17 CHAPTER 2 DESIGN AND DEVELOPMENT OF DOUBLE WINDING INDUCTION MOTOR 2.1 INTRODUCTION Conventional induction motor consists of only one set of winding in its stator and DWIM consists of two sets of windings in the same stator. A three phase supply is applied to one of the stator windings, a revolving magnetic field is developed in the air gap and this field is shared by both windings. Two separate windings with displaced angle between them are provided in the same stator for the improvement inefficiency. The behaviour of an alternator with two three phase stator windings displaced by an angle is analyzed by means of an orthogonal transformation (Fuchs 1974). Weber (1992) presented a dual stator induction motor for energy conservation which consists of two sets of RUN windings. Out of two sets of windings, one set of RUN winding is energised to have sufficient MMF to meet the reduced mechanical load, thereby the flux density in stator core reduces, reduced eddy current losses and copper losses. Depending on the shaft load of the machine, second set of RUN winding is excited through a power source. 18 The main RUN winding is energized to have sufficient MMF to meet the mechanical load. From the above discussion, it is learnt that most of the methods suggested by researchers for double winding induction motors are based on speed control applications and improvement of performance by exciting both windings. As further modification and improvement in energy conservation, DWIM is suggested in this thesis. In the proposed model, in addition to energy conservation, improvement in power factor and efficiency is also obtained by loading both windings. 2.2 DESIGN OF DOUBLE WINDING INDUCTION MOTOR In a double winding induction motor, when one of the windings is connected to a three phase supply, a revolving magnetic field of constant magnitude is developed in the air gap. This is utilized by both the stator windings to work as induction motor to meet mechanical load while, a three phase EMF is induced in the second set of winding to which electrical load can be connected to work as an Induction alternator. 2.2.1 Representation of DWIM Razik (2006) explained that the stator windings of double winding induction motor can be arranged with different shift angles. In DWIM, shift angle of 60 degrees or zero degrees are the best choice. In the proposed model, to obtain optimum utilisation, both the windings are placed with zero degree phase angle displacement between them and the representation of proposed DWIM is shown in Figure 2.1. 19 Figure.2.1 Double Winding Induction Motor 2.2.2 Design Considerations Design of the double winding induction motor is affected by various constraints such as thermal limit, overload capacity and utility of stator slots. Energy conserving double winding induction motor is ideal to be used for low power operations due to the limitation in thermal insulation value. The value of air gap flux density is large which determines large overload capacity. Use of semi-enclosed slots results in silent operation. The stator of DWIM consists of two sets of stator windings placed in the same slot and therefore slot utility is increased. Slot utility factor for designed DWIM is 43.3% whereas for a conventional induction motor, it is about 29%. 2.2.3 Design of stator Design procedure is presented for a 3kW, 415V, 50Hz, Double Winding Induction Motor. Electrical loading, magnetic loading, efficiency and power factor of the machine are chosen as given below: Flux density in the stator core Bav = 0.44 Wb/m2 Electrical loading = 18000 ac/m 20 Efficiency = 80 % Power factor = 0.85 Winding factor Kw = 0.9 Output Co-efficient C0 = 11 x Bav x Kw x ac x 10-3 = 11 x 0.44 x 0.9 x18 = 83.2 kVA output of the motor Q =3 / 0.8 x 0.85 = 4.41 kVA The product of the diameter and the length of the core D2 L = Q / C0 x ns = 4.41 / 83.2 x 25 = 2.12 x 10-3 m3 For good overall design L / ration is chosen as 1 Length of core L = 0.785 D Diameter of the core = 0.139 m Length of the core = 0.11 m DWIM presented in this thesis consists of two