Air handling unit connection ERQ-AW1 air conditioning systems technical data Air handling unit connection ERQ-AW1 air conditioning systems technical data • Air handling unit connection • ERQ-AW1 TABLE OF CONTENTS ERQ-AW1 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3 4 3 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 4 Integrated heating capacity coefficient . . . . . . . . . . . . . . . . . . . . . . . . . . 6 5 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Combination table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Cooling capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Heating capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Capacity correction factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 6 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 21 Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 23 7 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 8 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 10 11 28 30 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sound power spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 31 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Installation method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fixation and foundation of units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 • Air Handling Unit Connection • Heat pump 33 1 • Air handling unit connection • ERQ-AW1 1 n i lp md nu 1ap W hH A t - ra Q ieR H•AE • 2 Features Wide range of Daikin units offers maximum application potential plus flexible control options. • Control box and expansion valve kit are required for each combination plus an air handling unit. The system provides optimized air conditions such as fresh air and humidity control, both in heating and in cooling, and can be used in small warehouses, showrooms and offices. • Air Handling Unit Connection • Heat pump • Air handling unit connection • ERQ-AW1 2 Specifications 2-1 Nominal Capacity and Nominal Input Nominal Capacity Nominal Input ERQ125A7W1B ERQ200A7W1B Cooling capacity Standard kW 14.0 22.4 28.0 Heating capacity Standard kW 16.0 25.0 31.5 Cooling Standard kW 3.52 5.22 7.42 Heating Standard kW 4.00 5.56 7.70 Nominal 3.98 4.29 3.77 Nominal 4.00 4.50 4.09 ERQ125A7W1B ERQ200A7W1B ERQ250A7W1B 5 8 10 EER For combination indoor units + outdoor COP units 2-2 Technical Specifications Capacity range HP PED category Casing Dimensions 2 Colour Daikin White Material Painted galvanized steel plate Unit Packing Weight Packing Height mm Width mm Depth mm Height mm Width mm Depth mm 1,680 635 930 765 1,855 796 1,055 860 Unit kg 159 187 240 Packed Unit kg 181.65 217.35 273 kg 3.8 Material Carton Weight 4.02 Material Wood Weight kg 19.15 20.85 Material Plastic Weight Heat Exchanger Dimensions Length kg 0.215 mm 1,483 0.265 1,778 Nr of Rows Fin Pitch 54 mm Nr of Passes Face Area m² 2 8 18 1.762 2.112 Nr of Stages 2 Tube type Hi-XSS(8) Fin Type Non-symmetric waffle louvre Treatment Fan Hydrophilic and corrosion resistant Type Propeller Discharge direction Vertical Quantity Air Flow Rate (nominal at 230V) 1 Cooling m³/min 95 171 185 Heating m³/min 95 171 185 Max Motor Pa 78 Pa in high static pressure Quantity 1 Model Output Compressor ERQ250A7W1B Brushless DC W 350 Quantity Motor 750 1 Model 2 Inverter Type Hermetically sealed scroll compressor Speed rpm Motor Output W Crankcase Heater W 6,300 7,980 6,300 2.8 3.8 1.2 33 Model ON-OFF Type Hermetically sealed scroll compressor Speed rpm Motor Output W 4.5 Crankcase Heater W 33 • Air Handling Unit Connection • Heat pump 2,900 3 • Air handling unit connection • ERQ-AW1 2 Specifications 2-2 Technical Specifications Operation Range ERQ125A7W1B Cooling Heating °CDB Max °CDB 43 Min °CWB -20 Max °CWB Sound Level (nominal) Sound power Sound pressure Refrigerant ERQ200A7W1B Min 15 dBA 72 dBA 54 78 57 Type kg 6.2 7.7 Control Piping connections Liquid (OD) 8.4 Expansion valve (electronic type) Nr of Circuits Type 58 R-410A Charge Refrigerant Oil ERQ250A7W1B -5 1 Synthetic (ether) oil