A-A SERVICE TRANSFORMER SECONDARY A 1 GROUND ROD LENGTH SEPARATION MINIMUM OF 10' EXOTHERMIC WELD CONNECTION (TYP) GROUNDING KEY NOTES 1 B TRANSFORMER FRAME GROUND BOLTED ON CONNECTION C 10'x 3/4" COPPER CLAD GROUND ROD (TYP OF 2) EXOTHERMIC WELD CONNECTION 3 4 CONNECTION TO LIGHTNING PROTECTION SYSTEM (IF APPLICABLE) EXOTHERMIC WELD CONNECTION (TYP) 5 1 2 10'x 3/4" COPPER CLAD GROUND ROD (TYP OF 2) 25' MIN. N 5 NATURAL GAS OR PROPANE SERVICE 3 BUILDING STEEL 6 APPROVED GROUNDING METHOD (SEE GENERAL NOTE 1) 2 NEUTRAL CONDUCTOR SIZED TO MATCH PHASE CONDUCTORS MINIMUM. PLANS AND ONE-LINES FOR ADDITIONAL INFORMATION. REFER TO FLOOR EQUIPMENT GROUNDING CONDUCTOR SIZED BASED ON SWITCHGEAR MAIN OVERCURRENT PROTECTION DEVICE PER NEC TABLE 250-122. REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. 5/8" X 10' COPPERCLAD GROUND ROD PLAN VIEW REFER TO DWGS. TELECOM DRAWINGS FOR ADDITIONAL INFORMATION. TRANSFORMER GROUND RING SHALL CONSIST OF MINIMUM 1/0 BARE COPPER CONDUCTOR BURIED MINIMUM 12" FROM EDGE OF TRANSFORMER FOUNDATION AND 18"-24" BELOW FINAL GRADE. PROVIDE MINIMUM OF TWO (2) 10'-0"X 3/4" COPPER CLAD GROUND RODS DRIVEN AT OPPOSITE CORNERS. PROVIDE ADEQUATE GROUNDING WHIP FOR BOLTED CONNECTION TO TRANSFORMER FRAME GROUND. PROVIDE EXOTHERMIC WELDS OF GROUND RING TO GROUND RODS AND GROUNDING WHIP TO RING. DO NOT CONNECT TO BUILDING SERVICE GROUND. TOP OF FOUNDATION 2' PROVIDE ENGRAVED NAMEPLATE ON ALL GROUND CABLE CONNECTIONS AT THE BUS BAR AND AFFIX WITH WIRE TIES. GROUND BAR 6 6 6 6 PEDESTAL GROUNDING DIAGRAM NO SCALE SECTION A-A NOTES: TRANSFORMER GROUND MAT DETAILS NO SCALE EXOTHERMIC WELD CONNECTION 6 PROVIDE SCREW FASTENED LAMACOID LABELS IDENTIFYING EACH GROUND BAR CONNECTION ELECTRIC POWER GROUNDING DETAIL SCALE: NONE GENERAL NOTES: 1. A GROUNDING JUMPER SHALL BE PROVIDED AROUND THE WATER OR GAS METER AND BACKFLOW PREVENTER. 2. PVC CONDUIT IS THE PREFERRED METHOD OF PROTECTION FOR THE GROUNDING CONDUCTORS. DISCUSS WITH PSU ENGINEERING SERVICES FOR ANY DEVIATIONS. #4/0 AWG, SOFT DRAWN TINNED SOLID COPPER CONDUCTOR CADWELD CONNECTION 10"Ø x 42" GROUND ACCESS WELL WITH STEEL COVER, SIMILAR TO HARGER MODEL 360P42 WITH COVER 10PS. 3/4" x 10' COPPER CLAD GROUND ROD GROUND ROD ACCESS WELL DETAIL SCALE: NONE AT LEAST 25% OF PEDESTAL SHALL BE GROUNDED. 2. GROUNDING CLAMP AND BUSHING SHALL BE APPROVED TYPE FOR RAISED FLOOR SYSTEM. 4. 4 TWO HOLE BOLTED CONNECTION (TYP) 1. 3. ALL WORK ON THIS DETAIL SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. COMMON GROUNDING BAR IN ELECTRIC ROOM (MIN. 4"x1/4"x 24"), 2-HOLE LUGS, MOUNTED TO ELECTRIC ROOM WALL WITH INSULATED STANDOFFS BONDING CONDUCTOR TO NEXT PEDESTAL #4 AWG BARE STRANDED COPPER WIRE DRILL 1"Ø HOLE IN THE UPPER CORNER OF FOUNDATION FOR GROUND WIRE ENTRANCE. #2/0 BARE COPPER TELECOMM ROOM GROUND BAR EXOTHERMIC WELD CONNECTION RAISED FLOOR DO NOT CUT THE GROUND WIRE FINISHED GRADE GROUND ROD SERVICE ENTRANCE EQUIPMENT NEUTRAL BAR GROUND CLAMP BOLLARD (WHERE REQUIRED) TELECOMMUNICATIONS ROOM MAIN GROUND BUSBAR GROUNDING CONDUCTOR SHALL BE MINIMUM 4/0 AWG. APPROVED GROUNDING METHOD (SEE GENERAL NOTE 1) 3 #2/0 7-STRAND BARE SOFT DRAWN COPPER WIRE DIRECT BURIED 2' BFG (TYP). FRONT GROUNDING ELECTRODE CONDUCTOR SIZED BASED ON PHASE CONDUCTORS PER NEC TABLE 250.66, MINIMUM OF 1/0 AWG. REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. WATER SERVICE EXOTHERMIC WELD CONNECTION