, factory pressure tested, non-code stamped vessel–standard. ASME, Section VIII Code stamped vessels, corrosion resistant
vessels available
• Model range: 43 gallon through 1,285 gallon
BHTS
• Water storage to full overflow: 15 minutes
• Factory piped pump re-circulation
• Oversize pump suction lines
• Additional opening for future applications
• Auxiliary relief vent(s)
• Can be custom configured to meet
customer requirements
• Factory insulation and jacketing available
• Option to pre-heat boiler feedwater
56
Condensate Return System
Condensate Return System Features
• Many motor and voltage options available.
• Many trim, electrical and control panel options available.
• Modular configuration to meet customer requirements includes: tank, pump(s), float control/alternator, control panel and trim options.
• Pump options:
- 1750 RPM - 1/4 HP/1.5 GPM at 1
0 psig through 3 HP/75 GPM at 20 psig
- 345
0 RPM - 1/3 HP/1.5 GPM at 1
0 psig through 10 HP/150 GPM at 60 psig
• Inexpensive/efficient mechanism for the capture and return of condensed steam. Units may be converted to act as a small boiler feedwater units.
• “NO OPTION/QUICK SHIP” units available (15 to 21 gallon cast iron tank, 10 and 16 gallon steel tank, simplex or duplex, single phase with float switch, NO ALTERNATOR; 6 gallon cast iron
• Available in either rectangular steel tank (16-20 gallon) or rectangular cast iron tank (15-110 gallon).
57
Blowdown Heat Recovery System
Flash Economizer
• Reduces dissolved solids from the top level of water in the boiler.
• Recovers heat from surface blowdown to heat boiler feed or make-up water.
• ASME Section VIII code-stamped flash
separator and coil.
• Separator is sized to accommodate a given percent surface blowdown/flow rate from boiler operating pressure to a given vent psig.
• Coil is sized to accommodate make-up flow rate at between 8 and 18 psig pressure drop.
• Model Range: HR-39 (3 GPM blowdown/9 GPM make-up) through HR-30150 (30 GPM blowdown/150 GPM make-up).
• Complete system configured to include:
flash separator mounted above and flanged to a stainless steel or copper coil on stainless steel stand with trap, ball valve, gauge glass, safety valve, 3 thermometers and factory piping.
• Stainless steel striking plate standard.
• Openings to facilitate cleaning and
inspection standard.
• Options include multiple boiler manifold and mounting of conductivity controller.
• Flash separator flanged to coil section for ease or
removal for cleaning.
58
Blowdown Heat Recovery System
(Flash Economizer)
Specifications
Model
Blowdown
Capacity
GPM
Make-up
Capacity
GPM
Pressure
Drop*
A
B
C
D
E
F
G
H
HR-39
3
9
9 psi
97
50
36
10
1
2-1/2
1
1
HR-315
3
15
9 psi
96
44
44-1/4
8
1
2-1/2
1
3/4
HR-612
6
12
8 psi
111
53
46
12
1-1/2
3
1
1-1/4
HR-630
6
30
10 psi
110
49
50
10
1-1/2
3
1
3/4
HR-1020
10
20
13 psi
106
50
44
16
1-1/2
4
2
1-1/2
HR-1050
10
50
10 psi
100
44
42
16
1-1/2
4
2
1-1/4
HR-2040
20
40
18 psi
140
67
62
18
1-1/2
6
2
2
HR-20100
20
100
10 psi
140
67
62
18
1-1/2
6
2
1-1/2
HR-3060
30
60
15 psi
172
76
85
18
1-1/2
6-8
2
1-1/2
HR-30150
30
150
18 psi
132-1/2
67
53-1/4
24
1-1/2
6-8
2
2-1/2
* Across water coil at maximum flow
Constructed in accordance with ASME Code, Secion VIII, Division 1, for MAWP of 150 PSIG.
Hydrostatic tested at 225 PSIG. Safety Relief Valve set at 150 PSIG.
© 2006 Burnham Commercial - Lancaster, PA
Phone: 1-888-791-3790
www.burnhamcommercial.com
59
Bottom Blowdown Tank
• Eliminate precipitated solids from the bottom of the boiler.
• Cools blowdown to 140°F or below before dumping to drain by storing one entire blowdown in a reservoir and using it to cool the next blowdown.
• ASME Section VIII code-stamped tank.
• Sized either to accommodate one complete boiler blowdown or to satisfy New Jersey regulations.
• Model Range:
18” diameter x 24” height through
72” diameter x 92” height
• Modular configuration to meet customer requirements includes: tank, legs, gauge glass and pressure gauge.
• Can be custom configured to meet customer requirements.
• Stainless steel striking plate standard.
• Openings to facilitate cleaning and inspection standard.
• Safety valve and thermometer may be included as options.
