SPECIFICATION – TECHNICAL TEMPERATURE CONTROL

advertisement
CONTRACT
SPECIFICATION – TECHNICAL
TEMPERATURE CONTROL WATER SUPPLY VALVES
MAINTENANCE TYPE:
STATUTORY
1.0
SCOPE OF SERVICES
The Contractor shall provide the maintenance Services for Temperature Control Water Supply Valves
such as thermostatic mixing valves, tempering valves, temperature/pressure relief valves and
expansion control valves covered by this Contract. The Services shall be carried out at the intervals
stated below unless otherwise stated in the Equipment and Pricing Schedule.
2.0
MINIMUM STANDARD
The minimum standards for periodic inspection and servicing shall be as stated below and in
accordance with the requirements of the current editions of:
•
Queensland Building Act
•
Building Code of Australia
•
AS/NZS 3666.2
Air-handling and water systems of buildings - Microbial control - Operation and
maintenance
•
AS/NZS 3500.4
Plumbing and drainage - Heated water services
•
AS 4032.3
Water supply - Valves for the control of heated water supply temperatures Requirements for field-testing, maintenance or replacement of thermostatic
mixing valves, tempering valves and end-of-line temperature control devices
3.0
MINIMUM QUALIFICATIONS
The Contractor shall ensure that it has the appropriate licences issued by the Queensland Building
Services Authority to perform the Services under the Contract and must provide evidence to the
satisfaction of the Principal.
The Contractor is to ensure that only licensed plumbers holding a current Thermostatic Mixing Valve
endorsement issued by the Plumbing Industry Council perform the testing and maintenance of
Thermostatic Mixing Valves.
4.0
GENERAL
4.1
Before Commencement of Work
The Owner, occupier or facility manager shall be notified that the water service will be affected and
that delivery temperature may vary during the test procedures. Special arrangements may have to be
made so that interruptions to service will not create a hardship and danger to the user (e.g. patient
care areas).
4.2
Replacement Components
Only replacement components, supplied or approved by the manufacturer of the device, shall be used
for repair.
Use only tools, spare parts, lubricants or materials, maintenance/service procedures which are
recommended in the valve manufacturer's/supplier's published service instructions or as appropriate to
the particular task. Materials in contact with potable water shall comply with AS 4020.
4.3
Commissioning
After repairs or replacements have been completed, the device shall be commissioned in accordance
with the manufacturer’s instructions.
Document: TSW00138
Date Issued:
©The State of Queensland (Department of Housing and Public Works)
Page 1 of 4
CONTRACT
4.4
Allowable Ranges
The allowable ranges in warm water temperature measured at each outlet fixture as required are as
follows:
a) Patient care areas in health buildings:
ALLOWABLE
TEMPERATURE RANGE
FOR WARM WATER
MAXIMUM POSSIBLE PEAK
TEMPERATURE DURING 'FAIL SAFE'
TEST (Hot Water Safety Shut Off)
Adults
40.5 – 43.5 °C
46.0 °C
Children
38.0 – 40.5 °C
43.0 °C
Neonatal (Babies)
35.0 – 38.0 °C
39.0 °C
CLASSIFICATION
(ref: Code of Practice for Thermostatic Mixing Valves in Health Care Facilities, HOSPLAN, 1990)
b) All other areas:
AREA
MAXIMUM DELIVERY
TEMPERATURE
Early childhood centres, primary and secondary schools or similar
facilities for young, aged, sick, or people with disabilities.
45°C
All other buildings
50°C
Consultation with the nominated officer in charge of the site about the classification of the premises is
desirable which can be cross-checked with the above.
4.5
Maintenance Records
Service details for each valve are to be entered onto the Service Report.
4.6
Service Label
Provide a metal tag attached to the valve showing name and telephone number of the Service
Company and date of the next service.
The Contractor will stamp the tag to indicate the month and year of Service.
The tag shall be made of a suitable metal and shall be not less than 0.3 mm thick; plastics shall not be
used.
The size and content of the tag shall be as per example below.
Minimum requirement for maintenance record tag
When ordering maintenance record tags, the year on the main body of the tag shall commence with
the previous year, capturing the record of the previous year's service history.
Document: TSW00138
Date Issued:
©The State of Queensland (Department of Housing and Public Works)
Page 2 of 4
CONTRACT
5.0
MAINTENANCE SERVICE AND FREQUENCY
The following actions are required concerning the under listed situations:
(a) Unsafe operation of mixing valves (risk to occupants). Consult promptly with the Principal’s
Representative regarding correcting the deficiency. Record details in the Service Report.
(b) Servicing of non-approved mixing valves. Consult promptly with Principal’s Representative
regarding replacement with a mixing valve that is authorised for use in the particular application.
Record details in the Service Report.
(c) Deficiencies in hot and cold water supply systems or water heaters. Consult promptly with
Principal’s Representative regarding correcting the deficiency. Record details in the Service
Report.
Perform all of the service requirements as detailed under:
5.1
Thermostatic Mixing Valve
5.2
1
Check and clean strainer.
2
Check non-return valve operation (integral or independently fitted).
3
Check condition of o-rings and seals.
4
Check condition of element.
5
Record temperatures of hot and cold water supply to valve.
6
Record discharge temperature measured at the nearest outlet to the valve for
high and low flow.
7
Perform hot water and cold water isolation tests.
8
Replaced actuator (shall be at five years interval from commissioning)
9
Replace and lubricate dynamic o-rings and seals (shall be at five years interval
from commissioning)
Five Yearly
Service Item
Yearly
Item No.
Frequency
Tempering Valve
Service Item
1
Check and clean strainer (if fitted).
2
Check non-return valve operation (integral or independently fitted).
3
Record temperatures of hot and cold water supply to valve.
4
Record discharge temperature measured at the nearest outlet to the valve for
high and low flow.
5
Perform cold water isolation test.
Document: TSW00138
Date Issued:
©The State of Queensland (Department of Housing and Public Works)
Yearly
Item No.
Frequency
Page 3 of 4
CONTRACT
5.3
Temperature / Pressure Relief Valve
1
Check valve operation.
Expansion Control Valve
1
5.5
Service Item
Yearly
Frequency
Item No.
5.4
Service Item
Yearly
Item No.
Frequency
Check valve operation.
Five-yearly Maintenance Items
The Contractor shall advise the Principal’s Representative when a Five-yearly service is required. The
work is to be priced separately to the contract work and will be the subject of a separate order.
Document: TSW00138
Date Issued:
©The State of Queensland (Department of Housing and Public Works)
Page 4 of 4
Download