Just click on the products in the selection table. Click on the HELUKABEL logo at the end of the page to go back. Cables & Wires Selection table for cables installation cables www.helukabel.com INSTALLATION CABLES Designation Properties YV patch cable / YR bell sheathed cable in accordance with VDE 0812 Approvals Page 516 NYM-J/-O PVC sheathed cable VDE approved 517 (N) YM (St)-J PVC sheathed cable screened 518 NHMH-O halogen-free, i.e. free of harmful substances, sheathed cable 300/500V 519 NHMH-J halogen-free, i.e. free of harmful substances, sheathed cable 300/500V 520 NHXHM-O/-J halogen-free sheathed cable 300/500 V, VDE approved 521 O 515 CW&A Edition 27 (published 01.04.2015) Installation Cables YV-Equipment Wires / YR-Bell Sheathed Cables according to VDE 0812 Technical data YV-Equipment Wires Ⴠ Equipment wires with PVC core insulation to DIN VDE 0812 Ⴠ Temperature range flexing -5°C to +70°C fixed installation -30°C to +70°C Ⴠ Electrical characteristics Operating voltage (peak voltage) to DIN VDE 0812 YR-Bell Sheathed Cables Ⴠ adapted to DIN VDE 0812 Ⴠ Minimum bending radius 15x cable Ø Cable structure YV-Equipment Wires Ⴠ Tinned copper-conductor, solid 0,3 to 1,8 mm Ø Ⴠ Core insulation of PVC compound type YI3 to DIN VDE 0207 part 4 Ⴠ Mono or twin colour wires, twin colour wires have a base colour with the second colour superimposed in ring form Ⴠ Core identification to DIN 47002 YR-Bell Sheathed Cables Ⴠ Bare copper conductor, solid 0,8 mm Ⴠ Cores stranded in layer Ⴠ Core identification see Technical Informations Ⴠ Outer sheath of PVC Ⴠ Sheath colour white Properties YV-Equipment Wires Tests Ⴠ PVC self-extinguishing and flame retardant acc. to IEC 60332-2 (equivalent DIN VDE 0472 part 804 test method A) Installation notes Ⴠ The equipment wires are to be so uncoiled from drums or coils so that no kinks or twisting torsional stress can be occured Those are allowed to install as self-supporting shaped wires independently ensuring the free-movements so as to gain a compensating bending These are used without any mechanical stress, pull, pressure, abrasion and notch Several equipment wires are used together in form of a bunch. The insulating coverings are not be cut through the binding materials. The binding materials must be nonconductive and not allowed to swell or shrink in humidity. During the soldering process without jointing clamp, the soldering period is to be shortened so that the insulating covering should not be shrinked or injured. Application YV-Equipment Wires Single core cables for use in small apparatus, switching and intercom system and for data transmission. These cables are not allowed for the installation of heavy current operation. Equipment wire are used for wiring to the switchbords, amplifiers and dial intercommunicating systems, measuring instruments, telephone exchange, clock centrals and data processing apparatus etc. These wires are