60
• General - All Blowdown Tanks, whether of the closed or vented type should be of the following dimensions in relation to the boiler rating, and must have approved
openings for cleaning and inspections:
Boiler
Blow-off
Pressure Line Pipe Vent Pipe
Outlet
Diameter
PSIG
Size
Size
Pipe Size of Tank
New Jersey Regulations for Blowdown Tanks
100
3/4”
1”
1-1/4”
1-1/2”
2”
2-1/2”
2-1/2”
3”
3-1/2”
4”
5”
6”
3”
3”
4”
5”
6”
6”
20”
24”
30”
42”
48”
54”
3’6”
4’0”
4’2”
4’0”
4’6”
6’0”
150
3/4”
1”
1-1/4”
1-1/2”
2”
2-1/2”
3”
3-1/2”
4”
5”
6”
8”
3
3-1/2”
4”
5”
6”
8”
20”
24”
36”
42”
54”
60”
3’6”
5’0”
5’0”
5’0”
5’6”
6’0”
200
3/4”
1”
1-1/4”
1-1/2”
2”
2-1/2”
3”
4”
5”
6”
8”
8”
3”
4”
5”
6”
8”
8”
20”
30”
36”
42”
48”
60”
4’3”
4’6”
5’0”
6’0”
7’3”
7’0”
250
3/4”
1”
1-1/4”
1-1/2”
2”
2-1/2”
3-1/2”
4”
5”
6”
8”
10”
3”
4”
5”
6”
8”
10”
24”
30”
42”
48”
54”
60”
4’0”
4’6”
4’6”
5’0”
7’0”
7’2”
300
3/4”
1”
1-1/4”
1-1/2”
2”
2-1/2”
3-1/2”
5”
6”
8”
8”
10”
3-1/2”
5”
6”
8”
8”
10”
24”
30”
42”
48”
60”
66”
4’6”
5’6”
5’0”
5’6”
6’3”
7’8”
350
3/4”
1”
1-1/4”
1-1/2”
2”
2-1/2”
4”
5”
6”
8”
10”
10”
4”
5”
6”
8”
8”
10”
24”
30”
42”
48”
60”
72”
5’0”
5’6”
5’6”
6’2”
6’10”
7’0”
400
3/4”
1”
1-1/4”
1-1/2”
2”
2-1/2”
4”
5”
6”
8”
10”
10”
4”
5”
6”
8”
8”
10”
24”
30”
42”
48”
66”
72”
5’6”
6’0”
6’0”
6’4”
6’0”
8’0”
• Closed or Pressure Type - A Blowdown Tank subjected to the maximum steam boiler pressure must be
constructed for such pressure and stamped with either New Jersey, National Board or ASME Standard.
• When the blowdown from any steam boiler is disposed in a sewer or other interconnected system, a Blowdown Tank must be placed between the boiler and the sewer or system.
• The minimum metal thickness of Blowdown Tanks, whether pressure or atmospheric, must not be less than 5/16”.
• Atmospheric or Vented Type - The outlet from the Blowdown Tank shall be twice the area of the boiler blowdown pipe and made to extend internally within 6” from the bottom of the tank.
• A vent pipe, at least twice the diameter to the inlet, shall lead to the outside atmosphere. • Vents shall be as direct as possible to the outside of the
atmosphere and discharge at a point not less than seven feet above the adjacent walkway or areas without a valve or other possible obstruction such as a water pocket.
© 2006 Burnham Commercial - Lancaster, PA
Phone: 1-888-791-3790
www.burnhamcommercial.com
61
Height
of Tank
Boiler Rating
HP
Cu. Ft.
Minimum Size Tank
Gallons
2 - 20
3.5
18” diameter x 24”
26.4
21 - 50
7.7
24” diameter x 30”
59
51 - 100
14.7
30” diameter x 36”
110
101 - 200
21.6
36” diameter x 36”
160
201 - 400
24.8
36” diameter x 42”
185
401 - 800
39.5
42” diameter x 48”
288
801 - 1000
63.0
48” diameter x 60”
470
Flash Separator
• Reduces steam pressure or vents process steam directly to atmosphere.
• Eliminates moisture from process steam (cyclonic spinning mechanism permits the use of smaller tanks to completely separate flash steam from condensate).
• ASME Section VIII “UE” stamped separator standard up to model BFS-16-56.
• ASME Section VIII “U” stamped separator standard for models BFS-16-56 and above.
• Sized to accommodate a given #/hour flow rate of steam from a given source psig to a given vent psig.
• Model Range:
6” diameter x 34” high through 36” diameter x 108” high.
• Modular configuration to meet customer requirements includes a flash separator and the following options: trap, check valve, ball valve, safety relief valve and gauge glass.
• Can be custom configured to meet customer requirements.
• Stainless steel striking plate standard.
62
Pressure From...
Pressure To...
700
600
500
400
300
200
100
50
30
15
7
0.0
800
2.5
5.2
7.9
10.8
14.1
18.0
23.1
26.9
29.0
31.1
32.6
34.3
700
600
500
400
300
200
100
75
50
25
2.7
5.5
8.5
11.9
15.8
21.0
24.9
27.0
29.2
30.7
32.4
2.9
6.0
9.4
13.5
18.8
22.7
24.9
27.1
28.6
30.4
3.2
6.7
10.9
16.3
20.4
22.6
24.8
26.4
28.2
3.7
7.9
13.5
17.6
19.9
22.2
23.8
25.6
4.4
10.2
14.4
16.7
19.0
20.7
22.5
6.0
10.4
12.8
15.2
16.9
18.7
4.6
7.1
9.6
11.3
13.3
2.5
5.1
7.6
9.4
11.9
2.6
5.2
7.0
9.0
1.8
3.7
5.8
Follow the “Pressure From...” down vertically on the
chart at left to the “Pressure To...”.
Example:
75 PSIG condensate flashed to low pressure heating system at 15 PSIG gives 7.6% condensate flashed into system.
After determining the percent of flash from the chart above, determine the size of Flash Separator from the chart below.
Example: Referring back to the chart above, you have a 7.6% flash, If you have 30,000 #/hour condensate at 75PSIG, 2,280 #/hour steam (30,000 x .076). Locate 30,000
in the left column below, go across to 2,280 #/hour flash steam column (3,000). You would use a 56” high x 18” diameter Flash Separator with a 3” draft and 5” vent.