Charged Volume l 1.7 2.1 Type Diameter (OD) Gas mm 9.52 Type Piping Length 4.3 Braze connection Braze connection Diameter (OD) mm Maximum m 15.9 19.1 22,2 55 Heat Insulation Both liquid and gas pipes Defrost Method Reversed cycle Defrost Control Sensor for outdoor heat exchanger temperature Capacity Control Method Capacity control Inverter controlled Cooling Maximum 100% Safety Devices High pressure switch Fan motor driver overload protector Overcurrent relay Inverter overload protector PC board fuse Standard Accessories Item Installation manual Quantity 1 Item Operation manual Quantity 1 Item Connection pipes Quantity 4 Notes Sound power level is an absolute value that a sound generates. Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings Sound values are measured in a semi-anechoic room. Nominal cooling capacities are based on: indoor temperature: 27°CDB/19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 7.5m, level difference: 0m Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB/ 6°CWB, equivalent refrigerant piping: 7.5m, level difference: 0m 2-3 Electrical Specifications Power Supply ERQ125A7W1B Name W1 Phase 3N~ Frequency Hz 50 Voltage V 400 Voltage range Current 4 ERQ200A7W1B Nominal running current (RLA) Minimum V -10% Maximum V +10% ERQ250A7W1B Cooling A 5.1 7.5 11.3 Heating A 5.8 8.2 11.1 889 842 Starting current (cooling/heating) A Minimum Ssc value kVa 74 Minimum circuit amps (MCA) A 11.9 Maximum fuse amps (MFA) A 16 Total overcurrent amps (TOCA) A 15.6 16.5 31.5 Full load amps (FLA) A 0.4 0.7 0.9 • Air Handling Unit Connection • Heat pump 18.5 21.6 25 • Air handling unit connection • ERQ-AW1 2 Specifications 2-3 Electrical Specifications Wiring connections ERQ125A7W1B For Power Supply For connection with indoor ERQ200A7W1B Quantity 5 Remark Earth wire included Quantity 2 Remark F1 - F2 Power Supply Intake ERQ250A7W1B Both indoor and outdoor unit Notes MFA is used to select the circuit breaker and the ground fault circuit interrupter MSC means the maximum current during start up of the compressor Maximum allowable voltage range variation between phases is 2%. RLA is based on following conditions: indoor temperature: 27°CDB/19°CWB, outdoor temperature: 35°CDB Select wire size based on the value of MCA or TOCA TOCA means the total value of each OC set Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits FLA means the full load amps of the fan motor. In accordance with EN/IEC 61000-3-11 (1), respectively EN/IEC 61000-3-12 (2), it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (4) smaller than or equal to Zmax, respecti (1) European/international technical standard setting the limits for voltage changers, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated smaller than or equal to 75A. (2) European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A smaller than or equal to 75A per phase. (3) Short-circuit power (4) System impedance 3 Options ERQ-AW1 N° Item 1 Cool/heat selector 2 One option per module is required 3 Central drain pan kit ERQ200A7W1B ERQ250A7W1B ERQ125A7W1B KRC19-26A6 KJB111A KWC26B160 KWC26B280 4TW32031-4 Notes: 1. All options are kits. 2. Only 1 option per installation is needed. 3. One option per module is required 4. The option should be installed inside the outdoor unit. • Air Handling Unit Connection • Heat pump 5 • Air handling unit connection • ERQ-AW1 4 Integrated heating capacity coefficient ERQ-AW1 Integrated heating capacity coefficient The heating capacity tables do not take account of the reduction in capacity, when frost has accumulated or while the defrosting operation is in progress. The capacity values, which take these factors into account, in other words, the integrated heating capacity values, can be calculated as follows Formula: Integrated heating capacity = A Value given in table of capacity characteristics = B Integrating correction factor for frost accumulation (kW) = C A=BxC Correction factor for finding integrated heating capacity Inlet port temperature of heat exchanger (°C/RH 85%) Integrating correction factor for frost accumulation -5 0,93 -3 0,87 0 0,81 3 0,83 5 0,89 7 1,0 Note: 1. The figures shows that the integrated heating capacity expresses the integrated capacity for a single cycle (from defrost operation to defrost operation) in terms of time. Defrosting operation Heating capacity Defrosting operation -7 0,96 Time One cycle Please note that, when there is an accumulation of snow against the outside surface of the outdoor unit heat exchanger, there will always be a temporary redusion in capacity, although this will of course vary in degree in accordance with a number of other factors, such as the outdoor temperature (°CDB), relative humidity (RH) and the amount of frosting which occurs. 3TW27232-7 6 • Air Handling Unit Connection • Heat pump • Air handling unit connection • ERQ-AW1 5 Capacity tables 5-1 Combination table ERQ-AW1 Combination table Outdoor unit ERQ100 ERQ125 ERQ140 ERQ125 ERQ200 ERQ250 1 ph 3 ph Control box EKEQDCBV3 EKEQFCBV3 P P P P P P P P P P P P EKEXV63 P P P - EKEXV80 P P P P - EKEXV100 P P P P P - Expansion valve kit EKEXV125 P P P P P P EKEXV140 P P P P P EKEXV200 P P EKEXV250 P P Heat pump P: Pair: Combination depending on AHU heat exchanger volume and capacity Allowed heat exchanger volume (dm3) EKEXV Class 63 80 100 125 140 200 250 Allowed heat exchanger capacity (kW) Minimum Maximum Minimum Maximum 1.66 2.09 2.65 3.31 4.13 4.63 6.61 2.08 2.64 3.3 4.12 4.62 6.6 8.25 6.3 7.9 10 12.4 15.5 17.7 24.7 7.8 9.9 12.3 15.4 17.6 24.6 30.8 Saturated suction temperature (SST) = 6°C, Superheat (SH) = 5K Air temperature =27°CDB/19°CWB If conflicting result occurs, capacity selection has priority over volume. 3TW32009-1 • Air Handling Unit Connection • Heat pump 7 • Air handling unit connection • ERQ-AW1 5 Capacity tables 5-2 Cooling capacity tables ERQ125AW1 Cooling Combination % kW (Capacity index) TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor) Outdoor air temp. (°CDB) 14.0 °CWB 20.0 °CDB TC PI 16.0 °CWB 23.0 °CDB TC PI 18.0 °CWB 26.0 °CDB TC PI Indoor air temp. °CWB 19.0 °CWB 20.0 °CWB 27.0 °CDB 28.0 °CDB TC PI TC PI 22.0 °CWB 30.0 °CDB TC PI 24.0 °CWB 32.0 °CDB TC PI 4TW32032-1 NOTES - ANMERKUNGEN - ƧƺƸƼǏDŽƸƼǃ - NOTAS - REMARQUES - NOTE - OPMERKINGEN - ȎȏȇȋȄȖǿȌȇȞ - NOTLAR 1 8 The above table shows the average value of conditions which may occur. Die obige Tabelle zeigt den Durchschnittswert der Bedingungen. die auftreten können. ƧDžǁƿ ƴǂƴƯƿNJ Ʋƿƴƽƴ ƴƿƴƶǂƯLJƸDžƴƼ ƺ ưDŽƺ DžƼƱ ƶƼƴ DŽdžƿƻƱƽƸǃ ǁdž ǁǂƸƲ ƿƴ ǂǁƽǎljǁdžƿ. La tabla de arriba muestra el valor medio de condiciones que pueden ocurrir. Le tableau ci-dessus donne la valeur moyenne pour des conditions qui peuvent survenir. La tabella in alto mostra il valore delle condizioni medie che si possono riscontrare. De tabel hierboven geeft de gemiddelde waarde aan van situaties die kunnen voorvallen. DZǿȀȊȇȕǿ ȏǿȐȎȍȊȍȅȄȌȌǿȞ ȁȚȗȄ ȎȍȉǿȆȚȁǿȄȑ ȐȏȄȃȌȄȄ ȆȌǿȖȄȌȇȄ ȒȐȊȍȁȇȈ. ȉȍȑȍȏȚȄ ȋȍȂȒȑ ȌǿȐȑȒȎȇȑț. <XNDUÕGDNLWDEORPH\GDQDJHOHELOHFHNNRúXOODUÕQRUWDODPDGH÷erini göstermektedir. • Air Handling Unit Connection • Heat pump • Air handling unit connection • ERQ-AW1 5 Capacity tables 5-2 Cooling capacity tables ERQ125AW1 Cooling Combination % kW (Capacity index) TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor) Outdoor air temp. (°CDB) 14.0 °CWB 20.0 °CDB TC PI 16.0 °CWB 23.0 °CDB TC PI 18.0 °CWB 26.0 °CDB TC PI Indoor air temp. °CWB 19.0 °CWB 20.0 °CWB 27.0 °CDB 28.0 °CDB TC PI TC PI • Air Handling Unit Connection • Heat pump 22.0 °CWB 30.0 °CDB TC PI 24.0 °CWB 32.0 °CDB TC PI 9 • Air handling unit connection • ERQ-AW1 5 Capacity tables 5-2 Cooling capacity tables ERQ200AW1 Cooling Combination % kW (Capacity index) TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor) Outdoor air temp. (°CDB) 14.0 °CWB 20.0 °CDB TC PI 16.0 °CWB 23.0 °CDB TC PI 18.0 °CWB 26.0 °CDB TC PI Indoor air temp. °CWB 19.0 °CWB 20.0 °CWB 27.0 °CDB 28.0 °CDB TC PI TC PI 22.0 °CWB 30.0 °CDB TC PI 24.0 °CWB 32.0 °CDB TC PI 4TW32032-1 NOTES - ANMERKUNGEN - ƧƺƸƼǏDŽƸƼǃ - NOTAS - REMARQUES - NOTE - OPMERKINGEN - ȎȏȇȋȄȖǿȌȇȞ - NOTLAR 1 10 The above table shows the average value of conditions which may occur. Die obige Tabelle zeigt den Durchschnittswert der Bedingungen. die auftreten können. ƧDžǁƿ ƴǂƴƯƿNJ Ʋƿƴƽƴ ƴƿƴƶǂƯLJƸDžƴƼ ƺ ưDŽƺ DžƼƱ ƶƼƴ DŽdžƿƻƱƽƸǃ ǁdž ǁǂƸƲ ƿƴ ǂǁƽǎljǁdžƿ. La tabla de arriba muestra el valor medio de condiciones que pueden ocurrir. Le tableau ci-dessus donne la valeur moyenne pour des conditions qui peuvent survenir. La tabella in alto mostra il valore delle condizioni medie che si possono riscontrare. De tabel hierboven geeft de gemiddelde waarde aan van situaties die kunnen voorvallen. DZǿȀȊȇȕǿ ȏǿȐȎȍȊȍȅȄȌȌǿȞ ȁȚȗȄ ȎȍȉǿȆȚȁǿȄȑ ȐȏȄȃȌȄȄ ȆȌǿȖȄȌȇȄ ȒȐȊȍȁȇȈ. ȉȍȑȍȏȚȄ ȋȍȂȒȑ ȌǿȐȑȒȎȇȑț. <XNDUÕGDNLWDEORPH\GDQDJHOHELOHFHNNRúXOODUÕQRUWDODPDGH÷erini göstermektedir. • Air Handling Unit Connection • Heat pump • Air handling unit connection • ERQ-AW1 5 Capacity tables 5-2 Cooling capacity tables ERQ200AW1 Cooling Combination % kW (Capacity index) TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor) Outdoor air temp. (°CDB) 14.0 °CWB 20.0 °CDB TC PI 16.0 °CWB 23.0 °CDB TC PI 18.0 °CWB 26.0 °CDB TC PI Indoor air temp. °CWB 19.0 °CWB 20.0 °CWB 27.0 °CDB 28.0 °CDB TC PI TC PI • Air Handling Unit Connection • Heat pump 22.0 °CWB 30.0 °CDB TC PI 24.0 °CWB 32.0 °CDB TC PI 11 • Air handling unit connection • ERQ-AW1 5 Capacity tables 5-2 Cooling capacity tables ERQ250AW1 Cooling Combination % kW (Capacity index) TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor) Outdoor air temp. (°CDB) 14.0 °CWB 20.0 °CDB TC PI 16.0 °CWB 23.0 °CDB TC PI 18.0 °CWB 26.0 °CDB TC PI Indoor air temp. °CWB 19.0 °CWB 20.0 °CWB 27.0 °CDB 28.0 °CDB TC PI TC PI 22.0 °CWB 30.0 °CDB TC PI 24.0 °CWB 32.0 °CDB TC PI 4TW32032-1 NOTES - ANMERKUNGEN - ƧƺƸƼǏDŽƸƼǃ - NOTAS - REMARQUES - NOTE - OPMERKINGEN - ȎȏȇȋȄȖǿȌȇȞ - NOTLAR 1 12 The above table shows the average value of conditions which may occur. Die obige Tabelle zeigt den Durchschnittswert der Bedingungen. die auftreten können. ƧDžǁƿ ƴǂƴƯƿNJ Ʋƿƴƽƴ ƴƿƴƶǂƯLJƸDžƴƼ ƺ ưDŽƺ DžƼƱ ƶƼƴ DŽdžƿƻƱƽƸǃ ǁdž ǁǂƸƲ ƿƴ ǂǁƽǎljǁdžƿ. La tabla de arriba muestra el valor medio de condiciones que pueden ocurrir. Le tableau ci-dessus donne la valeur moyenne pour des conditions qui peuvent survenir. La tabella in alto mostra il valore delle condizioni medie che si possono riscontrare. De tabel hierboven geeft de gemiddelde waarde aan van situaties die kunnen voorvallen. DZǿȀȊȇȕǿ ȏǿȐȎȍȊȍȅȄȌȌǿȞ ȁȚȗȄ ȎȍȉǿȆȚȁǿȄȑ ȐȏȄȃȌȄȄ ȆȌǿȖȄȌȇȄ ȒȐȊȍȁȇȈ. ȉȍȑȍȏȚȄ ȋȍȂȒȑ ȌǿȐȑȒȎȇȑț. <XNDUÕGDNLWDEORPH\GDQDJHOHELOHFHNNRúXOODUÕQRUWDODPDGH÷erini göstermektedir. • Air Handling Unit Connection • Heat pump • Air handling unit connection • ERQ-AW1 5 Capacity tables 5-2 Cooling capacity tables ERQ250AW1 Cooling Combination % kW (Capacity index) TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor) Outdoor air temp. (°CDB) 14.0 °CWB 20.0 °CDB TC PI 16.0 °CWB 23.0 °CDB TC PI 18.0 °CWB 26.0 °CDB TC PI Indoor air temp. °CWB 19.0 °CWB 20.0 °CWB 27.0 °CDB 28.0 °CDB TC PI TC PI • Air Handling Unit Connection • Heat pump 22.0 °CWB 30.0 °CDB TC PI 24.0 °CWB 32.0 °CDB TC PI 13 • Air handling unit connection • ERQ-AW1 5 Capacity tables 5-3 Heating capacity tables ERQ125AW1 Heating TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor) Combination % kW (Capacity index) Outdoor air temp. °CDB °CWB TC kW 16.0 PI kW TC kW 18.0 Indoor air temp. °CWB 20.0 21.0 TC PI TC PI kW kW kW kW PI kW TC kW 22.0 PI kW TC kW 24.0 PI kW 4TW32032-2 NOTES - ANMERKUNGEN - ƧƺƸƼǏDŽƸƼǃ - NOTAS - REMARQUES - NOTE - OPMERKINGEN - ȎȏȇȋȄȖǿȌȇȞ - NOTLAR 1 14 ■ is shown as reference When selecting the unit models, avoid the outdoor air temperature range shown by ■ ■ dient als Verweis. Vermeiden Sie bei der Auswahl der Gerätemodelle den als ■ markierten Temperaturbereich der Außenluft. ■İȝijĮȞȓȗİIJĮȚıĮȞIJȚȝȒĮȞĮijȠȡȐȢ ȀĮIJȐIJȘȞİʌȚȜȠȖȒȝȠȞIJȑȜȦȞȝȠȞȐįȦȞĮʌȠijȪȖİIJİIJȘȞʌİȡȚȠȤȒ șİȡȝȠțȡĮıȓĮȢİȟȦIJİȡȚțȠȪĮȑȡĮʌȠȣİȝijĮȞȓȗİIJĮȚıIJȠ■ ■ se muestra a modo de referencia. Cuando seleccione los modelos de unidad, evite el intervalo