Istruction Manual

advertisement
Instruction Manual
BRWC
Water-cooled water chillers
BRWH
Water / water heat pumps
BRRC
Condenserless units
R134a (320-1200kW)
EN
EN
Release: 1.3
Data: November 2012
The technical data shown in the manual are not binding.
The images shown in this manual are for descriptive purposes only. They may therefore differ from specific
models which are selected.
UNIFLAIR SpA policy is one of continuous technological innovation and the Company therefore reserves the
right to amend any data herein without prior notice.
2
Release 1.3 – November 2012
CONTENTS
IMPORTANT WARNINGS
4
SYMBOLS USED
SAFETY
5
5
Documentation included with the unit
General description
Intended use of the unit
Unit codes & options
Data plate & electrical data
Main features
Operation limits
Description of the main components of the unit
Access to main components
Dimensions and weights
Partial and local heat recovery
Heat pump series
6
7
8
9
10
11
12
15
19
20
21
22
INSTALLATION
Transport and movement
Receiving and storing the unit
Movement
Positioning the unit – operation space
Hydraulic connections
Electrical connections
Connection to remote condenser
Piping diagram to remote condenser
23
23
24
25
26
27
29
32
TECHNICAL DATA
Performance
Electrical Data
Noise levels
Evaporator pressure drop
Condenser pressure drop
Overall dimensions
Lifting Diagrams
34
35
38
41
43
44
45
54
This unit has been subjected to risk analysis under 2006/42/EEC Directive. The technical solutions
implemented during the design phase are described in the unit’s technical file.
This equipment is manufactured to function safely for the purposes for which it was designed as long as the
installation, operation and maintenance are carried out according to the instructions in this manual
and on the labels attached to the unit.
This machine is subjected to the European Community Directive 97/23/EEC regarding Pressure
Equipment. Any intervention on the pressure circuit must be authorized by Uniflair, and the
personnel must be approved by Uniflair. If any of the following components: compressors, liquid
receivers, safety valves, refrigerant pressostats are to be replaced, Uniflair must be immediately
informed of the serial number of the new and of the replaced devices, otherwise Uniflair shall not
guarantee the integrity of the equipment.
Additionally, if any soldered join needs to be repaired on site, Uniflair must be immediately informed
of which join and of the name of the engineer.
Warnings in this manual which are particularly important for user safety are shown by the danger symbol.
If these instructions are NOT complied with, the warranty shall be void.
Release 1.3 – November 2012
3
IMPORTANT WARNINGS
This unit contains refrigerant gas circuits, chilled water under pressure, live electrical components,
hot surfaces, sharp edges (the fins on the coils) and rotating devices such as the fans.
All service and maintenance operations which require access to the inside of the unit while
it is in operation must be performed by qualified and experienced personnel who are aware
of the necessary precautions.
Before accessing the inside of the unit, disconnect it from the electrical power supply.
In any case, all safety legislation regarding the installation location must be followed.
In the event of fire, water and other conductive substances must not be used to put out the fire
near live electrical components. This warning must be displayed on notices in the unit installation
location.
If refrigerants used come into contact with fire they decompose, forming acids and other irritants.
The smell of these substances, even at concentrations below danger levels, gives enough
warning to allow evacuation of the area at risk.
Make sure that the mains supply to the unit is the same as that shown on the data plate.
This unit is designed to cool/heat fluid like water and anti-freeze mixture. If another mixture
is used, it can cause corrosion and deterioration.
This unit is not suitable for operation in aggressive environments.
Emptying of the unit is recommended in the event of prolonged stoppage.
Drain all the water from the system before the winter to avoid freezing.
In periods in which the temperature may fall below 0°C, empty the unit in order to prevent serious
damage caused by the formation of ice.
This precaution is not necessary if the unit is charged with an appropriate anti-freeze
mixture.
If the unit is fitted with the optional heating cable, it must be turned off without cutting the electrical
power supply.
Install a mechanical filter in the section of tubing near the intake of the unit to prevent the
heat exchanger being blocked with pieces of welding or flakes of oxidised metal from the water
mains.
In compliance with Community directive 94/9/CE these units are not to be used in potentially
explosive environments.
R134a  GWP = 1100
4
Release 1.3 – November 2012
SYMBOL USED
SYMBOL
MEANING
DANGER
SYMBOL
MEANING
HOT SURFACE – DANGER OF
BURNING
HIGH VOLTAGE – ELECTRICAL
RISK
IMPORTANT WARNING
SAFETY
The new range BRWC-BRWH-BRRC units features state-of-the-art technology ensuring maximum reliability,
safety, quiet operation and respect for the environment.
1)
RELIABILITY: Trouble-free operation of Uniflair precision chillers is ensured by rigorous production
process controls under ISO 9001-certified quality procedures:
quality control of components;
pressure testing of refrigerant and water circuits;
testing of current absorption and IEC safety testing;
calibration and testing of instruments and safety devices;
final testing of unit under operating conditions.
2)
ACTIVE SAFETY: UNIFLAIR safety and control systems have a supervision and prevention function
with:
automatic blocking of components in dangerous conditions;
indication of function status;
reading and continuous display of circulating fluid temperature;
management of compressor start-ups to reduce excessive switching on and off;
Alarm signal in the event of a refrigerant leak;
Indication of anomalous function conditions and / or alarms;
Compressor crankcase heater activation when the compressor is switched off;
Anti-freeze protection to prevent freezing of the evaporator.
3)
PASSIVE SAFETY: The essential functions of these units are protected against anomalous function
conditions and potential damage by:
high and low pressure switches on the refrigerant circuit (HP with manual re-set);
safety valve on the high and low pressure refrigerant line;
compressor motor electrical protection;
water circuit safety;
compressor oil circuit safety.
4)
PERSONAL SAFETY. The design and wiring of all UNIFLAIR chillers and heat pump is conforms to
IEC electro-technical standards. Electrical panels have auxiliary 24V circuits and are equipped with:
general switch and door lock switch;
automatic circuit-breaker switches.
Release 1.3 – November 2012
5
DOCUMENTATION INCLUDED WITH THE UNIT
Each unit is delivered complete with the following documentation:
Machine and microprocessor control instruction manuals
Unit installation diagrams
Diagrams of the refrigerant and hydraulic circuits of the unit
Electrical diagrams
List of spare parts
CE declaration with list of European directives and norms to which the unit conforms
Warranty Conditions
R134a safety data sheet
6
Release 1.3 – November 2012
Aquaflair
B.R.W./R
B.R.W./R.
The AQUAFLAIR
range is composed of eleven water-cooled chillers with semihermetic double screw compressors with nominal cooling capacities ranging from 300 to 1200 kW, available
in the following series:
-
cooling only
heat pump
condenserless
Our commitment to respect environmental regulations, a commitment typical of UNIFLAIR products, is fully
maintained in these series. The units have been designed for standard operation with the refrigerant
R134a.
The BRWC/H and BRRC units are based on cutting-edge technology and include many innovative features
and details. Even the basic version, for example, includes an electronic expansion valve.
The unit is fully controlled by the UPC1m control system: two I/O boards connected to the mP20II user
interface for full control of the all the unit's parameters.
The following items complete the hardware: a LAN card and a Clock card, both standard items, and the
serial RS485 adaptor (optional) for connection to the Uniflair supervision system or to a Building
Management System.
The design criteria of B.R.W.-R.* models is based on three key words: efficiency, reliability and flexibility.
Twin screw compressors, R134a refrigerant and Electronic Expansion Valves allow high energy efficiency in
all operating conditions.
Great attention has been paid to the creation of a completely flexible system: the footprint is one of the
smallest available, with a width and height which allows the units of up to 700kW to pass through a standard
doorframe.
These chillers can be supplied in a low-noise version, recording noise emission values among the lowest in
the category.
The units can also be installed externally and can operate with condensation water temperatures of up to
55°C.
Particular attention has been paid to reliability, both in the choice of components for adjustment / control:
each component is monitored so that it operates within optimum operating parameters.