not permitted to apply outside of equipment for high power ratings. YR-Bell Sheathed Cables For different applications up to max. 100 V operating voltage, for fixed installation above and beneath plaster. = The product is conformed with the EC Low-Voltage Directive 2006/95/EC. YV-Equipment Wires Part no. 28900 28901 28902 28903 28904 28905 28906 28907 28908 28909 28910 28911 28912 28913 28914 28915 28916 28917 28918 No.cores x cond. Ø / core Ø mm 1 x 0,3 / 0,7 2 x 0,3 / 0,7 3 x 0,3 / 0,7 1 x 0,4 / 0,8 2 x 0,4 / 0,8 3 x 0,4 / 0,8 1 x 0,5 / 0,9 2 x 0,5 / 0,9 3 x 0,5 / 0,9 4 x 0,5 / 0,9 1 x 0,8 / 1,4 2 x 0,8 / 1,4 3 x 0,8 / 1,4 4 x 0,8 / 1,4 1 x 1 / 1,8 2 x 1 / 1,8 3 x 1 / 1,8 1 x 1,4 / 2,2 1 x 1,8 / 2,8 Outer Ø Cop. approx. mm weight kg / km 0,7 0,7 1,4 1,4 1,6 2,1 0,8 1,3 1,6 2,5 1,8 3,8 0,9 2,0 1,8 3,9 2,0 5,9 2,2 7,9 1,4 5,0 2,8 10,0 3,0 15,0 3,4 20,0 1,8 7,9 3,6 16,0 4,0 24,0 2,2 15,0 2,8 25,0 Weight approx. kg / km 1,2 2,4 3,6 1,8 3,6 5,4 2,5 5,0 7,5 10,0 6,0 12,0 18,0 24,0 10,0 20,0 30,0 17,0 27,5 Dimensions and specifications may be changed without prior notice. (RO01) 516 CW&A Edition 27 (published 01.04.2015) YR-Bell Sheathed Cables Part no. - 28919 28920 28921 28922 28923 28924 28925 28926 28927 28928 No.cores x cond. Ø / core Ø mm 2 x 0,8 / 1,4 3 x 0,8 / 1,4 4 x 0,8 / 1,4 5 x 0,8 / 1,4 6 x 0,8 / 1,4 8 x 0,8 / 1,4 10 x 0,8 / 1,4 12 x 0,8 / 1,4 16 x 0,8 / 1,4 24 x 0,8 / 1,4 Outer Ø Cop. approx. mm weight kg / km 4,0 9,6 4,4 14,4 4,9 19,2 5,3 24,0 5,8 28,8 6,5 38,0 7,6 48,0 7,7 58,0 8,6 77,0 10,5 115,0 Weight approx. kg / km 27,0 33,0 41,0 48,0 56,0 70,0 84,0 98,0 124,0 188,0 - Installation Cables NYM-J/-O PVC-Sheathed Cable VDE approved Technical data Ⴠ PVC-sheathed cable to DIN VDE 0250 part 204 Ⴠ Temperature range flexing +5°C to +70°C fixed installation -40°C to +70°C Ⴠ Nominal voltage U0/U 300/500 V Ⴠ Test voltage 2000 V Ⴠ Minimum bending radius fixed installation 4x cable Ø Ⴠ Radiation resistance up to 80x106 cJ/kg (up to 80 Mrad) Ⴠ Caloric load values see Technical Informations Cable structure Ⴠ Solid or stranded, plain copper conductor to DIN VDE 0295 cl.1 or cl.2, BS 6360 cl.1 or cl.2 and IEC 60228 cl.1 or cl.2 Ⴠ Core insulation of PVC compound type TI1 to DIN VDE 0207-363-3 / DIN EN 50363-3 Ⴠ Core identification to DIN VDE 0293-308 Ⴠ Cores stranded in layers with optimal lay-length Ⴠ Filler Ⴠ Outer sheath of PVC compound type TM1 to DIN VDE 0207-363-4-1 / DIN EN 50363-4-1 Ⴠ Sheath colour grey (RAL 7035) Properties Tests Ⴠ PVC self-extinguishing and flame retardant acc. to DIN VDE 0482-332-1-2, DIN EN 60332-1-2, IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B) Note Ⴠ re = round conductor, single-wire rm = round conductor, multi-wire Ⴠ G = with green-yellow conductor x = without green-yellow conductor (OZ) Ⴠ AWG sizes are approximate equivalent values. The actual cross-section is in mm². Application For industrial- and wiring purposes. Usable in