de temperaturas del aire exterior indicado mediante ■ ■ est indiqué à titre de référence. Lors de la sélection des modèles d’unité, évitez la plage de température d’air extérieur repérée par ■ ■ viene mostrato come riferimento. Nel selezionare i modelli delle unità, non considerare i valori di temperatura dell’aria esterna indicati con il colore ■ ■ wordt ter referentie opgegeven Bij selectie van de modellen dient u het gemarkeerde ■ bereik voor de buitenluchttemperatuur te vermijden. ■ ɩɪɢɜɟɞɟɧɨɞɥɹɫɩɪɚɜɤɢ ɉɪɢɜɵɛɨɪɟɦɨɞɟɥɟɣɛɥɨɤɨɜɢɡɛɟɝɚɣɬɟɞɢɚɩɚɡɨɧɬɟɦɩɟɪɚɬɭɪɚ ɧɚɪɭɠɧɨɝɨɜɨɡɞɭɯɚɩɨɤɚɡɚɧɧɵɣɜ■ referans olarak görülmektedir. hQLWHPRGHOOHULQLVHoHUNHQJ|UOHQGÕúKDYDVÕFDNOÕ÷ÕDUDOÕ÷ÕQGDQ NDoÕQÕQ■ ■ 2 The above table shows the average value of conditions which may occur. Die obige Tabelle zeigt den Durchschnittswert der Bedingungen. die auftreten können. ƧDžǁƿ ƴǂƴƯƿNJ Ʋƿƴƽƴ ƴƿƴƶǂƯLJƸDžƴƼ ƺ ưDŽƺ DžƼƱ ƶƼƴ DŽdžƿƻƱƽƸǃ ǁdž ǁǂƸƲ ƿƴ ǂǁƽǎljǁdžƿ. La tabla de arriba muestra el valor medio de condiciones que pueden ocurrir. Le tableau ci-dessus donne la valeur moyenne pour des conditions qui peuvent survenir. La tabella in alto mostra il valore delle condizioni medie che si possono riscontrare. De tabel hierboven geeft de gemiddelde waarde aan van situaties die kunnen voorvallen. DZǿȀȊȇȕǿ ȏǿȐȎȍȊȍȅȄȌȌǿȞ ȁȚȗȄ ȎȍȉǿȆȚȁǿȄȑ ȐȏȄȃȌȄȄ ȆȌǿȖȄȌȇȄ ȒȐȊȍȁȇȈ. ȉȍȑȍȏȚȄ ȋȍȂȒȑ ȌǿȐȑȒȎȇȑț. <XNDUÕGDNLWDEORPH\GDQDJHOHELOHFHNNRúXOODUÕQRUWDODPDGH÷erini göstermektedir. • Air Handling Unit Connection • Heat pump • Air handling unit connection • ERQ-AW1 5 Capacity tables 5-3 Heating capacity tables ERQ125AW1 Heating TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor) Combination % kW (Capacity index) Outdoor air temp. °CDB °CWB TC kW 16.0 PI kW TC kW 18.0 PI kW Indoor air temp. °CWB 20.0 21.0 TC PI TC PI kW kW kW kW TC kW 22.0 PI kW TC kW 24.0 PI kW 4TW32032-2 • Air Handling Unit Connection • Heat pump 15 • Air handling unit connection • ERQ-AW1 5 Capacity tables 5-3 Heating capacity tables ERQ200AW1 Heating TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor) Combination % kW (Capacity index) Outdoor air temp. °CDB °CWB TC kW 16.0 PI kW TC kW 18.0 Indoor air temp. °CWB 20.0 21.0 TC PI TC PI kW kW kW kW PI kW TC kW 22.0 PI kW TC kW 24.0 PI kW 4TW32032-2 NOTES - ANMERKUNGEN - ƧƺƸƼǏDŽƸƼǃ - NOTAS - REMARQUES - NOTE - OPMERKINGEN - ȎȏȇȋȄȖǿȌȇȞ - NOTLAR 1 16 ■ is shown as reference When selecting the unit models, avoid the outdoor air temperature range shown by ■ ■ dient als Verweis. Vermeiden Sie bei der Auswahl der Gerätemodelle den als ■ markierten Temperaturbereich der Außenluft. ■İȝijĮȞȓȗİIJĮȚıĮȞIJȚȝȒĮȞĮijȠȡȐȢ ȀĮIJȐIJȘȞİʌȚȜȠȖȒȝȠȞIJȑȜȦȞȝȠȞȐįȦȞĮʌȠijȪȖİIJİIJȘȞʌİȡȚȠȤȒ șİȡȝȠțȡĮıȓĮȢİȟȦIJİȡȚțȠȪĮȑȡĮʌȠȣİȝijĮȞȓȗİIJĮȚıIJȠ■ ■ se muestra a modo de referencia. Cuando seleccione los modelos de unidad, evite el intervalo de temperaturas del aire exterior indicado mediante ■ ■ est indiqué à titre de référence. Lors de la sélection des modèles d’unité, évitez la plage de température d’air extérieur repérée par ■ ■ viene mostrato come riferimento. Nel selezionare i modelli delle unità, non considerare i valori di temperatura dell’aria esterna indicati con il colore ■ ■ wordt ter referentie opgegeven Bij selectie van de modellen dient u het gemarkeerde ■ bereik voor de buitenluchttemperatuur te vermijden. ■ ɩɪɢɜɟɞɟɧɨɞɥɹɫɩɪɚɜɤɢ ɉɪɢɜɵɛɨɪɟɦɨɞɟɥɟɣɛɥɨɤɨɜɢɡɛɟɝɚɣɬɟɞɢɚɩɚɡɨɧɬɟɦɩɟɪɚɬɭɪɚ ɧɚɪɭɠɧɨɝɨɜɨɡɞɭɯɚɩɨɤɚɡɚɧɧɵɣɜ■ referans olarak görülmektedir. hQLWHPRGHOOHULQLVHoHUNHQJ|UOHQGÕúKDYDVÕFDNOÕ÷ÕDUDOÕ÷ÕQGDQ NDoÕQÕQ■ ■ 2 The above table shows the average value of conditions which may occur. Die obige Tabelle zeigt den Durchschnittswert der Bedingungen. die auftreten können. ƧDžǁƿ ƴǂƴƯƿNJ Ʋƿƴƽƴ ƴƿƴƶǂƯLJƸDžƴƼ ƺ ưDŽƺ DžƼƱ ƶƼƴ DŽdžƿƻƱƽƸǃ ǁdž ǁǂƸƲ ƿƴ ǂǁƽǎljǁdžƿ. La tabla de arriba muestra el valor medio de condiciones que pueden ocurrir. Le tableau ci-dessus donne la valeur moyenne pour des conditions qui peuvent survenir. La tabella in alto mostra il valore delle condizioni medie che si possono riscontrare. De tabel hierboven geeft de gemiddelde