#/Hour
Condensate
100,000
90,000
80,000
70,000
60,000
50,000
40,000
30,000
20,000
10,000
5,000
3,000
2,000
1,000
500
Height
Diameter
Drain
Vent
Height
Diameter
Drain
Vent
Height
Diameter
Drain
Vent
Height
Diameter
Drain
Vent
Height
Diameter
Drain
Vent
Height
Diameter
Drain
Vent
Height
Diameter
Drain
Vent
Height
Diameter
Drain
Vent
Height
Diameter
Drain
Vent
Height
Diameter
Drain
Vent
Height
Diameter
Drain
Vent
Height
Diameter
Drain
Vent
Height
Diameter
Drain
Vent
Height
Diameter
Drain
Vent
Height
Diameter
Drain
Vent
100
108
30
5
2
96
30
5
2
96
24
5
2
72
24
4
2
56
24
4
2
72
20
4
2
56
20
4
2
56
18
3
2
56
14
2-1/2
2
34
14
2
2
34
10
1-1/2
2
34
10
1-1/4
2
34
8
1-1/4
2
34
6
1
2
34
6
1
2
500
108
30
5
2
96
30
5
2
96
24
5
2
72
24
4
2
56
24
4
2
72
20
4
2
56
20
4
2
56
18
3
2
56
14
2-1/2
2
34
14
2
2
34
10
1-1/2
2
34
10
1-1/4
2
34
8
1-1/4
2
34
8
1
2
34
6
1
2
700
108
30
5
2-1/2
96
30
5
2-1/2
96
24
5
2-1/2
72
24
4
2-1/2
56
24
4
2-1/2
72
20
4
2-1/2
56
20
4
2-1/2
56
18
3
2-1/2
56
14
2-1/2
2-1/2
34
14
2
2-1/2
34
10
1-1/2
2-1/2
34
10
1-1/4
2-1/2
34
8
1
2-1/2
34
8
1
2-1/2
1,000
108
30
5
3
96
30
5
3
96
24
5
3
72
24
4
3
56
24
4
3
72
20
4
3
56
20
4
3
56
18
3
3
56
16
2-1/2
3
34
14
2
3
34
10
1-1/2
3
34
10
1-1/4
3
34
10
1
3
2,000
108
30
54
4
96
30
5
4
96
24
5
4
72
24
4
4
56
24
4
4
72
20
4
4
56
20
4
4
56
18
3
4
56
16
2-1/2
4
34
14
2
4
34
14
1-1/2
4
34
14
1-1/4
4
3,000
108
30
5
5
96
30
5
5
96
24
5
5
72
24
4
5
56
24
4
5
72
20
4
5
56
20
4
5
56
18
3
5
56
16
2-1/2
5
34
14
2
5
34
14
1-1/2
5
#/Hour Flash Steam
4,000
8,000
108
108
30
30
5
5
6
8
96
96
30
30
5
5
6
8
96
96
24
24
5
5
6
8
72
72
24
24
4
4
6
8
56
56
24
24
4
4
6
8
72
72
20
20
4
4
6
8
56
56
20
20
4
4
6
8
56
56
18
18
3
3
6
8
56
56
16
16
2-1/2
2-1/2
6
8
34
34
14
16
2
1-1/2
6
8
34
14
1-1/4
6
12,000
108
30
50
10
96
30
5
10
96
24
4
10
72
24
4
10
56
24
4
10
72
20
4
10
56
20
3
10
56
20
3
10
56
20
2
10
18,000
108
30
5
12
96
30
5
12
96
24
4
12
72
24
4
12
56
24
4
12
72
24
4
12
56
24
3
12
56
24
2-1/2
12
21,000
108
30
5
14
96
30
4
14
96
30
4
14
72
30
4
14
56
30
4
14
72
30
3
14
56
30
3
14
25,000
108
36
5
16
96
36
4
16
96
36
4
16
72
36
4
16
56
36
4
16
72
36
3
16
35,000
108
36
4
18
96
36
4
18
96
36
4
18
72
36
4
18
*Flash Separators over 18” diameter,
cleanout will be 2” NPT coupling.
Dimension Chart Model BFS
Inlet - Specify inlet to match your return line or blowoff line
I
34
56
72
96 108
H
6
8
10
14
16
18 20 24 30 36
Dia.
1
1-1/4 1-1/2 2 2-1/2 3
4
5
D
2
2-1/2
3
4
5
6
8
10 12 14
V
PL 5/16 3/8
© 2006 Burnham Commercial - Lancaster, PA
Phone: 1-888-791-3790
www.burnhamcommercial.com
63
16
18
Bottom Blowdown Separator
• Eliminate precipitated solids from the bottom of the boiler.
• Cools blowdown to 140°F or below before dumping to drain by introducing cooling water via an aftercooler.
• ASME Section VIII “UE” stamped separator.
(“U” stamp available as option)
• Sized to accommodate flow based on boiler blowdown line size and boiler operating pressure.
• Model Range:
14” diameter x 22” through 56” in height for standard boilers
(10” diameter x 14” high option available for boilers under 1000 #/hour)
• Modular configuration to meet customer requirements includes: separator, legs (or wall bracket), aftercooler, temperature regulating valve and thermometer
• Can be custom configured to meet customer requirements.
• Stainless steel striking plate standard and • Multiple separators with manifold for high internal steel restrictor plates standard.
pressure applications available.
