COASTAL ENERGEN PRIVATE LIMITED 2 X 600 MW THERMAL POWER PLANT ABB Doc No: 1013-3VYN294303-01 Rev No:00 SIZING CALCULATION OF GENERATOR NEUTRAL GROUNDING TRANSFORMER (NGTR) I. EQUIPMENT DATA : Generator Voltage, VL-L = 20000 V Generator stator winding capacitance / phase ( in ref. to 600MW HPE Generator data) a = 0.227 mF Capacitor considered per phase = (in ref. to standard manufacturer data) b = 0.25 mF Busduct capacitance main run (in ref. to standard Manufacturer's Data) Total length of IBPD Total Busduct capacitance/phase c = = = 108.8 pF/m/ph 84 m 0.009139 mF Busduct capacitance Delta run (in ref. to standard Manufacturer's Data) Total length of IBPD Total Busduct capacitance/phase d = = = 66.1 pF/m/ph 27 m 0.001785 mF Busduct capacitance Tap off run (in ref. to standard Manufacturer's Data) Total length of IBPD Total Busduct capacitance/phase e = = = 43.94 pF/m/ph 53 m 0.002329 mF Equivalent GT capacitance / phase (From GT manufacturer Data) f = = 14700 pF/m/ph 0.0147 mF Equivalent UT-1A capacitance / phase (From UT manufacturer Data) g = = 3000 pF/m/ph 0.003 mF Equivalent UT-1B capacitance / phase (From UT manufacturer Data) h = = 3000 pF/m/ph 0.003 mF Equivalent ST-1 capacitance / phase (From ST manufacturer Data) i = = 3280 pF/m/ph 0.0033 mF Selected primary Voltage of the Grounding Transformer Vp = 20000 V Selected secondary Voltage of the Grounding Transformer Hence, turns ratio Vs N = = 240 V 83.333 = 11547 V = 15011 = 0.514233 mF II. CALCULATION OF NGT PARAMETER : Normal Phase to Neutral Voltage = VP1 = VL-L / Sqrt(3) Considering 30% of force field condition Normal phase to neutral voltage =1.3X Vp1 Vff Total zero sequence capacitance C = (a)+(b)+(c)+(d)+(e)+(f)+(g)+(h)+(i) Zero-sequence Capacitive reactance to ground XC XC = = 1/2pifC ohms/ph 6190.00 ohms/ph Zero-Sequence Capacitive charging current/phase = Vff x Xc Ic = 2.425 Amps Total system Capacitive charging current, 3 * Ic It = 7.275 Amps Power rating of the grounding transformer = (VpXIt)/1000 P = 145.50 kVA Power rating of the grounding transformer with overloading factor of 2.6 in ref. to table1 of IEEE C62.92.02-1989 for 10sec duty = 13.86 kVA Selected Neutral Grounding Transformer rating = 15 kVA = 2063.33 ohm III. CALCULATION OF NGR PARAMETER : Residual Capacitive reactance Xc/3 XCt A per IEEE C62.92.02 - 1989, The grounding resistor is sized so that the ratio between Capacitive Reactance (XCt) and effective resistance (Req) between the generator neutral and ground is 1. Hence, Req = XCt Resistance value required at secondary side, Rsec = Req/N^2 Rsec Selected value of neutral grounding resistor IV. CALCULATION OF NGR CURRENT RATING : Page 1 of 2 = 0.297 ohm = 0.297 ohm COASTAL ENERGEN PRIVATE LIMITED 2 X 600 MW THERMAL POWER PLANT ABB Selected Grounding Resistor value reflected in the primary side (Rsec/N^2) Doc No: 1013-3VYN294303-01 Rev No:00 Rp = 2063.33 ohms Fault current through generator neutral under single line to ground fault condition If = Vff/ Rp Amps Single line to ground fault current (NGT's self impedance is not considered) If = 5.60 Amps Isec = 466 Amps Required rating of the Neutral Grounding Transformer (NGT) : : : : : Current in secondary of Neutral Grounding Transformer V. SUMMARY : A Selected rating of the Neutral Grounding Transformer (NGT) continious Ratio Duty Short Time Rating of Trafo = Overloading factor x Continuous Rating Selected rating of the Neutral Grounding Transformer (NGT) for short time rating of 10sec B Resistance Value of Grounding Resistor (NGR) Resistance Value of Grounding Resistor at 75% Tap Resistance Value of Grounding Resistor at 50% Tap Resistance Value of Grounding Resistor at 25% Tap Current Rating Duty 13.86 kVA 15 kVA 20000/240 Volts 10 sec 157.5 kVA : 175 kVA : : : : : : 0.297 Ohms 0.223 Ohms 0.149 Ohms 0.074 Ohms 500 Amps 10 sec Note: As per TCE/Energn contract the ground fault limiting current for generator neutral is 1A. As per system capacitance considered (As per above calculation), The capacitive current value is 7.275Amps. But according to the design philosophy the resistive component of the ground fault current should be greater than or equal to capacitive component, to minimize the voltage surges. Hence 1A is not a realistic figure as a limiting current for generator nuetral Page 2 of 2