waarde aan van situaties die kunnen voorvallen. DZǿȀȊȇȕǿ ȏǿȐȎȍȊȍȅȄȌȌǿȞ ȁȚȗȄ ȎȍȉǿȆȚȁǿȄȑ ȐȏȄȃȌȄȄ ȆȌǿȖȄȌȇȄ ȒȐȊȍȁȇȈ. ȉȍȑȍȏȚȄ ȋȍȂȒȑ ȌǿȐȑȒȎȇȑț. <XNDUÕGDNLWDEORPH\GDQDJHOHELOHFHNNRúXOODUÕQRUWDODPDGH÷erini göstermektedir. • Air Handling Unit Connection • Heat pump • Air handling unit connection • ERQ-AW1 5 Capacity tables 5-3 Heating capacity tables ERQ200AW1 Heating TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor) Combination % kW (Capacity index) Outdoor air temp. °CDB °CWB TC kW 16.0 PI kW TC kW 18.0 PI kW Indoor air temp. °CWB 20.0 21.0 TC PI TC PI kW kW kW kW TC kW 22.0 PI kW TC kW 24.0 PI kW 4TW32032-2 • Air Handling Unit Connection • Heat pump 17 • Air handling unit connection • ERQ-AW1 5 Capacity tables 5-3 Heating capacity tables ERQ250AW1 Heating TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor) Combination % kW (Capacity index) Outdoor air temp. °CDB °CWB TC kW 16.0 PI kW TC kW 18.0 Indoor air temp. °CWB 20.0 21.0 TC PI TC PI kW kW kW kW PI kW TC kW 22.0 PI kW TC kW 24.0 PI kW 4TW32032-2 NOTES - ANMERKUNGEN - ƧƺƸƼǏDŽƸƼǃ - NOTAS - REMARQUES - NOTE - OPMERKINGEN - ȎȏȇȋȄȖǿȌȇȞ - NOTLAR 1 18 ■ is shown as reference When selecting the unit models, avoid the outdoor air temperature range shown by ■ ■ dient als Verweis. Vermeiden Sie bei der Auswahl der Gerätemodelle den als ■ markierten Temperaturbereich der Außenluft. ■İȝijĮȞȓȗİIJĮȚıĮȞIJȚȝȒĮȞĮijȠȡȐȢ ȀĮIJȐIJȘȞİʌȚȜȠȖȒȝȠȞIJȑȜȦȞȝȠȞȐįȦȞĮʌȠijȪȖİIJİIJȘȞʌİȡȚȠȤȒ șİȡȝȠțȡĮıȓĮȢİȟȦIJİȡȚțȠȪĮȑȡĮʌȠȣİȝijĮȞȓȗİIJĮȚıIJȠ■ ■ se muestra a modo de referencia. Cuando seleccione los modelos de unidad, evite el intervalo de temperaturas del aire exterior indicado mediante ■ ■ est indiqué à titre de référence. Lors de la sélection des modèles d’unité, évitez la plage de température d’air extérieur repérée par ■ ■ viene mostrato come riferimento. Nel selezionare i modelli delle unità, non considerare i valori di temperatura dell’aria esterna indicati con il colore ■ ■ wordt ter referentie opgegeven Bij selectie van de modellen dient u het gemarkeerde ■ bereik voor de buitenluchttemperatuur te vermijden. ■ ɩɪɢɜɟɞɟɧɨɞɥɹɫɩɪɚɜɤɢ ɉɪɢɜɵɛɨɪɟɦɨɞɟɥɟɣɛɥɨɤɨɜɢɡɛɟɝɚɣɬɟɞɢɚɩɚɡɨɧɬɟɦɩɟɪɚɬɭɪɚ ɧɚɪɭɠɧɨɝɨɜɨɡɞɭɯɚɩɨɤɚɡɚɧɧɵɣɜ■ referans olarak görülmektedir. hQLWHPRGHOOHULQLVHoHUNHQJ|UOHQGÕúKDYDVÕFDNOÕ÷ÕDUDOÕ÷ÕQGDQ NDoÕQÕQ■ ■ 2 The above table shows the average value of conditions which may occur. Die obige Tabelle zeigt den Durchschnittswert der Bedingungen. die auftreten können. ƧDžǁƿ ƴǂƴƯƿNJ Ʋƿƴƽƴ ƴƿƴƶǂƯLJƸDžƴƼ ƺ ưDŽƺ DžƼƱ ƶƼƴ DŽdžƿƻƱƽƸǃ ǁdž ǁǂƸƲ ƿƴ ǂǁƽǎljǁdžƿ. La tabla de arriba muestra el valor medio de condiciones que pueden ocurrir. Le tableau ci-dessus donne la valeur moyenne pour des conditions qui peuvent survenir. La tabella in alto mostra il valore delle condizioni medie che si possono riscontrare. De tabel hierboven geeft de gemiddelde waarde aan van situaties die kunnen voorvallen. DZǿȀȊȇȕǿ ȏǿȐȎȍȊȍȅȄȌȌǿȞ ȁȚȗȄ ȎȍȉǿȆȚȁǿȄȑ ȐȏȄȃȌȄȄ ȆȌǿȖȄȌȇȄ ȒȐȊȍȁȇȈ. ȉȍȑȍȏȚȄ ȋȍȂȒȑ ȌǿȐȑȒȎȇȑț. <XNDUÕGDNLWDEORPH\GDQDJHOHELOHFHNNRúXOODUÕQRUWDODPDGH÷erini göstermektedir. • Air Handling Unit Connection • Heat pump • Air handling unit connection • ERQ-AW1 5 Capacity tables 5-3 Heating capacity tables ERQ250AW1 Heating TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor) Combination % kW (Capacity index) Outdoor air temp. °CDB °CWB TC kW 16.0 PI kW TC kW 18.0 PI kW Indoor air temp. °CWB 20.0 21.0 TC PI TC PI kW kW kW kW TC kW 22.0 PI kW TC kW 24.0 PI kW 4TW32032-2 • Air Handling Unit Connection • Heat pump 19 • Air handling unit connection • ERQ-AW1 5 Capacity tables 5-4 Capacity correction factor Correction factor for piping length (α) Cooling ERQ-AW1 125 Class 200 Class Correction factor for piping length (α) Heating 125,200,250Class Explanation of symbols: Hp: Level difference between air handling unit and outdoorunit when air handling unit is installed below the outdoor unit Hm: Level difference between air handling unit and outdoorunit when air handling unit is installed above the outdoor unit L: Equivalent piping length (m) α: Capacity correction factor 250 Class Diameter of pipes: Outdoor unit class 125 200 250 Gas J15.9 J19.1 J22.2 Notes: 1 These figures illustrate the correction factor for piping length of the system at maximum load under standard conditions. Under patrial load conditions there is only minor deviation from the correction factor shown in the figures above. 