64
Chart A — Boiler Blowdown Separators
Blowdown Valve
Size Separator
H
Dimensions
Boiler Operating Pressure
0 - 15
14
16 - 50
20
51 - 100
20
101 - 125
34
126 - 150
34
151 - 175
34
176 - 200
34
201 - 225
34
**226 - 300
56
I
* 1”
D
1
1
1
1
1
1
1
1
1
2
2
3
3
3
3
3
4
4
1¼”
1½”
2”
2½”
3”
V
H
I
D
V
H
I
D
V
H
I
D
V
H
I
D
V
H
I
D
V
2½
2½
2½
3
3
4
4
4
4
20
20
34
34
34
34
34
56
56
1¼
1¼
1¼
1¼
1¼
1¼
1¼
1¼
1¼
3
3
4
4
4
4
4
4
4
4
4
4
4
4
4
5
5
5
20
34
34
34
34
34
56
56
56
1½
1½
1½
1½
1½
1½
1½
1½
1½
3
3
4
4
4
4
5
5
5
4
4
4
4
5
5
5
5
6
20
34
34
34
56
56
56
56
56
2
2
2
2
2
2
2
2
2
4
4
5
5
5
5
6
6
6
5
5
5
5
6
6
6
6
6
34
34
34
56
56
56
56
56
56
2½
2½
2½
2½
2½
2½
2½
2½
2½
5
5
6
6
6
6
6
8
8
6
6
6
6
6
8
8
8
8
34
34
34
—
—
—
—
—
—
3
3
3
—
—
—
—
—
—
6
6
8
—
—
—
—
—
—
5
5
6
—
—
—
—
—
—
*Minature Boilers: ½” - 1” Blowdown Valve up to 1000 #/hr. Blowdown use 14” high, 1” Inlet, 2” Drain, 2½” Vent.
** 251 - 300 PSIG required.
U Symbol Construction and Stamping. See price sheet for adder.
Chart B — Cooling Water Line and Valve Size
Separator
Inlet Size
Cooling Water Pressure (PSI)
Boiler Operating Pressure
0 - 50
51 - 100
101 - 125
Use for 50 - 70°F
126 - 175
Cooling Water
Temperature
176 - 225
226 - 250
251 - 300
0 - 50
51 - 100
101 - 125
Use for 71 - 80°F
126 - 175
Cooling Water
Temperature
176 - 225
226 - 250
251 - 300
40#
1”
60#
80#
40#
1¼”
60#
80#
40#
1½”
60#
80#
40#
2”
60#
80#
40#
2½”
60#
80#
40#
3”
60#
80#
½
1
1
1
1
1¼
1¼
¾
1
1
1
1
1¼
1¼
½
¾
¾
1
1
1¼
1¼
½
¾
1
1
1
1¼
1¼
½
¾
¾
1
1
1
1
½
¾
¾
1
1
1
1¼
1
1
1¼
1¼
1¼
1¼
1¼
1
1¼
1¼
1¼
1¼
1¼
1½
1
1
1
1¼
1¼
1¼
1¼
1
1
1¼
1¼
1¼
1¼
1¼
¾
1
1
1
1¼
1¼
1¼
1
1
1
1¼
1¼
1¼
1
1¼
1¼
1¼
1¼
1½
1½
1½
1
1¼
1¼
1¼
1¼
1¼
1½
1
1¼
1¼
1¼
1¼
1¼
1¼
1
1¼
1¼
1¼
1¼
1¼
1½
1
1
1¼
1¼
1¼
1¼
1¼
1
1¼
1¼
1¼
1¼
1¼
1½
1¼
1½
2
2
2
2
2
1¼
2
2
2
2
2½
2½
1¼
1¼
1½
2
2
2
2
1¼
1½
2
2
2
2
2
1¼
1¼
1¼
1½
2
2
2
1¼
1¼
1½
2
2
2
2
1½
2
2
2½
2½
2½
2½
2
2
2½
2½
2½
2½
2½
1½
2
2
2
2
2
2½
1½
2
2
2
2½
2½
2½
1¼
2
2
2
2
2
2
1½
2
2
2
2
2
2½
2
2½
2½
2½
3
3
3
2½
2½
2½
3
4
4
4
2
2½
2½
2½
2½
2½
3
2
2½
2½
2½
3
3
3
2
2
2½
2½
2½
2½
2½
2
2
2½
2½
2½
2½
2½
© 2006 Burnham Commercial - Lancaster, PA
Phone: 1-888-791-3790
www.burnhamcommercial.com
65
Conductivity Controller
Surface Blowdown Solid
State Intermittent Sampling
• Controls boiler total dissolved solids (TDS) using conductivity measurement and automatic surface blowdown via intermittent sampling.
• Adjustable interval timer (1/4 - 3 hours) periodically opens an electric valve to sample boiler water conductivity.
• If the sample is below the micromhos set point • Adjustable sample duration timer (12 - 10 • Complete system includes: enclosure, on the potentiometer, blowdown is not required and the valve will close. If the sample is above the micromhos set point on the potentiometer, blowdown is required, and the valve will remain open.
minutes) again samples to determine if sample is below the micromhos set point on the potentiometer to permit the valve to close.
potentiometer, two timers and LED lights.
• 120 VAC, 50/60 HZ, 15 amp
• Solid state electronics
• Valve assemblies purchased separately include: solenoid or motor-operated factory-piped valve with probe, tee assembly and orifice kit.
• NEMA 4X enclosure 66
Conductivity Controller
(Surface blowdown solid state intermittent sampling)
Conductivity Range
0 - 7,000 Microsiemens/cm.
