DAIKIN GAS HEAT PUMP - Air conditioning

advertisement
PCVAU1410
DAIKIN
GAS
HEAT PUMP
AIR CONDITIONING SYSTEM
Heat Pump / Heat Recover y 50 Hz
Air Conditioned Comfort, Powered by Natural Gas.
Benefits of Gas Heat Pump (GHP)
Daikin's Gas Heat Pump (GHP) air conditioning system is designed to
operate primarily on natural gas. GHP systems consume less electrical
power than conventional Electrical Heat Pump systems, whilst
delivering air conditioned comfort to the modern building.
Lower CO 2 Emission
Natural gas is used as the main energy
source. Natural gas emissions are
comparatively lower than other fossil fuels.
CO2 emissions
This unique gas powered air conditioning system is available both as a
Heat Pump and Heat Recovery system to suit a broad range of
applications, and when combined with an Electrical Heat Pump system
can provide an enhanced value proposition.
100
80
Coal
60
Natural gas
Petroleum
Reduced Power Consumption
What is GHP ?
The compressor is the heart of an
air conditioner and consumes
the most energy. In a Gas Heat Pump (GHP)
air conditioner, the compressor is
driven by a gas engine using natural gas,
whereas an Electric Heat Pump (EHP)
uses an electric motor.
Indoor Unit
Image of
heating
In GHP system, only the condenser
fans and the indoor units consume
electricity. In comparison to EHP, the
electrical power required to operate
GHP is significantly less, thereby
enabling the electrical substation and
switch gear equipment to be
downsized compared to EHP.
Power consumption
100
Fans
10
Heat
exchanger
E HP
Compressor
* CO2 emissions from coal = 100.
* Source: Natural Gas Prospects 2010, 1986/
EA Report on Thermal Power Plant Atmospheric
Impact Assessment Technology Demonstration
Surveys, March 1990/Institute of Applied Energy
GHP
* Power consumption of the EHP = 100.
Gas
Electricity
As the load changes during the day, GHP systems are able to match the varying load
by adjusting compressor capacity output through engine speed control.
GHP
EHP
Time
Heating capacity
How is capacity controlled?
01
Rapid and Powerful Heating
Outdoor Unit
Room temperature
Gas engine
-10°C Outdoor temperature
GHP
EHP
10°C
The ability to harness the waste heat
from the coolant circuit enables rapid
and powerful heating performance.
This feature also results in less
frequent defrost operation for GHP
systems.
Comparison of heating start speed and heating capacity (image)
02
3 Types available to various application
Daikin offers a range of Heat Pump and Heat Recovery systems
that are ideally suited for wide range of applications.
Heat Pump Standard Series
Footprint 1.46 m2
16-25 class
Heat Pump Large-capacity Series
Centralised control
Compact and Light Weight
Footprint 1.23 m2
8-13 class
Outdoor Unit Lineup
Heat Pump Large-capacity Series
By controlling both EHP and GHP systems off a common centralised control system,
the designer can capitalize on the unique characteristic and features of both
systems to deliver an engineered solution that meets the demands of the modern building.
Weight : 565 kg
13 class series
Control is centralised
by one controller.
D
Weight : 745 kg
-NET communication
20 class series
Space Saving Design
Both systems can be
controlled by the
centralised controller,
which makes it simple to
operate.
D
-NET communication
VRV System
GHP System
Outdoor Unit Lineup
Heat Pump Standard Series
Combine with VRV system
Outdoor Unit Lineup
Heat Recovery Series
Outdoor Unit Lineup
SYSTEM
(Electric Heat Pump)
Space Saving Design
Simultaneous Heating and Cooling Operation
Footprint 1.35 m2
20 class
Indoor units with constant
comfort and unified design
Since both systems are
connected to the same indoor
units, both the comfort level
and operation procedures are
the same. The designs of
front panels, etc. can also be
consistent.
Footprint 1.68 m2
30 class
For Replacement Use
Water Cooled Model
For Small-sized Building
Control Systems
Heat Recovery Series
Indoor Unit Lineup
Footprint 1.68 m2
30 class
Capacity range
Heat pump
standard series
Heat pump
large-capacity series
Heat recovery series
03
22.4 kW
28.0 kW
35.5 kW
45.0 kW
56.0 kW
71.0 kW
85.0 kW
8 class
10 class
13 class
16 class
20 class
25 class
30 class
Common models of indoor units
Common models of indoor units
Common indoor models for both GHP and EHP systems ensure
a consistent look for exposed units whilst maintaining similar
comfort levels and keeping operational control.
Air Treatment
Equipment Lineup
DAIKIN GAS HEAT PUMP AIR CONDITIONING SYSTEM LINEUP
04
Outdoor Unit Lineup
Heat Pump Standard Series
Outdoor Unit Lineup
Heat Pump – Standard Series 8/10/13/16/20/25 class
Compact Design
Installation Flexibility
Compact, lightweight outdoor units increase installation flexibility.
Long piping length
8 / 10 / 13
class series
The long piping length provides more design flexibility, to meet the needs of large commercial buildings.
16 / 20 / 25
class series
Weight :
565 kg
2,077
mm
Max. actual
piping length
20 class series
165 m
745 kg
2,077
mm
13 class series
Weight :
880 mm
880 mm
Max. equivalent
piping length
190 m
*1
a
Max. total piping length
520 m
1,400 mm
1,660 mm
First indoor branch
Max. level difference
Footprint 1.23 m
2
b
h
e
d
c
i
j
between the outdoor units and
the indoor units
Footprint 1.46 m
2
g
f
k
Outdoor unit above indoor unit:
Compact size allows the outdoor unit
to be transported in an elevator.
The compact outdoor unit can be installed on
the service balcony of each floor.
(Unit: mm)
External static
pressure:
30 Pa
50 m
Outdoor unit below indoor unit:
40 m
Colours in the diagram above are merely for identifying pipes referenced with symbols such as a .
Actual
piping length
Example
Equivalent
piping length
Refrigerant piping length
165 m
a+f+g+h+i
190 m *1
Total piping length
520 m
a+b+c+d+e+f+g+h+i
—
Between the first indoor branch and the farthest indoor unit
60 m
f+g+h+i
—
Level
Difference
Example
15 m
k
If the outdoor unit is above.
50 m
j
If the outdoor unit is below.
40 m
j
*1
Elevator
Outdoor unit
Outdoor unit
8 / 10 / 13 class series
2,077
1,400
* Check the dimensions of
the elevator to be used.
* Allow the specified space for service.
A discharge duct may need to be
installed on the outdoor unit.
Maximum
allowable
piping length
Maintenance
space
Balcony
*1. Field setting is necessary.
880
Maximum
allowable
level difference
Wide Operating Range
Quiet Operation
System can operate under a wide range
of outdoor temperature.
Use of cutting edge technology delivers quiet
operations. Enabling the quiet mode further
lowers operating noise levels.
Heating
Cooling
−10°C
−10°C
18°C (WB)
43°C
dB(A) 60
55
54
52
56
57
45
40
Easy Maintenance
10 class
13 class
* The outdoor unit enters
power-saving operation in quiet
mode.
Frequent oil change is not required.
Engine oil needs to be topped up periodically to recommended operational uses. Oil change only required after 30,000hrs of operation.
* Use the engine oil specified by Daikin.
05
Connection ratio
Maximum connection ratio is 130%.
Connection ratio
50%–130%
Normal mode
Quiet mode
50
8 class
Between the outdoor units
and the indoor units
*1. When the equivalent piping length between outdoor and indoor units is 100 m or more, the size of main pipes (both gas-side and liquid-side) must be
increased.Refer to the Engineering Data Book.
59
54
Between the indoor units
Connection ratio =
Total capacity index of the indoor units
Capacity index of the outdoor units
Outdoor unit combination
Model name *1
GYAQ8ANV1
GYAQ10ANV1
GYAQ13ANV1
GYAQ16ANV1
GYAQ20ANV1
GYAQ25ANV1
kW
22.4
28.0
35.5
45.0
56.0
71.0
Class
8
10
13
16
20
25
Capacity
index
200
250
320
400
500
630
Total capacity index of connectable indoor units *2
Combination (%) *2
50%
100
125
160
200
250
315
100%
200
250
320
400
500
630
130%
260
325
416
520
650
819
Maximum number of
connectable indoor units
13
16
20
26
33
41
*1.Only single outdoor unit can be connected.
*2.Total capacity index of connectable indoor units must be 50%-130% of the capacity index of the outdoor unit.
06
Outdoor Unit Lineup
Heat Pump Standard Series
Outdoor Unit Lineup
Heat Pump – Standard Series 8/10/13/16/20/25 class
Operation range
INDOOR TEMPERATURE (°CWB)
Cooling operation
Model
GYAQ8ANV1
GYAQ10ANV1
Power supply
Gas
GYAQ13ANV1
1
Capacity
22.4
28.0
35.5
45.0
56.0
71.0
76,400
95,500
121,000
154,000
191,000
242,000
kcal/h
19,300
24,100
30,500
38,700
48,200
61,100
25.0
31.5
40.0
50.0
63.0
80.0
Btu/h
85,300
107,000
136,000
171,000
215,000
273,000
kcal/h
21,500
27,100
34,400
43,000
54,200
68,800
kW
2
Ivory white (9.9Y8.4/1.2)
mm
2,077
2,077
2,077
2,077
2,077
2,077
mm
1,400
1,400
1,400
1,660
1,660
1,660
Depth
mm
880
880
880
880
880
880
Height
Cooling
Power
consumption
Heating
kW
0.34
0.44
0.57
1.26
1.26
1.53
kW
0.42
0.58
0.74
1.11
1.11
1.34
Cooling
Fuel gas
consumption Heating
kW
15.0
19.2
26.4
31.0
41.7
58.5
kW
15.9
20.3
27.0
32.7
42.0
57.2
Scrollx1
Scrollx1
Scrollx1
Scrollx2
Scrollx2
Scrollx2
Type
Type
Propeller fan
Number of units
Motor output
W
Airflow rate
m3/min
2
2
2
2
2
2
275x2
275x2
275x2
350+600
350+600
600x2
167
194
213
346
346
388
15.9
15.9
15.9
Drive
Refrigerant
Piping
Direct drive
Liquid
mm
Gas
9.5
9.5
mm
19.1
22.2
25.4
28.6
28.6
31.8
inch
R3/4
R3/4
R3/4
R3/4
R3/4
R3/4
Exhaust vent outside dia.
mm
80
80
80
100
100
100
Drain pipe for exhaust inside dia. mm
30
30
30
30
30
30
565
565
565
745
745
755
R-410A
R-410A
R-410A
R-410A
R-410A
R-410A
11.0
11.0
11.0
11.5
11.5
11.5
62
kg
Type
Charge
kg
Engine Lubricant Type
Engine
coolant
14
-10
43
-10
0
10
20
30
OUTDOOR TEMPERATURE (°CDB)
40
OPERATION
10
10
-30
-10
-20
-10
18
0
10
20
OUTDOOR TEMPERATURE (°CWB)
Options
Option name
Cool/Heat selector *1
Fixing box
Harness kit for Cool/Heat Selector *2
REFNET header
Model
GYAQ8ANV1
GYAQ10ANV1
GYAQ16ANV1
GYAQ20ANV1
GYAQ25ANV1
KRC19-26A
KJB111A
AGKRC19E1
KHRP26M22H (Max. 4 branch)
KHRP26M33H (Max. 8 branch)
KHRP26M22H (Max. 4 branch)
KHRP26M33H (Max. 8 branch)
KHRP26M72H (Max. 8 branch)
KHRP26A22T
KHRP26A33T
KHRP26A22T
KHRP26A33T
KHRP26A72T
Distributive
piping
REFNET joint
GYAQ13ANV1
KHRP26M22H
KHRP26M33H
KHRP26M72H
KHRP26M73H
4
8
8
8
branch)
branch)
branch)
branch)
KHRP26A22T
KHRP26A33T
KHRP26A72T
KHRP26A73T
KHRP26M73TP
KHRP26M73HP
Pipe size reducer
Antivibration mount *3
Air direction adjuster *4
Deodorizer kit
(Max.
(Max.
(Max.
(Max.
K-GBM13B70
AGFJ280E1
AGBJ280E1
K-GBM13B71
AGFJ560E2
AGBJ560E1
*1. The Cool/Heat Selector is required when selecting cool/heat mode from the outdoor unit.
*2. The harness kit is required when using the Cooling/Heating Selector.
*3. Use an antivibration mount when operating noise or vibration could cause problems in lower floors or nearby rooms as a result of installing the outdoor unit on the roof.
The specified antivibration mount must be used. Otherwise abnormal vibration may occur.
*4. The Air direction adjuster is designed to prevent snow from accumulating on the air outlet of the outdoor unit and to change the air direction to the front or back if the air outlet is
blocked by an obstacle. If The Air direction adjuster is installed, the operation sound may increase slightly depending on ambient conditions.
Aisin Coolant S
Freezing temperature
-35
Normal mode
Sound
pressure level Quiet mode
dB(A)
54
56
59
56
59
dB(A)
52
54
57
54
57
60
Piping length;equivalent/actual
m
190/165
190/165
190/165
190/165
190/165
190/165
Height difference between O/U is above m
indoor and out door units O/U is below m
50
50
50
50
50
50
40
40
40
40
40
40
Height difference between indoor units m
15
15
15
15
15
15
13
16
20
26
33
41
50-130
50-130
50-130
50-130
50-130
50-130
Note:
10
RANGE FOR CONTINUOUS OPERATION
RANGE FOR CONTINUOUS
20
Aisin Gas Engine Oil L-10000G
Type
Connectable indoor units
07
12.7
Fuel gas pipe
Weight
Refrigerant
20
28
* If the unit is used out of the operation temperature range (especially at high outdoor temperature), it may malfunction, or the protection circuit may trip and deactivate the unit.
Dimensions Width
Fans
24
30
GYAQ25ANV1
Btu/h
Casing colour (Munsell no.)
Compressor
30
Natural gas
kW
Heating
GYAQ20ANV1
1- phase , 230 V , 50 Hz
Type
Cooling
GYAQ16ANV1
Heating operation
INDOOR TEMPERATURE (°CDB)
Specifications
number
capacity
%
1 Indoor temp.: 27 °CDB, 19°CWB / outdoor temp.: 35 °CDB / Equivalent piping length: 7.5 m, level difference: 0 m
2 Indoor temp.: 20 °CDB / outdoor temp.: 7°CDB, 6°CWB/ Equivalent piping length: 7.5 m, level difference: 0 m
08
Outdoor Unit Lineup
Space Saving Design
Installation flexibility
Space saving design allows for
flexible installation.
Long piping length
Weight :
Outdoor Unit Lineup
Heat Pump Large-capacity Series
Heat Pump – Large Capacity Series 30 class
The long piping length provides more design flexibility, which can match even large-sized buildings.
1080 kg
2,170
mm
Max. actual
piping length
Footprint 1.68 m2
800 mm
Max. equivalent
piping length
170 m
200 m
a
Max. total piping length
640 m
2,100 mm
The compact outdoor unit can be installed on the service balcony of each floor.
External static
pressure:
First indoor branch
c
Maintenance
space
*1. Field setting is necessary.
Wider Operating Range
System can operate under a wider
range of outdoor temperature.
Heating
−21°C
18°C (WB)
Cooling
−10°C
46°C
Quiet Operation
k
Colours in the diagram above are merely for identifying pipes referenced with symbols such as a .
dB(A) 65
60
Maximum
allowable
piping length
Maximum allowable
level difference
Use of cutting edge technology delivers
quiet operations. Enabling the quiet mode
further lowers operating noise levels.
i
50 m
Actual
piping length
Balcony
e
d
between the outdoor units and
the indoor units
*1
* Allow the specified space for service.
A discharge duct may need to be
installed on the outdoor unit.
b
h
j
Max. level difference
30 Pa
Outdoor unit
g
f
Example
Equivalent
piping length
Refrigerant piping length
170 m
a+f+g+h+i
200 m
Total piping length
640 m
a+b+c+d+e+f+g+h+i
—
Between the first indoor branch and the farthest indoor unit
90 m *1
f+g+h+i
—
Level
Difference
Example
Between the indoor units
15 m *1
k
Between the outdoor units and the indoor units
50 m
j
*1.When the piping length between the indoor branch and the farthest indoor unit is 40 m or more, the maximum allowable level difference between the indoor
units is decreased.Refer to the Engineering Data Book.
62
59
55
Normal mode
Connection ratio
Quiet mode
Maximum connection ratio is 130%.
Connection ratio
50%–130%
50
45
30 class
* The outdoor unit enters power-saving
operation in quiet mode.
Easy Maintenance
Frequent oil change is not required.
Engine oil needs to be topped up periodically to recommended operational uses. Oil change only required after 20,000hrs of operation.
Connection ratio =
Total capacity index of the indoor units
Capacity index of the outdoor units
Outdoor unit combination
Model name *1
GYAQ30ANV1
kW
85.0
Class
30
Capacity
index
750
Total capacity index of connectable indoor units *2
Combination (%) *2
50%
375
100%
750
130%
975
Maximum number of
connectable indoor units
48
*1.Only single outdoor unit can be connected.
*2.Total capacity index of connectable indoor units must be 50%-130% of the capacity index of the outdoor unit.
* Use the engine oil specified by Daikin.
09
10
Outdoor Unit Lineup
Heat Pump – Large Capacity Series 30 class
Specifications
Operation range
GYAQ30ANV1
Power supply
Gas
1- phase , 230 V , 50 Hz
Type
1
Capacity
290,000
kcal/h
73,100
Btu/h
2
kcal/h
Casing colour (Munsell no.)