the open, in dry, damp and wet environments in the open and concealed, as well as in masonry and in beton, not suitable for imbedding in solidified- or compressed-concrete. Outdoor usage is only possible, as long as the cable is protected against direct sunlight. = The product is conformed with the EC Low-Voltage Directive 2006/95/EC. Part no. 39050 39001 39006 39056 39007 39058 39009 39066 39017 39072 39023 39076 39077 39055 39024 39057 39008 39059 39010 39067 39018 39075 39051 39002 39074 39060 39011 39068 39019 39052 39003 39078 No.cores x cross-sec. mm² 1 G 1,5 re 1 x 1,5 re 2 x 1,5 re 3 G 1,5 re 3 x 1,5 re 4 G 1,5 re 4 x 1,5 re 5 G 1,5 re 5 x 1,5 re 7 G 1,5 re 7 x 1,5 re 10 G 1,5 re 12 G 1,5 re 1 G 2,5 re 1 x 2,5 re 3 G 2,5 re 3 x 2,5 re 4 G 2,5 re 4 x 2,5 re 5 G 2,5 re 5 x 2,5 re 7 G 2,5 re 1G4 re 1x4 re 3G4 re 4G4 re 4x4 re 5G4 re 5x4 re 1G6 re 1x6 re 3G6 re Outer Ø Cop. approx. mm weight kg / km 5,4 14,4 5,4 14,4 8,7 29,0 9,1 43,0 9,1 43,0 9,8 58,0 9,8 58,0 10,3 72,0 10,3 72,0 11,5 101,0 11,5 101,0 13,8 144,0 14,4 173,0 6,0 24,0 6,0 24,0 10,4 72,0 10,4 72,0 11,3 96,0 11,3 96,0 12,0 120,0 12,0 120,0 13,2 168,0 6,6 38,0 6,6 38,0 12,0 115,0 13,0 154,0 13,0 154,0 14,5 192,0 14,5 192,0 7,2 58,0 7,2 58,0 13,0 173,0 Weight AWG-No. approx. kg / km 40,0 40,0 170,0 135,0 135,0 160,0 160,0 190,0 190,0 235,0 235,0 330,0 405,0 70,0 70,0 190,0 190,0 230,0 230,0 270,0 270,0 342,0 80,0 80,0 258,0 330,0 330,0 410,0 410,0 105,0 105,0 320,0 16 16 16 16 16 16 16 16 16 16 16 16 16 14 14 14 14 14 14 14 14 14 12 12 12 12 12 12 12 10 10 10 Part no. 39061 39012 39069 39020 39053 39004 39062 39013 39070 39021 39054 39005 39063 39014 39071 39022 39079 39064 39015 39073 39065 39016 No.cores x cross-sec. mm² 4G6 re 4x6 re 5G6 re 5x6 re 1 G 10 re 1 x 10 re 4 G 10 re 4 x 10 re 5 G 10 re 5 x 10 re 1 G 16 rm 1 x 16 rm 4 G 16 rm 4 x 16 rm 5 G 16 rm 5 x 16 rm 1 G 25 rm 4 G 25 rm 4 x 25 rm 5 G 25 rm 4 G 35 rm 4 x 35 rm Outer Ø Cop. approx. mm weight kg / km 15,1 230,0 15,1 230,0 16,1 288,0 16,1 288,0 8,4 96,0 8,4 96,0 17,6 384,0 17,6 384,0 19,2 480,0 19,2 480,0 9,9 154,0 9,9 154,0 21,3 614,0 21,3 614,0 23,4 768,0 23,4 768,0 12,0 240,0 25,8 960,0 25,8 960,0 28,7 1200,0 28,5 1344,0 28,5 1344,0 Weight AWG-No. approx. kg / km 460,0 460,0 540,0 540,0 155,0 155,0 680,0 680,0 850,0 850,0 230,0 230,0 1048,0 1048,0 1280,0 1280,0 325,0 1649,0 1649,0 1970,0 2000,0 2000,0 10 10 10 10 8 8 8 8 8 8 6 6 6 6 6 6 4 4 4 4 2 2 Dimensions and specifications may be changed without prior notice. (RO01) 517 CW&A Edition 27 (published 01.04.2015) O Installation Cables (N)YM(St)-J PVC-sheathed cable screened Technical data Ⴠ screened PVC-sheathed cable adapted to DIN VDE 0250 part 204 Ⴠ Temperature range flexing +5°C to +70°C fixed installation -40°C to +70°C Ⴠ Permissible working temperature at the conductor +70°C Ⴠ Nominal voltage U0/U 300/500 V Ⴠ Test voltage 2000 V Ⴠ Minimum bending radius fixed installation 4x