Release 1.3 – November 2012
7
BRWC
Refrigerant R134a
Electronic Expansion Valve (EEV)
High and low pressure gauges, switches and ratiometrical transducers
Discharge shut-off valve on compressors
Water flow pressure switch on evaporator and condensers
3-way pressostatic valve
Protection fuses on compressors
Oil heaters
Compressors with thermal protection
Electrical board overheating control
Advanced microprocessor control system UPC1m
Local user terminal mP20II
LAN card for local area network connection of multiple chillers
Clock card
BRWH
Refrigerant R134a
Electronic Expansion Valve (EEV)
High and low pressure gauges, switches and ratiometrical transducers
Discharge shut-off valve on compressors
Water flow pressure switch on evaporator and condensers
3-way pressostatic valve
Protection fuses on compressors
Oil heaters
Compressors with thermal protection
Electrical board overheating control
Advanced microprocessor control system UPC1m
Local user terminal mP20II
LAN card for local area network connection of multiple chillers
Clock card
BRRC
BASIC VERSION
Refrigerant R134a
Electronic Expansion Valve (EEV)
High and low pressure gauges, switches and ratiometrical transducers
Discharge shut-off valve on compressors
Refrigerant line shut-off valves
Water flow pressure switch on evaporator
3-way pressostatic valve
Protection fuses on compressors
Oil heaters
Compressors with thermal protection
Electrical board overheating control
Advanced microprocessor control system UPC1m
Local user terminal mP20II
LAN card for local area network connection of multiple chillers
Clock card
8
Release 1.3 – November 2012
UNIT CODES & OPTIONS
Versions
RS485
LON FTT10
TCP/IP
Total heat recovery
Sound-proofed compressor housing and vibration absorber
Suction shut-off valve (on each compressor)
Power phase capacitors
Accessories
Serial
adaptor
Version with sea water condensers
High condensing water temperature
Low temperature water production (down to -10°C)
Other
options
Basic version
Low ambient temperature version: this option features:
o Electrical board anti-condensing heater
o Evaporator anti-freeze heater
o Condenser anti-freeze heaters
o Condenser insulation
Water
BRWC/H
Remote user terminal
Spring anti-vibration supports
Neoprene anti-vibration supports
Modulating condensation control valves kit
Versions
RS485
LON FTT10
TCP/IP
Sound-proofed compressor housing and vibration absorber
Suction shut-off valve (on each compressor)
Power phase capacitors
Accessories
Serial
adaptor
High condensing water temperature (available only for: 1402A, 2002A, 2202A, 3202A, 3602A models)
Low temperature water production (down to -10°C)
Other
options
Basic version
Low ambient temperature version: this option features:
o Electrical board anti-condensing heater
o Evaporator anti-freeze heater
Water
BRRC – Condenserless series
Remote user terminal
Spring anti-vibration supports
Neoprene anti-vibration supports
Release 1.3 – November 2012
9
DATA PLATE
The chiller data plate is in the electrical panel and gives the following information:
Model of the unit
Serial number
Voltage, number of phases and power supply frequency for primary and auxiliary circuits
Current and power absorbed
OA (Operating current), FLA (Full load current) and LRA ( Locked rotor current )
Safety device settings
Refrigerant type and charge in kg for each circuit
TENS.
400V/3Ph/50Hz
AUX. 230/24
NO. TENS.
VOLT
rev.
SERIAL No.
OA
FLA
LRA
kW TOT
AP1 - AP2
STOP:
22,5 bar;
(/1)
(/1)
(/1)
(*)
BP1 - BP2
STOP:
0,7
DIFF:
0,5
bar
VSA1 - VSA2
SAFETY VALVE OPEN AT:
25
bar
COMPRESSOR 1 (CIRC. 1)
1
400/3 116,2
196
612
65,8
COMPRESSOR 2 (CIRC. 1)
1
400/3 116,2
196
612
65,8
bar;
MAN. RESET.
R134a
FACTORY CHARGE:
kg./CIRC. 1
FACTORY CHARGE:
kg./CIRC. 2
Icu=15kA (CEI EN 60947-2)
(*) nominal absorbed power
TOTAL (kW)
10
MOD.
BRWC2502A
0,0
Release 1.3 – November 2012
MAIN FEATURES
MAIN FEATURES
B.R.W./R.
AQUAFLAIR
condenserless units are designed for INTERNAL installation (or external installation but it
must be protected from rain; for example with a shed) in residential, commercial and technological applications.
The chilled water which is produced can be sent to the fan coils or other terminal units for climate control or the air
conditioning of technological environments. It can also be used for industrial process cooling.
Thanks to the UPC1m microprocessor control, the units can be connected in parallel on a single water circuit in
order to increase the units’ cooling capacity when needed. With the UPC1m control, a local area network can be
created which links the microprocessor control boards, creating solutions to satisfy all needs.
B.R.W./R.
AQUAFLAIR
water chillers and heat pumps feature state-of-the-art technology allowing maximum
reliability, safety, quietness of operation and respect for the environment.
EASY TO INSTALL AND TO MAINTAIN
All models are fitted with a general door interlock switch allowing direct connection to the mains power supply
without the need for an external switch; short-circuit protection fuses should, however, be fitted in order to protect
the power supply line.
Water chillers and heat pumps are assembled and fully tested in the factory, making installation simply a question
of connection to the electrical power supply and water circuits.
Particular attention has been paid to planning the position of the components to allow easy access for ordinary
and emergency maintenance.
(
Finally, the units have been produced in order for then to also be installed externally On request).
FOOTPRINT
Particular attention has been paid to creating a completely flexible installation: the footprint of this unit is one of
the smallest available, with a width and height which allow units of up to 750kW to pass through a standard
doorframe.
RESISTANCE TO THE ELEMENT
Corrosion resistance is an essential feature of UNIFLAIR units. They are built to operate even under extremely
severe environmental conditions. The self-standing framework is made of galvanised sheet steel, with panels
painted with epoxy powder paints (colour RAL 7037) conforming to the ASTM B117 standard. Furthermore, all
external screws, nuts, etc are in stainless steel.
ENVIRONMENTALLY FRIENDLY
B.R.W./R.
UNIFLAIR products have always been built with respect for the environment. With the AQUAFLAIR
range,
UNIFLAIR continues to offer solutions which are at the forefront of technology and which are aimed at reducing
environmental impact. These solutions cover many aspects: use of the ecological refrigerant R134a, elimination of
non-recyclable materials, lower consumption of energy by using components with improved thermo-dynamic
efficiency and adopting compressors with high energy performance.
ENERGY EFFICIENCY
B.R.W./R.
The AQUAFLAIR
units are designed in order to obtain maximum performance levels with minimum
energy absorption. Such a result is made possible by the use of 8-step partialisazion in the units.
The thermal range in each exchanger drops at partial pressure loads in each refrigerating circuit. This leads to an
increase of the evaporation temperature and a reduction of the condensation temperature, resulting in a very high
COP (Coefficient Of Performance).
Release 1.3 – November 2012
11
BRWC - OPERATION LIMITS
The different options which influence operation are:
Basic version without options
Low evaporating water temperature option
High condensing water temperature option
Units with 2-way valves for condensation control
60
Condenser inlet water temeperature [ °C]
high condensing water temperature opt
50
40
standard
low water temperature
production opt
30
20
with pressostatic valve kit
10
0
-15
-10
-5
0
5
10
15
20
25
30
Evaporator outlet fluid (water / glycol) temperature [°C]
Note 1
-10°C with 30% glycol mix
In the table the volume of ethylene glycol which is necessary according to the outlet temperature of the chilled
fluid is indicated.
Note 2
Correct operation of the microprocessor board and the user terminal is only guaranteed for temperatures
between -10°C and +65°C.
12
Release 1.3 – November 2012
BRWH - OPERATION LIMITS
The different options which influence operation are:
Basic version without options
High condensing water temperature option
Low evaporator water temperature option
70
Condenser outlet
water temeperature [ °C]
60
high condensing water temperature opt
50
standard
40
low water temperature opt
30
20
10
0
-10
-5
0
5
10
15
20
25
30
35
Evaporator inlet fluid (water / glycol) temperature [°C]
Note 1
-10°C with 30% glycol mix
In the table the volume of ethylene glycol which is necessary according to the outlet temperature of the chilled
fluid is indicated.
Note 2
Correct operation of the microprocessor board and the user terminal is only guaranteed for temperatures
between -10°C and +65°C.