Sample Timers
Interval: 15 Minutes to 3 Hours / Duration: 30 Seconds to 10 Minutes
Display
LED Indicators: Power, Blowdown and Conductivity Calibration
Accuracy
+/-400 Microsiemens
Drift
Less than 0.25% Per Month
Input Power
115 VAC, 50/60 HZ, 10 Amps
Output/Control
115 VAC, 50/60 HZ, 10 Amps. Maximum Combined Load / Pre-wired for 2 or 4 Wire Blowdown Valve
Environment
Ambient Temperature: 40°F to 140°F (4°C to 60°C) Humidity: 1-100% R.H. Non-condensing
Enclosure
Nema 4X Weatherproof. See through Door with Padlockable Hasp. (3) 7/8” Diameter Holes Provided for 1/2” Conduit Connections: Blowdown Valve, AC Power, Probe and Optional Electrical Device.
Dimensions
H. 10” x W. 8” x D. 4” (25 x 20 x 10 cm)
Net Weight
5.89 Lbs. (2.67 Kgs.) / 7.43 Lbs (3.48 Kgs.) - With Flow through Plumbing Assembly
Note: Specifications subject to change without prior notice.
© 2006 Burnham Commercial - Lancaster, PA
Phone: 1-888-791-3790
www.burnhamcommercial.com
67
Water Softener Systems
BS & BP
Steel Tanks Electronic Demand Controller Features
• Exchanges "soft" sodium ions for "hard" calcium
and magnesium ions.
• BS - Model range:
30-3/4 through BS-1200-3, twin or single (30,000 grain at 8 GPM through 1,200,000 grain at 280 GPM).
• BP - Model range: 30-3/4 through BP-600-3, twin or single (30,000 grain at 8 GPM through 600,000 grain at 240 GPM). • Available in alternating "twin" configuration with flow meter and VIP computer demand controller or "single" configuration with time clock regeneration. Alternating twin system may be run in parallel twin mode.
• Modular configuration to meet customer requirements for alternating system includes: resin tanks, resin, gravel, brine tank, control valve, blocking valves, flow meter and VIP computer demand controller.
• VIP computer demand controller standard.
• BS - Resin tanks:
Steel "polybond" lined and primed, pressure-
tested to 100 psig, non-code stamped (code stamped resin tanks available).
• BP - Resin tanks: fiberglass reinforced polyester, pressure-tested, non-code stamped (code stamped resin tanks NOT available).
• Provided with industry standard 30,000 grain per cubic foot resin.
• Fleck control valve standard.
• BS - Skid mounting (pre-piped/pre-wired) available as option.
• BP - Skid mounting NOT available.
68
Twin
Drawing
Number
Single
Drawing
Number
900225-1
900225-3
Cap. Max
Grains (1,000) Cu. Ft. Continuous
per GPM
PSI
Max.
Min.
Tank Flow Drop
Peak
PSI
Drop
Drain
Flow
Max
12
7
24
20
15
29
9
36
32
12
5
40
120
6
210
140
BS-240-1.5
240
272B
BS-270-1.5
900253-8
302B
900227-1
900254-1
900227-2
Tank Dimensions
Regeneration
Resin
Brine
Salt
Cap.
Lbs.
2
10 x 52
18 x 38
400
15
6
3
12 x 52
18 x 38
400
30
12
25
5
14 x 66
18 x 38
400
45
18
16
5
14 x 66
18 x 38
400
45
18
48
22
7
18 x 66
21 x 43
450
60
24
13
58
25
7
18 x 66
21 x 43
450
75
30
42
15
59
25
10
18 x 66
27 x 51
1000
90
36
7
45
15
60
25
10
24 x 66
27 x 51
1000
105
42
160
8
45
15
60
25
10
24 x 66
27 x 51
1000
120
48
270
180
9
45
15
60
25
10
24 x 66
27 x 51
1000
135
54
BS-300-1.5
300
200
10
45
15
60
25
15
24 x 66
27 x 51
1000
150
60
122C
BS-120-2
120
80
4
32
7
48
12
15
18 x 66
27 x 51
450
60
24
900254-2
152C
BS-150-2
150
100
5
40
6
60
11
15
18 x 66
27 x 51
450
75
30
900227-3
900254-3
182C
BS-180-2
180
120
6
48
9
72
15
15
18 x 66
27 x 51
1000
90
36
900227-4
900254-4
212C
BS-210-2
210
140
7
58
8
84
15
15
24 x 66
27 x 51
1000
105
42
900227-5
900254-5
242C
BS-240-2
240
160
8
64
11
96
20
15
24 x 66
27 x 51
1000
120
48
900227-6
900254-6
272C
BS-270-2
270
180
9
72
13
108
25
15
24 x 66
27 x 51
1000
135
54
900227-7
900254-7
302C
BS-300-2
300
200
10
78
15
108
25
15
24 x 66
27 x 51
1000
150
60
900227-8
900254-8
452C
BS-450-2
450
300
15
87
15
118
25
20
30 x 66
32 x 51
1500
225
90
900227-9
900254-9
602C
BS-600-2
600
400
20
94
15
125
25
25
36 x 71
42 x 51
2500
300
120
900228-1
900255-1
602E
BS-600-3
600
400
20
160
15
240
25
30
36 x 71
42 x 51
2500
300
120
900228-2
900255-2
902E
BS-900-3
900
600
30
200
15
270
25
40
42 x 71
42 x 51
2500
450
180
900228-3
900225-3
1202E
BS-1200-3
1200
800
40
210
15
280
25
50
48 x 71
52 x 60
4500
600
240
Model
Type
Model
Number
900252-1
32Z
BS-30-.75
30
20
1
8
4
900252-3
62A
BS-60-1
60
40
2
17
15
900225-4
900252-4
92A
BS-90-1
90
60
3
21
900226-1
900253-1
92B
BS-90-1.5
90
60
3
24
900226-2
900253-2
122B
BS-120-1.5
120
80
4
900226-3
900253-3
152B
BS-150-1.5
150
100
900226-4
900253-4
182B
BS-180-1.5
180
900226-5
900253-5
212B
BS-210-1.5
900226-6
900253-6
242B
900226-7
900253-7
900226-8
GPM
Flow
Max.