cable Ø Ⴠ Radiation resistance up to 80x106 cJ/kg (up to 80 Mrad) Cable structure Ⴠ Bare copper-conductor, to DIN VDE 0295 cl.1 or cl.2, single-wire or multi-wire, BS 6360 cl.1 or cl.2, IEC 60228 cl.1 or cl.2 Ⴠ Core insualtion of PVC compound type TI1 to DIN VDE 0207-363-4-1/DIN EN 50363-4-1 Ⴠ Core identification to DIN VDE 0293-308 Ⴠ Cores stranded in layers with optimal lay-length Ⴠ Solid copper drain-wire, tinned Ⴠ Coated aluminium foil screening Ⴠ Outer sheath of PVC compound type TM1 to DIN VDE 0207-363-4-1/DIN EN 50363-4-1 Ⴠ Sheath colour grey (RAL 7035) Properties Tests Ⴠ PVC self-extinguishing and flame retardant acc. to DIN VDE 0482-332-1-2, DIN EN 60332-1-2, IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B) Note Ⴠ re = round conductor, single-wire rm = round conductor, multi-wire Ⴠ Also availabel in an halogen-free version Ⴠ AWG sizes are approximate equivalent values. The actual cross-section is in mm². Application These installation cables are made for an effective range of electromagnetic interference alternating fields by a static screen. This screening is specially used for the installation in computer sector, hospitals or industry measuring observation points with measuring instruments which are sensitive to interferences. These cables are also ideal for installations in the living rooms of those peoples who are extreme sensitive to radiation. The cable is suitable for laying on, in and under plaster in dry and damp places as well as in concrete and masonry (a direct laying in shaked or stamped concrete is excluded). Outdoor laying only is possible if the cable is not exposed to direct sunlight or if the cable is layed in cable conduits. Use in dangerous areas is not allowed. = The product is conformed with the EC Low-Voltage Directive 2006/95/EC. Part no. No.cores x cross-sec. mm² 43050 3 G 1,5 43051 4 G 1,5 43052 5 G 1,5 43053 7 G 1,5 43054 3 G 2,5 43055 4 G 2,5 43056 5 G 2,5 43057 3G4 43058 4G4 43059 5G4 43060 3G6 43061 4G6 43062 5G6 re re re re re re re re re re re re re Drainwire mm² 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 Outer Ø Cop. approx. weight mm kg / km 10,5 51,0 11,5 63,0 12,0 80,0 13,0 106,0 12,0 80,0 13,0 104,0 13,5 128,0 13,5 123,0 14,5 159,0 16,5 200,0 15,0 187,0 16,5 235,0 17,5 293,0 Weight approx. kg / km 154,0 184,0 208,0 250,0 217,0 256,0 280,0 228,0 359,0 440,0 378,0 477,0 565,0 AWG-No. 16 16 16 16 14 14 14 12 12 12 10 10 10 Dimensions and specifications may be changed without prior notice. (RO01) Suitable accessories can be found in Chapter X. • Tool - DUO Stripper 200 518 CW&A Edition 27 (published 01.04.2015) Part no. No.cores x cross-sec. mm² 43063 5 G 10 re 43064 5 G 16 rm 43065 5 G 25 rm Drainwire mm² 1,5 2,5 2,5 Outer Ø approx. mm 21,5 26,0 31,5 Cop. weight kg / km 485,0 773,0 1205,0 Weight approx. kg / km 840,0 1353,0 2017,0 AWG-No. 8 6 4 Installation Cables NHMH-O halogen-free for fixed