Release 1.3 – November 2012
13
BRRC - OPERATION LIMITS
The different options which influence operation are:
Basic version without options
High condensing water temperature option
Low evaporator water temperature option
80
70
high condensing temperature opt
R134a condensing
temperature [ °C]
60
50
standard
low water temperature
production opt
40
30
20
10
0
-15
-10
-5
0
5
10
15
20
25
30
Evaporator outlet fluid (water / glycol) temperature [°C]
Note 1
-10°C with 30% glycol mix
In the table the volume of ethylene glycol which is necessary according to the outlet temperature of the chilled
fluid is indicated.
Note 2
Correct operation of the microprocessor board and the user terminal is only guaranteed for temperatures
between -10°C and +65°C.
14
Release 1.3 – November 2012
MAIN COMPONENTS
ELECTRIC PANEL
The panel is built to conform to the 2006/95/EEC directive and to its relevant standards.
The panel has a general door interlock switch and is housed in an appropriate compartment protected by a panel
fastened with ¼ turn screws.
The maximum internal temperature of the electrical panel is controlled by a thermostat, and is maintained
within parameters which ensure that the panel is protected by the ventilation of external air.
Furthermore, versions supplied with low ambient temperature option, include a system for controlling the
minimum internal temperature of the electrical panel by means of a self-adjusting anti-condensate electrical
heater.
Main features:
phase sequence relay, minimum voltage and asymmetrical relay
IP42 protection class (IP44 on request)
24V auxiliary circuit for the main board
230 V auxiliary circuit for compressor contactors and anti-freeze heaters (optional)
phase monitor to ensure correct screw rotation
fuse protection for each compressor against short-circuits
contactors provided for compressors;
2 voltage-free contacts for remote signalling of addressable alarms
contact for external pump group start-up
contact for control of the 4-way valve (only for BRWH)
Release 1.3 – November 2012
15
COMPRESSORS
UNITS EQUIPPED WITH SCREW COMPRESSORS
These compressors are supplied by the market's leading
manufacturers.
They are supplied with: a temperature sensor fitted in the
over-current protection windings, a non-return valve on the
delivery line both for preventing screw reverse rotation and
to allow equalisation of the pressure values inside the
compressor for pressure free starting.
Both compressors have partial heat recovery in four steps (0 – 25 – 50 – 75 – 100%), the temperature of the
discharged water, therefore, is controlled in 8 heat recovery steps.
0%
13%
25%
38%
50%
63%
75%
88%
100%
This ensures high COP values at part loads.
Furthermore, the compressor can be supplied with a slide valve with built-in economiser. This ensures greater
liquid supercooling. In addition, thanks to the modulating inlet midway along the screw, the compressor process
can be improved by eliminating the low pressure at which the compressor normally operates. This ensures that
the COP is increased also at underpressure values, since the increase in yield is much higher than the increase
in absorbed power.
Furthermore, the units can be supplied on request with continuous modulation of refrigerating power to
further improve the COP.
In this way, the refrigerator only absorbs the energy required by the system at any time, therefore
considerably cutting down electrical consumption.
To attenuate transmission of vibrations, and therefore reduce noise levels and possible faults, each compressor
is fitted on rubber anti-vibration supports.
UNIFLAIR is a highly environmentally conscious company and has designed these units for use with HFCR134a, an environmentally friendly refrigerant.
LUBRIFICATING OIL RACCOMENDED (POE): BSE 170
CONDENSER
The units are equipped with two condensing heat
exchangers, one for each refrigerant circuit.
These shell & tube exchangers feature two water-side
passages and one refrigerant-side passage.
They are made from copper tubing and built in such a way
as to ensure high efficiency for the entire life of the
exchanger: in fact, the tube is equipped with a special spiral
which stops incrustation forming.
The units can also be supplied on request with special
condensers which are suitable for operation with sea water
(Cu/Ni tubes)
16
Release 1.3 – November 2012
EVAPORATOR
The removable shell & tube evaporator features two cooling circuits and a single water circuit which
operates with a very low pressure drop and is built with high-efficiency pipes in order to guarantee oil
outflow.
It is completely covered in closed-cell expanded polyurethane to prevent the formation of condensation and
to reduce thermal dispersion.
Furthermore, this material is UV resistant.
ANTI-SEISMIC SPRING ANTIVIBRATION SUPPORTS
The anti-vibration mount line is formed of:
Spring in pre-stressed steel UNI 7900 with surface protected by cataphoric treatment
2 graphite plates: a base container and an upper plate with a M24 hole
Screw TE M24 to control the level of the machine to be insulated
Guide gaskets in anti-oil elastomer allow the upper plate to slide into the base container, so to assure sonic
insulation continuity even when there are transversal thrusts
A non-slip anti-oil elastomer bearing placed on the base enables the support to withstand friction
An anti-oil elastomer bearing to be applied on the upper plate
Release 1.3 – November 2012
17
NEOPRENE ANTIVIBRATION SUPPORTS
Vertical static load [daN]
The anti-vibration support is composed of:
Height-adjustable steel bell with levelling screw
Vulcanized steel plate with rubber base
Hardness: 70°shA
4000
3000
2000
1000
0
0
1
2
3
Deflection [mm]
18
Release 1.3 – November 2012
4
5
ACCESS TO MAIN COMPONENTS
COMPRESSORS
To reach the compressors (inside the compartment in the base of the unit), remove the guards.
With the guards removed, you have direct access to the compressors.
WARNING: HOT SURFACE, BURN HAZARD. With the guards removed, the
compressors and the cooling circuit’s delivery pipes are within reach. During the
unit’s regular operation these parts get very hot and therefore are potentially
hazardous.
WARNING: When performing maintenance, ALWAYS set the master switch IG to “0”
ELECTRICAL PANEL
For access to the electrical panel, turn the handle of master switch IG to “0”, turn the latches a ¼ turn and
lift using the grip.
This procedure enables you to open the panel which is hinged on the top of the electrical panel.
ATTENZIONE
PRIMA DI QUALSIASI INTERVENTO LEGGERE ATTENTAMENTE IL LIBRETTO DI ISTRUZIONI.
APPARECCHIO IN TENSIONE : PRIMA DI INTERVENIRE SU QUALSIASI PARTE ELETTRICA
TOGLIERE TENSIONE ALL’APPARECCHIO.
WARNING
BEFORE ANY OPERATIONS ON THIS UNIT READ THE INSTRUCTION MANUAL CAREFULLY.
THIS EQUIPMENT CONTAINS COMPONENTS AT MAINS VOLTAGE : DISCONNECT POWER
BEFORE ANY OPERATION ON ELECTRICAL COMPONENTS.
ACTHUNG
VOR ALLEN ARBEITEN AN DIESEM GERÄT IST DIE BEDIENUNGSANLEITUNG GENAU STUDIEREN.
DIESES GERÄT ENTHÄLT BUTEILE, DIE UNTER SPANNUNG STEHEN SOWIE SICH DREHENDE
VENTILATOREN: VOR ARBEITEN IM GERÄT IST DIE NETZZULEITUNG ABZUSCHALTEN.
ATTENTION
LIRE ATTENTIVEMENT LE MANUEL D’INSTRUCTIONS AVANT TUOTE INTERVENTION.
CET EQUIPEMENT UTILISE DES COMPOSANTS ÉLECTRIQUE SOUS TENSION.
COUPER L'ALIMENTATION AU DISJONCTEUR AVANT TOOTE INTERVENTION SUR
LES COMPOSANTS ELECTRIQUES.
ATENCION
ANTES DE CUALQUIER INTERVENCIÓN LEER ATENTAMENTE EL MANUAL DE INSTRUCCIONES.
APARATO BAJO TENSIÓN. ANTES DE INTERVENIR SOBRE CUALQUIER PARTE ELÈTRICA
QUITAR TENSION AL APPARATO.
WARNING: Before removing the panel, you must set the master switch IG to “0” to
prevent the compressors, reaching HIGH PRESSURE ALARM level.
