VRF system
Heat pump:
AJT040LCLAH
AJT045LCLAH
AJT054LCLAH
4HP
5HP
6HP
Feature
This model is much more compact than conventional 6HP comparable outdoor units. Even when installed on the balcony it fits within the height of the fence. The compact size with a height of less than 1 m allows it to be installed under windows and in tight spaces
Conventional model /
6 HP class
Height:1334mm
Weight:117kg
N E W model / 6 HP class
Hight difference
998 mm
▲25%
Light weight
87 kg
▲26%
Lower noise operation is possible by low noise mode than rated noise level.
dB(A)
Rated noise mode
Low noise mode
-3 dB
Small VRF system achieves high EER/COP by using advanced components and inverter technologies.
EER
COP
(For 040 type)
3.52
4.40
• Optimized inverter control
• DC fan motor
• Compact & High efficiency heat exchanger
• DC twin rotary compressor
Flexible design
Long Piping Length
Total pipe length
80 m max.
Actual piping length
50m max.
Piping length from first separation tube to the farthest indoor unit
40m max.
Various indoor units and controllers
High capacity connection
Height difference between indoor and outdoor units
30m max.
Height difference between indoor and indoor units
15m max.
1: Only 4HP is up to 7.
Dimensions
Models : AJT040LCLAH / AJT045LCLAH / AJT054LCLAH
Connectable indoor unit capacity range
50
130
Connectable indoor unit number
8
*1
(Unit : mm)
Connectable indoor unit
12
53
capacity range 2.2kW to 14kW
T op view
Individual and centralized controllers same asV-II series
Fr on t view Side view Rear view
Specifications
Rating Capacity range
Model name
Maximum Connectable Indoor Unit
Power source
Capacity
Input Power
EER
COP
Air flow rate
Sound pressure level
Heat exchanger fin
Cooling/Heating
Cooling/Heating
Cooling
Heating
Cooling/Heating
Dimensions
Height
Width
Depth
Weight
Connection pipe diameter
Liquid
Gas
Max.Pipe Length
Max.Height Difference
Operation range
Cooling
Heating
HP
V/ Ø/Hz kW kW
W/W
I/s dB(A) mm mm mm kg mm m
°C
4
AJT040LCLAH
7
1 Phase, ~230V, 50Hz
12.1 / 13.6
3.44 / 3.09
3.52
4.40
1,122
51 / 54
Blue fin
998
970
370
86
ø9.52
ø15.88
80
30
-5 to 46
-20 to 21
Note : Specifications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating : Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
The protective function may work when using it outside the operation range.
*Data were not available at time of production.
5
AJT045LCLAH
8
1 Phase, ~230V, 50Hz
14.0 / 16.0
4.23 / 3.93
3.31
4.07
1,167
53 / 55
Blue fin
998
970
370
86
ø9.52
ø15.88
80
30
-5 to 46
-20 to 21
(Tentative)
6
AJT054LCLAH
8
1 Phase, ~230V, 50Hz
15.1 / 16.5
4.58 / 4.11
3.30
4.01
1,167
56 / 56
Blue fin
998
970
370
87
ø9.52
ø15.88
80
30
-5 to 46
-20 to 21
N807
All products specified in this brochure comply with the Australian
Communications Authority's (ACA) requirements for Electromagnetic
ISO 9001
Certified number : 01 100 79269
ISO 14001
Certified number : 310102-UK
Fujitsu General (Shanghai) Co., Ltd.
• “ ” are worldwide trademarks of FUJITSU GENERAL LIMITED and are registered trademarks in Japan and other countries or areas.
• O ther company and product names mentioned herein may be registered trademarks, trademarks or trade names of their respective owners.
•Specifications and design are subject to change without notice for further improvement.
•Actual products’ colors may be different from the colors shown in this printed material.
Distributed by :
1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan http://www.fujitsu-general.com/
Copyright© 2014 Fujitsu General Limited. All rights reserved. 6OFNP0-1404E