installation, emission-free, 300/500 V Technical data Ⴠ Plastic-sheathed cable, halogen-free, for fixed installation to DIN VDE 0250 part 215 Ⴠ Permissible working temperature at the conductor +70°C Ⴠ Nominal voltage U0/U 300/500 V Ⴠ Minimum bending radius fixed installation 4x cable Ø Ⴠ Caloric load values see Technical Informations Cable structure Ⴠ Bare copper-conductor, single-wire or multi-wire Ⴠ Core insulation of halogen-free thermoplastic polymer compound with optimum wall thickness Ⴠ Core identification to DIN VDE 0293-308 1-core version - core colour BK Ⴠ Cores stranded in layer Ⴠ Outer sheath of non-cross-linked, halogen-free thermoplastic polymer compound Ⴠ Sheath colour grey (RAL 7035) Properties Tests Ⴠ Corrosive nature of combustion gases (halogen-free verification) testing acc. to DIN VDE 0482 part 267, DIN EN 50267-2-2, IEC 60754-2, HD 602 (equivalent DIN VDE 0472 part 813) Ⴠ Behaviour in fire self-extinguishing and flame retardant to DIN VDE 0482-332-1-2, DIN EN 60332-1-2,IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B) Ⴠ Low smoke testing acc. to DIN VDE 0472 part 818 Note Ⴠ re = round conductor, single-wire rm = round conductor, multi-wire Ⴠ x = without green-yellow conductor Ⴠ O-version: single-core conductor with black core insulation. Cables between two and seven cores are without gn-ye core. Ⴠ AWG sizes are approximate equivalent values. The actual cross-section is in mm². Application This plastic-sheathed cable of defined behaviour in case of fire is used for installations in residential dwellings, public buildings as well as in industrial constructions. Suitable for applications in dry, damp or wet environments for installation above, on, in and beneath plaster, as well as in masonry and concrete walls, not however for embedding in vibration, compacted or tamped concrete. The cable is also approved for outdoor applications provided these are not exposed to direct sunlight radiation. Installation of this cable in earth or in water is not permitted. = The product is conformed with the EC Low-Voltage Directive 2006/95/EC. Part no. 51970 51976 51981 51983 51991 51971 51977 51982 51984 51972 51978 51985 51973 51979 51986 No.cores x cross-sec. mm² 1 x 1,5 re 2 x 1,5 re 3 x 1,5 re 4 x 1,5 re 7 x 1,5 re 1 x 2,5 re 2 x 2,5 re 3 x 2,5 re 4 x 2,5 re 1x4 re 2x4 re 4x4 re 1x6 re 2x6 re 4x6 re Outer Ø Cop. approx. mm weight kg / km 8,3 14,4 8,9 29,0 9,2 43,0 9,9 58,0 11,5 101,0 9,0 24,0 10,0 48,0 10,6 72,0 11,0 96,0 9,5 38,0 11,5 77,0 13,4 154,0 10,0 58,0 12,4 115,0 15,9 230,0 Weight AWG-No. approx. kg / km 39,0 82,0 92,0 115,0 167,0 47,0 110,0 128,0 152,0 62,0 160,0 244,0 83,0 208,0 345,0 16 16 16 16 16 14 14 14 14 12 12 12 10 10 10 Part no. 51974 51980 51987 51975 51988 51989 51990 No.cores x cross-sec. mm² 1 x 10 re 2 x 10 re 4 x 10 re 1 x 16 rm 4 x 16 rm 4 x 25 rm 4 x 35 rm Outer Ø Cop. approx. mm weight kg / km 11,5 96,0 14,9 192,0 17,5 384,0 12,9 154,0 