Release 1.3 – November 2012
19
BRWC / H - DIMENSIONS AND WEIGHTS
BRWC/H
1402A 1602A 1802A 2002A 2202A 2502A 2802A 3202A 3602A 4202A 4802A
Dimensions
Height
mm 2060
2060
2060
2060
2060
2060
2060
2210
2210
2210
2210
Length
mm 3700
3700
3700
3700
3700
3900
3900
4130
4130
4130
4130
Width
mm
850
850
850
850
850
850
850
1400
1400
1400
1400
Width with heat recovery mm 1680
1680
1680
1680
1680
1752
1752
1660
1660
1660
1660
3,1
3,1
3,1
3,1
3,1
3,3
3,3
5,7
5,7
5,7
5,7
2
Footprint
m
Water content
Lt
263
263
248
234
234
287
287
388
473
485
455
Water content with heat
recovery
Lt
305
305
289
284
284
349
349
467
568
592
562
Basic version
Kg
2815
2865
2930
3649
3707
3797
3818
5360
5481
5638
5719
Version with heat
recovery
Kg
3425
3475
3570
4289
4385
4563
4584
6314
6435
6628
6709
Compressor housing
Kg
170
170
170
170
170
170
170
220
220
220
220
Weight
(1)
BRRC
1402A 1602A 1802A 2002A 2202A 2502A 2802A 3202A 3602A 4202A 4802A
Dimensions
Height
mm 2010
2010
2010
2010
2010
2010
2010
1870
1870
1870
1870
Length
mm 3700
3700
3700
3700
3700
3900
3900
4130
4130
4130
4130
Width
mm
850
850
850
850
850
850
850
1400
1400
1400
1400
Footprint
m
3,1
3,1
3,1
3,1
3,1
3,3
3,3
5,7
5,7
5,7
5,7
Water content
Lt
222
222
207
184
184
225
225
310
378
378
348
Basic version
Kg
2335
2385
2420
3139
3159
3191
3212
4616
4737
4858
4939
Compressor housing
Kg
170
170
170
170
170
170
170
220
220
220
220
Weight
2
(2)
(1) Data refer to a unit with refrigerant charge and empty hydraulic circuit
(2) Data refer to a unit pre-charged with refrigerant and empty hydraulic circuit
Release 1.3 – November 2012
20
TOTAL AND PARTIAL HEAT RECOVERY
B.R.W./R.
Total and partial heat recovery is achieved in the AQUAFLAIR
series by means of two shell and tube
heat exchangers. This option means heat which would otherwise be released outside by the condenser, is
used to produce hot water, typically for domestic use.
Total and partial heat recovery is achieved as illustrated in the following diagram: if hot water needs to be
produced, the water should be made to flow through the dedicated exchanger; in this way part or all of the
condensing occurs inside the heat recovery exchanger (R) rather than through the condenser (CN).
VSM
R
IN R
OUT R
C
VSA
IN CN
OUT CN
IN EV
OUT EV
CN
EV
EEV
C
Compressor
VSM
High pressure safety valve
R
Heat recovery exchanger
CN
Condenser
EEV
Electronic expansion valve
EV
Evaporator
VSA
Low pressure safety valve
IN EV
Evaporator water inlet
OUT EV
IN R
Evaporator water outlet
Heat recovery water inlet
OUT R
Heat recovery water outlet
IN CN
Condenser water inlet
OUT CN
Condenser water outlet
Release 1.3 – November 2012
21
HEAT PUMP : WATER-SIDE CYCLE INVERSION
CN
C
EEV
V
EV
UTILITY
LOAD
DISSIPATION
4-way valve
4-way valve
CUSTOMER CARE
CHILLER
AMBIENT
EXTERNAL
4-way valve
4-way valve
CUSTOMER CARE
HEAT PUMP
22
Release 1.3 – November 2012
INSTALLATION GUIDE
TRANSPORT AND MOVEMENT
The symbols on the packaging conform to the ISO7000 standard and are explained below.
SYMBOL
MEANING
SYMBOL
MEANING
FRAGILE: handle with care.
THIS SIDE UP shows
orientation of the unit.
the
PROTECT
AGAINST
MOISTURE: the packaged unit
must be stored in a dry place.
TEMPERATURE LIMITS: the unit
must not be stored outside these
limits.
CENTRE OF GRAVITY: shows
the centre of gravity of the
packaged unit.
NO HOOKS: do not use hooks to
lift the packed unit.
KEEP AWAY FROM HEAT: the
unit must be kept away from heat
sources.
DO NOT STACK.
Carry the unit as near to the installation site as possible before removing packaging.
The unit must be lifted using equipment and procedures illustrated in the drawings in the last section of this
manual.
WARNING: check the drawing attached to the unit or the installation drawings printed on the last few
pages of this manual.
Unit dimensions are given in the technical data tables and installation drawings included with the unit.
RECEIVING AND STORING THE UNIT
Each unit leaves the factory in perfect condition. Therefore please check the unit very carefully on delivery
and notify the transport company immediately and in writing of any damage.
Check that the load capacity of the floor is sufficient to support the weight of the unit.
The unit must be set on a solid, level surface. Once positioned, level the unit with the aid of a suitable spirit
level using the adjustable feet and, where necessary, shims: the gradient should not exceed 0.5 degrees
under any circumstances.
Warning: the unit must not be turned on its side or upside down.
Release 1.3 – November 2012
23
MOVEMENT
In order to allow for simple movement, the units are equipped with eyebolts for connection to the lifting straps (for
detail please see the movement diagrams shown at the end of this document).
24
Release 1.3 – November 2012
OPERATING SPACE
Do not install the unit near the sea or near sulphur springs.
If the installation location is particularly harsh, contact the Uniflair Sales Department for possible technical
solutions.
INSTALLATION TIPS
CLEARANCE
BRWC/H 1402…2802
1000 mm
In the figures below, the minimum advised distances both for correct operation of the unit and for
accessibility to the internal components for standard maintenance are shown.
Removing the tubes from inside the evaporator and a compressor is considered extra-ordinary maintenance
and, therefore, it is necessary to be able to move the unit to carry out these procedures. If this is not
possible, the distances must be:
- Evaporator : behind the evaporator 2000mm
- Compressor:
1402A-2802A models: 2500mm from the evaporator hydraulic connections opposite side
3202A-4802A models: 2500mm from the electrical board
1300 mm
1000 mm
1000 mm
600 mm
BRWC/H 3202…4802
600 mm
1500 mm
600 mm
Release 1.3 – November 2012
25
The last section of the manual features diagrams for each unit, summarizing:
Weight distribution
Plumbing and wiring
Overall dimensions
HYDRAULIC CONNECTIONS
(see also the enclosed installation drawings and hydraulic diagram)
1) CHECK that the section of the chilled water pipes and the circulation pump fitted are adequate. An
inadequate water flow significantly reduces the cooling capacity of the unit.
2) CHECK the water intake/output directions. There are labels next to the intake and output connections as
shown in the diagram below.
INLET
OUTLET
3) CONNECT the chiller using flexible tubes to stop the transmission of vibrations. Fit shut-off valves so that
the unit can be isolated from the water circuit;
4) INSULATE the chilled water pipes to stop the formation of condensation;
5) FIT temperature measuring points on the pipes near the intake and output connections;
6) INSTALL a metal filter in the section of pipe next to the unit intake to prevent pieces of welding or flakes of
rust entering the heat exchanger.
7) PROVIDE a discharge well near the output connection in case the unit needs to be emptied.
26
Release 1.3 – November 2012
WIRING
(consult wiring diagram)
Before performing any work on electrical parts, make sure they are not connected
to the power supply.
In order for accidents to be prevented and for the chiller to provide good, lasting,
unaltered service, it is that essential wiring is carried out correctly, in a professional
manner and in accordance with the regulations in force.
GENERAL INSTRUCTIONS
CONNECTION TO SUPPLY MAINS
To connect the power cables, remove the cover plate on the bottom of the unit.
IP42 insulation protection must be maintained, therefore suitable cable clamps/sheath clamps and/or
junction boxes must be used.
Cables must be connected fastening the wire terminals of the cables to the relevant holes provided
for this purpose.
It is vital that the phases are connected correctly in the position indicated on the wiring diagram
which is supplied with the unit since if they are connected in any other way, the unit will not work.
Electrical connections must be made by qualified installers.
Power leads must be protected upstream against the effects of short-circuits and current overload:
Particular attention must be made to the following:
Electrical connections must be made by qualified installers.
Power leads must be protected upstream against the effects of short-circuits and current overload.