Lbs.
Min.
Lbs.
NOTE: Some flow rates are shown at a rate less than the standard 15 PSI drop for continuous and 25 PSI drop for decreased softening capacity as these flows are exceeded.
Cap. Max
Grains (1,000)
Continuous
Cu. Ft.
per
GPM PSI
Tank Flow Drop
Twin
Drawing
Number
Single
Drawing
Number
Model
Type
Model
Number
Max.
Min.
900245-1
900232-1
31Z
BP-30-.75
30
20
1
8
900245-3
900232-3
61A
BP-60-1
60
40
2
900245-4
900232-4
91A
BP-90-1
90
60
3
900246-1
900233-1
91B
BP-90-1.5
90
60
3
900246-2
900233-2
121B
BP-120-1.5
120
80
4
900246-3
900233-3
151B
BP-150-1.5
150
100
900246-4
900233-4
181B
BP-180-1.5
180
900246-5
900233-5
211B
BP-210-1.5
210
900246-6
900233-6
241B
BP-240-1.5
900246-7
900233-7
271B
BP-270-1.5
900246-8
900233-8
301B
900247-1
900234-1
900247-2
900234-2
900247-3
900247-4
Peak
GPM
Flow
PSI
Drop
Drain
Flow
Max
4
12
7
16
10
24
21
15
29
24
9
32
11
5
36
120
6
140
7
240
160
270
180
BP-300-1.5
300
121C
BP-120-2
151C
BP-150-2
900234-3
181C
900234-4
211C
900247-5
900234-5
900247-6
900247-7
Tank Dimensions
Resin
Brine
Salt
Cap.
Lbs.
2
9 x 48
18 x 38
20
3
12 x 52
25
5
14 x 65
36
16
5
48
20
7
15
52
25
38
15
56
45
15
60
8
45
15
9
45
15
200
10
45
120
80
4
150
100
5
BP-180-2
180
120
BP-210-2
210
140
241C
BP-240-2
240
160
900234-6
271C
BP-270-2
270
900234-7
301C
BP-300-2
300
900247-8
900234-8
451C
BP-450-2
900247-9
900234-9
601C
BP-600-2
900248-1
900235-1
601E
BP-600-3
Regeneration
Max.
Lbs.
Min.
Lbs.
400
15
6
18 x 38
400
30
12
18 x 38
400
45
18
14 x 65
18 x 38
400
45
18
17 x 58
21 x 43
450
60
24
7
17 x 72
21 x 43
450
75
30
25
7
17 x 72
27 x 51
1000
90
36
25
15
24 x 71
27 x 51
1000
105
42
60
25
15
24 x 71
27 x 51
1000
120
48
60
25
15
24 x 71
27 x 51
1000
135
54
15
60
25
15
24 x 71
27 x 51
1000
150
60
32
6
48
10
7
17 x 58
21 x 43
450
60
24
40
10
60
16
7
17 x 72
21 x 43
450
75
30
6
48
9
72
23
7
17 x 72
27 x 51
1000
90
36
7
56
8
84
15
15
24 x 71
27 x 51
1000
105
42
8
64
11
96
20
15
24 x 71
27 x 51
1000
120
48
180
9
72
13
108
25
15
24 x 71
27 x 51
1000
135
54
200
10
78
15
108
25
15
24 x 71
27 x 51
1000
150
60
450
300
15
87
15
118
25
20
30 x 72
32 x 51
1500
225
90
600
400
20
94
15
125
25
25
36 x 72
42 x 51
2500
300
120
600
400
20
160
14
240
24
25
36 x 72
42 x 51
2500
300
120
NOTE: Some flow rates are shown at a rate less than the standard 15 PSI drop for continuous and 25 PSI drop for decreased softening capacity as these flows are exceeded.
© 2006 Burnham Commercial - Lancaster, PA
Phone: 1-888-791-3790
www.burnhamcommercial.com
69
Horizontal and Integral Deaerators
The spray type deaerator is rated for oxygen removal to .005cc/I (7PPB) and CO 2 to zero measurable across its entire
operating range. With its all stainless steel spring-loaded spray valve and second stage steam scrubber, the spray
type deaerator is a good choice for all deaerator applications. Units are available with a complete range of boiler
feedpumps and control options making them a total deaerator package with minimal amount of field assembly.