95.0
324,000
81,700
Ivory white(5Y7.5/1)
mm
2,170
Dimensions Width
mm
2,100
Depth
mm
800
Cooling
Power
consumption Heating
kW
1.66
kW
1.51
Cooling
Fuel gas
consumption Heating
kW
67.7
Height
Compressor
kW
66.3
Type
Scrollx2
Type
Propeller fan
Number of units
Fans
3
Motor output
W
Airflow rate
m3/min
Drive
570
Direct drive
mm
Gas
mm
31.8
Fuel gas pipe
inch
R3/4
Exhaust vent outside dia.
mm
60.5
Drain pipe for exhaust inside dia. mm
Weight
Refrigerant
370x3
Liquid
Refrigerant
Piping
20
10
(Note 1)
RANGE FOR CONTINUOUS OPERATION
14
-10
-10
46
0
10
20
30
OUTDOOR TEMPERATURE (°CDB)
40
50
30
RANGE FOR CONTINUOUS OPERATION
20
15
-21
18
10
-30
-20
-10
0
10
20
OUTDOOR TEMPERATURE (°CWB)
Note 1: An optional air guard is required.
* If the unit is used out of the operation temperature range (especially at high outdoor temperature), it may malfunction, or the protection circuit may trip and deactivate the unit.
85.0
Btu/h
kW
Heating
25
30
Natural gas
kW
Cooling
30
Outdoor Unit Lineup
Heat Pump Large-capacity Series
Model
Heating operation
INDOOR TEMPERATURE (°CDB)
INDOOR TEMPERATURE (°CWB)
Cooling operation
kg
Type
19.1
Option name
Cool/Heat selector
Fixing box
REFNET header
Distributive
piping
REFNET joint
Pipe size reducer
Antivibration mount *1
Air direction adjuster
Air guard
Exhaust extension adaptor
Exhaust extension external drain filter
Water discharge kit
External contact output harness *2
Model
GYAQ30ANV1
KRC19-26A
KJB111A
KHRP26M22H
KHRP26M33H
KHRP26M72H
KHRP26M73H
(Max.
(Max.
(Max.
(Max.
4
8
8
8
branch)
branch)
branch)
branch)
KHRP26A22T
KHRP26A33T
KHRP26A72T
KHRP26A73T
KHRP26M73TP , KHRP26M73HP
YGAS850J1
FKA850H
ARD850H
HA850H
DFB19E
RGA850H1
OSH850J
*1. Use an antivibration mount when operating noise or vibration could cause problems in lower floors or nearby rooms as a result of installing the outdoor unit on the roof.
The specified antivibration mount must be used. Otherwise abnormal vibration may occur.
*2. Only use of input contact point is possible. Use of output contact point is not possible. (only for 30 class heat pump)
15
1080
R-410A
Charge
kg
Engine Lubricant Type
11.8
Yanmar genuine GHP oil
Engine
coolant
Type
Sound
pressure level
Normal mode
dB(A)
Quiet mode
dB(A)
Yanmar genuine LLC (for GHP)
Freezing temperature
Piping length;equivalent/actual
-35
m
62
59
200/170
Height difference between O/U is above m
indoor and out door units O/U is below m
50
Height difference between indoor units m
15
Connectable indoor units
Options
number
capacity
50
48
%
50-130
Note:
1 Indoor temp.: 27 °CDB, 19 °CWB / outdoor temp.: 35 °CDB / Equivalent piping length: 7.5 m, level difference: 0 m
2 Indoor temp.: 20 °CDB / outdoor temp.: 7°CDB, 6°CWB/ Equivalent piping length: 7.5 m, level difference: 0 m
11
12
Outdoor Unit Lineup
Heat Recovery Series 20/30 class
Heat Recovery Operation
Large Capacity & Space Saving Design
Simultaneous heating and cooling operation within refrigerant system
Space –saving outdoor units allow flexible installation.
BS unit
Indoor unit
(Heating)
800 mm
Indoor unit
(Cooling)
1,690 mm
Heat radiation operation
(all cooling operation)
BS
Unit
Heat radiation
cooling
cooling
cooling
Indoor Unit
For example,
the heat recovery system can
meet the following needs:
2,100 mm
Footprint 1.35 m2
Heat recovery operation mode
Outdoor Unit
1040 kg
2,170
mm
800 mm
Heat recovery operation!
(A)
Weight :
860 kg
2,170
mm
By adding suction gas piping and a BS
unit (sold separately), simultaneous
heating and cooling operation can be
provided by a single system.
BS unit
30 class
series
Weight :
BS unit
High and low pressure gas piping
Suction gas piping
Liquid piping
Outdoor unit
20 class
series
Footprint 1.68 m2
The compact outdoor unit can be installed on the balcony of each floor.
cooling
External static
pressure:
Heat radiation tendency
heat recovery operation
(B)
cooling,
( mainly
part heating operation )
Heat radiation
Outdoor Unit Lineup
Heat Recovery Series
In mainly cooling, partly heating mode, the system recycles heat exhausted from the cooling operation to use for heating.
In mainly heating, partly cooling mode, the system uses cooled post-heating operation refrigerant for cooling. Efficiency
improves when simultaneous operation is performed.
Heating
Window
cooling
cooling
cooling
Cooling
Cooling
BS unit
*1
* Allow the specified space for service.
A discharge duct may need to be
installed on the outdoor unit.
heating
Heat recovery operation
30 Pa
Outdoor unit
Office building in transition period to winter
(cooling and heating operation)
The difference between heat generated from the interior zone
and the cool air load in the perimeter zone is large.
(C)
Maintenance
space
Balcony
*1. Field setting is necessary.
cooling
cooling
heating
heating
Heat absorption tendency
heat recovery operation
(D)
Heat absorption
Cooling
Heating
heating,
( mainly
part cooling operation )
BS unit
cooling
heating
heating
Hallway
heating
Wide Operating Range
Quiet Operation
System can operate under a wide
range of outdoor temperature.
Use of cutting edge technology delivers
quiet operations. Enabling the quiet mode
further lowers operating noise levels.
Hotel in transition period
Heat absorption operation
Indoor units can independently meet the need for cooling
and heating.
(all heating operation)
(E)
heating
heating
heating
heating
Heating
−11°C
18°C (WB)
Cooling
−10°C
43°C
Note: Operation modes (A) and (E) are applicable when the outdoor temperature is 35°C and 7°C respectively;
The other modes are applicable under typical outdoor conditions.
dB(A) 65
60
55
62
58
59
55
Normal mode
Quiet mode
50
Thanks to the heat recovery system.
13
* The outdoor unit enters power-saving
operation in silent mode.
45
20 class
Automatic cooling-heating switching
Heat recovery saves energy
The system automatically switches the
operation mode to cooling or heating based on
the difference between the set temperature and
the indoor temperature. It is not necessary to
use the remote controller to switch the
operation mode to cooling or heating.
Operation efficiency can be
further increased by
recovering cooling exhaust
heat within the same system
and using it effectively as
heating energy.
30 class
Easy Maintenance
Heating
Cooling
Cooling exhaust heat is
recovered
as heating energy.
Frequent oil change is not required.
Engine oil needs to be topped up periodically to recommended operational uses. Oil change only required after 20,000hrs of operation.
* Use the engine oil specified by Daikin.
14
Outdoor Unit Lineup
Heat Recovery Series 20/30 class
Installation Flexibility
Specifications
Long piping length
The long piping length provides more design flexibility, which can match even large-sized buildings.
Max. actual
piping length
Max. equivalent
piping length
170 m
200 m
640 m
First indoor branch
Max. level difference
between the outdoor units and the indoor units
g
f
b
Model
h
d
c
GYEQ20AN
Power supply
e
Gas
i
Natural gas
Type
kW
Cooling
j
1
Capacity
50 m
k
56.0
85.0
Btu/h
191,000
290,000
kcal/h
48,200
73,100
kW
Heating
2
63.0
95.0
Btu/h
215,000
324,000
kcal/h
54,200
Casing colour (Munsell no.)
Maximum
allowable
piping length
Actual
piping length
Example
Refrigerant piping length
170 m
a+f+g+h+i
200 m
Total piping length
640 m
a+b+c+d+e+f+g+h+i
—
f+g+h+i
—
Between the first indoor branch and the farthest indoor unit
90 m*
1
Equivalent
piping length
mm
2,170
2,170
mm
1,690
2,100
Depth
mm
800
800
Cooling
Power
consumption
Heating
kW
1.17
1.77
kW
1.10
1.57
Cooling
Fuel gas
consumption Heating
kW
47.4
67.7
kW
46.6
66.3
Scrollx2
Scrollx2
Compressor
Type
Type
Propeller fan
Number of units
Maximum allowable
level difference
Level
Difference
Example
Between the indoor units
15 m*1
k
Between the outdoor units and the indoor units
50 m
j
Fans
50%–130%
Connection ratio =
Total capacity index of the indoor units
Capacity index of the outdoor units
20
30
Capacity
index
500
750
Total capacity index of connectable indoor units *2
Combination (%) *2
50%
250
375
*1.Only single outdoor unit can be connected.
*2.Total capacity index of connectable indoor units must be 50%-130% of the capacity index of the outdoor unit.
100%
500
750
130%
650
975
Maximum number of
connectable indoor units
32
48
570
15.9
19.1
28.6
31.8
mm
22.2
28.6
Fuel gas pipe
inch
R3/4
R3/4
Exhaust vent outside dia.
mm
60.5
60.5
kg
Refrigerant
Type
Charge
kg
15
15
860
1040
R-410A
R-410A
11.8
Engine Lubricant Type
11.8
Yanmar genuine GHP oil
Type
Yanmar genuine LLC (for GHP)
Freezing temperature
-35
Sound
pressure level Quiet mode
dB(A)
58
dB(A)
55
59
Piping length;equivalent/actual
m
200/170
200/170
Height difference between O/U is above m
indoor and out door units O/U is below m
50
50
50
50
Height difference between indoor units m
15
15
Connectable indoor units
Note:
15
380
mm
Normal mode
outdoor unit combination
Class
370x3
mm
Weight
Connection ratio
3
370x2
Direct drive
Discharge
Engine
coolant
56.0
85.0
m3/min
Drain pipe for exhaust inside dia. mm
Maximum connection ratio is 130%.
GYEQ20AN
GYEQ30AN
Airflow rate
Refrigerant Suction
Piping
kW
W
Liquid
1. When the piping length between the indoor branch and the farthest indoor unit is 40 m or more, the maximum allowable level difference between the indoor units is
decreased.Refer to the Engineering Data Book.
Model name *1
Motor output
2
Drive
Connection ratio
81,700
Ivory white(5Y7.5/1)
Dimensions Width
Height
Colours in the diagram above are merely for identifying pipes referenced with symbols such as a .
GYEQ30AN
1- phase , 200 V , 50 Hz
Outdoor Unit Lineup
Heat Recovery Series
a
Max. total piping length
number
capacity
%
62
32
48
50-130
50-130
1 Indoor temp.: 27 °CDB, 19 °CWB / outdoor temp.: 35 °CDB / Equivalent piping length: 7.5 m, level difference: 0 m
2 Indoor temp.: 20 °CDB / outdoor temp.: 7 °CDB, 6 °CWB/ Equivalent piping length: 7.5 m, level difference: 0 m
16
Outdoor Unit Lineup
Heat Recovery Series 20/30 class
BS Unit: Specifications
Operation range
Heating operation
25
20
10
(Note 1)
RANGE FOR CONTINUOUS OPERATION
14
-10
-10
43
0
10
20
30
OUTDOOR TEMPERATURE (°CDB)
40
30
30
RANGE FOR CONTINUOUS
OPERATION
20
15
18
-11
10
-30
-20
-10
0
10
20
OUTDOOR TEMPERATURE (°CWB)
Note 1: An optional air guard is required.
* If the unit is used out of the operation temperature range (especially at high outdoor temperature), it may malfunction, or the protection circuit may trip and deactivate the unit.
MODEL
BSGQ100PV1
Power supply
Total capacity index of connectable indoor units
No. of connectable indoor units
Model
GYEQ20AN
GYEQ30AN
KRC19-26A
KJB111A
REFNET header
KHRP25M33H (Max. 8 branch)
KHRP25M72H (Max. 8 branch)
KHRP25M73H (Max. 8 branch)
REFNET joint
KHRP25A22T,KHRP25A33T
(KHRP25A72T+KHRP25M72TP)
(KHRP25A73T+KHRP25M73TP)
Distributive
piping
Antivibration mount *1
Air direction adjuster
Air guard
Exhaust extension adaptor
Exhaust extension external drain filter
Water discharge kit
External contact output harness
20 to 100
More than 100 but 160 or less
More than 160 but 250 or less
Max. 5
Max. 8
Max. 8
Casing
Galvanised steel plate
Dimensions (HXWXD)
Option name
Cool/Heat selector
Fixing box
YGAS560J1
FKA560H
ARD560H
Piping
connections
Indoor Liquid
Unit
Gas
YGAS850J1
FKA850H
ARD850H
Notes:
mm
mm
Liquid
Outdoor
mm
Suction gas
Unit
High and low pressure gas
Machine weight
Sound level
BSGQ250PV1
1
No. of branches
Outdoor Unit: Options
BSGQ160PV1
1-phase, 220-240 V, 50 Hz
207x388x 326
9.5 (Brazing) 1
9.5 (Brazing)
9.5 (Brazing)
15.9 (Brazing) 1
15.9 (Brazing) 2
22.2 (Brazing) 3
9.5 (Brazing)
9.5 (Brazing)
9.5 (Brazing)
15.9 (Brazing)
15.9 (Brazing) 2
22.2 (Brazing) 3
12.7 (Brazing)
12.7 (Brazing) 2
kg
12.0
12.0
dB(A)
42 (32) 4
43 (32) 4
Outdoor Unit Lineup
Heat Recovery Series
30
INDOOR TEMPERATURE (°CDB)
INDOOR TEMPERATURE (°CWB)
Cooling operation
19.1 (Brazing) 3
15.0
44 (34) 4
1 When connecting with an indoor unit with a capacity index between 20 and 50, connect the attached pipe to the field pipe. (Braze the connection between the attached and field pipe.)
2 When connecting with indoor units with total capacity indexes between 150 and 160, connect the attached pipe to the field pipe. (Braze the connection between the attached and field pipe.)
3 When connecting with indoor units with a capacity index of 200, or with total capacity indexes between 160 and 200, connect the attached pipe to the field pipe.
(Braze the connection between the attached and field pipe.)
4 Figures in brackets ( ) indicate sound levels when the all indoor units connected to the BS unit are not operating but other indoor units within the same system are operating.
HA850H
DFB19E
RGA850H1
OSH850J
*1. Use an antivibration mount when operating noise or vibration could cause problems in lower floors or nearby rooms as a result of installing the outdoor unit on the roof.
The specified antivibration mount must be used. Otherwise abnormal vibration may occur.
17
18
Indoor Unit Lineup
Daikin’s indoor units are available in 90 models of 16 types to deliver comfortable
air conditioning whilst matching the varied requirements of the modern office and
residential building.
Ceiling Suspended Type
Wall Mounted Type
Slim body with quiet and wide
airflow
Stylish flat panel design
harmonised with your interior
décor
Lineup
FXFQ-SVM
Ceiling Mounted Cassette
(Round Flow) Type
FXFQ-PVE
To be launched
in June 2014
Presence of people and floor
temperature can be detected to
provide comfort and energy savings
Ceiling Mounted Cassette
(Compact Multi Flow) Type
Quiet, compact, and designed for
user comfort
Floor Standing Type
360 airflow improves temperature
distribution and offers a
comfortable living environment.
4-Way Flow Ceiling
Suspended Type
This slim and stylish indoor unit
achieves optimum air distribution,
and can be installed without the
need for ceiling cavity.
Concealed Floor Standing Type
Suitable for perimeter zone air
conditioning
Indoor units
(kW)
2.2
2.8
3.6
4.5
FXFQ-SVM
To be launched
in June 2014
Ceiling Mounted Cassette
(Double Flow) Type
Thin, lightweight, and easy to install in
narrow ceiling spaces
Slim Ceiling Mounted Duct Type
FXDQ-PBVE
FXFQ-PVE
Ceiling Mounted Cassette
Corner Type
8
9
11.2
14
16
145
16.2
145
180
20
180
22.4
28
Ceiling Mounted Built-in Type
FXSYQ-MVE
FXDQ-NBVE
Ceiling Concealed
(Duct) Type
7.1
Slim design for flexible installation
Ceiling Mounted
Built-in
Slim design, quietness and
static pressure switching
5.6
Indoor Unit Lineup
Ceiling Mounted Cassette
(Round Flow with Sensing) Type
Ceiling Concealed
(Duct)
FXSYQ-MVE
FXDYQ-M(A)V1
Highly flexible for various
application
Ceiling Mounted Duct Type
FXDYQ-M(A)V1
High static pressure offers flexible
duct design that blends in with any
interior décor in stores and offices
19
High external static pressure
allows flexible installations
This FXUQ model is not compatible both Heat Pump 30 class and Heat Recovery systems.
20
Indoor Unit Lineup
Ceiling Mounted Cassette (Round Flow with Sensing) Type
Airflow block function *3
Auto airflow rate mode + Auto airflow direction mode
FXFQ25S/FXFQ32S/FXFQ40S
Floor temperature is detected and over cooling prevented.
FXFQ50S/FXFQ63S/FXFQ80S
Without sensing function
FXFQ100S/FXFQ125S
To be launched
in June 2014
With sensing function
Room temperature is
calculated as 27°C in the area which
is in the vicinity of the person.
Infrared presence sensor
24°C near floor
The floor temperature, which is lower
than near the ceiling, is detected.
Energy savings
The temperature near the person is automatically calculated by
detecting the temperature of the floor. Energy is saved, because
the area around the feet does not get too cold.
Indoor unit offers 360° airflow discharges air in all
directions with more uniform temperature distribution.
Sensing sensor mode
Infrared floor sensor
The sensor detects the floor temperature and automatically
adjusts operation of the indoor unit to reduce the temperature
difference between the ceiling and the floor.