2 Method of calculating cooling capacity (max. capacity) Cooling capacity = Cooling capacity obtained from the cooling capacity characteristics table X Capacity correction factor 3 Method of calculating heating capacity (max. capacity) Heating capacity= Heating capacity obtained from the heating capacity characteristics tableX Capacity correction factor 20 • Air Handling Unit Connection • Heat pump Liquid J9.5 J9.5 J9.5 3TW32032-2 • Air handling unit connection • ERQ-AW1 6 Dimensional drawing & centre of gravity 6-1 Dimensional drawing ERQ125AW1 4-15X22,5-mm-Oblong holes (foundation bolt hole) Note) 1. Detail for front side and detail for bottom side indicate the dimensions after fixing the attached piping. (Pitch of foundation bolt holes) (Pitch of foundation bolt holes) Detail for front side (Knock-out hole) (Knock-out hole) Detail for bottom side (Knock-out hole) (Knock-out hole) (Knock-out hole) 1 2 3 4 5 6 7 8 9 10 Liquid pipe connection port J9.5 Brazing connection Gas pipe connection port J15.9 Brazing connection Grounding terminal inside of switch box (M8) Power cord routing hole (side) J62 Power cord routing hole (front) J45 Power cord routing hole (front) J27 Power cord routing hole (bottom) J50 Wire routing hole (front) J27 Pipe routing hole (front) Pipe routing hole (bottom) 3D051448E ERQ200,250AW1 4-15X22,5-mm-Oblong holes (foundation bolt hole) (Pitch of foundation bolt holes) (Pitch of foundation bolt holes) Notes) 1 Detail for front side and detail for bottom side indicate the dimensions after fixing the attached piping. 2 Gas pipe (Heat pump type) J19.1 Brazing connection ... 8PY1 type J22.2 Brazing connection ... 10PY1 type Liquid pipe (Heat pump type) J9.5 Brazing connection ... 8-10PY1 type 6 (for 8HP) Detail for front side (Knock-out hole) (Knock-out hole) Detail for bottom side (Knock-out hole) (Knock-out hole) (Knock-out hole) 1 2 3 4 5 6 7 8 9 10 Liquid pipe connection port (see note) 2. Gas pipe connection port see note 2. Grounding terminal inside of switch box (M8) Power cord routing hole (side) J62 Power cord routing hole (front) J45 Power cord routing hole (front) J27 Power cord routing hole (bottom) J65.5 Wire routing hole (front) J27 Pipe routing hole (front) Pipe routing hole (bottom) • Air Handling Unit Connection • Heat pump 3D051449H 21 • Air handling unit connection • ERQ-AW1 6 Dimensional drawing & centre of gravity 6-1 Dimensional drawing ERQ125AW1 Central drain pan kit (KWC26B160) 3TW27234-1 ERQ200,250AW1 Central drain pan kit (KWC26B280) 22 • Air Handling Unit Connection • Heat pump 3TW27244-1 • Air handling unit connection • ERQ-AW1 6 Dimensional drawing & centre of gravity 6-2 Centre of gravity ERQ125AW1 Center of foundation bolt hole Center of foundation bolt hole Center of foundation bolt hole (Slot) Center of foundation bolt hole 4D052145D Center of foundation bolt hole (Slot) ERQ200AW1 Center of foundation bolt hole Center of foundation bolt hole Center of foundation bolt hole (Slot) Center of foundation bolt hole Center of foundation bolt hole (Slot) • Air Handling Unit Connection • Heat pump 4D052146J 23 • Air handling unit connection • ERQ-AW1 6 Dimensional drawing & centre of gravity 6-2 Centre of gravity ERQ250AW1 Center of foundation bolt hole Center of foundation bolt hole Center of foundation bolt hole (Slot) 24 Center of foundation bolt hole Center of foundation bolt hole (Slot) • Air Handling Unit Connection • Heat pump 4D052147H • Air handling unit connection • ERQ-AW1 Piping diagram ERQ125AW1 FAN Electronic expansion valve Filter Pressure regulating valve Heat exchanger Electronic expansion valve Accumulator Capillary tube Solenoid valve 4-way valve Filter High pressure