TOPLINE SWITHCGEAR PVT. LTD. Survey No. 797, Opp: Riddhi Plastic, Vadsar, Kalol, Gandhinagar. Ph: 9909906782, 02764-286556. E-mail : psg@psgindia.net 11 kV, 200 Amp. Gang Operated Air Break Isolating Switch 11 KV, 200 A GOAB ISOLATING SWITCH Application The triple pole air break switch is gang operated and designed for outdoor application. The switch is intended for switching of the Transformer, Overhead lines and Cables from distribution system. Construction The A.B. Switch have triple pole construction and shall be suitable for Vertical / Horizontal mounting. Each pole consist of galvanized steel base, insulators of reputed make, copper alloy male and female contacts, arcing horns of adequate section to break magnetizing current of transformer. M.S. square coupling rod of adequate length for rocking operation, required length of G.I. pipe for operation from ground level and operating handle is specially design for smooth operation. Adjustable pins are provided to limit over travel of moving post. Ferrous parts are galvanized and non-ferrous parts are heavily tinned. Jumper is of EC grade braided copper of appropriate size to complete the current path from moving post to fix post. Operation quick for fast extinguishing the arc. The handle is provided with locking arrangement. Page designed for smooth, sturdy and trouble free operation. On and off operation should be 1 The handle, fabricated from channel and angular lever, fabricated from angle, are TOPLINE SWITHCGEAR PVT. LTD. Survey No. 797, Opp: Riddhi Plastic, Vadsar, Kalol, Gandhinagar. Ph: 9909906782, 02764-286556. E-mail : psg@psgindia.net Installation It can be mount vertically and horizontally on 2 nos. channels based on two-pole structure. Install three phases of AB switch on structure, pass the square coupling rod through bracket on center post, tighten all the bolts on moving brackets, keep the switch in ON position, fix the round pipe vertically and clamp the handle in ON position. Make it ON and OFF several times. G.L. TECHNICAL PARTICULARS 1 SYSTEM VOLTAGE 11 KV 2 RATED VOLTAGE 12 KV 3 RATED CURRENT 4 IMPULSE WITHSTAND VOLTAGE TO EATH 75 KV ACROSS THE TERMINALS 85 KV 5 POWER FREQ. WITH STAND VOLT TO EARTH ACROSS THE TERMINALS 6 RATED SHORT TIME CURRENT FOR 1 SEC. 7 WEIGHT OF ISOLATOR (APP) 8 GOVERNING SPECIFICATION No. PART NAME 200 AMP. 1 - M.S. ELE. GALV. 18 LOCKING BOLT 6 3/8" M.S. 17 MOVING MECHANISAM 1 - M.S. ELE. GALV. ELE. GALV. 16 COUPLING ROD 1 25X25X1800 M.S. ROD ELE. GALV. 15 OPERATING PIPE & COUPLING 2 Ø1" GALV. PIPE A CLASS ELE. GALV. 14 ARCING CONTACT 9 Ø6 MM M.S. ROD 13 INCOMING TERMINAL 3 - G.M.CASTING TIN PLATED 12 11 kV POST INSULATOR 9 330 CD. PORCELAIN 11 MALE CONTACT 3 - G.M.CASTING TIN PLATED 10 FEMALE CONTACT 3 - 9 JUMPER CARRIER 3 25 X 3 G.M.CASTING TIN PLATED ELE. GALV. M.S. FLAT 8 BRAIDED JUMPER 3 25 x 3 COPPER 7 OUT GOING TERMINAL 3 - G.M.CASTING TIN PLATED 6 TAIL CONTACT 3 - 5 LIMIT OF MOVING POST 3 25X6 M.S. FLAT M.S.SHEET 4 MOVING BASE OF CTR. POST 3 10 SWG 32 KV 3 MOUNTING HOLE (15" C.D.) 1 1/2" HOLE - 40 KA 2 EARTHING TERMINAL 3 3/8" BOLT - 85 KG. 1 MOUNTING CHANNEL 3 75X40X630 QTY TIN PLATED G.M.CASTING TIN PLATED ELE. GALV. 28 KV IS 9921-1985 REPUTED MAKE M.S. ELE. GALV. ELE'TE GALV. ELE. GALV. ELE. GALV. 2 TERMINAL PAD DETAIL HANDLE WITH LOCKING Page '0' SWG CU WIRE OR ACSR RABBIT COND. 19