sets of identical coils in the same stator core. Hence the design of one set is similar to the other. Stator voltage per phase Vph = 240 V Flux per pole = (Bav x x D x L) / P m = 5.28 mWb Turns per phase Tph = Vph / (4.44 x 50 x 5.28 x 10-3 x 0.9) 21 = 228 turns Slot per pole per phase =3 Number of stator slots = 36 Slot pitch = D / Ss = x 0.139 x 103 / 36 = 12 mm Total stator conductors for each winding = 3 x 2 x 228 = 1368 conductors Conductors per slot for each winding = 1368 / 36 = 38 Stator current per phase is = 3x 103/ 3 x 240 x 0.8 x 0.85 = 6.1 A 18 SWG enameled copper coil is chosen for the winding Diameter of the conductor = 1.22 mm Area of Stator conductor = 1.17 mm2 Current density = 6.1 / 1.17 s = 5.21 A / mm2 Area of conductors per slot = 1.17 x 76 = 88.92 mm2 Area of each slot = 205 mm2 Space factor = 88.92 / 205 = 0.433 22 2.3 PERFORMANCE OF DWIM Bu et al (2003) presented a double winding induction machine and its speed control methods. One stator acts as a motor and the other as a generator. By controlling the voltage supplied to the generator winding, the rotor speed can be adjusted. One of the stator winding of DWIM is connected to a three phase supply, a revolving magnetic field is developed in the air gap. With respect to first winding, this field interacts with rotor conductors and develops torque to meet mechanical load, whereas a three phase EMF is developed in second set of winding to which an additional electrical load can be connected. The main scope of thesis is energy conservation, efficiency and power factor improvement at reduced mechanical load of DWIM. 2.3.1 Load test with Electrical and Mechanical loads In the proposed DWIM, both stator windings are of identical nature. In order to obtain performance characteristics as conventional induction motor, one of the windings is connected to a three phase supply and other set of winding is left free. Load test has been carried out with brake drum arrangement and electrical load on second set of winding to study the performance of machine. Experimental set up with both electrical and mechanical loading is shown in Figure 2.2. Table 2.1 shows the reading observed considering one set of winding to operate the machine as induction motor to meet the mechanical load and the second set of winding is unloaded. Efficiency and power factor characteristic is shown in Figure 2.3. The maximum efficiency of the machine is 83.6% and the corresponding power factor is 0.63. 23 Figure 2.2 Experimental Setup Speed in rpm Power factor % Slip 480 1466 0 0 0 0.27 2.3 415 3.0 720 1458 3.6 549 76.3 0.33 2.8 415 3.5 1240 1448 6.4 968 78.1 0.49 3.5 415 4.0 1680 1442 9.1 1368 81.4 0.58 3.9 415 4.5 2040 1438 11.3 1705 83.6 0.63 4.1 415 5.0 2250 1426 12.2 1814 81.6 0.63 4.9 415 5.5 2880 1416 15.7 2320 80.6 0.73 5.6 415 6.0 3360 1408 18.1 2672 79.5 0.78 6.1 % Efficiency Input power (W) 2.5 Output power (W) Line current 415 Torque in Nm Input voltage Table 2.1 Conventional load test 24 Figure 2.3 Efficiency and power factor Characteristics (DWIM) Test performance have been compared with IEC 60034-30, it is observed that the standard efficiency for 3kW, 4- pole induction motor is 81.5%, but in tested machine efficiency is 79.9%. DWIM consists of two identical windings, when a three phase 415V supply is applied to one winding, the same magnitude of 415 V is induced in second winding. A lamp load is used to test the machine whose power factor is unity. Table 2.2 shows the reading observed with 1A electrical load on second set of winding in addition to the mechanical load. Efficiency and power factor characteristic are shown in Figure 2.4. The maximum efficiency of the machine is 86% and the corresponding power factor is 0.78. 