DESCRIPTION OF PROCEDURE
1) OPEN the door of the master electrical panel which is located on the front of the unit above the
compressor compartment;
2) MAKE SURE that the mains voltage matches the voltage given on the data plate of the unit (voltage,
number and frequency of the phases)
3) INTRODUCE the feeding cable through the flange indicated in the position in the diagram.
Remove the flange which is placed low on the left of unit, and make the necessary entry holes (this must be
done in such a way as to fix the cable to the upright of the unit until it reaches the electrical panel).
There is an extractable flange on the left of the base of the electrical panel and two holes on the right hand
side to allow the power supply and signal cables to enter.
a. for the power supply cables, which will be connected to the terminals on the IG general switch on the
central hand side of the electrical panel, it is necessary to unscrew the flange and make two holes
where needed.
b. for the s ignal cables, which will be connected to the terminals on the microprocessor board on
the right hand side of the electrical panel, only the plugs on the holes which have already been
made need to be removed.
The power supply lead is not supplied by UNIFLAIR S.p.A and the installer must choose an appropriately
sized cable.
The power lead’s cross-section must be chosen based on the length of the lead, how it is to be laid, the
chiller's maximum current demand, and in such a way that an excessive drop in voltage is avoided (the
supply voltage must be within ± 10% of the rated value).
The power supply connection must be supported by the entry flange provided for this purpose.
Release 1.3 – November 2012
27
Models 1402…2802
Inlet electrical
cables
Models 3202…4802
Inlet electrical
cables
28
Release 1.3 – November 2012
CONNECTION TO REMOTE CONDENSER
REFRIGERANT PIPING
For condenserless units with remote air-cooled or evaporating condensers, the units are supplied with a
nitrogen pre-charge.
Therefore, it is important that the unit is kept tightly closed until the remote condenser is installed and
connected to the unit.
It is the installer / contractor’s responsibility to:
size and install the system
test the piping, as well as the entire system, for leaks
evacuate the system
load the refrigerant charge
Piping
The sizing and installing of the refrigerant piping to and from the condenserless unit should be carried out
according to the procedure stated in the latest ASHRAE Handbook (see the suggested sizing in the next table).
The brazed discharge and liquid line must be carried out with all the necessary cleaning precautions
It is important that the piping has sound and vibration isolation between the tubing and the support. Moreover,
the discharge lines should be looped near the condenser and trapped near the compressor in order to prevent
refrigerant and oil draining into the compressors from the condenser.
Looping the discharge line also provides greater line flexibility.
After the equipment has been properly installed, leak tested, and evacuated, it can be charged with R134a
refrigerant and switched on.
The charge needs to be added until the liquid line sight glass is clear, with no bubbles flowing to the expansion
valve. The total operating charge will depend on the type of air-cooled condenser used and volume of the
refrigerant piping.
The discharge lines must be designed to handle oil correctly and to protect the compressor from damage caused
by liquid in the refrigerant line after the unit has been switched-off.
50 kPA should be considered the correct value for the discharge line pressure drop.
Careful consideration must be made when sizing each section of piping so that the gas is able to carry the oil in
all operating conditions.
If the gas velocity in the vertical discharge risers is too low (particularly at partial loads), a considerable amount
of oil can collect in the riser and in the horizontal headers, causing the compressor to lose its oil and
consequently being damaged by a lack of lubrication.
When the compressor load is increased, the oil collected during partial loads can be carried as a slug through the
system and back to the compressor, where a sudden increase of oil concentration may cause liquid slugging and
damage to the compressor.
Each horizontal discharge pipe should have an incline of approximately 10mm. This is necessary to move any
oil lying in the header by means of gravity. Pockets of oil must be avoided because this could prevent the
compressor receiving the correct lubrication.
Each line connecting to a horizontal discharge header should rise above its centreline. This is necessary to
prevent oil draining into the compressor when it is switched off.
Release 1.3 – November 2012
29
The addition of oil must be the same as used in the compressor (refer to page 17)
It is important that the liquid reaches the expansion valve without flash gas, since this gas will reduce the
capacity of the valve. Since “flashing” can be caused by a pressure drop in the liquid line, pressure losses due to
friction and changes in the static head should be kept to a minimum.
A check valve must be installed in the liquid line in all applications where the external temperature could drop
below the room temperature.
This prevents liquid flowing into the condenser and helps maintain a supply of refrigerant in the liquid line for
initial start-up.
Moreover, a relief valve must be used in the liquid line to relieve potentially dangerous pressures which could be
created when the cool liquid refrigerant in the line between the check valve and the expansion or shut-off
valve warms up.
Relief devices for discharge piping are installed in the factory as standard equipment.
30
Release 1.3 – November 2012
RECOMMENDED REFRIGERANT PIPE SIZE
Horizontal or Downflow Discharge Line Size
Equivalent length up to mt.
Model
1402A
1602A
1802A
2002A
2202A
2502A
2802A
3202A
3602A
4202A
4802A
25
Equivalent length up to mt.
50
Connection size
Diameter
Velocity
Pressure drop
Diameter
Velocity
Pressure drop
mm
42
42
42
54
54
54
54
67
67
67
67
mm
42
42
42
54
54
54
54
67
67
67
67
m/s
14,5
17,2
19,2
12,3
14,4
16,4
18,7
13,7
15,9
17,7
20,2
°C
1,2
1,6
1,9
0,7
0,9
1,1
1,3
0,6
0,8
0,9
1,1
mm
42
42
42
54
54
54
54
67
67
67
67
m/s
14,5
17,2
19,2
12,3
14,4
16,4
18,7
13,7
15,9
17,7
20,2
°C
2,2
3,0
3,6
1,3
1,6
2,0
2,5
1,2
1,5
1,7
2,2
Vertical Upflow Discharge Line Size
Equivalent length up to mt.
Model
1402A
1602A
1802A
2002A
2202A
2502A
2802A
3202A
3602A
4202A
4802A
15
Equivalent length up to mt.
30
Connection size
Diameter
Velocity
Pressure drop
Diameter
Velocity
Pressure drop
mm
42
42
42
54
54
54
54
67
67
67
67
mm
35,00
42,00
42,00
42,00
42,00
42,00
54,00
54,00
54,00
67,00
67,00
m/s
21,6
17,2
19,2
21,0
24,6
28,0
18,7
21,5
25,0
17,7
20,2
°C
1,8
1,0
1,2
1,3
1,7
2,1
0,8
1,0
1,3
0,6
0,7
mm
35
42
42
42
42
54
54
54
54
67
67
m/s
21,6
17,2
19,2
21,0
24,6
16,4
18,7
21,5
25,0
17,7
20,2
°C
3,4
1,8
2,2
2,6
3,3
1,2
1,5
1,9
2,5
1,1
1,3
Liquid Line Size
Equivalent length up to mt
Model
1402A
1602A
1802A
2002A
2202A
2502A
2802A
3202A
3602A
4202A
4802A
25
Equivalent length up to mt
50
Connection size
Diameter
Velocity
Pressure drop
Diameter
Velocity
Pressure drop
mm
28
28
28
35
35
35
35
42
42
42
42
mm
28
28
28
35
35
35
35
42
42
42
42
m/s
1,9
2,3
2,5
1,7
2,0
2,3
2,6
2,2
2,5
2,8
3,2
°C
0,9
1,2
1,4
0,6
0,7
0,9
1,1
0,7
0,9
1,0
1,3
mm
28
28
28
35
35
35
35
42
42
42
42
m/s
1,9
2,3
2,5
1,7
2,0
2,3
2,6
2,2
2,5
2,8
3,2
°C
1,9
2,5
3,0
1,2
1,6
2,0
2,4
1,5
1,9
2,2
2,8
Release 1.3 – November 2012
31
PIPING DIAGRAM TO REMOTE CONDENSER
(for each circuit)
Liquid receiver
The receiver is used when a refrigerant storage capacity is required.
It is recommended that the receiver is installed when the remote condenser is further than 25 meters from the
internal unit.
The receiver must be installed near the BRRC unit or it may also be installed near the remote condenser if it has
a subcoling circuit.
Condenser pressure control
Since the internal BRRC unit control is not able to manage to remote air-cooled condenser fans, each remote
condenser must have its own fan speed controller based on the condensing temperature (suggested set-point
50°C).