19,9 614,0 27,4 960,0 30,4 1344,0 Weight AWG-No. approx. kg / km 125,0 340,0 522,0 188,0 815,0 1305,0 1750,0 8 8 8 6 6 4 2 Dimensions and specifications may be changed without prior notice. (RO01) Suitable accessories can be found in Chapter X. • Tool - DUO Stripper 200 519 CW&A Edition 27 (published 01.04.2015) O Installation Cables NHMH-J halogen-free for fixed installation, emission-free, 300/500 V Technical data Ⴠ Plastic-sheathed cable, halogen-free, for fixed installation to DIN VDE 0250 part 215 Ⴠ Permissible working temperature at the conductor +70°C Ⴠ Nominal voltage U0/U 300/500 V Ⴠ Minimum bending radius fixed installation 4x cable Ø Ⴠ Caloric load values see Technical Informations Cable structure Ⴠ Bare copper-conductor, single-wire or multi-wire Ⴠ Core insulation of halogen-free thermoplastic polymer compound with optimum wall thickness Ⴠ Core identification to DIN VDE 0293-308 1-core version - core colour GN-YE Ⴠ GN-YE conductor, 3 cores and above Ⴠ Cores stranded in layer Ⴠ Outer sheath of non-cross-linked, halogen-free thermoplastic polymer compound Ⴠ Sheath colour grey (RAL 7035) Properties Ⴠ Corrosive nature of combustion gases (halogen-free verification) testing acc. to DIN VDE 0482 part 267, DIN EN 50267-2-2, IEC 60754-2, HD 602 (equivalent DIN VDE 0472 part 813) Ⴠ Behaviour in fire self-extinguishing and flame retardant to DIN VDE 0482-332-1-2, DIN EN 60332-1-2,IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B) Ⴠ Low smoke testing acc. to DIN VDE 0472 part 818 Note Ⴠ re = round conductor, single-wire rm = round conductor, multi-wire Ⴠ G = with green-yellow conductor Ⴠ J-version: with green-yellow core insulation. Ⴠ AWG sizes are approximate equivalent values. The actual cross-section is in mm². Application This plastic-sheathed cable of defined behaviour in case of fire is used for installations in residential dwellings, public buildings as well as in industrial constructions. Suitable for applications in dry, damp or wet environments for installation above, on, in and beneath plaster, as well as in masonry and concrete walls, not however for embedding in vibration, compacted or tamped concrete. The cable is also approved for outdoor applications provided these are not exposed to direct sunlight radiation. Installation of this cable in earth or in water is not permitted. = The product is conformed with the EC Low-Voltage Directive 2006/95/EC. Part no. 51996 52001 52009 52016 51997 52002 52010 52017 51992 51998 52003 52011 51993 51999 52004 52012 51994 52000 52005 52013 51995 52006 No.cores x cross-sec. mm² 3 G 1,5 re 4 G 1,5 re 5 G 1,5 re 7 G 1,5 re 3 G 2,5 re 4 G 2,5 re 5 G 2,5 re 7 G 2,5 re 1G4 re 3G4 re 4G4 re 5G4 re 1G6 re 3G6 re 4G6 re 5G6 re 1 G 10 re 3 G 10 re 4 G 10 re 5 G 10 re 1 G 16 rm 4 G 16 rm Outer Ø Cop. approx. mm weight kg / km 9,4 43,0 10,2 58,0 10,8 72,0 11,4 101,0 10,4 72,0 11,3 96,0 11,9 120,0 13,5 158,0 8,6 38,0 11,8 