Individual airflow direction control
Thanks to the individual airflow direction control function, airflow
direction can be individually adjusted for each air discharge
outlet. 5 directions of airflow and auto-swing can be selected
with wired remote controller BRC1E62, which realises the
optimum air distribution.
Individual airflow direction example case
21
Position 2
Swing
Comfortable airflow
Airflow rate automatically increases during hot or cold periods (when there
is a large difference with set temperature), and operation is rapidly
performed for cooling or heating.When the difference with set temperature
becomes small, drafts are prevented by automatically reducing airflow rate,
and raising the flap to a horizontal position during cooling operation.
Dead spot of airflow
Energy efficiency has been improved thanks to the
adoption of a new heat exchanger with smaller tubes,
DC fan motor and DC drain pump motor.
Low operation sound level
FXFQ-S
Sound
level
(H/M/L)
25/32
40
50
63
80
100
125
30/28.5/27 31/29/27 36/32/28 38/33/28 38/35/31 44/38/32 45/40/35
Control of airflow rate can be selected from 3-step
control, which provides comfortable airflow. Auto airflow
rate control can be selected with wired remote controller
BRC1E62.
Drain pump is equipped as
standard accessory with 850 mm
lift.
Airflow block function prevents uncomfortable
drafts by reducing air velocity to approx. 0.3m/s.*4
Airflow block
for cabinet side
Also can support
such this case
New airflow block function prevents
uncomfortable drafts by reducing air velocity.
It can be set using the BRC1E62 remote controller.
There is no need for sealing material of air discharge
outlet (option).
This function only works when all-round flow
is used. It cannot be used when sealing material is
used in the air discharge outlet (option).
Easy setup with remote controller
Sensing sensor low mode *1. 2
When there are no people in a room,
the set temperature is shifted automatically.
850 mm
Example: • Cooling setpoint: 26°C
• Shift temperature: 1.0°C
Setpoint (°C)
Detecting the
average
temperature of
indoor floor
Position 3
Automatic
control using
the temperature
near the person
as the room
temperature.
30°C near ceiling
Dual sensors detect the presence of people and floor temperature
to provide comfortable air-conditioning and energy savings.
Position 0
Area around feet gets
too cold because air
conditioner continues
until the temperature
near the ceiling reaches
the set temperature.
Room
temperature is
detected as
30°C.
20°C near floor
Presence of
people in 4
areas
Airflow block
air velocity
approx. 0.3m/s*4
30°C near ceiling
Presence of people and floor temperature can be
detected to provide comfort and energy savings
The sensor detects human presence and adjusts
the airflow direction automatically to prevent drafts.
Energy saving control can be performed
when no people are detected.
Total comfort by individual airflow direction control
and newly-equipped “airflow block function”
Indoor Unit Lineup
Sensing function
28
27
26
27°C
26°C
Occupied
• Shift time: 30 min.
• Limit cooling temperature: 30°C
28°C
Unoccupied
After 30 min
After another 30 min
26°C
Automatically
reverts when
people return.
Horizontal flow
The airflow block function is
useful when rearranging the
room layout.
Time
If people do not return, the air conditioner will raise the
temperature 1°C every 30 minutes and then operate at 30°C.
Shift temperature and time can be selected from 0.5 to 4°C in 0.5°C increments
and 15, 30, 45, 60, 90 or 120 minutes respectively with remote controller.
Airflow block
Airflow
block
500 mm*5
Wall
*3. Works in one direction only.
*4. In case of FXFQ63S type (Data is based on Daikin research.)
*5. A gap of 1500 mm is required if the air block function is not used.
Sensing sensor stop mode *1. 2
When there are no people in a room, the system
stops automatically.
Absent stop time can be selected from 1 to 24 hrs in 1 hr
increments with remote controller.
*1. These functions are not available when using the group control system.
*2. User can set these functions with remote controller.
22
Indoor Unit
UnitsLineup
Ceiling Mounted Cassette (Compact Multi Flow) Type
Ceiling Mounted Cassette (Round Flow) Type
FXFQ25P/FXFQ32P/FXFQ40P
FXZQ20M / FXZQ25M / FXZQ32M
FXFQ50P/FXFQ63P/FXFQ80P
FXZQ40M / FXZQ50M
FXFQ100P/FXFQ125P
360° airflow improves temperature distribution
and offers a comfortable living environment.
The industry’s first* Round Flow Ceiling Mounted
Cassette type offers 360° airflow with improved
temperature distribution.
4-way flow
Quiet, compact, and designed for user comfort
Dimensions correspond with 600 mm X 600 mm
architectural module ceiling design specifications.
Low operation sound level
Round Flow
(240 V)(dB(A))
FXZQ-M
20/25
32
40
50
Sound level
(H/L)
32/26
34/28
37/29
42/35
Comfortable airflow
1
There are much fewer
areas of uneven temperature.
Wide discharge angle: 0° to 60°
Indoor Unit Lineup
There are areas of
uneven temperature.
Auto swing
* As of April 2004, the release date for Japan.
The light weight unit at 19.5 kg for FXFQ25-50P
models makes installation easy.
Drain pump is equipped as a
standard accessory with a 850 mm
lift.
A modern sophisticated decoration panel has been
applied, with a panel surface that has been treated with
a dirt-repellant coating.
Treated surface
Untreated surface
Dirt and
grime • Condition after
exposure to the
smoke of 600
3
cigarettes in 1 m
enclosed space.
Resists
soiling
Control of the airflow rate can be selected from 3-step
control.
Low operation sound level
FXFQ-P
25/32
40
50
(dB(A))
63
80
100
125
Sound
level
30/28.5/27 31/29/27 32/29.5/27 34/31/28 36/33.5/31 43/37.5/32 44/39/34
(HH/H/L)
Example of airflow patterns:
0°
850 mm
All-round flow
60°
60°
Fixed angles: 5 levels
An antibacterial treatment that uses silver ions has
been applied to the drain pan, preventing the growth
of slime, mould and bacteria that cause blockages
and odours.
The horizontal louvres prevent dew condensation.
Their non-flocking surfaces, which repel dirt, are
easy to clean.
The air filter has an anti-mould and antibacterial
treatment that prevents the growth of mould
generated from dust or moisture that may adhere to
the filter.
4-way flow
3-way flow
0°
0°
60°
Drain pump is equipped as standard accessory with
750 mm lift.
60°
*Angles can be also set on site to prevent drafts (0°-35°)
or soiling of the ceiling (25°-60°), other than standard setting (0°-60°).
2
2-, 3-, and 4-way airflow patterns are available,
enabling installation in the corner of a room.
750 mm
L-shaped 2-way flow
All-round flow is available, as well as 2-way to
4-way flows, so you can choose the most
suitable airflow pattern depending on location or
room layout.
Note: Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing material (option) must be used to close each unused outlet.
23
0°
4-way flow
3-way flow
L-shaped
2-way flow
*For 3-way or 2-way flow installation, the sealing member for air discharge outlet
(option) must be used to close each unused outlet.
24
Indoor Unit
UnitsLineup
Ceiling Mounted Cassette (Double Flow) Type
4-Way Flow Ceiling Suspended Type
FXCQ20M/FXCQ25M/FXCQ32M
FXCQ40M/FXCQ50M/FXCQ63M
FXUQ71A/FXUQ100A
FXCQ80M/FXCQ125M
This model is not compatible both Heat Pump 30 class and Heat
Recovery systems.
This slim and stylish indoor unit achieves
optimum air distribution, and can be installed
without the need for ceiling cavity.
Unit body and suction
panel adopted round
shapes and realised a
slim appearance design.
The unit can be used for
various locations such as
the ceilings with no cavity
and bare ceilings.
Thin, lightweight, and easy to install in
narrow ceiling spaces
The thin unit (only 305 mm high) can be installed in a
ceiling space as narrow as 350 mm. All models feature a
compact design with a depth of only 600 mm.
Indoor Unit Lineup
305 mm
(When a high-efficiency filter is attached, the unit's height is
400 mm.)
Flaps close automatically when the unit stops, which gives
a simple appearance.
Unified slim height of 198 mm
for all models that gives the
unified impression even when
models with different
capacities are installed in the
same area.
198 mm
With adoption of the individual flap control, airflow
direction adjustment can be individually set for each air
outlet. 5 directions of airflow and auto-swing can be
selected with wired remote controller BRC1E62, which
realises the optimum air distribution.
Low operation sound level
Control of the airflow rate has been improved from
2-step to 3-step control. Auto airflow rate control can
be selected with wired remote controller BRC1E62.
Energy efficiency has been improved thanks to the
adoption of a new heat exchanger with smaller
tubes, DC fan motor and DC drain pump motor.
Drain pump is equipped as a standard accessory, and the
lift height has been improved from 500 mm to 600 mm.
Depending on installation site requirements or room
conditions, 2-way, 3-way and 4-way discharge
patterns are available.
4-way flow
3-way flow
(240 V)(dB(A))
FXCQ-M
20
25/32
40/50
63
80
125
Sound level
(H/L)
34/29
36/30
37/32
39/34
41/36
46/40
Designed with higher airflow suitable for high ceiling
application up to 3 metres.
Providing 2 different settings of standard and ceiling soiling
prevention, the auto swing mechanism realises even
distribution of airflow and room temperature.
Drain pump is equipped as standard accessory with
600 mm lift.
Two types of optional high-efficiency filter are available
(65% and 95%, colourimetric method).
A long-life filter (maintenance free up to one year*) is
equipped as standard accessory.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
Individual airflow direction example case
Position 0
Position 2
600 mm
Position 3
25
Swing
L-shaped 2-way flow
Major maintenance work can be performed by removing
the panel. A flat-type suction grille and a detachable
blade make cleaning easy.
26
Indoor Unit Lineup
Slim Ceiling Mounted Duct Type
Ceiling Mounted Cassette Corner Type
Slim design, quietness and
static pressure switching
FXKQ25MA/FXKQ32MA
FXKQ40MA/FXKQ63MA
Suited to use in drop-ceilings!
Slim design for flexible installation
Providing 3 different settings of standard, draft
prevention and ceiling soiling prevention, the
auto swing mechanism realises even
distribution of airflow and room temperature.
(m)
3
Min.195 mm
Panel spacer
20 mm
Single-flow type allows effective air discharge
from corner or from drop-ceiling.
Drain pump is equipped as standard
accessory with 500 mm lift.
2
28˚C
32˚C 30˚C
26˚C
Only 700 mm in width and 23 kg in weight, this
model is suitable to install in limited spaces like
drop-ceilings in hotels.
Great for
hotel use!
22˚C
20˚C
1
2
3
4
5
Only
6 (m)
200 mm
700 mm
200 mm
900 mm
* 1,100 mm in width for the FXDQ63NB model.
Front discharge is possible with an air
discharge unit (option), which allows the
installation in the drop-ceiling or sagging wall.
Suspension bolt*
Air filter
240 mm
AIR
Main body
500 mm
Only 200 mm in height, this model can be installed in
rooms with as little as 240 mm depth between the
drop-ceiling and ceiling slab.
24˚C
1
0
FXDQ40NB /FXDQ50NB / FXDQ63NB
Indoor Unit Lineup
Slim body needs only 220 mm space above the
ceiling. If you use a panel spacer (option), the
unit can be installed in the minimum space of
195 mm.
FXDQ20PB /FXDQ25PB /FXDQ32PB
Discharge grille *
AIR
Downward discharge
Suction grille *
* To be obtained locally
External static pressure selectable by remote controller
switching make this indoor unit a very comfortable and
flexible model.
Air discharge grille (Option)
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models.
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models.
Set for front discharge using a suspended ceiling.
Drain pump is equipped as standard accessory with
750 mm lift.
Main body
Air discharge grille
(Option)
Downward discharge is shut off and air is blown straight out
(front discharge).
A long-life filter (maintenance free up to one
year*) is equipped as standard accessory.
Control of the airflow rate has been improved from 2-step
to 3-step control.
Low operation sound level
750 mm
(dB(A))
FXDQ-PB/NB
20/25/32
40
50
63
Sound level
(HH/H/L)
33/31/29
34/32/30
35/33/31
36/34/32
Ceiling
* The values of operation sound level represent those for rear-suction operation.
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).
* Values are based on the following conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure
of 15 Pa.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
27
28
Indoor Unit
UnitsLineup
Ceiling Concealed (Duct) Type
Ceiling Mounted Built-in Type
FXSYQ20M/FXSYQ25M/FXSYQ32M
FXSYQ40M/FXSYQ50M /FXSYQ63M
FXSYQ80M/FXSYQ100M
FXSYQ125M
FXDYQ80MA/FXDYQ100MA
FXDYQ125MA/FXDYQ145MA
FXDYQ180M/FXDYQ200M
FXDYQ250M
High static pressure offers flexible duct design
that blends in with any interior décor in stores and offices
Highly flexible for various application
Installation examples ( Optional parts)
Highly flexible installation is possible with a
complete lineup of optional kits to satisfy
various needs, such as the design concept,
interior decoration and so on.
Standard
Cassette style (standard filter)
Long-life filter
High efficiency Hi-X heat exchanger
coils that provide even more energy
savings.
Air suction
canvas bellows
The unit can be installed, if there is a space
of 350 mm above ceiling.
(when suction panel is used.)
Air suction panel
Cassette style (high efficiency filter)
High efficiency
filter
Air suction
canvas bellows
With duct
Min.
350 mm
Air suction panel
Screening
door
Drain pump is equipped as standard
accessory with 250 mm lift.
Access panel
High external static pressure allows
comprehensive duct layout for various
applications.
120 Pa for FXDYQ80MA–145MA
150 Pa for FXDYQ180M
180 Pa for FXDYQ200M
200 Pa for FXDYQ250M
Ceiling return
Indoor Unit Lineup
Long-life filter
Long-life filter
Access panel
Design of indoor units allows installation
in limited roof spaces.
250 mm
Return air spigots included for ease of
installation for FXDYQ80MA-145MA
models.
High external static pressure allows the use of flexible
ducts of various length.
Low operation sound level
FXSYQ-M
Sound level
(H/L)
20/25/32
40
41/33.5 41/34.5
(230 V)(dB(A))
50
63
80/100
125
43/37
45/38.5
48/43
49/41.5
The values of operation sound level are based on Australian Standard 1217.6-1985.
Measurement is based on bottom-return air entry.
29
Two external static pressure settings for
added flexibility.
Quiet yet powerful supply air fan.
High strength galvanised steel casing.
30
Indoor Unit Lineup
Ceiling Suspended Type
Ceiling Mounted Duct Type
FXMQ20P/FXMQ25P/FXMQ32P
FXMQ40P/FXMQ50P/FXMQ63P
FXMQ80P/FXMQ100P/FXMQ125P
FXMQ140P
FXHQ32MA/FXHQ63MA
FXHQ100MA
Slim body with quiet and wide airflow
Middle and high static pressure
allows for flexible duct design
Adoption of QUIET STREAM FAN
Uses the quiet stream fan and many
more advanced technologies.
A DC fan motor increases the external static
pressure capacity range to include middle to high
static pressures, increasing design flexibility.
Sound absorption
member
30 Pa–100 Pa for FXMQ20P-32P
30 Pa–160 Pa for FXMQ40P
50 Pa–200 Pa for FXMQ50P-125P
50 Pa–140 Pa for FXMQ140P
Drain pump is equipped as
standard accessory with
700 mm lift.
Control of the airflow rate has been improved
from 2-step to 3-step control.
Low operation sound level
(dB(A))
32
40
50
63
80/100
125
140
Sound
level 33/31/29 34/32/30 39/37/35 41/39/37 42/40/38 43/41/39 44/42/40 46/45/43
(HH/H/L)
Energy-efficient
The adopted DC fan motor is much more efficient than
the conventional AC motor, yielding an approximate
20% decrease in energy consumption (FXMQ125P).
FXMQ200MA/FXMQ250MA
Quiet stream fan
Straightening vane
Low operation sound level
700 mm
Ceiling
FXMQ-P 20/25
Turbulent flow
is produced
Improved ease of installation
Airflow rate can be controlled using a remote controller during
test operation. With the conventional model, the airflow rate
was controlled from the PC board. It is automatically adjusted to
the range between approximately ±10% of the rated HH tap
airflow for FXMQ20P–125P.
Housing the drain pump inside the unit reduces the
space required for installation.
Without drain pump
32
63
100
Sound level
(H/L)
36/31
39/34
45/37
Installation is easy
Drain pump kit (option) can be easily incorporated.
600 mm
Wide air discharge openings produce a spreading 100°
airflow.
470 mm
Simplified Static Pressure Control
External static pressure can be easily adjusted using
a change-over switch inside the electrical box to meet
the resistance in the duct system.
31
25 mm
Indoor unit
222 mm
Bristle-free Flap minimises
contamination and makes
cleaning simpler.
Non-dew Flap
Easy-to-clean flat design
Maintenance is easier because everything can be
performed from below the unit.
0–250
470 mm
Maintenance is easy
Non-dew Flap with no implanted bristles
Drain pump kit
(built inside main unit)
With drain pump
mm
(dB(A))
FXHQ-MA
Improved ease of maintenance
The drain pan can be detached for easy cleaning. An
antibacterial treatment that uses silver ions has been applied to
the drain pan, preventing the growth of slime, mould and
bacteria that cause blockages and odours.
Built-in Drain Pump (Option)
Indoor Unit Lineup
All models are only 300 mm in height, an
improvement over the 390 mm height of
conventional models. The weight of the
FXMQ40P has been reduced from 44 kg to 28 kg.
100°
A long-life filter (maintenance free up to one year*) is
equipped as standard accessory.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
Indoor unit
32
Indoor Unit Lineup
Floor Standing Type
Wall Mounted Type
FXAQ20P/FXAQ25P
FXLQ20MA/FXLQ25MA
FXAQ50P/FXAQ63P
FXLQ50MA/FXLQ63MA
FXLQ32MA/FXLQ40MA
FXAQ32P/FXAQ40P
Stylish flat panel design harmonised
with your interior décor
Stylish flat panel design creates a graceful harmony that
enhances any interior space.