Performance Features
• Oxygen removal to .005 cc/I (7PPB)
• CO2 removal to 0% measurable
• Reduce chemical costs
• Reduce boiler and system corrosion
• Improve boiler efficiency
• Pre-heat boiler feedwater
• Quick equipment payback compared to chemical
oxygen removal
Construction Features
• Constructed to ASME Section VIII, Division 1 for 50 PSIG
• Easily accessible manway
• Standard ten minute deaerator storage
• Internal vent condenser for minimum steam loss
• Self-adjusting spring-loaded stainless steel spray valve
• Structural steel stand/pump platform
• Two-stage deaeration
• Available as completely packaged unit including pumps and control panel
Horizontal Tank Design
Integral Tank Design
70
Horizontal and Integral Deaerators
Horizontal Tank Design
Integral Tank Design
1 High water level control
9 Pump suction
2 Low water level control
10 Pump bypass
3 Make-up water control
11 Chemical port
4 Vacuum breaker
12 Drain
5 Temperature gauge
13 Sample port
6 Pressure gauge
14 High temperature condensate return
7 Overflow trap
15 Gauge glass
8 Vent
16 Manway access opening
© 2006 Burnham Commercial - Lancaster, PA
Phone: 1-888-791-3790
www.burnhamcommercial.com
71
Engineering & Application Data
72
ENG-3
73
ENG-4
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
TERMS AND CONDITIONS OF SALE FOR BURNHAM COMMERCIAL STEEL BOILERS
PRICES AND TERMS OF PAYMENT
A. Prices quoted are firm for no more then 30 days from the date of quotation
subject to any conditions stated in Seller’s quotation or in an order submitted
by Buyer and expressly accepted in writing by Seller. Seller will not be bound
by any price sheet or quote other then a price quote signed by an authorized
representative of Seller.
B. Prices on orders accepted by Seller are firm, to the extent stated in the
accepted order, subject to the following:
1. The purchase order must provide for shipment within six months of the
date of purchase order.
2. Any shipment made more then six months after such a date is subject to a
price adjustment, at Seller’s sole discretion, to the Seller’s price in effect at
the time of shipment, which will not exceed 125% of the price on the
acknowledged purchase order.
3. Any shipment more then 12 months after the date of purchase order will be
invoiced at Seller’s price in effect at the time of shipment.
C. On orders having a total price of less then $100,000 payment will be due “net
in 30 days” from date of shipment, unless otherwise specifically agreed by
Seller. On orders having a total purchase prices of $100,000 or more terms
are 10% with order, 45% upon Seller’s receipt of Buyer’s approval of drawings,
45% within 30 days after shipment and 5% at the start-up of the products or
within 90 days of shipment, which ever occurs sooner.
D. The price of parts, components and other items not manufactured by Seller is
subject to adjustments by Seller to reflect price changes by Seller’s suppliers.
E. Orders accepted by Seller are subject to credit investigation and approval. If
Buyer’s financial condition at any time does not justify the terms specified,
Seller may require payment in advance of shipment or, if shipment has been
made, recover shipment from the carrier. A service charge of 1-1/2% per
month will be added to all accounts 30 days past due.
F. Any tax or governmental change now or hereafter levied upon the production,
sale, use or shipment of products ordered or sold will be charged to and paid
by the Buyer, unless the Buyer has provided Seller with a tax exemption
certification acceptable to the applicable taxing authorities. Such taxes are not
covered in the selling price unless expressly stated on the quotation form.
damages, consequential damages or penalties, whether on account of lost profits,
or otherwise, unless specifically agree in writing signed by an authorized
representative of Seller.
SECURITY INTERESTS
Not withstanding transfer of title to Buyer, the Seller retains and the Buyer
hereby grants to the Seller a purchase money security interest in all products
sold, and Buyer hereby irrevocably appoints Seller as its attorney-in-fact to
execute and deliver, in Buyer’s name, any such financing statement of other
documents as may be necessary under the Uniform Commercial Code or other
applicable laws governing the items sold herein to perfect Seller’s interest therein.
COMPLETE AGREEMENT
The complete agreement between Seller and Buyer is contained herein and any
specifications signed by the Seller, and no additional or different terms or
conditions stated by Buyer shall be binding unless agreed to by Seller in writing.
Neither course of dealings, not usage of trade shall be relevant to supplement or
explain any terms used in this Agreement, and this Agreement may be modified
only by a writing signed by both Seller and Buyer. The failure of Seller to insist
upon strict performance of any of the terms and conditions stated herein shall not
be considered as a continuing waiver of any such terms and conditions or any of
Seller’s other rights.
Buyer will obtain and maintain insurance against the loss or damage naming Seller
as an additional insured in an amount sufficient to protect Seller’s interest in all
products until the purchase price has been paid in full.
CHANGES, ORDERS AND CANCELLATION
Seller may adjust the selling price to cover any requested change in specification
or other terms after the receipt of the Buyer’s order. Orders accepted by
Burnham Commercial shall not be canceled by the Buyer except at Burnham
Commercial’s sole discretion. In the event of any cancellation, Burnham
Commercial reserves the right to impose a cancellation charge sufficient to cover
all losses and out-of-pocket costs incurred by Seller in connection to such order,
including materials and labor charges and cancellation charges from vendors, plus
a cancellation charge of 20% of the original face amount of the order to
compensate the Seller for its loss in profit.
RETURNED GOODS
Products may not be returned for refund or credit until after Seller has agreed to
accept them. Inspection by a Seller representative may be required before return
authorization is granted. A minimum restocking and handling charge of 25% (plus
cost of any missing parts or components and inbound freight) will apply to all
such returned products. All transportation charges for such products must be paid
by Buyer.
TRANSPORTATION TERMS AND CLAIMS
Unless otherwise stated on Seller’s quotation form, all process are F.O.B Seller’s
shipping point. Delivery to the initial carrier shall constitute delivery to the Buyer.
Seller’s responsibility ceases and title the goods passes, subject to Seller’s
security interests upon delivery in good order to such carrier, and all products are
shipped at the Buyer’s risk. The Buyer agrees to examine all deliveries carefully
before signing transportation receipts. If products are visibly damaged the Buyer
shall require that written confirmation of damage be noted on the carrier’s
delivery receipt and confirmed by the driver for the carrier. If damage is
discovered after unpacking, the carrier shall be notified at once so that an
inspection can be made and the claimed damage substantiated by the carrier.
