TOPLINE SWITHCGEAR PVT. LTD. Survey No. 797, Opp: Riddhi Plastic, Vadsar, Kalol, Gandhinagar. Ph: 9909906782, 02764-286556. E-mail : psg@psgindia.net 11 kV, 400 Amp. Gang Operated Air Break Switch 11 KV, 400A GOAB SWITCH Application The triple pole air break switch is gang operated and designed for outdoor application. The switch is intended for switching of the Transformer, Overhead lines and Cables from distribution system. Construction The A.B. Switch have triple pole construction and shall be suitable for Vertical / Horizontal mounting. Each pole consist of galvanized steel base, insulators of reputed make, copper alloy male and female contacts, arcing horns of adequate section to break magnetizing current of transformer. M.S. square coupling rod of adequate length for rocking operation, required length of G.I. pipe for operation from ground level and operating handle is specially design for smooth operation. Adjustable pins are provided to limit over travel of moving post. Ferrous parts are galvanized and non-ferrous parts are heavily tinned. Jumper is of EC grade braided copper of appropriate size to complete the current path from moving post to fix post. Operation The handle, fabricated from channel and angular lever, fabricated from angle, are designed for smooth, sturdy and trouble free operation. On and off operation should be Page 1 quick for fast extinguishing the arc. The handle is provided with locking arrangement. TOPLINE SWITHCGEAR PVT. LTD. Survey No. 797, Opp: Riddhi Plastic, Vadsar, Kalol, Gandhinagar. Ph: 9909906782, 02764-286556. E-mail : psg@psgindia.net Installation It can be mounting vertically and horizontally on 2 nos. channels based on two-pole structure. Install three phases of AB switch on structure, pass the square coupling rod through bracket on center post, tighten all the bolts on moving brackets, keep the switch in ON position, fix the round pipe vertically and clamp the handle in ON position. Make it ON and OFF several times. G.L. TECHNICAL PARTICULARS 11 KV 2 RATED VOLTAGE 12 KV 3 RATED CURRENT 200 AMP. 4 IMPULSE WITHSTAND VOLTAGE TO EATH 75 KV ACROSS THE TERMINALS HOTDIP GALV. M.S. ROD HOTDIP GALV. 13 MOVING MECHANISAM 1 - M.S. HOTDIP GALV. 12 COUPLING ROD 1 25X25X2000 M.S. ROD HOTDIP GALV. 11 OPERATING PIPE & COUPLING 2 Ø1" GALV. PIPE A CLASS 10 ARCING CONTACT 6 Ø8 MM M.S. ROD HOTDIP GALV. G.M.CASTING TIN PLATED 9 INCOMING TERMINAL 3 - 8 11 kV POST INSULATOR 9 330 CD. PORCELAIN 7 MALE CONTACT 3 - G.M.CASTING TIN PLATED JSI/AC MAKE FEMALE CONTACT 3 - G.M.CASTING TIN PLATED OUT GOING TERMINAL 3 - G.M.CASTING TIN PLATED 85 KV 4 MOVING BASE OF CTR. POST 3 10 SWG M.S.SHEET HOTDIP GALV. 28 KV 3 MOUNTING HOLE (115MM C.D.) 1 Ø18MM HOLE - ELE'TE GALV. 32 KV 2 EARTHING TERMINAL 3 3/8" BOLT 1 MOUNTING CHANNEL 3 100X50X630 6 RATED SHORT TIME CURRENT FOR 1 SEC. 7 WEIGHT OF ISOLATOR (APP) 60 KG. 8 GOVERNING SPECIFICATION IS 9921-1985 PART NAME M.S. Ø8MM 6 POWER FREQ. WITH STAND VOLT TO EARTH No. - 1 5 5 ACROSS THE TERMINALS 1 I BOLT FOR GUIDING PIPE 40 KA M.S. ELE'TE GALV. HOTDIP GALV. QTY 2 SYSTEM VOLTAGE HANDLE WITH LOCKING 14 Page 1 15