LAY-IN GROUND BUSHING LUG PROVIDE 15' WIRE TAILS INSIDE FOUNDATION. TRANSFORMER CONCRETE FOUNDATION. #4/0 AWG SOLID SOFT DRAWN TINNED COPPER CONDUCTOR CADWELD CONNECTION 3/4" x 10' COPPER CLAD GROUND ROD GROUND ROD DETAIL SCALE: NONE ALL THE DEVICES SHALL BE PLATED TO PROVIDE LOW CONTACT RESISTANCE GROUNDING CLAMP AND BUSHING SHALL BE SIZED BASE ON SIZE OF PEDESTAL AND GROUND WIRE. SERVICE TRANSFORMER SECONDARY A 1 GROUND ROD LENGTH SEPARATION MINIMUM OF 10' EXOTHERMIC WELD CONNECTION (TYP) GROUNDING KEY NOTES 1 B 25' MIN. N TRANSFORMER FRAME GROUND BOLTED ON CONNECTION C 10'x 3/4" COPPER CLAD GROUND ROD (TYP OF 2) 5 EXOTHERMIC WELD CONNECTION 3 3 4 CONNECTION TO LIGHTNING PROTECTION SYSTEM (IF APPLICABLE) EXOTHERMIC WELD CONNECTION (TYP) 1 2 10'x 3/4" COPPER CLAD GROUND ROD (TYP OF 2) 5 NATURAL GAS OR PROPANE SERVICE BUILDING STEEL 6 APPROVED GROUNDING METHOD (SEE GENERAL NOTE 1) 2 NEUTRAL CONDUCTOR SIZED TO MATCH PHASE CONDUCTORS MINIMUM. PLANS AND ONE-LINES FOR ADDITIONAL INFORMATION. REFER TO FLOOR EQUIPMENT GROUNDING CONDUCTOR SIZED BASED ON SWITCHGEAR MAIN OVERCURRENT PROTECTION DEVICE PER NEC TABLE 250-122. REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. GROUNDING ELECTRODE CONDUCTOR SIZED BASED ON PHASE CONDUCTORS PER NEC TABLE 250.66, MINIMUM OF 1/0 AWG. REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. TELECOMMUNICATIONS ROOM MAIN GROUND BUSBAR GROUNDING CONDUCTOR SHALL BE MINIMUM 4/0 AWG. REFER TO DWGS. TELECOM DRAWINGS FOR ADDITIONAL INFORMATION. TRANSFORMER GROUND RING SHALL CONSIST OF MINIMUM 1/0 BARE COPPER CONDUCTOR BURIED MINIMUM 12" FROM EDGE OF TRANSFORMER FOUNDATION AND 18"-24" BELOW FINAL GRADE. PROVIDE MINIMUM OF TWO (2) 10'-0"X 3/4" COPPER CLAD GROUND RODS DRIVEN AT OPPOSITE CORNERS. PROVIDE ADEQUATE GROUNDING WHIP FOR BOLTED CONNECTION TO TRANSFORMER FRAME GROUND. PROVIDE EXOTHERMIC WELDS OF GROUND RING TO GROUND RODS AND GROUNDING WHIP TO RING. DO NOT CONNECT TO BUILDING SERVICE GROUND. PROVIDE ENGRAVED NAMEPLATE ON ALL GROUND CABLE CONNECTIONS AT THE BUS BAR AND AFFIX WITH WIRE TIES. WATER SERVICE EXOTHERMIC WELD CONNECTION APPROVED GROUNDING METHOD (SEE GENERAL NOTE 1) SERVICE ENTRANCE EQUIPMENT TELECOMM ROOM GROUND BAR EXOTHERMIC WELD CONNECTION 3 NEUTRAL BAR GROUND BAR 6 6 6 6 #4/0 AWG, SOFT DRAWN TINNED SOLID COPPER CONDUCTOR 4 6 COMMON GROUNDING BAR IN ELECTRIC ROOM (MIN. 4"x1/4"x 24"), 2-HOLE LUGS, MOUNTED TO ELECTRIC ROOM WALL WITH INSULATED STANDOFFS BONDING CONDUCTOR EXOTHERMIC WELD CONNECTION TWO HOLE BOLTED CONNECTION (TYP) #4/0 AWG SOLID SOFT DRAWN TINNED COPPER CONDUCTOR 10"Ø x 42" GROUND ACCESS WELL WITH STEEL COVER, SIMILAR TO HARGER MODEL 360P42 WITH COVER 10PS. PROVIDE SCREW FASTENED LAMACOID LABELS IDENTIFYING EACH GROUND BAR CONNECTION 3/4" x 10' COPPER CLAD GROUND ROD CADWELD CONNECTION 3/4" x 10' COPPER CLAD GROUND ROD CADWELD CONNECTION GENERAL NOTES: 1. A GROUNDING JUMPER SHALL BE PROVIDED AROUND THE WATER OR GAS METER AND BACKFLOW PREVENTER. 2. PVC CONDUIT IS THE PREFERRED METHOD OF PROTECTION FOR THE GROUNDING CONDUCTORS. DISCUSS WITH PSU ENGINEERING SERVICES FOR ANY DEVIATIONS. GROUND ROD ACCESS WELL DETAIL SCALE: NONE GROUND ROD DETAIL REVISION: 1.1 SCALE: NONE REVISION LOG 1.0 1.1 DATE 10/2014 ORIGINAL EDIT GROUND BAR CALLOUT DETAIL 02/2016 PSU OPP STANDARD DETAIL TITLE: TYPICAL GROUNDING DETAILS SCALE: NONE PAGE #1 OF 1 DETAIL #: 260526-D01 DATE: 10/20/2014