The pressure differential between the suction and discharge compressor must be guaranteed and the
compressor must enter its field of operation within 20 seconds; to do this, the remote condenser must
be able to work in all environmental conditions with, ultimately, a pressure difference of 6.4 bar.
The figures below show a typical piping arrangement involving a remote air-cooled condenser.
Please note that the hot gas line is looped at the top and bottom of the vertical line. This is in order to prevent oil
and liquid flowing back into the compressor.
The highest point in the discharge line should always be above the highest point in the condenser coil.
It is necessary to install at the highest point a purge valve.
Receiver near the internal unit
32
Release 1.3 – November 2012
Receiver near the external unit
Release 1.3 – November 2012
33
TECHNICAL DATA
BRWC/H
1402A 1602A 1802A 2002A 2202A 2502A 2802A 3202A 3602A 4202A 4802A
Power supply
400V / 3ph / 50Hz
No.circuits / No. compressors
2/2
Compressor type
Double screw semi-hermetic
No. / type evaporator / No.
refrigerant circuit
1 / shell&tube / 2 refrigerant circuits
No. / type condenser / No.
water steps
2 / shell&tube / 2 water-side steps
Evaporator hydraulic
connections (victaulic)
8’’
8’’
8’’
8’’
8’’
8’’
8’’
8’’
8’’
8’’
8’’
Condenser hydraulic
connections (BSP)
2’’
2 ½’’
2 ½’’
2 ½’’
2 ½’’
3’’
3’’
3’’
3’’
3’’
3’’
Heat recovery hydraulic
connections (BSP)
2’’
2 ½’’
2 ½’’
2 ½’’
2 ½’’
3’’
3’’
3’’
3’’
3’’
3’’
BRRC
1402A 1602A 1802A 2002A 2202A 2502A 2802A 3202A 3602A 4202A 4802A
Power supply
400V / 3ph / 50Hz
No.circuits / No. compressors
2/2
Compressor type
Double screw semi-hermetic
No. / type evaporator / No.
refrigerant circuit
1 / shell&tube / 2 refrigerant circuits
Evaporator hydraulic
connections (victaulic)
8’’
8’’
8’’
8’’
8’’
8’’
8’’
8’’
8’’
8’’
8’’
Gas refrigerant connections to
remote condenser (Do mm)
42
42
42
54
54
54
54
67
67
67
67
Liquid refrigerant connections
from remote condenser (Do
mm)
28
28
28
35
35
35
35
42
42
42
42
Heat recovery hydraulic
connections (BSP)
2’’
2 ½’’
2 ½’’
2 ½’’
2 ½’’
3’’
3’’
3’’
3’’
3’’
3’’
34
Release 1.3 – November 2012
TECHNICAL DATA
BRWC
Cooling only series
1402A 1602A 1802A 2002A 2202A 2502A 2802A 3202A 3602A 4202A 4802A
Cooling capacity
(1)
kW
330
389
430
Absorbed power
(1)
kW 71,8
82,2
96,9 100,2 116,6 131,5
146
172,8 196,3 225,9 249,0
476
544
631
712
830
954
1072 1204
EER
(1)
4,61
4,73
4,44
4,75
4,67
4,80
4,87
4,80
4,86
4,75
4,84
IPLV
(3)
5,10
5,52
5,00
5,52
5,88
5,50
5,68
5,63
6,03
5,50
5,63
4,78
5,11
4,67
5,11
5,35
5,08
5,26
5,15
5,45
5,03
5,20
ESEER
(4)
Evaporator water flow
(1)
l/h 56934 67083 74148 82070 93769 108756 122736 143064 164405 184756 207477
Evaporator pressure drop
(1)
Condenser thermal
(1)
capacity
Condenser water flow
(1)
33
45
47
33
42
46
57
kW
402
472
527
577
661
763
859
46
47
54
50
1003 1151 1298 1453
l/h 69718 81746 91396 99940 114544 132215 148825 173891 199424 225039 251899
Condenser pressure drop
(1)
Heat recovery Heating
(2)
capacity
Heat recovery water flow
kPa
(2)
Heat recovery pressure drop
(2)
kPa
59
79
96
74
94
93
115
87
kW
377
440
494
540
627
715
806
938
77
79
97
1091 1216 1368
l/h 65638 76586 85874 93989 108995 124308 140216 163196 189661 211511 237920
kPa
51
67
83
63
83
80
100
75
67
68
84
(1) Data refer to nominal conditions: Evaporator Inlet / outlet water temperature: 12/7°C; Condenser In/Out water temperature: 30/35C; condenser
fouling factor: 0,000043m2°C/W; evaporator fouling factor: 0,000043m2°C/W; Refrigerant R134a
(2) Data refer to nominal conditions: Evaporator Inlet / outlet water temperature: 12/7°C; Condenser Inlet / outlet water temperature: 40/45C;
condenser fouling factor: 0,000043m2°C/W; evaporator fouling factor: 0,000043m2°C/W; Refrigerant R134a
(3) Integrated Partial Load Value: based on ARI conditions
(4) European Seasonal Energy Efficiency Ratio
Release 1.3 – November 2012
35
TECHNICAL DATA
BRWH
Heat pump series
1402A 1602A 1802A 2002A 2202A 2502A 2802A 3202A 3602A 4202A 4802A
Heating capacity
(1)
kW
377
440
494
541
627
715
806
938
1091 1216 1368
Cooling capacity
(1)
kW
292
342
379
421
484
559
630
732
850
Absorbed power
(1)
kW 85,6
COP
(1)
Evaporator water flow
4,41
(1)
(1)
(1)
98,2 114,6 119,6 143,1 156,0 176,3 206,1 240,5 268,1 300,6
4,49
4,31
4,52
4,38
4,58
4,57
4,55
4,54
4,54
4,55
kPa
27
36
37
27
34
37
46
37
38
43
40
l/h 65638 76586 85874 93989 108995 124308 140216 163196 189661 211511 237920
Condenser pressure drop
(1)
Heat recovery Heating
(2)
capacity
Heat recovery water flow
1068
l/h 50285 58965 65337 72520 83326 96279 108541 126164 146467 163364 183915
Evaporator pressure drop
Condenser water flow
948
(2)
Heat recovery pressure drop
(2)
kPa
51
67
83
63
83
80
100
75
kW
377
440
494
540
627
715
806
938
67
68
84
1091 1216 1368
l/h 65638 76586 85874 93989 108995 124308 140216 163196 189661 211511 237920
kPa
51
67
83
63
83
80
100
75
67
68
84
(1) Data refer to nominal conditions: Evaporator Inlet / outlet water temperature: 12/7°C; Condenser Inlet / outlet water temperature: 40/45C;
condenser fouling factor: : 0,000043m2°C/W; evaporator fouling factor: 0,000043m2°C/W; Refrigerant R134a
(2) Data refer to nominal conditions: Evaporator Inlet / outlet water temperature: 12/7°C; Condenser Inlet / outlet water temperature: 40/45C;
condenser fouling factor: : 0,000043m2°C/W; evaporator fouling factor: 0,000043m2°C/W; Refrigerant R134a
(3) Integrated Partial Load Value: based on ARI conditions
(4) European Seasonal Energy Efficiency Ratio
36
Release 1.3 – November 2012