115,0 13,3 154,0 14,8 192,0 9,9 58,0 13,4 173,0 14,8 230,0 16,0 288,0 11,2 96,0 16,0 288,0 17,4 384,0 18,9 480,0 11,9 154,0 21,6 614,0 Weight AWG-No. approx. kg / km 92,0 115,0 133,0 168,0 128,0 152,0 182,0 250,0 62,0 192,0 244,0 300,0 83,0 267,0 345,0 400,0 125,0 628,0 522,0 620,0 188,0 815,0 16 16 16 16 14 14 14 14 12 12 12 12 10 10 10 10 8 8 8 8 6 6 Dimensions and specifications may be changed without prior notice. (RO01) Suitable accessories can be found in Chapter X. • Tool - DUO Stripper 200 520 CW&A Edition 27 (published 01.04.2015) Part no. 52014 52007 52015 52008 No.cores x cross-sec. mm² 5 G 16 rm 4 G 25 rm 5 G 25 rm 4 G 35 rm Outer Ø Cop. approx. mm weight kg / km 23,8 768,0 27,0 960,0 29,0 1200,0 29,9 1344,0 Weight AWG-No. approx. kg / km 995,0 1305,0 1580,0 1750,0 6 4 4 2 Installation Cables NHXMH-O/-J halogen-free plastic sheathed cable 300/500 V, VDE approved Technical data Ⴠ Halogen-free plastic-sheathed cable with enhanced characteristics in case of fire, acc. to DIN VDE 0250 part 214 Ⴠ Conductor resistance (at 20°C) acc. to DIN VDE 0295 and IEC 60228 Ⴠ Max. temperature at the conductor during operation +70°C in case of short circuit +250°C Ⴠ Temperature range during installation -5°C to +50°C fixed installation -30°C to +70°C Ⴠ Nominal voltage U0/U 300/500 V Ⴠ Test voltage 2000 V Ⴠ Minimum bending radius fixed installation 4x cable Ø Ⴠ Caloric load values see Technical Informations Cable structure Ⴠ Bare copper-conductor to DIN VDE 0295, BS 6360, IEC 60228 up to 10 mm² cl.1: single-wire 16-35 mm² cl.2: multi-wire Ⴠ Core insulation of cross-linked polymer, compound type 2XI1 to DIN VDE 0207 part 22 Ⴠ Core identification to DIN VDE 0293-308 1-core version - core colour BK or GN-YE Ⴠ Cores stranded in layers with optimal lay-length Ⴠ Overall core sheath of halogen-free filling compound (may be omitted for single-core cables) Ⴠ Outer sheath of flame-retardant, halogen-free polymer compound type HM2 to DIN VDE 0207 part 24 Ⴠ Sheath colour grey (RAL 7035) Properties Ⴠ Flame-retardant Ⴠ Halogen-free, no liberation of corrosive or toxic gases Ⴠ Limited propagation of fire Ⴠ Low smoke development Ⴠ Ozone resistant Tests Ⴠ Flame test acc. to DIN VDE 0482-332-3, BS 4066 part 3, DIN EN 60332-3, IEC 60332-3 (previously DIN VDE 0472 part 804 test method C) Ⴠ Corrosiveness of combustion gases acc. to DIN VDE 0482 part 267, DIN EN 50267-2-2, IEC 60754-2 (equivalent DIN VDE 0472 part 813) Ⴠ Halogen-free acc. to DIN VDE 0482 part 267, DIN EN 50267-2-1, IEC 60754-1 (equivalent DIN VDE 0472 part 815) Ⴠ Smoke density acc. to DIN VDE 0482 part 268, HD 606, EN 50268-1+2, IEC 61034-1+2, BS 7622 part 1+2 (equivalent DIN VDE 0472 part 816) Ⴠ Ozone resistance acc. to DIN VDE 0472 part 805 Ⴠ Also deliverable in screened (St) version Note Ⴠ re = round conductor, single-wire rm = round conductor, multi-wire Ⴠ LS0H = Low Smoke Zero Halogen Ⴠ AWG sizes are approximate equivalent