25 Total % Efficiency Power factor % Slip 0 0 720 720 85 0.49 0.93 1380 1470 2.3 354 720 1074 78 0.64 1.60 3.5 1840 1468 5.6 859 720 1579 86 0.73 2.13 415 4.0 2240 1458 8.0 1220 720 1940 86 0.78 2.80 415 4.5 2760 1452 10.8 1640 720 2360 85 0.85 3.20 415 5.0 3080 1444 12.0 1810 720 2530 82 0.86 3.73 415 6.0 3640 1420 14.7 2185 720 2905 80 0.84 4.93 Input power (W) Speed (rpm) 2.4 840 1480 415 3.0 415 Mechanical (W) Line current (A) 415 Torque (Nm) Voltage (V) output Electrical output (W) output (W) Table 2.2 Mechanical load with 1A Electrical Load Figure 2.4 Efficiency and power factor with 1A Electrical load (DWIM) 26 Table.2.3 shows the reading observed with 1A electrical load with capacitor across the load and efficiency and power factor characteristics is shown in Figure.2.5. When a capacitor of 20µF is included across the load, the maximum efficiency increased to 85.8% and the corresponding power factor is improved to 0.94. Input Voltage Line Current (A) Input Power (W) Speed in rpm Torque Nm Mechanical Output (W) Electrical Output (W) Total Output (W) % Efficiency Power Factor Table 2.3 Mechanical load with 1A Electrical Load and Capacitance 415 2.7 1800 1440 6.6 994 480 1474 81.8 0.93 415 3.1 2080 1435 8.0 1207 520 1727 83.0 0.93 415 3.6 2440 1435 10.5 1573 520 2093 85.8 0.94 415 4.1 2780 1420 12.4 1838 520 2358 84.8 0.94 415 4.7 3160 1410 14.2 2097 520 2617 82.8 0.94 415 5.4 3660 1400 16.7 2446 520 2966 81.1 0.94 Figure 2.5 Efficiency and power factor with 1A load and capacitor (DWIM) 27 Table 2.4 shows the reading observed with 2A electrical load on the second set of winding in addition to the mechanical load and the corresponding performance characteristics is shown in Figure 2.6. The maximum efficiency of the machine is 84% and the corresponding power factor is 0.85. Input Voltage Line Current (A) Input Power (W) Speed in rpm Torque in Nm Mechanical Output (W) Electrical Output (W) Total Output (W) % Efficiency Power Factor Table 2.4 Mechanical Load with 2A Electrical Load 415 3.0 1560 1488 0 0 1200 1200 77 0.72 415 4.0 2360 1472 4.9 756 1200 1956 83 0.82 415 4.5 2680 1464 7.9 1203 1200 2403 90 0.83 415 5.0 3040 1452 8.8 1342 1200 2542 84 0.85 415 5.5 3440 1438 10.8 1624 1200 2824 82 0.87 Figure 2.6 Efficiency and power factor with 2A Electrical load (DWIM) 28 Table 2.5 shows the reading observed with 3 A electrical load on the second set of winding in addition to the mechanical load and the corresponding performance characteristics is shown in Figure 2.7. The maximum efficiency of the machine is 92% and the corresponding power factor is 0.91. Electrical Output (W) Total Output (W) % Efficiency Power Factor 0 0 2125 2125 86 0.93 1.7 415 4.0 2640 1460 2.0 301 2125 2426 92 0.91 2.7 415 4.5 3120 1452 3.7 715 2125 2840 91 0.96 3.2 415 5.0 3480 1440 6.6 1035 2125 3160 90 0.97 4.0 415 5.5 3920 1430 9.4 1410 2125 3535 90 0.99 4.7 415 6.1 4360 1426 11.6 1728 2125 3853 88 099 % Slip Mechanical Output (W) 415 3.7 2480 1474 Speed in rpm Torque Nm Input Power (W) Line Current (A) Input Voltage Table 2.5 Mechanical load with 3A Electrical Load 4.9 Figure 2.7 Efficiency and power factor with 3A Electrical load (DWIM) 29 Table 2.4 corresponds to the reading with 2A electrical load in the second winding and Table 2.5 shows the reading with 3A electrical load in the second winding. The efficiency and power comparison is shown in Figure 2.8. Main focus of this thesis is to improve efficiency and power factor when the machine is lightly loaded with mechanical output. When operated as a conventional induction motor for a load current of 3A, efficiency is 76.3% and power factor 0.33. For the same load current, electrical load of 720 W is added in the second winding and hence efficiency is improved to 78% and power factor to 0.64. With a capacitor of 20 µF across the load, efficiency is improved to 83% and power factor to 0.93. Figure 2.8 Efficiency and power factor comparison for 2A and 3A (DWIM) 2.3.2 Modes of operation A controller circuit has been designed to operate DWIM in power balancing and maximum efficiency modes of operation. Initially, mode of operation is selected. In Mode I operation, controller is designed to operate the machine at its maximum efficiency, but at its rated capacity in Mode II of operation. Contactors are energised through relay coils and a controller to connect electrical load to second set of stator coils. The operation of DWIM 30 for the