Flat panel can be cleaned with only the single pass of a
cloth across their smooth surface.
Flat panel can also be easily removed and washed for
more thorough cleaning.
The adoption of a fibre-less discharge grille featuring an
original design to prevent condensation also helps
prevent staining and makes cleaning easier.
A long-life filter (maintenance free up to one year*) is
equipped as standard accessory.
(dB(A))
FXAQ-P
20
25
32
40
50
63
Sound level
(H/L)
35/31
36/31
38/31
39/34
42/37
47/41
Floor Standing types can be hung on the wall for easier
cleaning. Running the piping from the back allows the
unit to be hung on walls. Cleaning under the unit, where
dust tends to accumulate, is considerably easier.
Wall hanging
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
Floor installation
Concealed Floor Standing Type
Drain pan and air filter can be kept clean by mould-proof
polystyrene.
FXNQ20MA/FXNQ25MA
Vertical auto-swing realises efficiency of air distribution.
The louvre closes automatically when the unit stops.
5 steps of discharge angle can be set by remote
controller.
Discharge angle is automatically set at the same angle
as the previous operation when restarting. (Initial setting:
10° for cooling and 70° for heating)
Flexible installation
Drain pipe can be fitted to from either left or
right sides.
FXNQ32MA/FXNQ40MA
FXNQ50MA/FXNQ63MA
Drain pump kit is available as optional accessory, which
lifts the drain 1,000 mm from the bottom of the unit.
Height of drain-up
Designed to be concealed in the perimeter skirting-wall
1,000 mm
Drain pump kit
The unit is concealed in skirting-wall of perimeter, that
enables to create high class interior design.
Indoor unit
The connecting port faces downward,
greatly facilitating on-site piping work.
A long-life filter (maintenance free up
to one year*) is equipped as standard
accessory.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
33
Indoor Unit Lineup
Low operation sound level
Suitable for perimeter zone air conditioning
Connecting
port
Refrigerant
piping
* Applies also to Floor Standing type (FXLQ-MA).
34
Indoor Unit Specifications
Indoor Units
Ceiling Mounted Cassette (Round Flow with Sensing) Type
kcal/h
Cooling capacity
Btu/h
kW
kcal/h
Heating capacity
Cooling
Power consumption
Heating
Casing
Sound power (H/M/L)
Dimensions (H×W×D)
12,300
2.8
2,800
Liquid (Flare)
Gas (Flare)
3,900
4,800
6,100
7,700
9,600
12,000
15,400
19,100
24,200
30,700
38,200
47,800
4,300
Dimensions(H×W×D)
Weight
8,600
10,800
13,800
12.5
16.0
13,600
17,100
21,500
27,300
34,100
3.2
4.0
5.0
6.3
8.0
10.0
0.031
0.041
0.080
0.095
0.194
0.219
0.027
0.037
0.075
0.090
0.180
0.199
kW
kW
dB(A)
dB(A)
mm
Galvanised steel plate
208/191/166
241/216/183 365/291/224 391/308/224 391/324/249 549/433/316 574/458/349
14.5/13.0/11.0 22.0/17.5/13.5 23.5/18.5/13.5 23.5/19.5/15.0 33.0/26.0/19.0 34.5/27.5/21.0
47/45.5/44
19
mm
12.7
Panel
(Option)
Power consumption
Casing
Cooling
Heating
Airflow rate (HH/H/L)
Sound level (HH/H/L)
Sound power (HH/H/L)
Dimensions (H×W×D)
Machine weight
Piping
connections
Panel
(Option)
3,900
4,800
6,100
7,700
9,600
12,000
Btu/h
9,600
12,300
15,400
19,100
2.8
3.6
4.5
5.6
24,200
30,700
38,200
47,800
kW
7.1
9.0
11.2
14.0
3,400
4,300
5,400
17,100
21,500
kW
3.2
4.0
Gas (Flare)
Weight
54,600
42,700
6.3
8.0
12.5
16.0
0.052
0.066
0.093
0.187
0.209
kW
0.027
0.034
0.038
0.053
0.075
0.174
0.200
/s
216/191/166
250/216/183 266/225/183 316/275/225 350/300/250 533/433/333 550/466/375
dB(A)
30/28.5/27
31/29/27 32/29.5/27 34/31/28 36/33.5/31 43/37.5/32 44/39/34
48/46.5/45
49/47/45 50/47.5/45 52/49/46 53/51.5/49 60/54.5/50 61/56/52
m3/min
dB(A)
13/11.5/10
mm
10.0
Galvanised steel plate
15/13/11 16/13.5/11 19/16.5/13.5 21/18/15
mm
19.5
246×840×840
32/26/20 33/28/22.5
288×840×840
22
6.4
25
9.5
12.7
15.9
VP25 (External Dia, 32/Internal Dia, 25)
BYCP125K-W1
Model
Dimensions(H×W×D)
13,800
10,800
5.0
Drain
Colour
34,100
0.047
kg
Liquid (Flare)
8,600
6,900
27,300
0.033
kW
Fresh white
mm
50X950X950
kg
5.5
Note: Specifications are based on the following conditions;
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
35
8,500
10,900
2.5
3.2
0.073
3.6
3,400
13,600
4.0
0.076
4,800
3,900
15,400
4.5
17,100
5.0
21,500
6.3
0.115
0.089
183/133
233/166
240 V dB(A)
32/26
240 V dB(A)
49
34/28
37/29
42/35
0.064
Galvanised steel plate
9/7
9.5/7.5
51
mm
Dimensions(H×W×D)
11/8
54
kg
18
mm
12.7
59
6.4
VP20 (External Dia, 26/Internal Dia, 20)
BYFQ60B8W1
White (6.5Y9.5/0.5)
mm
55×700×700
2.7
kg
MODEL
1-phase, 220-240 V/220-230 V, 50/60 Hz
Btu/h
kW
kcal/h
Btu/h
Heating capacity
kW
6,900
9,600
27,300
38,200
8.0
11.2
7,700
10,800
30,700
42,700
9.0
Cooling
kW
Heating
0.090
kW
0.073
Casing
FXUQ100AVEB
FXUQ71AVEB
kcal/h
Cooling capacity
12.5
0.200
0.179
Fresh white
/s
375/325/267
517/433/350
m3/min
22.5/19.5/16
31/26/21
Sound level (H/M/L)
dB(A)
47/44/40
Sound power (H/M/L)
dB(A)
40/38/36
Dimensions (H×W×D)
mm
Airflow rate (H/M/L)
Machine weight
kg
Liquid (Flare)
Piping
Gas (Flare)
connections
Drain
14/10
286×575×575
Colour
Power
consumption
5.6
158/125
Power supply
This model is not
compatible both Heat
Pump 30 class and Heat
Recovery systems.
19,100
5,400
4,300
4-way Flow Ceiling Suspended Type
1-phase, 220-240 V/220 V, 50/60 Hz
3,100
13,600
2.8
2,800
3,100
12,300
150/116
/s
Weight
2,400
2,800
2.2
2,200
Model
5.5
10,900
9,600
0.107
Piping
Gas (Flare)
connections
Drain
50×950×950
Btu/h
7,500
FXZQ50MVE
0.080
Dimensions (H×W×D)
Fresh white
FXZQ40MVE
0.068
m3/min
Sound power (H)
FXZQ32MVE
1-phase, 220-240 V/220 V, 50/60 Hz
Liquid (Flare)
kcal/h
kcal/h
kW
Machine weight
FXFQ25PVE FXFQ32PVE FXFQ40PVE FXFQ50PVE FXFQ63PVE FXFQ80PVE FXFQ100PVE FXFQ125PVE
Power supply
Heating
Sound level (H/L)
BYCQ125B-W1
kg
kW
Airflow rate (H/L)
15.9
mm
Cooling
Casing
I.D. 25×O.D. 32(VP25)
MODEL
Heating capacity
Power
consumption
9.5
Ceiling Mounted Cassette (Round Flow) Type
Cooling capacity
kW
26
23
2,400
Btu/h
Heating capacity
288×840×840
6.4
1,900
Btu/h
kW
48/46/44 53/49/45 55/50/45 55/52/48 60/54/48 61/56/51
246×840×840
FXZQ25MVE
kcal/h
31/29/27 36/32/28 38/33/28 38/35/31 44/38/32 45/40/35
30/28.5/27
FXZQ20MVE
kcal/h
Cooling capacity
54,600
42,700
12.5/11.5/10.0
Model
Colour
6,900
MODEL
Power supply
14.0
11.2
9.0
7.1
5,400
10,900
Drain
Panel
(Option)
5.6
4.5
3.6
3,400
kg
Machine weight
Piping
connections
3,100
9,600
kW
m3/min
Sound level (H/M/L)
2,400
Btu/h
/s
Airflow rate (H/M/L)
1-phase, 220 -240 V/220-230 V, 50/60 Hz
Indoor Unit Lineup
FXFQ25SVM FXFQ32SVM FXFQ40SVM FXFQ50SVM FXFQ63SVM FXFQ80SVM FXFQ100SVM FXFQ125SVM
MODEL
Power supply
Ceiling Mounted Cassette (Compact Multi Flow) Type
58/56/54
65/62/58
198×950×950
26
27
9.5
mm
15.9
VP20 (External Dia, 26/Internal Dia, 20)
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
(See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
36
Indoor Unit Specifications
Indoor Units
FXCQ20MVE FXCQ25MVE FXCQ32MVE FXCQ40MVE FXCQ50MVE FXCQ63MVE FXCQ80MVE FXCQ125MVE
MODEL
1-phase, 220-240 V/220 V, 50/60 Hz
Power supply
kcal/h
1,900
2,400
3,100
3,900
4,800
6,100
7,700
12,000
Btu/h
7,500
9,600
12,300
15,400
19,100
24,200
30,700
47,800
kcal/h
2,200
2,800
3,400
4,300
5,400
6,900
8,600
13,800
Btu/h
8,500
10,900
13,600
17,100
21,500
27,300
34,100
54,600
kW
Cooling
2.5
3.2
4.0
5.0
6.3
8.0
10.0
16.0
kW
Heating
0.077
0.092
0.130
0.106
0.209
0.256
kW
0.044
0.059
0.097
0.126
0.176
0.223
Cooling capacity
kW
Heating capacity
Power
consumption
Slim Ceiling Mounted Duct Type (700 mm width type)
2.2
2.8
3.6
5.6
7.1
9.0
14.0
Galvanised steel plate
Casing
/s
Airflow rate (H/L)
m3/min
Sound level (H/L)
240 V
Dimensions (H×W×D)
Machine weight
dB(A)
mm
116/83
150/108
200/150
275/216
433/350
550/416
7/5
9/6.5
12/9
16.5/13
26/21
33/25
34/29
36/30
37/32
39/34
41/36
46/40
305×990×600
305×775×600
26.0
kg
31.0
Liquid (Flare)
Piping
Gas (Flare)
connections
Drain
mm
Colour
Weight
32.0
35.0
mm
53×1,030×680
kg
8.0
305×1,665×600
47.0
48.0
6.4
9.5
12.7
15.9
BYBC32G-W1
Dimensions(H×W×D)
305×1,175×600
VP25 (External Dia, 32/Internal Dia, 25)
Model
Panel
(Option)
4.5
53×1,245×680
53×1,430×680
53×1,920×680
8.5
9.5
12.0
Ceiling Mounted Cassette Corner Type
kcal/h
Cooling capacity
Btu/h
kW
kcal/h
Heating capacity
Power
consumption
Casing
Btu/h
Cooling
Heating
Airflow rate (H/L)
Sound level (H/L)
240 V
kW
kW
mm
kg
Dimensions(H×W×D)
Weight
3,900
mm
kg
6,100
12,300
15,400
24,200
2,800
3,400
4,300
6,900
2.8
3.6
10,900
3.2
13,600
4.0
0.066
11/9
40/35
4.5
7.1
17,100
27,300
0.076
0.105
5.0
0.056
Galvanised steel plate
216/166
215X1,110X710
13/10
42/36
31
6.4
12.7
VP25 (External Dia, 32/Internal Dia, 25)
Model
Colour
3,100
FXKQ63MAVE
9,600
183/150
Liquid (Flare)
Piping
connections Gas (Flare)
Drain
Panel
(Option)
2,400
/s
mm
FXKQ40MAVE
1-phase, 220 -240 V/220 V, 50/60 Hz
0.046
Dimensions (H×W×D)
Machine weight
FXKQ32MAVE
kW
m3/min
dB(A)
BYK45FJW1
White (10Y9/0.5)
8.0
0.085
300/250
18/15
44/39
215X1,310X710
34
9.5
15.9
BYK71FJW1
70X1,240X800
70X1,440X800
8.5
9.5
Note: Specifications are based on the following conditions;
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
•Sound level: (FXCQ-M) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
(FXKQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
37
FXDQ20PBVE
Power consumption
1
Cooling
Heating
Casing
Airflow rate (HH/H/L)
External static pressure
Sound level (HH/H/L)
1 3
kcal/h
1,900
Btu/h
7,500
FXDQ25PBVE
1-phase, 220-240 V/220 V, 50/60 Hz
2,400
kW
2.2
2.8
3.6
2,200
2,800
3,400
Btu/h
8,500
10,900
13,600
kW
2.5
3.2
kW
0.086
kW
0.067
4.0
0.089
0.070
Galvanised steel plate
/s
133/120/106
m3/min
8.0/7.2/6.4
Pa
30-10
dB(A)
2
33/31/29
51
mm
200×700×620
kg
23.0
6.4
Liquid (Flare)
Piping
Gas (Flare)
connections
Drain
3,100
12,300
9,600
dB(A)
Sound power (HH)
FXDQ32PBVE
kcal/h
mm
12.7
VP20 (External Dia, 26/Internal Dia, 20)
Slim Ceiling Mounted Duct Type (900/1,100 mm width type)
MODEL
FXKQ25MAVE
MODEL
Power supply
Heating capacity
Machine weight
BYBC125G-W1
White (10Y9/0.5)
Cooling capacity
Dimensions (H×W×D)
BYBC63G-W1
BYBC50G-W1
MODEL
Power supply
FXDQ40NBVE
Power supply
Cooling capacity
Heating capacity
Power consumption
1
Cooling
Heating
Casing
Airflow rate (HH/H/L)
External static pressure
Sound level (HH/H/L)
1 3
Sound power (HH)
Dimensions (H×W×D)
Machine weight
Liquid (Flare)
Piping
Gas (Flare)
connections
Drain
FXDQ50NBVE
1-phase, 220-240 V/220 V, 50/60 Hz
FXDQ63NBVE
kcal/h
3,900
4,800
6,100
Btu/h
15,400
19,100
24,200
kW
4.5
5.6
7.1
kcal/h
4,300
5,400
6,900
Btu/h
17,100
21,500
27,300
kW
5.0
6.3
8.0
kW
0.160
0.165
0.181
kW
0.147
0.152
0.168
/s
175/158/141
m3/min
Galvanised steel plate
208/183/166
10.5/9.5/8.5
12.5/11.0/10.0
34/32/30
35/33/31
52
53
Pa
dB(A)
dB(A)
mm
kg
mm
27.0
44-15
200×900×620
6.4
Indoor Unit Lineup
Ceiling Mounted Cassette (Double Flow) Type
275/241/216
16.5/14.5/13.0
2
28.0
12.7
36/34/32
54
200×1,100×620
31.0
9.5
15.9
VP20 (External Dia, 26/Internal Dia, 20)
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
1: Values are based on the following conditions: FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure of 15 Pa.
2: External static pressure is changeable to set by the remote controller. This pressure means "High static pressure - Standard". (Factory setting is
10 Pa for FXDQ-PB models and 15 Pa for FXDQ-NB models.)
3: The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be
obtained by adding 5 dB(A).