TECHNICAL DATA
BRRC
Condenserless series
1402A 1602A 1802A 2002A 2202A 2502A 2802A 3202A 3602A 4202A 4802A
Cooling capacity
(1)
kW
Absorbed power
(1)
kW 88,7 100,3 115,5 122,2 143,9 159,0 176,3 208,3 244,0 272,0 299,8
EER
(1)
Evaporator water flow
284
3,21
(1)
336
3,36
377
3,26
414
3,39
482
3,35
551
3,46
630
3,57
726
3,49
842
3,45
938
3,45
1069
3,57
l/h 49005 57968 64945 71298 83040 94859 108513 125163 145118 161555 184236
Evaporator pressure drop
(1)
kPa
26
35
37
26
34
36
46
36
Condenser thermal capacity
(1)
kW
373
436
492
536
626
710
806
935
38
42
40
1086 1210 1369
(1) Data refer to nominal conditions: Evaporator Inlet / outlet water temperature: 12/7°C; Condensing temperature:50 °C; evaporator fouling factor:
0,000043m2°C/W; Refrigerant R134a
Release 1.3 – November 2012
37
ELETTRICAL DATA
BRWC
Cooling only series
Compressor circuit 1
Compressor circuit 2
OP
OA
FLI
FLA
LRA
ST
OP
OA
FLI
FLA
LRA
ST
1402A
35,9
64,2
61,0
124,0
290
PW
35,9
64,2
61,0
124,0
290
PW
1602A
41,1
73,0
66,2
144,0
350
PW
41,1
73,0
66,2
144,0
350
PW
1802A
48,5
81,6
79,0
162,0
423
PW
48,5
81,6
79,0
162,0
423
PW
2002A
50,1
83,2
80,8
155,0
439
PW
50,1
83,2
80,8
155,0
439
PW
2202A
58,3
101,9
96,8
182,0
520
PW
58,3
101,9
96,8
182,0
520
PW
2502A
65,8
116,2
107,2
196,0
612
PW
65,8
116,2
107,2
196,0
612
PW
2802A
73,1
128,3
124,1
214,0
665
PW
73,1
128,3
124,1
214,0
665
PW
3202A
86,4
145,4
139,5
280,0
436
Y/D
86,4
145,4
139,5
280,0
436
Y/D
3602A
98,1
161,2
161,9
310,0
465
Y/D
98,1
161,2
161,9
310,0
465
Y/D
4202A
113,0
193,1
182,5
320,0
586
Y/D
113,0
193,1
182,5
320,0
586
Y/D
4802A
124,5
210,4
209,3
360,0
650
Y/D
124,5
210,4
209,3
360,0
650
Y/D
Complete unit
OP
OA
SC
FLI
FLA
LRA
Cosphi
Cosphi-rif
1402A
71,8
128,5
290
121,9
256
360
0,81
0,91
1602A
82,2
146,1
350
132,3
296
430
0,82
0,91
1802A
96,9
163,2
423
157,9
332
512
0,86
0,93
2002A
100,2
166,3
439
161,6
318
525
0,87
0,94
2202A
116,6
203,7
520
193,7
372
619
0,83
0,92
2502A
131,5
232,4
612
214,5
400
718
0,82
0,93
2802A
146
256,6
665
248,1
436
777
0,82
0,92
3202A
172,8
290,8
436
279,0
568
584
0,86
0,92
3602A
196,3
322,3
465
323,8
628
628
0,88
0,92
4202A
225,9
386,2
586
364,9
648
754
0,85
0,91
4802A
249,0
420,7
650
418,5
728
838
0,85
0,91
38
Release 1.3 – November 2012
ELETTRICAL DATA
BRWH
Heat pump series
Compressor circuit 1
Compressor circuit 2
OP
OA
FLI
FLA
LRA
ST
OP
OA
FLI
FLA
LRA
ST
1402A
42,8
74,1
61,0
124,0
290
PW
42,8
74,1
61,0
124,0
290
PW
1602A
49,1
84,3
66,2
144,0
350
PW
49,1
84,3
66,2
144,0
350
PW
1802A
57,3
94,8
79,0
162,0
423
PW
57,3
94,8
79,0
162,0
423
PW
2002A
59,8
97,7
80,8
155,0
439
PW
59,8
97,7
80,8
155,0
439
PW
2202A
71,6
120,9
96,8
182,0
520
PW
71,6
120,9
96,8
182,0
520
PW
2502A
78,0
133,5
107,2
196,0
612
PW
78,0
133,5
107,2
196,0
612
PW
2802A
88,15
150,1
124,1
214,0
665
PW
88,15
150,1
124,1
214,0
665
PW
3202A
103,1
170,3
139,5
280,0
436
Y/D
103,1
170,3
139,5
280,0
436
Y/D
3602A
120,2
194,2
161,9
310,0
465
Y/D
120,2
194,2
161,9
310,0
465
Y/D
4202A
134,0
223,6
182,5
320,0
586
Y/D
134,0
223,6
182,5
320,0
586
Y/D
4802A
150,3
248,7
209,3
360,0
650
Y/D
150,3
248,7
209,3
360,0
650
Y/D
Complete unit
OP
OA
SC
FLI
FLA
LRA
Cosphi
Cosphi-rif
1402A
85,6
148,2
290
121,9
256
360
0,85
0,93
1602A
98,2
168,6
350
132,3
296
430
0,85
0,92
1802A
114,6
189,5
423
157,9
332
512
0,88
0,94
2002A
119,6
195,3
439
161,6
318
525
0,89
0,94
2202A
143,1
241,8
520
193,7
372
619
0,86
0,93
2502A
156,0
267,0
612
214,5
400
718
0,85
0,94
2802A
176,3
300,1
665
248,1
436
777
0,85
0,93
3202A
206,1
340,5
436
279,0
568
584
0,88
0,93
3602A
240,5
388,4
465
323,8
628
628
0.89
0,93
4202A
268,1
447,3
586
364,9
648
754
0,87
0,92
4802A
300,6
497,4
650
418,5
728
838
0,87
0,92
Release 1.3 – November 2012
39
ELETTRICAL DATA
BRRC
Condenserless series
Compressor circuit 1
Compressor circuit 2
OP
OA
FLI
FLA
LRA
ST
OP
OA
FLI
FLA
LRA
ST
1402A
44,4
76,3
61,0
124,0
290
PW
44,4
76,3
61,0
124,0
290
PW
1602A
50,1
85,8
66,2
144,0
350
PW
50,1
85,8
66,2
144,0
350
PW
1802A
57,7
95,4
79,0
162,0
423
PW
57,7
95,4
79,0
162,0
423
PW
2002A
61,1
99,7
80,8
155,0
439
PW
61,1
99,7
80,8
155,0
439
PW
2202A
71,95
121,5
96,8
182,0
520
PW
71,95
121,5
96,8
182,0
520
PW
2502A
79,5
135,7
107,2
196,0
612
PW
79,5
135,7
107,2
196,0
612
PW
2802A
88,2
150,1
124,1
214,0
665
PW
88,2
150,1
124,1
214,0
665
PW
3202A
104,2
171,9
139,5
280,0
436
Y/D
104,2
171,9
139,5
280,0
436
Y/D
3602A
122,0
196,9
161,9
310,0
465
Y/D
122,0
196,9
161,9
310,0
465
Y/D
4202A
136,0
226,6
182,5
320,0
586
Y/D
136,0
226,6
182,5
320,0
586
Y/D
4802A
149,9
248,1
209,3
360,0
650
Y/D
149,9
248,1
209,3
360,0
650
Y/D
Complete unit
OP
OA
SC
FLI
FLA
LRA
Cosphi
Cosphi-rif
1402A
88,8
152,5
290
121,9
256
360
0,85
0,93
1602A
100,3
171,6
350
132,3
296
430
0,85
0,92
1802A
115,5
190,8
423
157,9
332
512
0,88
0,94
2002A
122,2
199,3
439
161,6
318
525
0,89
0,94
2202A
143,9
243,0
520
193,7
372
619
0,86
0,93
2502A
159,0
271,4
612
214,5
400
718
0,85
0,94
2802A
176,4
300,21
665
248,1
436
777
0,85
0,93
3202A
208,3
343,7
436
279,0
568
584
0,88
0,93
3602A
244,0
393,8
465
323,8
628
628
0.89
0,93
4202A
272,0
453,1
586
364,9
648
754
0,87
0,92
4802A
299,8
496,2
650
418,5
728
838
0,87
0,92
40
Release 1.3 – November 2012
NOISE LEVEL - Basic version
The SOUND PRESSURE levels (measured with BRÜEL & KJǼR class 1 sound-level meter mod. 2260) for
each octave band frequency are measured with units working at full load, free-field conditions with Q=2, 1m
away from the unit according to ISO3744-3746
SOUND POWER level for each octave band frequency supplied in compliance with standard ISO3744ISO3746.
The tolerance on the data is equivalent to +/- 1.5 dB.