two modes of operation is explained using a flow chart shown in Figure 2.9. The load current corresponding to maximum efficiency is 4.5A and load current corresponding to rated capacity of the machine is 6.1A. These values are arrived from load test results. The control circuit for power balancing mode of operation is shown in Figure 2.10. The contactor arrangement for Mode I and Mode II operation is shown are Figure 2.11 and Figure 2.12. PIC controller senses the load current due to the mechanical load and switches ON the external electrical load to the second set of winding in order to maintain total current of 4.5A, corresponds to maximum efficiency. Figure 2.9 Flowchart for modes of operation (DWIM) 31 Figure 2.10 Control circuit for power balancing mode of operation (DWIM) Figure 2.11 Contactor arrangements for Mode I operation (DWIM) 32 Figure 2.12 Contactor arrangements for Mode II operation (DWIM) A current transformer is coupled with a controller through a precision rectifier. Depending upon load current in the first winding, controller switches external electrical load through contactors C1, C2 and C3 in different combination. In power balancing mode of operation, controller is programmed such a way that the machine runs at its rated capacity. Contactor operation for different loading condition is shown in Table 2.6. The specification of PIC IC 16F877 is given below: 8K x 14 words of Flash Program Memory 368 x 8 bytes of Data Memory (RAM) 256 x 8 bytes of EEPROM data memory Wide operating voltage range: 2.5V to 5.5V High Sink/ Source current :25 mA USART/SCI with 9-bit address detection. 33 Table 2.6 Contactor operation Load current Corresponds to first winding Contactor C1 Contactor C2 Contactor C3 (1A load) (1 A load) (0.5A load) 2.0<I<3.5 ON ON ON 3.5< I <4.5 OFF ON ON 4.5< I <5.5 OFF OFF ON When load current is between 2A and 3.5A, then all the three contactors will be in closed condition such that additional load of 2.5 A can be added to the second set of winding. When the load current is between 3.5 A and 4.5 A, then C4 and C5 contactor will be closed such that additional load of 1.5 A is added to the second set of winding. Similarly, when the load current is between 4.5 A and 5.5 A, then C5 contactor alone will be closed such that 0.5 A is added to the second set of winding. 2.4 SUMMARY Double Winding Induction Motor consists two sets of winding in the same stator core. If the machine is operated as conventional induction motor, for a load current of 3.0 A, the efficiency and power factor are 76.3% and 0.33 respectively, then an electrical load of 720 W is connected in the second set of winding. Its efficiency is improved to 78% and power factor to 0.64. When a capacitor of 20 F is included in the load side and 520W load in the second set of winding its efficiency still improves to 83% and power factor to 0.93. By an appropriate control circuit, DWIM can be operated in power balancing mode or maximum efficiency mode. In this work, energy conservation is obtained by operating the machine at its rated capacity or at maximum efficiency using control circuit. 34 In addition to performance improvement, energy conservation is also obtained by loading both windings. Example for energy conservation is given below: Considering load test results with 1A electrical load in second set of winding Supply voltage : 415 V Line current : 4.5 A Input power : 2760 W Output power : 1640 W (Mechanical) Output power : 720 W (Electrical) In the above test result, electrical power of 720 watts has been tapped from second winding. If the machine is operated for 10 hours a day, without depending on separate supply, monthly energy conservation from the same machine will be 0.72X 10 X 30 = 216 kWhrs. DWIMs would be an alternative choice for rewound motors and induction motors operated continuously. By providing an additional load in second set of winding, in addition to efficiency and power factor improvement, energy conservation is possible. Thus, DWIM provides opportunity for energy conservation and performance improvement.