38
Indoor Unit Specifications
Indoor Units
Ceiling Mounted Duct Type
MODEL
FXSYQ20MVE FXSYQ25MVE FXSYQ32MVE FXSYQ40MVE FXSYQ50MVE FXSYQ63MVE FXSYQ80MVE FXSYQ100MVE FXSYQ125MVE
Power supply
Cooling capacity
1-phase, 220-240 V, 50 Hz
kcal/h
1,900
2,400
3,100
Btu/h
7,500
9,600
12,300
kW
kcal/h
Btu/h
Heating capacity
kW
Power
consumption
Cooling
kW
Heating
kW
Casing
/s
Airflow rate (H/L)
m3/min
Pa
External static pressure
2.2
2.8
3.6
2,200
2,800
3,400
10,900
13,600
3.2
4.0
8,500
2.5
0.089
0.096
0.089
0.096
Piping
Gas (Flare)
connections
Drain
Weight
24,200
30,700
38,000
47,800
7.1
9.0
11.2
14.0
5,400
6,900
8,600
10,800
13,800
34,100
42,700
54,600
10.0
12.5
16.0
0.304
0.309
0.366
0.304
0.309
0.366
5.6
4.5
4,300
21,500
17,100
27,300
6.3
5.0
8.0
0.145
0.106
0.178
0.145
0.106
0.178
350/235
450/355
466/370
21/14.1
27/21.3
28/22.2 38/27.42
98-65-33
1
191/143
1
88-57-27
96-65-57
1
86-58-43
41/33.5
41/34.5
43/37
58/50.5
58/51.5
60/54
30
34
35
300X550X800
300X700X800
1
115-84-52
1
140-122-61
1
138-118-53
1
98-58
2
48/43
49/41.5
62/55.5
65.5/60
66/59
300X1,000X800
300X1,400X800
44
57
6.4
9.5
12.7
15.9
BYBS45DJW1
633/457
45/38.5
VP25 (External Dia, 32/Internal Dia, 25)
BYBS32DJW1
Dimensions(H×W×D)
19,100
250/190
mm
Colour
12,000
158/112
Model
Panel
(Option)
9,600
9.5/6.72 11.5/8.58 15/11.4
kg
Liquid (Flare)
7,700
9/6.72
mm
Machine weight
6,100
150/112
Sound power (H/L) 230 V dB(A)
Dimensions (H×W×D)
15,400
4,800
Galvanised steel plate
230 V dB(A)
Sound level (H/L)
3,900
BYBS71DJW1
White (10Y9/0.5)
55X650X500
55X800X500
55X1,100X500
55X1,500X500
3.0
3.5
4.5
6.5
Cooling capacity
kcal/h
7,600
9,600
12,000
13,800
17,200
19,300
24,100
Btu/h
30,000
38,200
47,400
54,600
68,200
76,400
95,500
kcal/h
Btu/h
Heating capacity
kW
Power
consumption
Cooling
kW
Heating
kW
Casing
/s
Airflow rate (H)
m3/min
External static pressure (H)
Sound level (H)
Machine weight
Liquid (Flare)
Piping
Gas (Flare)
connections
Drain
8,480
33,800
11.2
mm
kg
mm
13.9
10,800
13,800
42,700
54,600
12.5
16.0
0.700
0.780
0.415
0.700
0.780
510
778
30.6
46.7
45
46
50
60
9.9
0.415
120
360X1168X869
16.0
15,800
62,800
18.4
0.880
20.0
22.4
19,300
21,500
76,400
85,300
22.4
25.0
0.980
0.880
0.980
852
957
51.1
57.4
1.020
3
360X1478X899
65
15.9
9.5
VP25 (External Dia, 32/Internal Dia, 25)
107,500
31.5
1.200
1,180
1,200
1,400
70.8
72.0
84.0
180
200
51
66
27,100
1.200
150
48
28.0
1.020
Galvanised steel plate
Pa
240 V dB(A)
Dimensions (H×W×D)
8.8
500X1210X910
77
79
19.1
500X1410X910
98
22.2
BSP 3/4 inch internal thread
Note: Specifications are based on the following conditions;
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
•Sound level: (FXSYQ) Anechoic chamber conversion value, based on Australian Standard 1217.6-1985. Measurement is based on bottom-return air entry.
(FXDYQ) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
•For FXDYQ models, an air filter is not a standard accessory. A suitable locally obtained filter must be installed in the return air duct.
1: External static pressure is changeable to change over the connectors inside electrical box, this pressure means
"High static pressure-Standard-Low static pressure".
2: External static pressure is changeable to change over the connectors inside electrical box, this pressure means "High static pressure-Standard".
3: External static pressure is changeable to change over the connectors inside electrical box (High static pressure-Standard static pressure).
The data above is for high static pressure setting.
39
1
1,900
2,400
3,100
3,900
4,800
Btu/h
7,500
9,600
12,300
15,400
19,100
kW
2.2
2.8
3.6
4.5
5.6
kcal/h
2,200
2,800
3,400
4,300
5,400
Btu/h
8,500
10,900
13,600
17,100
21,500
kW
2.5
3.2
4.0
5.0
6.3
0.060
0.151
0.128
0.073
0.182
0.203
158/133/116
267/216/183
300/275/250
9.5/8/7
16/13/11
Cooling
kW
0.056
Heating
kW
0.069
Casing
Airflow rate (HH/H/L)
External static pressure
Sound level (HH/H/L)
Sound power (H)
Dimensions (H×W×D)
Power supply
FXDYQ80MAV1 FXDYQ100MAV1 FXDYQ125MAV1 FXDYQ145MAV1 FXDYQ180MV1 FXDYQ200MV1 FXDYQ250MV1
kW
Power consumption
kcal/h
/s
9/7.5/6.5
Pa
2
30-100 (50)
dB(A)
dB(A)
30-160 (100)
33/31/29
34/32/30
51
52
mm
18/16.5/15
2
39/37/35
300X550X700
25
kg
50-200 (100)
2
41/39/37
57
59
300X700X700
300X1,000X700
28
36
6.4
mm
12.7
VP25 (External Dia, 32/Internal Dia, 25)
FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE FXMQ140PVE
1-phase, 220-240 V/220 V, 50/60 Hz
kcal/h
Cooling capacity
Btu/h
kW
Heating capacity
Power consumption
Galvanised steel plate
150/125/108
m3/min
MODEL
Ceiling Concealed (Duct) Type
1-phase, 220 -240 V, 50 Hz
Heating capacity
Piping
connections Gas (Flare)
Drain
kg
Power supply
Cooling capacity
Liquid (Flare)
mm
MODEL
1-phase, 220-240 V/220 V, 50/60 Hz
Machine weight
BYBS125DJW1
FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE
MODEL
Power supply
1
Cooling
Heating
6,100
7,700
9,600
12,000
13,800
24,200
30,700
38,200
47,800
54,600
7.1
9.0
11.2
14.0
16.0
kcal/h
6,900
8,600
10,800
13,800
15,500
Btu/h
27,300
34,100
42,700
54,600
61,400
kW
8.0
10.0
12.5
16.0
18.0
kW
0.138
0.185
0.215
0.284
0.405
kW
0.218
0.286
0.364
0.449
0.449
766/649/533
Indoor Unit Lineup
Ceiling Mounted Built-in Type
Galvanised steel plate
Casing
Airflow rate (HH/H/L)
External static pressure
Sound level (HH/H/L)
Sound power (H)
Dimensions (H×W×D)
Machine weight
Liquid (Flare)
Piping
connections Gas (Flare)
Drain
/s
m3/min
Pa
dB(A)
dB(A)
mm
kg
mm
325/292/267
417/375/333
533/450/383
650/550/466
19.5/17.5/16
25/22.5/20
32/27/23
39/33/28
50-200 (100)
2
46/39/32
50-140 (100)
42/40/38
43/41/39
44/42/40
46/45/43
60
61
62
64
2
300X1,400X700
300X1,000X700
36
46
47
9.5
15.9
VP25 (External Dia, 32/Internal Dia, 25)
Note: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
(See Engineering Data Book for details.)
•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
1: Power consumption values are based on conditions of rated external static pressure.
2: External static pressure can be modified using a remote controller that offers seven (FXMQ20-32P), thirteen (FXMQ40P), fourteen (FXMQ50125P) or ten (FXMQ140P) levels of control. These values indicate the lowest and highest possible static pressures. The standard static
pressure is 50 Pa for FXMQ20-32P and 100 Pa for FXMQ40-140P.
40
Indoor Unit Specifications
Indoor Units
Ceiling Mounted Duct Type
Wall Mounted Type
FXMQ200MAVE
MODEL
19,300
kW
Power consumption
Casing
Cooling
Heating
Btu/h
85,300
107,500
kW
25.0
kW
1.294
kW
1.294
240 V
Dimensions (H×W×D)
Machine weight
Piping
connections Gas (Flare)
Drain
1.465
1
1.465
Heating capacity
1
Power consumption
1
Pa
966/833
1,200/1,033
58/50
72/62
132-221
dB(A)
2
191-270
3,100
3,900
4,800
6,100
7,500
9,600
12,300
15,400
19,100
24,200
kcal/h
2,200
2,800
3,400
4,300
5,400
6,900
Btu/h
8,500
10,900
13,600
17,100
21,500
27,300
kW
2.5
3.2
4.0
5.0
6.3
8.0
kW
0.019
0.028
0.030
0.020
0.033
0.050
kW
0.029
0.034
0.035
0.020
0.039
0.060
/s
m3/min
dB(A)
Sound level (H/L)
2
Dimensions (H×W×D)
Machine weight
470X1,380X1,100
mm
2.2
2.8
Piping
connections Gas (Flare)
Drain
9.5
19.1
22.2
3.6
4.5
5.6
7.1
White (3.0Y8.5/0.5)
125/75
133/83
142/91
200/150
250/200
316/233
7.5/4.5
8/5
8.5/5.5
12/9
15/12
19/14
35/31
36/31
290×795×238
38/31
39/34
42/37
290×1,050×238
47/41
kg
11.0
Liquid (Flare)
137
mm
Heating
Airflow rate (H/L)
49/46
mm
Cooling
Casing
Galvanised steel plate
kg
Liquid (Flare)
31.5
1
2,400
kW
27,100
1-phase, 220-240 V/220 V, 50/60 Hz
1,900
Btu/h
28.0
21,500
m3/min
External static pressure
Sound level (H/L)
22.4
FXAQ20PVE FXAQ25PVE FXAQ32PVE FXAQ40PVE FXAQ50PVE FXAQ63PVE
kcal/h
Cooling capacity
95,500
kcal/h
/s
Airflow rate (H/L)
24,100
76,400
Btu/h
Heating capacity
MODEL
Power supply
1-phase, 220 -240 V/220 V, 50/60 Hz
kcal/h
Cooling capacity
FXMQ250MAVE
14.0
6.4
9.5
12.7
mm
15.9
VP13 (External Dia, 18/Internal Dia, 13)
PS1B
Floor Standing Type/Concealed Floor Standing Type
Ceiling Suspended Type
FXHQ32MAVE
MODEL
Power supply
kcal/h
Cooling capacity
Heating
Casing
Airflow rate (H/L)
9,600
38,200
3.6
7.1
11.2
kW
kW
kW
/s
m3/min
Machine weight
kg
Piping
connections Gas (Flare)
Drain
6,100
24,200
dB(A)
Liquid (Flare)
3,100
12,300
Sound level (H/L)
Dimensions (H×W×D)
FXHQ100MAVE
kW
Btu/h
Cooling
FXHQ63MAVE
1-phase, 220-240 V/220 V, 50/60 Hz
Btu/h
kcal/h
Heating capacity
Power consumption
mm
3,400
6,900
10,800
13,600
27,300
42,700
4.0
8.0
12.5
0.111
0.115
0.135
0.111
0.115
0.135
200/166
291/233
416/325
12/10
17.5/14
25/19.5
45/37
36/31
39/34
195×960×680
195×1,160×680
24.0
28.0
6.4
mm
White (10Y9/0.5)
12.7
195×1,400×680
33.0
9.5
15.9
VP20 (External Dia, 26/Internal Dia, 20)
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book
for details.)
• Sound level: (FXMQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
(FXHQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
During actual operation, these values are normally somewhat higher as a result of ambient conditions
1: Power consumption values are based on conditions of rated external static pressure.
2: External static pressure is changeable to change over the connectors inside electrical box, this pressure means "Standard-High static pressure".
41
FXLQ20MAVE FXLQ25MAVE FXLQ32MAVE FXLQ40MAVE FXLQ50MAVE FXLQ63MAVE
MODEL
Power supply
FXLQ
FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE
kcal/h
Cooling capacity
Btu/h
kW
Heating capacity
FXNQ
Power consumption
Cooling
Heating
Casing
Sound level (H/L)
Dimensions
(H×W×D)
FXNQ
Machine weight
FXLQ
FXNQ
3,900
4,800
6,100
9,600
12,300
15,400
19,100
24,200
2.2
2.8
3.6
4.5
5.6
7.1
2,800
3,400
4,300
5,400
6,900
Btu/h
8,500
10,900
13,600
17,100
21,500
27,300
kW
2.5
3.2
4.0
5.0
6.3
8.0
kW
0.049
0.090
0.110
kW
0.049
0.090
0.110
dB(A)
mm
kg
Liquid (Flare)
Piping
connections Gas (Flare)
Drain
3,100
7,500
2,200
m3/min
FXLQ
2,400
kcal/h
/s
Airflow rate (H/L)
1-phase, 220-240 V/220 V, 50/60 Hz
1,900
mm
Indoor Unit Lineup
Power supply
FXLQ: Ivory white (5Y7.5/1)/FXNQ: Galvanised steel plate
116/100
133/100
183/141
233/183
266/200
7/6
8/6
11/8.5
14/11
16/12
35/32
38/33
39/34
40/35
600×1,000×222
600×1,140×222
600×1,420×222
610×930×220
610×1,070×220
610×1,350×220
19.0
23.0
27.0
25.0
30.0
36.0
6.4
9.5
12.7
15.9
VP13 (External Dia, 18/Internal Dia, 13)
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book
for details.)
• Sound level: (FXAQ-P) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
(FXLQ-MA, FXNQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
42
Indoor Unit Option List
Indoor Units
No.
1
2
3
4
5
6
7
Type FXFQ25S FXFQ32S FXFQ40S FXFQ50S FXFQ63S FXFQ80S FXFQ100S FXFQ125S
Item
Decoration panel
Sealing material of air discharge outlet
Panel spacer
Filter related
High efficiency filter unit 65%
High efficiency filter unit 90%
Replacement high efficiency filter 65%
Replacement high efficiency filter 90%
Filter chamber
Long life replacement filter
Ultra long-life filter
Replacement ultra long-life filter
Fresh air intake kit
Chamber type Without T joint-pipe and fan
With T joint-pipe without fan
Direct installation type
Branch duct chamber
Insulation kit for high humidity
Slim Ceiling Mounted Duct Type (700 mm width type)
No.
1
BYCQ125B-W1
KDBHQ55B140
KDBP55H160FA
KAFP556B80
KAFP557B80
KAFP552B80
KAFP553B80
KDDFP55B160
KAFP551K160
KAFP55B160
KAFP55H160H
KDDQ55B140
KDDP55B160K
KDDP55X160
KDJP55B80
KDTP55K80
KAFP556B160
KAFP557B160
KAFP552B160
KAFP553B160
1
2
3
4
5
6
7
8
Decoration panel
Sealing material of air discharge outlet
Panel spacer
Filter related
High efficiency filter unit 65%
High efficiency filter unit 90%
Replacement high efficiency filter 65%
Replacement high efficiency filter 90%
Filter chamber
Long life replacement filter
Ultra long-life filter
Replacement ultra long-life filter
Fresh air intake kit
Chamber type Without T joint-pipe and fan
With T joint-pipe without fan
Direct installation type
Branch duct chamber
Chamber connection kit
Insulation kit for high humidity
No.
1
No.
KDJP55B160
KDTP55K160
BYCP125K-W1
KDBH55K160F
KDBP55H160FA
KAFP556B80
KAFP557B80
KAFP552B80
KAFP553B80
KDDFP55B160
KAFP551K160
KAFP55B160
KAFP55H160H
KDDP55B160
KDDP55B160K
KDDP55X160
KDJP55B80
KKSJ55KA160
KDTP55K80
KAFP556B160
KAFP557B160
KAFP552B160
KAFP553B160
KDTP55K160
Ceiling Mounted Cassette (Compact Multi Flow) Type
No.
1
2
3
4
5
Type
Item
4-way Flow Ceiling Suspended Type
No.
1
2
3
FXZQ20M
FXZQ25M
Decoration panel
Sealing material of air discharge outlet
Panel spacer
Replacement long-life filter
Fresh air intake kit
Direct installation type
Item
FXZQ32M
FXZQ40M
FXZQ50M
BYFQ60B8W1
KDBH44BA60
KDBQ44BA60A
KAFQ441BA60
KDDQ44XA60
Type
FXUQ71A
1
2
Decoration panel
Filter related
High efficiency filter 65% 1
High efficiency filter 90% 1
Filter chamber bottom suction
Long life replacement filter
Note: 1 Filter chamber is required if installing high efficiency filter.
FXCQ20M
FXCQ25M
43
Item
1
Panel related
2
Air inlet and air
discharge outlet related
Type
Decoration panel
Panel spacer
Long life replacement filter
Air discharge grille
Air discharge blind panel
Flexible duct (with shutter)
3
Air inlet related
BYBC32G-W1
KAFJ532G36
KAFJ533G36
KDDFJ53G36
KAFJ531G36
FXCQ50M
BYBC50G-W1
KAFJ532G56
KAFJ533G56
KDDFJ53G56
KAFJ531G56
FXCQ63M
No.
1
FXKQ32MA
BYK45FJW1
KPBJ52F56W
KAFJ521F56
K-HV7AW
KDBJ52F56W
KFDJ52FA56
Decoration panel
Access panel
High efficiency filter 65% 1
High efficiency filter 90% 1
Long life replacement filter
Filter chamber for bottom suction
Air suction canvas
Screening door
BYBC63G-W1
KAFJ532G80
KAFJ533G80
KDDFJ53G80
KAFJ531G80
FXCQ125M
BYBC125G-W1
KAFJ532G160
KAFJ533G160
KDDFJ53G160
KAFJ531G160
FXKQ40MA
FXDQ63NB
FXSYQ20M
FXSYQ25M
FXSYQ32M
BYBS32DJW1
KTBJ25K36W
KAFJ252L36
KAFJ253L36
KAFJ251K36
KAJ25L36D
KSA-25K36
KBBJ25K36
KDT25N63
FXSYQ40M
FXSYQ50M
FXSYQ63M
BYBS45DJW1
KTB25KA56W
KAF252LA56
KAF253LA56
KAFJ251K56
KAJ25LA56D
KSA-25KA56
KBBJ25KA56
BYBS71DJW1
KTB25KA80W
KAF252LA80
KAF253LA80
KAFJ251K80
KAJ25LA80D
KSA-25KA80
KBBJ25KA80
FXSYQ80M
FXSYQ100M
FXSYQ125M
BYBS125DJW1
KTB25KA160W
KAF252LA160
KAF253LA160
KAFJ251K160
KAJ25LA160D
KSA-25KA160
KBBJ25KA160
Type FXDYQ80MA FXDYQ100MA FXDYQ125MA FXDYQ145MA FXDYQ180M FXDYQ200M FXDYQ250M
Item
Run/fault status PCB
KRP1B5X
Ceiling Mounted Duct Type
Type
Item
1
2
Drain pump kit
High efficiency filter
3
4
5
6
Filter chamber
Long life replacement filter
Long life filter chamber kit
Service panel
7
Air discharge adaptor
65%
90%
White
Fresh white
Brown
Item
No.
1
Item
Drain pump kit
Item
Long life replacement filter
Concealed Floor Standing Type
No.