Note: the data supplied refers to units working based on factory settings
NOISE PRESSURE LEVEL
Model
63Hz
125Hz
250Hz
500Hz
1000Hz
2000Hz
4000Hz
8000Hz
Lp
[dB(A)]
1402A
24,6
38,7
60,9
65,6
70,5
67,0
60,3
48,5
73,5
1602A
25,4
38,4
59,8
67,1
71,1
65,7
58,9
47,9
73,7
1802A
26,8
47,6
60,4
66,6
70,7
67,7
56,6
43,8
73,8
2002A
33,4
37,6
53,8
75,6
73,5
65,5
53,7
41,8
78,0
2202A
23,1
34,4
61,3
75,7
76,3
68,9
56,1
43,1
79,5
2502A
32,8
37,9
62,0
71,3
78,1
71,2
57,7
44,1
79,7
2802A
37,1
38,6
71,5
72,8
76,9
69,2
53,4
39,7
79,6
3202A
29,3
52,8
66,5
69,5
75,1
67,5
62,1
47,9
77,3
3602A
22,3
47,1
68,6
68,9
71,3
66,6
58,5
47,0
75,3
4202A
27,4
44,6
72,0
71,8
67,3
68,4
48,8
35,2
76,3
4802A
28,3
48,6
72,2
72,7
73,6
70,5
51,7
40,3
78,4
NOISE POWER LEVEL
Model
63Hz
125Hz
250Hz
500Hz
1000Hz
2000Hz
4000Hz
8000Hz
Lw
[dB(A)]
1402A
43,0
57,1
79,3
84,0
88,9
85,4
78,7
66,9
91,9
1602A
43,8
56,8
78,2
85,5
89,5
84,1
77,3
66,3
92,1
1802A
45,2
66,0
78,8
85,0
89,1
86,1
75,1
62,2
92,2
2002A
51,8
56,0
72,2
94,0
91,9
83,9
72,1
60,2
96,4
2202A
41,5
52,8
79,7
94,1
94,7
87,3
74,5
61,5
97,9
2502A
51,4
56,5
80,6
89,9
96,6
89,8
76,2
62,7
98,3
2802A
55,7
57,1
90,1
91,4
95,5
87,7
72,0
58,3
98,2
3202A
48,5
72,1
85,7
88,8
94,4
86,8
81,3
67,2
96,5
3602A
41,5
66,4
87,8
88,2
90,6
85,8
77,8
66,3
94,6
4202A
46,6
63,8
91,2
91,0
86,5
87,6
68,0
54,4
95,6
4802A
47,6
67,9
91,4
91,9
92,8
89,8
71,0
59,6
97,7
Release 1.3 – November 2012
41
NOISE LEVEL - Low noise version
The SOUND PRESSURE levels (measured with BRÜEL & KJǼR class 1 sound-level meter mod. 2260) for
each octave band frequency are measured with units working at full load, free-field conditions with Q=2, 1m
away from the unit according ISO3744-ISO3746.
SOUND POWER level for each octave band frequency supplied in compliance with standard ISO3744ISO3746.
The tolerance on the data is equivalent to +/- 1.5 dB.
Note: the data supplied refers to units working based on factory settings.
NOISE PRESSURE LEVEL
Modello Model
63Hz
125Hz
250Hz
500Hz
1000Hz
2000Hz
4000Hz
8000Hz
Lp
[dB(A)]
1402A
20,6
34,7
54,2
57,0
61,2
55,3
50,3
38,5
64,0
1602A
44,6
47,5
58,7
58,6
58,8
49,9
44,8
36,0
63,9
1802A
46,0
56,7
59,3
58,1
58,3
51,8
42,6
31,9
64,6
2002A
52,6
46,7
52,7
67,1
61,2
49,6
39,7
29,9
68,5
2202A
42,3
43,5
60,2
67,2
63,9
53,0
42,1
31,2
69,6
2502A
52,0
47,0
60,9
62,8
65,7
55,3
43,6
32,2
68,7
2802A
56,3
47,6
70,5
64,3
64,6
53,3
39,4
27,8
72,4
3202A
45,1
61,9
65,4
61,0
62,8
51,7
48,1
36,0
69,3
3602A
38,1
56,2
67,5
60,5
59,0
50,7
44,5
35,1
69,1
4202A
43,2
53,6
70,9
63,3
54,9
52,5
34,7
23,2
71,8
4802A
47,5
57,7
71,1
64,2
61,2
54,6
37,7
28,4
72,5
NOISE POWER LEVEL
Modello Model
63Hz
125Hz
250Hz
500Hz
1000Hz
2000Hz
4000Hz
8000Hz
Lw
[dB(A)]
1402A
39,0
53,1
72,6
75,4
79,6
73,7
68,7
56,9
82,5
1602A
63,0
65,9
77,1
77,0
77,2
68,3
63,2
54,4
82,3
1802A
64,4
75,1
77,7
76,5
76,7
70,2
61,0
50,3
83,0
2002A
71,0
65,1
71,1
85,5
79,6
68,0
58,1
48,3
86,9
2202A
60,7
61,9
78,6
85,6
82,3
71,4
60,5
49,6
88,0
2502A
70,6
65,6
79,5
81,4
84,3
73,9
62,2
50,8
87,3
2802A
74,9
66,2
89,0
82,9
83,2
71,9
58,0
46,4
91,0
3202A
64,4
81,2
84,7
80,3
82,0
70,9
67,3
55,2
88,5
3602A
57,4
75,5
86,7
79,7
78,2
70,0
63,8
54,4
88,3
4202A
62,5
72,9
90,1
82,5
74,2
71,7
54,0
42,5
91,0
4802A
66,8
76,9
90,3
83,4
80,5
73,9
57,0
47,7
91,7
42
Release 1.3 – November 2012
EVAPORATOR PRESSURE DROP (water side)
Note: Data refers to 0% glycol
BRWC
480
2
420
2
180
2
220
2
160
2
140
2
100
250
2
320
2
360
2
Evaporator pressure drop
1402
1602
1802
Pressure Drop kpa
2202
2502
2802
3202
3602
4202
4802
10
10
100
1000
Flow m3/h
Pressure drop correction factor
Fluid Temp.
[°C]
- 10
-5
0
5
10
% Ethylene Glycol
0
10
20
30
40
50
1
1
1
1
1
1,09
1,08
1,07
1,06
1,05
1,21
1,19
1,16
1,13
1,10
1,34
1,30
1,25
1,20
1,14
1,46
1,41
1,35
1,27
1,17
1,58
1,52
1,44
1,34
1,21
Release 1.3 – November 2012
43
CONDENSER PRESSURE DROP (water side)
Note: Data refers to 0% glycol
BRWC
condenser pressure drop
4202
3602
4802
2802
3202
2502
2202
1602
1402
1802
100
1402
1602
pressure drop kpa
1802
2002
2202
2502
2802
3202
3602
4202
4802
10
10
100
1000
flow m3/h
Pressure drop correction factor
Fluid Temp.
[°C]
- 10
-5
0
5
10
44
% Ethylene Glycol
0
10
20
30
40
50
1
1
1
1
1
1,09
1,08
1,07
1,06
1,05
1,21
1,19
1,16
1,13
1,10
1,34
1,30
1,25
1,20
1,14
1,46
1,41
1,35
1,27
1,17
1,58
1,52
1,44
1,34
1,21
Release 1.3 – November 2012
Release 1.3 – November 2012
45
46
Release 1.3 – November 2012
Release 1.3 – November 2012
47
48
Release 1.3 – November 2012
Release 1.3 – November 2012
49
50
Release 1.3 – November 2012
Release 1.3 – November 2012
51
52
Release 1.3 – November 2012
Release 1.3 – November 2012
53
54
Release 1.3 – November 2012
Release 1.3 – November 2012
55
56
Release 1.3 – November 2012
Release 1.3 – November 2012
57
THIS PAGE HAS INTENTIONALLY BEEN LEFT BLANK
58
Release 1.3 – November 2012
Release 1.3 – November 2012
59
Uniflair SpA
Viale della Tecnica, 2
35026 Conselve (Pd) Italy
Tel. +39 049 5388211
Fax +39 049 5388212
info@uniflair.com
uniflair.com
Sede legale ed amministrativa
Registered office &
Administrative Headquarters:
Viale della Tecnica 2,
35026 Conselve (PD) Italy
P.IVA 02160760282
C.C.I.A.A. di PD
R.E.A. 212586 del 21/04/1988
R.I.N. 02160760282
M. PD004505
Cap. Soc. 19.550.000 i.v.
Owned and directed by Schneider Electric SA
Diretta e coordinata da Schneider Electric SA
Manual code @ digit: 06MM130@00B0130
NOVEMBER 2012
Download