FORCE MAJEURE AND STORAGE
A. Seller shall not be liable for any delay or failure in the delivery or shipment of
products or for any damages suffered by reason of such delay or failure
directly or indirectly, due to fire, flood, other weather conditions, accident,
riots, war, embargo, labor stoppages, inadequate transportation facilities,
shortage of materials or supplies, regulation by government authority or any
cause beyond the Seller’s control.
B. Seller reserves the right to allocate available production among its customers
in any fair and reasonable manner that it determines is necessary or
desirable.
C. If delivery is delayed due to any cause beyond the Seller’s control, Buyer
shall reimburse Seller for any added costs. Without limiting the foregoing,
product on which manufacturer or delivery is delayed due to cause may be
placed in storage by Seller, for the Buyers account and risk, and regular
charges therefore and expense in connection therewith shall be paid by the
Buyer. If, in Seller’s opinion, it is unable to obtain or continue such storage,
the Buyer will, on request, provide or arrange for suitable storage facilities and
assume all costs and risks in connection therewith.
SHORTAGES, VARIANCES AND WEIGHTS
No claims for variance from or shortages in orders will be considered unless
present within 30 days after receipt of products. Any shipping weights are given
or estimated are approximate, for the Buyer’s convenience only, and not
guaranteed by Seller.
LIMITS OF LIABILITY
Any action by Buyer on this contract, must be commenced within one year after
the cause of action accrues. Actions on Seller’s Warranties shall be limited as
provided therein. Seller shall in no event have any liability for any liquidated
PRODUCT CHANGES
Seller reserves the right to make changes in products of any kind without prior
notice, and to deliver revised designs or models of products against any order.
Seller shall have no responsibility whatsoever with respect to changes made by
the manufacturer of products sold but not manufactured by it.
PATENTS
Products manufactured and sold by Seller may be used by the Buyer pursuant to
such patent rights as Seller may own or enjoy. Seller shall not liable for any use
such products may be put as part of any system, mechanism or process covered
by patent rights of others.
TESTS
Any tests requested by the Buyer to determine the performance of products
covered by Seller’s quotation, must utilize procedures acceptable to Seller and the
Buyer is responsible for costs thereof. Whenever an order includes start-up or
service agreement, Seller shall not be obliged to provide start-up or other service
as long as payment to Seller is default.
CONFLICTING PROVISIONS OFFERED BY BUYER
Any terms and conditions of Buyer’s purchase order which are different, from, in
addition to inconsistent with the terms and conditions contained herein, are hereby
objected to, and will not be binding on Seller in any manner whatsoever unless
accepted by Seller in writing. Seller shall ship products referred to in this document
only on the condition that the terms and conditions of sale set forth hereon shall
be binding on the Buyer.
APPLICABLE LAW
Any order or contracts received by Seller from Buyer shall be governed by,
construed and enforced by the laws of the Commonwealth of Pennsylvania.
CHANGES IN TERMS
These terms and conditions of sale are subject to change by Seller from time to
time without prior notice.
LIMITED WARRANTY
LIMITED WARRANTY
Subject to the terms and conditions herein, Seller warrants to the original owner at
the original installation site that products manufactured by Seller (“Products”)
comply, at the time of manufacture, with recognized hydronics industry regulatory
agency standards and requirements therein effect and will be free from defects in
materials and workmanship for a period of 12 months after the date of start-up or
18 months after the date of shipment, whichever shall be less (the “Warranty
Period”)
REMEDY
A. The sole remedy for breach of this warranty is expressly limited to the repair
or replacement of any part found to be defective under conditions of normal
use within the Warranty Period. Installation is not included.
B. Warranty – The owner must notify the original installer of the Product and
Seller (Attention: Burnham Commercial, PO Box 3939, Lancaster, PA 17604) in
writing, within the Warranty Period, providing a detailed description of all
claimed defects. Transportation to a factory or other designated facility for
repairs or any products or alleged defective shall, in all events, be the
responsibility and at the cost of the owner.
EXCLUSIONS
Seller shall have no liability for:
A. Incidental, special or consequential damages, such as loss of the use of
products, facilities or production, inconvenience, loss of time or labor expense
involved in the repairing or replacing of the alleged defective product.
B. The performance of any Product under conditions varying materially from
those under such Products is usually tested under industry standards as of
the shipment time.
C. Any damage to the Product due to abrasion, erosion, corrosion, deterioration,
abnormal temperatures or the influence of foreign matter or energy.
D. The design or operation of owner’s plant or equipment or of any facility or
system of which any Product may be made a part.
E. The suitability of any Product for any particular application.
F. Any failure resulting from misuse, modification, not authorized by Seller in
writing, improper installation or lack of proper maintenance.
G. Equipment furnished by the owner, either mounted or unmounted, or when
contracted for by owner to be installed or handled.
Seller’s liability under this warranty shall not in any case exceed the amount paid
for the Product found defective.
THIRD-PARTY WARRANTIES
For goods or components not manufactured by Seller, the warranty obligations or
Seller shall, in all respects, conform and be limited to the warranty actually
extended to Seller by its vendors.
SEVERABILITY
To the extent that any provisions of this warranty would be void or prohibited under
applicable law, such provisions shall be limited in effect to the minimum extent
necessary to render the remaining provisions hereof enforceable.
93
NO OTHER WARRANTIES
Seller makes no implied warranty of merchantability or fitness for a particular
purpose, or other warranties with respect to any products or services except as
expressly set forth in this limited warranty.
Form No. PL8146561001 - 4/04