Type
Drain pump kit
Replacement long-life filter (Resin net)
L-type piping kit (for upward direction)
Floor Standing Type
1
FXKQ25MA
Type
Ceiling Concealed (Duct) Type
No.
FXCQ80M
FXDQ50NB
1 If installing a high efficiency filter in the Ceiling Mounted Built-in type, a filter chamber for bottom suction is required.
1
FXCQ40M
FXDQ32PB
KDT25N50
Wall Mounted Type
Ceiling Mounted Cassette Corner Type
No.
Filter related
1
2
3
KDBHP49B140
KDBTP49B140
KAFP551K160
Type
Item
2
No.
Ceiling Mounted Cassette (Double Flow) Type
No.
Item
Panel related
Note:
FXDQ40NB
Insulation kit for high humidity
Ceiling Suspended Type
FXUQ100A
Sealing material of air discharge outlet
Decoration panel for air discharge
Replacement long-life filter
Type
Item
1
No.
KDJP55B160
FXDQ25PB
KDT25N32
Ceiling Mounted Built-in Type
Type FXFQ25P FXFQ32P FXFQ40P FXFQ50P FXFQ63P FXFQ80P FXFQ100P FXFQ125P
Item
FXDQ20PB
Insulation kit for high humidity
Slim Ceiling Mounted Duct Type (900/1,100 mm width type)
Ceiling Mounted Cassette (Round Flow) Type
No.
Type
Item
Item
Long life replacement filter
FXMQ20P
FXMQ25P
FXMQ32P
FXMQ40P
KAF372AA36
KAF373AA36
KDDF37AA36
KAF371AA36
KAF375AA36
KTBJ25K36W
KTBJ25K36F
KTBJ25K36T
KDAJ25K36A
KAF372AA56
KAF373AA56
KDDF37AA56
KAF371AA56
KAF375AA56
KTB25KA56W
KTBJ25K56F
KTBJ25K56T
KDAJ25K56A
FXHQ32MA
KDU50N60VE
KAF501DA56
KHFP5MA63
Type
FXAQ20P
Type FXLQ20MA
—
FXMQ50P
FXMQ63P
FXMQ80P
KAF372AA80
KAF373AA80
KDDF37AA80
KAF371AA80
KAF375AA80
KTB25KA80W
KTBJ25K80F
KTBJ25K80T
KDAJ25K71A
FXHQ63MA
KAF501DA80
FXMQ100P
FXMQ125P
FXMQ140P
FXMQ200MA
FXMQ250MA
KAF372AA160
KAF373AA160
KDDF37AA160
KAF371AA160
KAF375AA160
KTB25KA160W
KTBJ25K160F
KTBJ25K160T
KDAJ25K140A
KDU50N125VE
KHFP5MA160
KDU30L250VE
KAFJ372L280
KAFJ373L280
KDJ3705L280
KAFJ371L280
—
FXHQ100MA
KAF501DA112
FXAQ25P
FXAQ32P
FXAQ40P
FXAQ50P
FXAQ63P
FXLQ25MA
FXLQ32MA
FXLQ40MA
FXLQ50MA
FXLQ63MA
KAFJ361K28
K-KDU572EVE
KAFJ361K45
Indoor Unit Lineup
Ceiling Mounted Cassette (Round Flow With Sensing) Type
KAFJ361K71
Type FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA
KAFJ361K28
KAFJ361K45
KAFJ361K71
FXKQ63MA
BYK71FJW1
KPBJ52F80W
KAFJ521F80
K-HV9AW
KDBJ52F80W
KFDJ52FA80
44
Control Systems
Individual Control Systems for Indoor Units
Convenience
“Nav Ease” (Wired remote controller) (Option)
This simple, contemporary remote controller with fresh white colour
matches your interior design. The clear, backlight display with large
easy-to-read text makes navigation easy and provides one-touch control
over your in-home comfort.
Clear display
Dot matrix display
A combination of fine dots enables various
icons.Large text display is easy to see.
Setback (default:OFF)
Maintains the room temperature in a specific range during unoccupied period
by temporarily starting air conditioner that was turned OFF.
Ex) Setback temperature Cooling : 35ºC
Recovery differential Cooling : -2ºC
When the room temperature goes above 35ºC, the air conditioner starts operating in Cooling automatically.
When room temperature reaches 33ºC, the air conditioner returns OFF.
Setback
temperature
Recovery
differential
Cooling
33
37ºC
-2
-8ºC
Heating
10
15ºC
+2
+8ºC
Weekly schedule
Backlight display
Backlight display helps operating in
dark rooms.
5 actions per day can be scheduled for each day of the week.
The holiday function will disable schedule timer for the days that have been set as holiday.
3 independent schedules can be set. (e.g. summer, winter, mid-season)
College classroom sample (a summer Monday case)
BRC1E62
1) 8:30
ON
2) 10:00
The first period starts and the
air conditioner starts the cooling
operation.
ON
Simple operation
OFF
3) 13:00
In the second period, the classroom
is unoccupied and the air conditioner
stops.
ON
4) 15:00
When the third period starts,
operation starts again.
OFF
ON
OFF
After the third period, the classroom
becomes vacant again and the
air conditioner stops.
OFF
Large buttons and arrow keys
Large buttons and arrow keys enable easy operation. Basic setting such as fan
speed and temperature can be intuitively operated. For other settings just select
the function from the menu list.
Guide on display
The display gives an explanation of each setting for easy operation.
Multingual display
Energy saving
11 display languages are available. (English, German, French, Spanish, Italian, Portuguese, Greek, Dutch, Russian, Turkish and Polish)
Until now only the temperature for one point could be set, but now the new
remote controller (BRC1E62) allows the setting of both Cooling and Heating,
and with the fan operation, mid-range temperatures are comfortable and
operation is more energy efficient.
20ºC
26ºC
Fan operation
operation
Saves energy by limiting the min. and max.
set temperature.
Avoids excessive cooling or heating.
This function is convenient when the remote
controller is installed at a place where any
number of people may operate it.
Individual airflow direction (*1)
Cooling / Heating
Heating
Setpoint range set
Comfort
2 setpoints
Airflow direction of each of the four air outlets can be controlled individually.
(Positions 0 to 4, Swing, and No individual setting are selectable.)
Cooling
operation
1
2
3
4
2
Setpoint auto reset
Even if the set temperature is changed, it returns
to the preset temperature after a preset period of
time.
Period selectable from 30 min / 60 min / 90 min /
120 min.
Outlet mark
1
3
Control Systems
Auto operation mode
Restaurant sample
Restaurant opened
Temperature is set to 27ºC
27 °C
Full tables at lunchtime
Then is lowered to 24ºC
for crowded room
24 °C
After 30 minutes*
Automatically returns to preset
temperature (27ºC) Returns to
27 °C
Off timer
Turns off the air conditioner after a preset
period of time.
Period can be preset from 30 to 180 minutes
in 10-minute increments.
03
45
4
automatically
Auto airflow rate (*1)
*Setting possible for after 30, 60, 90,
and 120 minutes.
Airflow rate is automatically controlled in accordance with the difference between room temperature and set temperature.
*1 Only available for 4-Way Flow Ceiling Suspended type FXUQ-A series and Ceiling Mounted Cassette (Round Flow with Sensing) type FXFQ-S series.
04
46
Control Systems
Individual Control Systems for Indoor Units
Wireless remote controller (Option)
The wired remote controller supports a wide range of control functions
Control of Cool/Heat
changeover
The same operation modes and settings as with wired remote controllers are
possible.
In all the series of GHP, Cool/Heat changeover in the same refrigerant circuit can be changed by the remote
controller of the indoor unit.
Outdoor
unit
* Individual airflow direction, auto airflow rate and sensing sensor control can be set only via wired remote controller
BRC1E62. Cannot be set via other remote controllers.
A compact signal receiver unit (separate type) to be mounted into a wall or ceiling
is included.
Group control
One remote controller can control the
operation of max.16 indoor units at the
same time.
Equipment
related to the
central control
• A signal receiver unit (installed type) for a Ceiling Mounted Cassette (Round Flow,
Compact Multi Flow, Double Flow) type, Ceiling Suspended type and Wall
Mounted type is mounted into the indoor unit.
Signal receiver unit can be
installed on the panel
Signal receiver unit
(Separate type)
Remote controller
Indoor unit
Remote controller
* Wireless remote controller and signal receiver unit are sold as a set.
* Refer to page 55 for the name of each model.
Forced OFF
input
Remote controller
Remote
controller
Remote controller
Heat Reclaim
Ventilator
Concealed type
Remote
controller
(For hotel use)
(BRC3A61)
Exposed type
(BRC2C51)
1
Signal receiver unit
(Installed type)
Simplified remote controller (Option)
Remote
controller
Remote
controller
ex. Ceiling Mounted Cassette (Round Flow) type
Wireless remote
controller
2
3
The remote controller
has centralised its
frequently used operation
selectors and switches
(on/off, operation mode,
temperature setting and
airflow volume), making
itself suitable for use in
hotel rooms or
conference rooms.
The concealed type remote controller smartly fits into a
night table or console panel in a hotel room.
The exposed type remote
controller is fitted with a
thermostat sensor.
4
1
Control by two remote controller
The indoor unit can be connected by the two remote
controller, for example one in the room and the other one
in the control room, which can control the operation of
indoor unit freely.(The last command has a priority.)
Of course, the group control by two remote controller is
also possible.
2
Remote control
The wiring of remote controller can be extended to max.
500 m and it is possible to install the remote controllers
for the different indoor units in one place.
FXFQ-S FXFQ-P
“Nav Ease”
(Wired remote controller)
(BRC1E62)
Wireless remote controller*
(Installed type signal receiver unit)
FXZQ
FXCQ
FXUQ
FXKQ
FXDQ
FXSYQ
FXDYQ
FXMQ
FXHQ
FXAQ
FXL(N)Q
Control Systems
Wide variation of remote controllers for indoor units
Wireless remote controller*
(Separate type signal receiver unit)
Simplified remote controller
3
Control for the combined operation
The operation of Heat Reclaim Ventilator can be
controlled by the remote controller of the indoor unit.
Of course, the remote controller can display the time to
clean the filter.
03
47
4
Expansion of system control
The system can be expanded to add several
controllers, such as BMS, Forced OFF input and etc.
(Exposed type)
(BRC2C51)
Simplified remote controller
(Concealed type: for Hotel use)
(BRC3A61)
*Refer to page 55 for the name of each model.
04
48
Control Systems
Centralised Control Systems for Indoor Units
•Up to 64 groups of indoor units (128 units) can be centrally controlled.
•Optional controllers for centralised control can be combined
freely, and system can be designed in accordance with building
scale and purpose.
•System integration with various air-conditioning peripheral
equipment such as Heat Reclaim Ventilator is easy.
•Wiring can be run up to a total length of 2 km, and adapts
DCS302CA61
Connection of
up to 8 units
possible
Independent
and centralised
control of Heat
Reclaim
Ventilator is
possible.
Address setting of central control can be
performed from the remote controller.
System without remote control is also available.
Max. 16 groups of indoor units can be operated
simultaneously/individually.
Group control of up to 16 units is possible
(group control via automatic address setting)
8 units
Schedule timer 1 unit
The VRV system can be combined.
DCS301BA61
Up to 2 units
connectable
Central control
adaptor kit
(DTA107A55).
Outdoor-air
processing
unit can be
connected.
7 cores max.
Unification adaptor for
computerised control (DCS302A52)
Interlink Building Management System
(host computer monitor panel) also
possible
Certain indoor units limit the functions of some control systems.
For more details, please refer to the Engineering Data.
03
49
Schedule timer (Option)
Max. 128 indoor units can be operated as programmed schedule.
•Max. 128 indoor units controllable
•When used in combination with a central remote controller, a maximum of 8 weekly
Interface adaptor for SkyAir
series
(DTA112BA51)
6 cores
Schedule timer (DST301BA61)
1 unit connection possible;
8 weekly schedule control patterns possible
Wiring adaptor
for other airconditioners
(DTA103A51)
•Max. 16 groups (128 indoor units) controllable
•2 remote controllers can be used to control from 2 different places.
•Operating status indication (Normal operation, Alarm)
•Centralised control indication
•Max. wiring length 1,000 m (Total: 2,000 m)
•Compact size casing (Thickness: 16 mm)
•Connectable with Central Remote controller, Schedule timer and BMS system
DST301BA61
•
•
•
•
schedule patterns can be set, while the central controller can be used to select desired
zones. Up to 2 ON/OFF pairs can be set per day.
Max. 48 hours back up power supply
Max. wiring length 1,000 m (Total: 2,000 m)
Compact size casing (Thickness: 16 mm)
Connectable with Central Remote controller, Unified ON/OFF controller and BMS
system
Control Systems
Forced
shut-down
input
Central remote
controller
(DCS302CA61)
•Max. 64 groups (128 indoor units) controllable
•Max. 128 groups (128 indoor units) are controllable by using 2 central remote
controllers, which can control from 2 different places.
•Zone control
•Malfunction code display
•Max. wiring length 1,000 m (Total: 2,000 m)
•Connectable with Unified ON/OFF controller, schedule timer and BMS system
•Airflow volume and direction can be controlled individually for indoor units in each group
operation.
•Ventilation volume and mode can be controlled for Heat Reclaim Ventilator.
•Up to 4 ON/OFF pairs can be set per day by connecting a schedule timer.
Unified ON/OFF controller (Option)
Connectable number of
centralised control
equipment
Unified on/off
controller
Max. 64 groups (zones) of indoor units can be controlled individually same as
LCD Remote controller.
easily to large-scale system expansion.
Unified on/off
controller
(DCS301BA61)
Central remote 2 units
controller
Central remote controller (Option)
04
50
Control Systems
Advanced Control Systems for Indoor Units
Interface for
Communication functions in the user-friendly icon-based multilingual controller
simplify centralised control of the GHP system.
BACnet
and LONWORKS
Integrated control systems that recognise the trend of open control systems
Ethernet
Please contact Daikin for compatibility with BMS system
BMS
DCS601C51
Lift
Pump
Lighting,etc
Fire alarm Security Power supply facility
DMS502B51
DMS504B51
(Interface for use in BACnet®) (Interface for use in LONWORKS®)
GHP System
Local Controller
D -NET
D -NET Plus Adaptor
DCS601A52 (Option)
Indoor Unit
Number of indoor units expanded from 64 to 128.
Features
•Colour LCD touch panel icon display
•Small manageable size
•Simplified engineering
•Multi language (English, French, Italian, German, Spanish,
Heat Reclaim
Ventilator
•Compatibility with BMS enhanced by utilising the international communication standards, BACnet® or LONWORKS®.
DMS502B51
Interface for use in BACnet®
DMS504B51
Interface for use in LONWORKS®
•Support for Heat Reclaim Ventilator VAM series
•Selectable temperature unit
•BTL Certification
•PPD data (Optional Di board is required.)
•ISO 16484-5 (Does not support IEEE 802.3 protocol for BACnet®)
•Up to 40 outdoor units and 256 indoor unit groups on one gateway (optional adaptor)
•XIF file for confirming of specifications of the units.
•Connectable up to 10 outdoor units and 64 indoor unit groups.
Control Systems
RS-232C
Heat
Reclaim
Ventilator
Dutch, Portuguese, Chinese and Korean)
•Yearly schedule
•Auto heat/cool change-over
•Temperature limitation
•Enhanced history function
•Built-in modem for connecting to Air Conditioning Network Service System (Option)
•Doubling of number of connectable indoor units by adding a D -NET Plus Adaptor (Option)
03
51
04
52
Control Systems
Integrated Building Monitoring System
DIII-NET Line
The high speed transmission of DIII-NET enables more advanced control of the GHP system, providing
you with enhanced comfort.
BACnet®/Ethernet or LONWORKS®
Network Communication Line
Contact Signal Line
The DIII-NET system provides for:
• Close control and monitoring by integrating a wide variety of air-conditioners in the entire building.
• Saving the in-building cabling using non-polar, two-wire cables. Easier wiring work with
tremendously fewer wiring errors.
• Additional setups readily up and running. An extendable cabling up to 2 km in total.
• Different control equipment flexibly joined in the system for hierarchical risk diversification.
• Daikin's total heat exchangers and other devices under integral control.
GHP
Controllers for Centralised Control
Heat Reclaim Ventilator
(DCS601C51)
D -NET
(High Speed Multiple
Transmission)
(DCM601A51)
Unified ON/OFF
Controller
(DCS301BA61)
Schedule Timer
(DST301BA61)
Control /Connection Interface
Unification adaptor
for computerised control
(DCS302A52)
DIII-NET, Daikin’s unique
high speed multiple
transmission system, links
air conditioners and
various other building
equipment―in
accordance with
applications, scale and
conditions―and transmits
vast amounts of
information between them.
BMS
Interface Adaptor for SkyAir Series
(DTA112BA51)
* No adaptor is required for the
FCQ-B and FHQ-BV.
Central Control Adaptor Kit
(DTA107A55)
Interface Adaptor for DIII-NET use
(KRP928BB2S)
(Obtain locally)
SkyAir
Packaged
Air-conditioner
Residential Air-conditioner
Interface for use in BACnet®
(DMS502B51)
Di unit (DEC101A51)
Dio unit (DEC102A51)
Interface for use in LONWORKS®
(DMS504B51)
GHP
Wiring adaptor
for electrical appendices
(KRP2A61/62/53)
03
53
Control Systems
Central Remote
Controller
(DCS302CA61)
VRV
Building services equipment
• Electrical equipment
• Supply water and drainage equipment
• Automatic fire alarm
• Parking equipment
• Lift
• Ventilation equipment
• Lighting
• Crime and fire prevention equipment
Caution:
Limitation may apply to some models and functions. Please contact your local sales office for details.
Consultation is necessary before employing this control system. Please contact your local sales office before
making a purchase.