values. The actual cross-section is in mm². Application Halogen-free plastic-sheathed cables with enhanced characteristics in case of fire are used for applications where harm to human life and damage to property must be prevented in the event of fire, e. g. in industrial installations, communal establishments, hotels, airports, underground stations, railway stations, hospitals, departmental stores, banks, schools, theatres, multi-storey buildings, process control centres etc. Suitable for installation in dry, damp or wet environments, for installation above, on, in and beneath plaster as well as in masonry walls and in concrete, not however for direct embedding in vibration, compacted or tamped concrete. These cables are also suitable for outdoor applications. = The product is conformed with the EC Low-Voltage Directive 2006/95/EC. NHXMH-O Part no. 53300 53306 53301 53307 53302 53308 53303 53304 53305 No.cores x cross-sec. mm² 1 x 1,5 re 2 x 1,5 re 1 x 2,5 re 2 x 2,5 re 1x4 re 2x4 re 1x6 re 1 x 10 re 1 x 16 rm NHXMH-J Part no. 53350 53358 53366 53374 53351 53359 53367 53375 No.cores x cross-sec. mm² 3 G 1,5 re 4 G 1,5 re 5 G 1,5 re 7 G 1,5 re 3 G 2,5 re 4 G 2,5 re 5 G 2,5 re 7 G 2,5 re Outer Ø min. - max. mm 5,0 - 8,4 7,6 - 9,2 5,4 - 8,8 8,4 - 10,1 6,0 - 9,5 9,6 - 11,6 6,4 - 10,0 7,4 - 11,3 8,5 - 12,4 Cop. weight kg / km 15,0 29,0 24,0 48,0 39,0 77,0 58,0 96,0 154,0 Weight AWG-No. approx. kg / km Outer Ø min. - max. mm 8,0 - 9,6 8,5 - 10,3 9,1 - 11,0 9,9 - 11,9 8,7 - 10,6 9,5 - 11,5 10,4 - 12,3 11,4 - 13,8 Cop. weight kg / km 43,0 58,0 72,0 101,0 72,0 96,0 120,0 168,0 Weight AWG-No. approx. kg / km 49,0 110,0 60,0 136,0 80,0 202,0 111,0 160,0 232,0 130,0 151,0 177,0 209,0 163,0 200,0 238,0 300,0 16 16 14 14 12 12 10 8 6 16 16 16 16 14 14 14 14 NHXMH-J Part no. 53192 53352 53360 53368 53193 53353 53361 53369 53194 53354 53362 53370 53195 53355 53363 53371 53356 53364 53372 53357 53365 53373 No.cores x cross-sec. mm² 1G4 re 3G4 re 4G4 re 5G4 re 1G6 re 3G6 re 4G6 re 5G6 re 1 G 10 re 3 G 10 re 4 G 10 re 5 G 10 re 1 G 16 rm 3 G 16 rm 4 G 16 rm 5 G 16 rm 3 G 25 rm 4 G 25 rm 5 G 25 rm 3 G 35 rm 4 G 35 rm 5 G 35 rm Outer Ø min. - max. mm 6,0 - 9,5 10,1 - 12,2 11,3 - 13,7 12,5 - 15,1 6,4 - 10,0 11,5 - 13,9 12,7 - 15,3 13,7 - 16,6 7,4 - 11,3 13,8 - 16,7 15,1 - 18,2 16,3 - 19,7 8,5 - 12,4 16,5 - 20,0 18,0 - 21,8 19,7 - 23,8 20,4 - 24,6 22,6 - 27,3 24,7 - 29,8 22,7 - 27,4 24,9 - 30,0 27,5 - 33,2 Cop. weight kg / km 39,0 115,0 154,0 192,0 58,0 173,0 230,0 288,0 96,0 288,0 384,0 480,0 154,0 461,0 615,0 768,0 720,0 960,0 1200,0 1008,0 1344,0 1680,0 Weight AWG-No. approx. kg / km 80,0 235,0 300,0 345,0 111,0 323,0 400,0 475,0 160,0 485,0 603,0 720,0 232,0 850,0 940,0 1142,0 1152,0 1432,0 1800,0 1503,0 1930,0 2490,0 12 12 12 12 10 10 10 10 8 8 8 8 6 6 6 6 4 4 4 2 2 2 Dimensions and specifications may be changed without prior notice. (RO01) 521 CW&A Edition 27 (published 01.04.2015) O