STRAY VOLTAGE Permanent Separation of Primary- Secondary Neutrals (NESC 97-D2) Materials Needed: • Stray Voltage Isolator • I 0-ft. Ground Rod • 40-ft. ± Cu 600 Volt Conductor Procedural steps to separate primary neutral circuit from the secondary neutral circuit when stray voltage (neutral-to-earth) study determines this procedure is necessary: 1. Observe and record the primary grounding electrode conductor (PGEC) to remote ground rod (RGR) readings at the transformer pole serving the affected diary farms. (a.) Other pole grounds in the immediate area should be measured to RGR and recorded. 2. De-energize transfonner and temporarily disconnect from primary. 3. Install new secondary grounding electrode conductor (SGEC) to a new 10' ground rod installed at least 10' away from existing pole ground rod. (This new conductor MUST be 600 volt insulated.) 4. Connect new SGEC to the X2 (neutral) bushing of the transformer. (a) Remove factory ' bonding strap' from X2 bushing to accomplish the separation of X2 bushing from transformer tank. (b) Remove the grounding jumper from primary neutral, to X2 bushing, continuing on to transformer tank grounding stud (near the base ofthe tank). 5. Verify the transformer tank grounding stud (which is internally connected to primary winding) is STILL bonded to the primary neutral via the existing PGEC. 6. Recheck all connections to make sure the 2 neutrals ARE NOT interconnected. However, the secondary neutral is connected to earth through the new insulated SG EC on ground rod. Also, verify the primary neutral and transformer tank are connected to earth through the original PGEC.