Note: BACnet® is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning
Engineers (ASHRAE). LONWORKS® is a trademark of Echelon Corporation registered in the United
States and other countries.
04
54
Control Systems
Option List
Operation Control System Optional Accessories
No.
1
2
3
4
5
6-1
6-2
7
Item
Type
Wireless
Remote controller
Navigation remote controller (Wired remote controller)
Simplified remote controller (Exposed type)
Remote controller for hotel use (Concealed type)
Adaptor for wiring
Wiring adaptor for electrical appendices (1)
Wiring adaptor for electrical appendices (2)
Remote sensor (for indoor temperature)
8
Installation box for adaptor PCB
9
10
External control adaptor for outdoor unit
Adaptor for multi tenant
No.
1
2
3
4
5
6-1
6-2
7
Item
Type
Remote controller
Wireless
Navigation remote controller (Wired remote controller)
Simplified remote controller (Exposed type)
Remote controller for hotel use (Concealed type)
Adaptor for wiring
Wiring adaptor for electrical appendices (1)
Wiring adaptor for electrical appendices (2)
Remote sensor (for indoor temperature)
8
Installation box for adaptor PCB
9
External control adaptor for outdoor unit
10
Adaptor for multi tenant
FXFQ-S
FXFQ-P
FXZQ-M
FXUQ-A
FXCQ-M
FXKQ-MA
BRC7F634F BRC7F634F BRC7E530W BRC7CB58 BRC7C62
BRC4C61
BRC1E62 Note 7
—
—
—
KRP1B61
KRP1C63
 KRP1BA57
KRP1B61
—
KRP2A61
KRP2A62
KRP2A62
KRP2A61
KRP4AA53
KRP4AA53 KRP4AA53 KRP4AA51 KRP4AA51
KRCS01-4B
KRCS01-1B KRCS01-4B
KRCS01-1B
Note 2, 3
Note 4, 6
KRP1H98
 DTA104A62
DTA114A61
KRP1BA101
DTA104A62
FXSYQ-M
FXDYQ-M(A)
FXMQ-P
BRC4C62
BRC4C62
BRC4C65
Note 5
BRC2C51
BRC3A61
KRP1C64
KRP2A61
KRP4AA51
KRCS01-4B
KRP1B61
KRP2A61
KRP4AA51
KRCS01-1B
—
Note 2, 3
KRP1BA97
—
FXHQ-MA
BRC4C62
BRC7EA63W
BRC1E62 Note 7
KRP1B61
KRP2A61
KRP4AA51
—
DTA104A61
 DTA104A61
DTA104A61
—
 DTA114A61
BRC4C65
BRC2C51
BRC3A61
KRP1B56
KRP2A53
KRP4A54
KRCS01-1B
Note 4, 6
—
KRP1B96
KRP1BA101
DTA104A61 DTA104A61 DTA104A53
—
FXMQ-MA
KRP4A96
KRP4A91
Note 2, 3
FXDQ-PB
FXDQ-NB
FXAQ-P
BRC7EA618
—
—
KRP1BA54
—
KRP2A62
KRP2A61
KRP4AA52 KRP4AA51
KRCS01-1B
Note 3
KRP1CA93
Note 2, 3
KRP4AA93
 DTA104A62  DTA104A61
—
DTA114A61
FXLQ-MA
FXNQ-MA
BRC4C62
BRC2C51
BRC3A61
KRP1B61
KRP2A61
KRP4AA51
—
DTA104A61
No.
Item
Model No.
1
Residential central remote controller
2
Central remote controller
• Up to 16 groups of indoor units (128 units) can be easily controlled using the
large LCD panel. ON/OFF, temperature settings and scheduling can be controlled
individually for indoor units.
DCS302CA61 • Up to 64 groups of indoor units(128 units) can be connected, and ON/OFF, temperature setting and monitoring can be accomplished individually or simultaneKJB311AA
ously. Connectable up to 2 controllers in one system.
DCS301BA61 • Up to 16 groups of indoor units(128 units) can be turned, ON/OFF individually or
KJB212AA
simultaneously, and operation and malfunction can be displayed. Can be used in
combination with up to 8 controllers.
KEK26-1A
• Programmed time weekly schedule can be controlled by unified control for up to
DST301BA61
64 groups of indoor units (128 units). Can turn units ON/OFF twice per day.
Note 2
DCS303A51
2-1
Electrical box with earth terminal (3 blocks)
3
3-1
3-2
Unified ON/OFF controller
Electrical box with earth terminal (2 blocks)
Noise filter (for electromagnetic interface use only)
4
Function
Schedule timer
7
For C(F)DK(X)S,
KRP928BB2S
FTK(X)S, FVXS, FLXS
• Adaptors required to connect products other than those of the VRV System to the
For FCQ-B, FFQ-B,
DTA112BA51 high-speed DIII-NET communication system adopted for the VRV System.
FHQ-BV, FBQ-B
* To use any of the above optional controllers, an appropriate adaptor must be
installed on the product unit to be controlled.
Central control adaptor kit For UAT(Y)-K(A),FD-K DTA107A55
8
Wiring adaptor for other air-conditioner
9
DIII-NET
Expander Adaptor
9-1
Fixing Plate for
DⅢ‐NET Expander
Adaptor
5
6
Interface adaptor for
residential indoor units
Interface adaptor for
SkyAir-series
DTA103A51
• Up to 1024 units can be centrally controlled in 64 different groups.
• Wiring restrictions (max. length: 1,000m, total wiring length: 2,000m, max. number of branches: 16) apply to each adaptor.
DTA109A51
For GYAQ8,10,13,16,
20,25ANV1
For GYAQ30ANV1,
GYEQ20,30AN
AGDTA109E1
COB850J
The fixing plate is required when using DⅢ-NET Expander Adaptor.
Note: 1. Installation box for  adaptor must be obtained locally.
2. For residential use only. Cannot be used with other centralised control equipment.
—
Notes: 1. Installation box  is necessary for each adaptor marked .
2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit.
4. Up to 2 installation boxes can be installed for each indoor unit.
5. Installation box  is necessary for second adaptor.
6. Installation box  is necessary for each adaptor.
7. Individual airflow direction, auto airflow rate and sensing sensor control can be set only via wired remote controller BRC1E62. Cannot be set via other remote controllers.
Building Management System
No.
1
1-1
Item
intelligent Touch
Controller
Basic
Option
intelligent Touch
Hardware
Controller
DIII-NET plus
Hardware
adaptor
Model No.
DCS601C51
DCS601A52
• Additional 64 groups (10 outdoor units) is possible.
1-2
Electrical box with earth terminal (4 blocks)
Basic
Hardware
intelligent Touch
Manager
KJB411A
2
DCM601A51
Option
Hardware iTM plus adaptor
DCM601A52
2-1
intelligent Touch
Manager
2-2
2-3
2-4
Di unit
3
3-1
3-2
Communication
interface
4
5
DEC101A51
Dio unit
Contact/analogue signal
Function
• Air-Conditioning management system that can be controlled by a
compact all-in-one unit.
DEC102A51
*1 Interface for use in BACnet ®
DMS502B51
Optional DIII board
DAM411B51
Optional Di board
DAM412B51
*2 Interface for use in LONWORKS ®
DMS504B51
Unification adaptor for computerised
control
DCS302A52
• Wall embedded switch box.
• Air-conditioning management system that can be controlled by touch
screen.
• Additional 64 groups (10 outdoor units) is possible.
Max. 7 iTM plus adaptors can be connected to intelligent Touch
Manager.
• 8 pairs based on a pair of ON/OFF input and abnormality input.
Control Systems
For indoor unit use
System Configuration
• 4 pairs based on a pair of ON/OFF input and abnormality input.
• Interface unit to allow communications between VRV and BMS.
Operation and monitoring of air-conditioning systems through BACnet ®
communication.
• Expansion kit, installed on DMS502B51, to provide 2 more DIII-NET
communication ports. Not usable independently.
• Expansion kit, installed on DMS502B51, to provide 16 more wattmeter
pulse input points. Not usable independently.
• Interface unit to allow communications between VRV and BMS.
Operation and monitoring of air-conditioning systems through
LonWorks ® communication.
• Interface between the central monitoring board and central control
units.
Notes: *1. BACnet ® is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
*2. LonWorks ® is a trademark of Echelon Corporation registered in the United States and other countries.
*3. Installation box for  adaptor must be obtained locally.
03
55
04
56
Air Treatment Equipment Lineup
For Heat Pump series outdoor units only
Combine fresh air treatment and air conditioning,supplied from a single system.
Lineup
Model Name FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1
Capacity Index
125
200
250
Fresh air treatment and air conditioning
can be achieved with a single system by
using heat pump technology—without the
usual troublesome air supply and air
discharge balance design. Fan coil units
for air conditioning and an outdoor-air
processing unit can be connected to the
same refrigerant line. The results are
enhanced design flexibility and a significant
reduction in total system costs.
* The system can operate with outdoor-air temperatures ranging
from -5 to 43℃. Heating performance is somewhat adversely
affected when the outdoor-air temperature is 0℃ or below.
* When shipped from the factory, the thermostat is set at 18℃
for cooling and 25℃ for heating. The set temperature can be varied
within the range of 13–25℃ during cooling operation, and 18–30℃
during heating operation, in the local setting mode using
the wired remote controller. The temperature, however, is not
displayed on the remote controller.
* While in machine protection mode and depending on outdoor air
conditions, discharge air temperature may not be at the set
temperature.
* The fan stops when operating in defrosting, oil returning and hot
start operations. The fan also may stop due to mechanical protection
control.
• Ceiling mounted duct units with three differing
capacities are available. These can be connected
to GHP outdoor units to meet a variety
of different requirements.
Combination with GHP
Airflow rate
Air conditioning and outdoor air processing can be accomplished using a single system.
• Optional equipment includes long-life filters.
Air
Conditioning
Outdoor
Air Supply
Heating
Supported
Range
Operation
–5
Connection Conditions
The following restrictions must be observed in order to maintain the indoor units connected to the same system.
• GHP heat recovery series outdoor unit can not be connected.
• When outdoor-air processing units are connected to GHP heat pump series 8-25 class outdoor unit, the total connection capacity index must be 50% to 100% of the capacity
index of the outdoor units. When outdoor-air processing units are connected to GHP heat pump series 30 class outdoor unit, the total connection capacity index must be 80%
to 108% of the capacity index of the outdoor unit.
• When outdoor-air processing units and standard indoor units are connected to GHP heat pump series 8-25 class outdoor unit, the total connection capacity index of the
outdoor-air processing units must not exceed 30% of the capacity index of the outdoor units.
• A mixed combination of outdoor-air processing units and standard indoor units can not be connected to GHP heat pump series 30 class outdoor unit.
57
Supported Cooling
Operation Range
o
td
Ou
e
ur
at
r
pe
m
Te )
ir WB
A
or (ºC
%
Indoor Unit
90
Indoor Unit
10
0%
H R
Re umi elat
lat dity ive
ive
Hu
m
idi 32
ty
Usage Limitations
Outdoor-Air Processing Unit
Fan
Operation
15
19
30%
R
ve
elati
idity
Hum
(33.5)
* Group control is not possible between
this unit and standard type indoor
units. Connect remote controllers to
each unit.
BRC1E62
“Nav Ease”
(Wired remote controller)
(option)
• The “self-diagnosis function” indicates the occurrence and nature of abnormalities in the system
by displaying codes on the remote controller.
* It is not possible to change the
discharge air temperature settings
from the central control system.
* Do not associate this equipment
into zones with standard indoor units,
as central control will not be possible.
• Compatible with outdoor temperatures from -5℃ to
43℃.
GHP Heat Pump series outdoor units
• As with the GHP system,
a variety of control systems
can be deployed, including
remote control from distances
of up to 500 m.
• A central control system
compatible with the GHP
can be installed.
1,080 m3/h
1,680 m3/h
2,100 m3/h
FXMQ125MFV1
FXMQ200MFV1
FXMQ250MFV1
• Outdoor-air processing units can be used without indoor units.
• High-performance filters with dust collection
efficiencies (JIS calorimetry) of 90% and 65% are
also available as options.
• The unit introduces outdoor air and adjusts
the outdoor air temperature via fixed discharge
temperature control, thereby reducing the air
conditioning load.
e
lativ
Re ity
20% umid
H
43
Notes:
1. The data shown in the graph illustrates the supported operation ranges under
the following conditions.
Indoor and Outdoor Unit
Effective piping length: 7.5 m
Height differential: 0 m
2. The discharge temperature can be set using the remote controller. However,
the actual temperature may not match the temperature setting under some
circumstances due to the outdoor-air processing load or mechanical protection
controls.
3. The system will not operate in fan mode when the outdoor air temperature is
5℃ or below.
DCS302CA61
Central remote controller
(option)
• As with the GHP, the equipment employs the “super
wiring system” so that the wiring linking indoor and
outdoor units can also be utilised for central control.
Notes:
* Linked control of the product and the Heat Reclaim Ventilator is
not supported.
* This equipment is intended for the treatment of outdoor air only.
It is not to be used for maintaining indoor air temperature. Install
and use with standard indoor units. Be sure to position the air
discharge openings of the product in positions where the airflow
will not blow on people directly. When outdoor-air processing is
in excess, the unit switches to thermo-off mode, and outdoor air
flows into the room directly.
* For outdoor ducts, be sure to provide heat insulation to prevent
condensation.
* Group control of the product and the standard indoor units is not
supported. A separate remote controller should be connected to
each individual unit.
* The system will not operate in fan mode when the outdoor air
temperature is 5℃ or below.
* If the product is allowed to operate 24 hours a day, maintenance
(part replacement, etc.) must be performed periodically.
* Temperature setting and Power Proportional Distribution (PPD)
are not possible even if the intelligent Touch Controller or the
intelligent Touch Manager is installed.
* The remote controller wired to the outdoor-air processing unit
must not be set as the master remote controller. Otherwise,
when set to “Auto,” the operation mode will switch according to
the outdoor air conditions, regardless of the indoor temperature.
Air Treatment
Equipment Lineup
Outdoor-Air Processing Unit
58
Air Treatment Equipment Lineup
Standard Specifications
Dimensions
Indoor unit
FXMQ125/200/250MFV1
28.0
kcal/h
7,700
12,000
15,000
Btu/h
30,400
47,400
59,400
8.9
13.9
17.4
0.548
0.638
Galvanised steel plate
Airflow rate
External static pressure
470X744X1,100
470X1,380X1,100
kW
/s
300
466
583
Pa
225
275
255
m3/min
240 V
0.380
18
28
Air filter
35
*2
Liquid
mm
Gas
mm
Drain
mm
Machine weight
Sound level *3
240 V
9.5 (flare)
15.9 (flare)
Range of the discharge
temperature *5
22.2 (brazing)
kg
86
123
dB(A)
43
48
8 class and above
Cooling
19 to 43℃
-5 to 15℃
Cooling
13 to 25℃
Heating
18 to 30℃
3
*4. Only Heat Pump series outdoor units can be connected. Refer to page 57 for connection
condition details.
*5. Local setting mode. Not displayed on the remote controller.
• This equipment cannot be incorporated into the remote group control of the GHP system.
FXMQ200/250MFV1
11X100=1100
1200
1230
30
1
2
3
4
5
6
Liquid pipe connection
Gas pipe connection
Drain piping connection
Electric parts box
Ground terminal
Name plate
7
8
9
10
11
12
Power supply wiring connection
Transmission wiring connection
Hanger bracket
Discharge companion flange
Water supply port
Attached piping (Note. 1)
12
8
61
20- 7 hole
(All around)
5X100=500
600
630
30
A View
8
DST301BA61
Wiring adaptor for electrical appendices (1)
KRP4AA51
KAFJ371L140
KAFJ371L280
KAFJ372L140
KAFJ372L280
KAFJ373L140
KAFJ373L280
KDJ3705L140
KDJ3705L280
Drain pump kit
Adaptor for wiring
Notes: *1. Filter chamber has a suction-type flange. (Main unit does not.)
• Dimensions and weight of the equipment may vary depending on the options used.
• Some options may not be usable due to the equipment installation conditions, so please
confirm prior to ordering.
KDU30L250VE
KRP1B61
• Some options may not be used in combination.
• Operating sound may increase somewhat depending on the options used.
200
346
360
330
200
1230
B View (For FXMQ200MFV1)
1004
360
Colourimetric method 90%
16-M5 hole
(All around)
KRP2A61
Wiring adaptor for electrical appendices (2)
5X200=1000
7
7
16-M5 hole
(All around)
7
10-M5 hole
(All around)
2X200=400
580
630
B View
Air Treatment
Equipment Lineup
DCS301BA61
Schedule timer
250
Unified ON/OFF controller
200
DCS302CA61
360
BRC1E62
Central remote controller
Colourimetric method 65%
FXMQ250MFV1
250
Operation remote controller
FXMQ200MFV1
330
FXMQ125MFV1
250
Operation/control
D
20- 4.7 hole
32- 4.7 hole
32- 4.7 hole
FXMQ125MFV1
245
60
32- 7 hole
(All around)
C
5X100=500
11X100=1100
11X100=1100
580
Long-life replacement filter
Filters
613
760
B
685
1296
1296
Notes:
1. The attached piping in the diagram is for FXMQ200MFV1 and
FXMQ250MFV1 only. The gas piping connection port ( 2 in the
diagram) has a different bore form with FXMQ125MFV1.
2. An air filter is not supplied with this unit. Be sure to mount an air
filter in the suction side.[Use a filter with dust collection efficiency of
at least 50% (gravimetric method). This is available as an option.]
3. For outdoor ducts, be sure to provide heat insulation to prevent
condensation.
A View
Model
59
Suction side (Note.2)
B View
Indoor unit
Filter chamber *1
5
*These diagrams are based on FXMQ200 and FXMQ250MFV1.
Options
High-efficiency
filter
2 11 6 4
30
1100
250
Notes: *1. Specifications are based on the following conditions;
• Cooling: Outdoor temp. of 33°CDB, 28°CWB (68% RH), and discharge temp. of 18°CDB.
• Heating: Outdoor temp. of 0°CDB, -2.9°CWB (50% RH), and discharge temp. of 25°CDB.
• Equivalent reference piping length: 7.5 m (0 m horizontal)
*2. An intake filter is not supplied, so be sure to install the optional long-life filter or high-efficiency filter.
Please mount it in the duct system of the suction side. Select a dust collection efficiency (gravity method)
of 50% or more.
*3. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
These values are normally somewhat higher during actual operation as a result of ambient conditions.
A View
10 class and above
Heating
1
Discharge side
PS1B female thread
Connectable outdoor units *4
Operation range
(Fan mode operation between 15 and 19°C)
19.1 (brazing)
1100 or more
(Service space)
Inspection hole 600 or more
390
Motor output
470
mm
Dimensions (HxWxD)
D
(All around)
296
0.359
50
kW
Casing
25
Power consumption
Table of dimensions
Model
A
FXMQ125MFV1 744
FXMQ200MFV1 1380
FXMQ250MFV1 1380
3X100=300
kW
360
330
3X100=300
Heating capacity *1
390
22.4
296
95,500
14.0
kW
A
76,400
B
24,100
47,800
Approx.
150
19,300
Btu/h
Liquid piping diameter
9.5
9.5
9.5
C
12,000
650 or more
(Service space)
kcal/h
Gas piping diameter
15.9
19.1 attached piping
22.2 attached piping
Model
FXMQ125MFV1
FXMQ200MFV1
FXMQ250MFV1
1-phase 220 - 240 V (also required for indoor units), 50 Hz
Cooling capacity *1
Refrigerant
piping
FXMQ250MFV1
25
Power supply
FXMQ200MFV1
360
330
FXMQ125MFV1
Local connection piping size
1148
3X100=300
Model
Fan
9
10
Ceiling Mounted Duct Type
250
Type
5X200=1000
1230
B View (For FXMQ250MFV1)
60
Air Treatment Equipment Lineup
Heat Reclaim Ventilator — VAM series
Air conditioning load reduced by approximately 31%!
23%
Total heat exchange ventilation
Model Names
VAM150GJVE, VAM250GJVE, VAM350GJVE,
VAM500GJVE, VAM650GJVE, VAM800GJVE,
VAM1000GJVE, VAM1500GJVE, VAM2000GJVE
Heat Reclaim Ventilator remote controller*
BRC301B61 (Option)
Improved Enthalpy Efficiency
2
Higher External Static Pressure
Enhanced Energy Saving Functions
1
* This remote controller is used in case of independent
operation of Heat Reclaim Ventilator.
This VAM series provides higher enthalpy efficiency 1, due to the greatly enhanced performance of the thin film
element. Furthermore, improved external static pressure 2 offers more flexibility for installation. Along with these three
outstanding improvements, the nighttime free cooling operation contributes to energy conservation and more
comfortable space.
EA
(Exhaust air to outdoors)
For models: VAM150/250/350/650/800/1000/2000GJVE
2 For models: VAM150/350/500GJVE
1
Due to the thinner film…
•Decreases the moisture resistance of the partition sheets drastically.
•Realises more space for extra layers in the element,
Thickness of
resulting in increased effective area that supply and
the partition sheet
exhaust air can be exposed to.
Moisture absorption increased by approx. 10%!
Indoor
Sheet structure
Outdoor
High-humidity air
Molecule of water
Miscellaneous gas
CO2 molecule, etc.
Exhaust air
(Fresh air from
outdoors)
Reduces air conditioning load by
not running the Heat Reclaim
Ventilator while air is still clean
soon after the air conditioner is
turned ON.
Precise, thin-film
material
RA
(unclean
indoor air)
Outdoor air
(fresh air)
Supply air
2%
Pre-cool,
Pre-heat Control
Exhaust air
RA
(Return air
from room)
Automatically switches the
ventilation mode (Total Heat
Exchange Mode/Bypass Mode)
according to the operating status
of the air conditioner.
Enthalpy efficiency drastically improved by employing
thin film element! (VAM-GJ model)
SA
OA
6%
Auto-ventilation Mode
Changeover Switching
This unit recovers heat energy lost through ventilation and
curbs room temperature changes caused by ventilation, thereby
conserving energy and reducing the load on the air conditioning
system.
Low-humidity air
Moisture exchange efficiency is greatly improved by using optimised
thinner films and moisture-absorption materials in the element.
Furthermore, miscellaneous gas barrier properties are maintained by
decreasing the porosity in the moisture-absorption materials.
31%
(Supply air
to room)
Daikin air conditioner
• The air conditioning load reduction values are based on the following conditions;
Application: Tokyo office building
Building form: 6 floors above ground, 2 floors underground, floor area 2,100 m2
Personnel density: 0.25 person/m2
Ventilation volume: 25 m3/h
Indoor air conditioning level: summer 25℃ 50% RH, intermediate seasons 24℃ 50%
RH, winter 22℃ 40% RH
Operating time: 2745 hours (9 hours per day, approx. 25 days per month)
Calculation method: simulation based on "MICRO-HASP/1982" of the Japan
Building Mechanical and Electrical Engineers Association.
Indoor unit
• ON/OFF signal
• Cooling/Heating mode signal
• Set temperature signal
• Ventilation signal
• Operating mode signal
• Filter cleaning signal
• Failure detection signal
Interlocking
61
Heat Reclaim
Ventilator
Compact Equipment
Energy Conservation
With a height of just 306 mm, the unit easily fits in limited
spaces, such as above ceilings.
Air conditioning load reduced by approximately 31%!
* For VAM500GJVE
Air Conditioning Load
Reduced by Approximately
20%
0%
Normal
ventilation fan
Nighttime free cooling operation*1
LCD remote controller
for indoor unit
306 mm
• The air conditioning load reduction values may vary according to weather and
other environmental conditions at the location of the machine's installation.
Air conditioning load reduction (%)
SA
Standard operation at
temperatures down to -15℃.
-15˚CDB
-20
-10
50˚CDB
0
10
20
30
40
50
VAM-GJ
Interlocked operation
with air conditioner
Air conditioning sensible
heat load reduced by
Nighttime free cooling operation is an energy-conserving function that works at night when air
*2
conditioners are off. By ventilating rooms containing office equipment that raises the room
approx.
temperature, nighttime free cooling operation reduces the The indoor accumulated heat is discharged at night.
cooling load when air conditioners are turned on in the
This reduces the air conditioning load the next day thereby increasing efficiency.
morning. It also alleviates feelings of discomfort in the
morning caused by heat accumulated during the night.
5% !
•Nighttime free cooling operation only works to cool and if connected to
Building Multi or VRV systems.
•Nighttime free cooling operation is set to “off” in the factory settings, so if
you wish to use it, request your dealer to turn it on.
Cold Climate Compatible
VAM-GJ
Individual operation
*1 This function can be operated only when interlocked with air conditioners.
*2 Value is based on the following conditions:
• Cooling operation performed from April to October.
• Calculated for air conditioning sensible heat load only
(latent heat load not included).
Cold air
Exhaust
heat
Generated
heat
Heat is discharged.
Indoor
unit
Exhaust
heat
Indoor
unit
Air Treatment
Equipment Lineup
The Heat Reclaim Ventilator Creates a High-Quality Environment by Interlocking
with the Air Conditioner
Comfortable!
The load is small so the temperature is rapidly reduced
to a comfortable level.
*Interlocked operation with an air conditioner
62
Air Treatment Equipment Lineup
Specifications
1-phase, 220-240 V/220 V, 50 Hz/60 Hz
%
High
Low
For Heating Ultra-High
%
High
Low
For Cooling Ultra-High
%
High
Low
Power
Consumption
Heat
Ultra-High
Exchange
High
Mode
W
Low
Bypass
Mode
Sound
Level
79
74
75
72
78
72
77
75
79
74
75
72
78
72
77
84
79
82
80
77
74
80.5
75.5
79
72
71
70
67
67.5
65
70
65
72
72
71
70
67
67.5
65
70
65
72
76
74
77
74
71.5
67.5
72.5
67
75
66
63
66
55
61
61
64
61
62
66
63
66
55
61
61
64
61
62
70
66
70
59
64
64
68.5
64
66
125
137
200
248
342
599
635
1,145
1,289
111
120
182
225
300
517
567
991
1,151
57
60
122
128
196
435
476
835
966
125
137
200
248
342
599
635
1,145
1,289
High
111
120
182
225
300
517
567
991
1,151
Low
57
60
122
128
196
435
476
835
966
27-28.5
27-29
31.5-33
33-35.5
34-36
39-40.5
39.5-41.5
39.5-41.5
41.5-43.5
26-27.5
26-27.5
30-31.5
31.5-34
33-34.5
37-39.5
37.5-39.5
37.5-39.5
39-43
20.5-21.5
21-22
23-25
25-28.5
27.5-29.5
35-37.5
35-37.5
35-37.5
36-39
28.5-29.5
28.5-30.5
33-34.5
34.5-36
35-37.5
40.5-42
40.5-42.5
41-43
43-45.5
High
27.5-28.5
27.5-29
31.5-33
33-34.5
33-35.5
38.5-40
38.5-40.5
39.5-41
40.5-45
Low
22.5-23.5
22.5-23
24.5-26.5
25.5-28.5
27.5-30.5
36-38.5
36-38.5
36.5-38
37.5-39.5
Ultra-High
W
Heat
Ultra-High dB(A)
Exchange
High
Mode
Low
Bypass
Mode
75
79
Ultra-High dB(A)
Casing
Galvanised steel plate
Insulation Material
Self-extinguishable polyurethane foam
Dimensions (HXWXD)
Machine Weigh
mm
278X810X551
kg
24
Heat Exchange System
306X879X800
338X973X832
32
45
External Static
Pressure
129
Ultra-High m3/h
150
250
350
500
650
800
1,000
1,500
2,000
High
150
250
350
500
650
800
1,000
1,500
2,000
Low
100
155
230
320
500
700
860
1,320
1,720
Ultra-High
41
69
97
138
180
222
277
416
555
High
/s
41
69
97
138
180
222
277
416
555
Low
27
43
63
88
138
194
238
366
477
120
70
169
105
85
133
168
112
116
High
106
54
141
66
53
92
110
73
58
Low
56
24
67
32
35
72
85
56
Ultra-High Pa
Motor Output
kW
Connection Duct Diameter
mm
0.030X2
100
0.090X2
150
0.140X2
200
0.280X2
250
45
Silencer (Option)
Duct
(Obtain locally)
Thermal insulation material (Obtain locally)
Option List
Type
Item
Heat Reclaim Ventilator remote controller
Residential central remote controller
Centralised Central remote controller
controlling
Unified ON/OFF controller
device
Schedule timer
Wiring adaptor for electrical
appendices
For humidifier
Installation box for adaptor PCB
For heater control kit
Notes: 1.
2.
3.
4.
OA
EA
BRC301B61
DCS303A51 *1
DCS302CA61
DCS301BA61
DST301BA61
KRP2A61
KRP50-2
KRP50-2A90 (Mounted electric component assy of Heat Reclaim Ventilator)
BRP4A50
FXFQ-S
FXDQ-PB
FXLQ-MA
Type
For wiring (indoor unit of GHP) FXFQ-P FXZQ-M FXUQ-A FXCQ-M FXKQ-MA FXDQ-NB FXSYQ-M FXDYQ-M(A) FXMQ-P FXMQ-MA FXHQ-MA FXAQ-P FXNQ-MA
Installation box for adaptor PCB
Sirocco fan
Unit Ambient Condition
KRP1C63 KRP1BA57 KRP1C67 KRP1B61 KRP1B61 KRP1B56
KRP1B61
Notes 2, 3 Note 4, 6
— Notes 2, 3 — Notes 4, 6 Notes 5
—
KRP1H98 KRP1BA101
KRP1B96
KRP1BA101 KRP4A91
Installation box is necessary for each adaptor marked .
Up to 2 adaptors can be fixed for each installation box.
Only one installation box can be installed for each indoor unit.
Up to 2 installation boxes can be installed for each indoor unit.
KRP1C64 KRP1B61 KRP1BA54 — KRP1B61
Notes 2, 3
Notes 2, 3
— Note 3
—
KRP4A96
KRP1CA93 KRP4AA93
5. Installation box is necessary for second adaptor.
6. Installation box is necessary for each adaptor.
7. *1 For residential use only. When connected with a Heat Reclaim Ventilator (VAM), you can
only switch the power ON/OFF. Cannot be used with other centralised control equipment.
Type VAM150GJVE VAM250GJVE VAM350GJVE VAM500GJVE VAM650GJVE VAM800GJVE VAM1000GJVE VAM1500GJVE VAM2000GJVE
—
KDDM24B50
KDDM24B100
KDDM24B100X2
Nominal pipe diameter mm
—
200
250
High efficiency filter
KAF242H25M
KAF242H50M
KAF242H65M KAF242H80M KAF242H100M KAF242H80MX2 KAF242H100MX2
Air filter for replacement
KAF241G25M
KAF241G50M
KAF241G65M KAF241G80M KAF241G100M KAF241G80MX2 KAF241G100MX2
Flexible duct (1 m)
K-FDS101D
K-FDS151D
K-FDS201D
K-FDS251D
Flexible duct (2 m)
K-FDS102D
K-FDS152D
K-FDS202D
K-FDS252D
Duct adaptor
—
YDFA25A1
Nominal pipe diameter mm
—
250
Item
Silencer
0.280X4
350
-15℃–50℃DB, 80%RH or less
Notes: 1. Sound level is measured at 1.5 m below the centre of the body.
2. Airflow rate can be changed over to Low mode or High mode.
3. Sound level is measured in an anechoic chamber.
Sound level generally becomes greater than this value depending on the operating conditions, reflected sound, and peripheral noise.
4. The sound level at the air discharge port is about 8 dB(A) higher than the unit's sound level.
5. The specifications, designs and information given here are subject to change without notice.
6. Temperature Exchange Efficiency is the mean value between cooling and heating.
7. Efficiency is measured under the following conditions:
Ratio of rated external static pressure has been maintained as follows; outdoor side to indoor side = 7 to 1.
8. In conformance with JIS standards (JIS B 8628), operating sound level is based on the value when one unit is operated, with the value converted for an anechoic chamber. This is transmission
sound from the main unit, and does not include sound from the discharge grille. Thus it is normal for the sound to be louder than the indicated value when the unit is actually installed.
9. Sound level from the discharge port causes the value to be approximately 8 dB(A) (models with the airflow rate of less than 150 to 500 m3/h) to approximately 11 dB(A) (models with
the airflow rate of 650 m3/h or more) greater than the indicated value. Furthermore, fan rotation and noise from the discharge grille may increase depending on the on-site duct
resistance conditions. Please consider noise countermeasures when installing the unit.
10. With large models in particular (1500 and 2000 m3/h models), if the supply air (SA) grille is installed near the main unit, the noise of the main unit may be heard from the discharge
grille via the duct, and this will result in a marked increase in noise. In such cases, if peripheral effects are included (such as reverberation of the floor and walls, combination with
other equipment, and background noise), sound level may be as much as 15 dB(A) higher than the indicated value. When installing a large model, please provide as much separation
as possible between the main unit and the discharge grille. If the equipment and discharge grille are near each other, please consider countermeasures such as the following:
•Use a sound-muffling box, flexible duct and sound-muffling air supply/discharge grilles
•Decentralised installation of discharge grilles
11. When installing in a location with particularly low background noise such as a classroom, please consider the following measures to avoid transmission sound from the main unit:
•Use of ceiling materials with high sound insulating properties (high transmission loss)
•Methods of blocking sound transmission, for example, by adding sound insulating materials around the bottom of the sound source.
Alternatively, consider supplementary methods such as installing the equipment in a different location (corridor, etc.)
63
SA
157
Multidirectional fibrous fleeces
Type
Airflow Rate
67
Specially processed nonflammable paper
Air Filter
Airflow Rate
55
Round hood
(Obtain locally)
Branch duct
(Obtain locally)
Air to air cross flow total heat (Sensible heat + latent heat) exchange
Heat Exchange Element Material
Fan
387X1,111X832 387X1,111X1,214 785X1,619X832 785X1,619X1,214
High efficient filter
(Option)
SA
Additional
function
Enthalpy
Exchange
Efficiency
79
Controlling device
Ultra-High
Flexible duct
(Option)
RA
PC Board Adaptor
Power Supply
Temp. Exchange
Efficiency
Air suction/discharge grille (Obtain locally)
VAM150GJVE VAM250GJVE VAM350GJVE VAM500GJVE VAM650GJVE VAM800GJVE VAM1000GJVE VAM1500GJVE VAM2000GJVE
PC board adaptor for heater control kit (BRP4A50)
When the installation of an electric heater is required in a cold region, this adaptor with an internal timer function eliminates the
complicated timer connecting work that was necessary with conventional heaters.
Indoor
RA
EA
Heat Reclaim Ventilator
SA
BRP4A50
Thermostat (Obtain locally)
(OFF when the temperature is at or more
than 5℃)
Outdoor
Heater
(Obtain locally)
OA
Thermostat
(Obtain locally)
(ON when the temperature
is at or below -10℃)
Power supply (Obtain locally)
Relay box
Notes when installing
Examine fully an installation place and specification for
using the electric heater based on the standard and
regulation of each country.
Supply the electric heater and safety production devices
such as a relay and a thermostat, etc of which qualities
satisfy the standard and regulation of each country at site.
Use a non-inflammable connecting duct to the electric
heater. Be sure to allow 2 m or more between the electric
heater and the Heat Reclaim Ventilator for safety.
Air Treatment
Equipment Lineup
MODEL
Options
For the Heat Reclaim Ventilator, use a different power
supply from that of the electric heater and install a circuit
breaker for each.
64
Memo