sensor Oil separator Filter Check valve Filter Filter Capillary tube High pressure switch Solenoid valve Filter Compressor Solenoid valve Capillary tube 7 Low pressure sensor Stop valve (with service port on field piping side J 7.9mm flare connection) • Air Handling Unit Connection • Heat pump 4TW27235-1 25 • Air handling unit connection • ERQ-AW1 7 Piping diagram ERQ200AW1 Check valve Electronic expansion valve FAN Electronic expansion valve Filter Pressure regulating valve Accumulator Heat exchanger 4-way valve High pressure sensor Filter Solenoid valve Oil separator High pressure switch Capillary tube Filter Filter Check valve Solenoid valve Capillary tube Filter Filter Compressor Low pressure sensor Stop valve (with service port on field piping side J 7.9mm flare connection) 26 • Air Handling Unit Connection • Heat pump 4TW27245-1 • Air handling unit connection • ERQ-AW1 Piping diagram ERQ250AW1 Check valve Electronic expansion valve Electronic expansion valve FAN Filter Pressure regulating valve Accumulator Heat exchanger 4-way valve High pressure sensor Filter Solenoid valve Check valve Oil separator High pressure switch Oil separator Filter Filter Filter Check valve Capillary tube High pressure switch Filter Filter Capillary tube Compressor Capillary tube Solenoid valve Filter 7 Compressor Low pressure sensor Stop valve (with service port on field piping side J 7.9mm flare connection) • Air Handling Unit Connection • Heat pump 4TW27255-1 27 • Air handling unit connection • ERQ-AW1 8 Wiring diagram 8-1 Wiring diagram ERQ125AW1 A1P A2P A3P A4P A5P BS1∼BS5 C1 C63,C66 DS1,DS2 E1HC F1U F1U,F2U F5U F400U H1P∼H8P [H2P] HAP K1 K2 K3R K4R K5R K7R K11R L1R M1C M1F PS Q1RP Q1DI R10 R50,R59 R95 R1T R1T R2T R3T R4T R5T R6T S1NPH S1NPL S1PH SD1 V1R V1R,V2R X1A,X2A X1M X1M X1M Y1E Y1S Y2S Y3S Y4S Z1C∼Z5C Z1F : Printed circuit board (Main) : Printed circuit board (Noise filter) : Printed circuit board (Inverter) : Printed circuit board (Fan) : Printed circuit board (ABC I/P) : Push button switch (Mode, set, return, test, reset) : Capacitor : Capacitor : Dip switch : Crankcase heater B ) (A4P) : Fuse (250V, 8A j T ) (A1P) : Fuse (250V, 3.15A j : Field fuse T ) (A2P) : Fuse (250V, 6.3A j : Pilotlamp (service monitor - orange) : Prepare test ----------- Flickering : Malfunction detection--- Light up : Pilotlamp (service monitor - green) : Magnetic relay : Magnetic contactor(M1C) : Magnetic relay (Y1S) : Magnetic relay (Y2S) : Magnetic relay (Y3S) : Magnetic relay (E1HC) : Magnetic relay (Y4S) : Reactor : Motor (compressor) : Motor (fan) : Switching power supply (A1P,A3P) : Phase reversal detect circuit : Earth leakage breaker : Resistor (Current sensor) (A4P) : Resistor : Resistor (current limiting) : Thermistor (air) (A1P) : Thermistor (Fin) (A3P) : Thermistor (Suction) : Thermistor (discharge pipe) (M1C) : Thermistor (Heat exch. deicer) : Thermistor (liquid pipe) : Thermistor (Accumulator) : Pressure sensor (High) : Pressure sensor (Low) : Pressure switch (High) : Safety devices input : Power module (A4P) : Power module (A3P) : Connector (M1F) : Terminal strip (Power supply) : Terminal strip (Control) (A1P) : Terminal strip (A5P) : Electronic expansion valve (Main) : Solenoid valve (Hot gas) : Solenoid valve (oil return) : Solenoid valve (4-way valve) : Solenoid valve (injection) : Noise filter (ferrite core) : Noise filter (with surge absorber) Power supply (Note 4) Cool/heat selector (Note 5) Cool Cool Cool Fan Heat Indoor (F1)(F2) Cool/heat selector (Option) Notes: 1. This wiring diagram only applies to the outdoor unit 2. : Field wiring, : Indication of parts outside switchbox : Terminal strip : Connector 3. : Protective earth (screw) : Terminal 4. When using the option adaptor, refer to the installation manual 5. Refer to the installation manual, for connection of the F1 - F2 transmission wiring and how to use BS1∼BS5 and DS1, DS2 switch. 6. Do not operate the unit by short-circuiting protection device S1PH 7. Colours: BLK: Black / WHT: White / RED: Red / BLU: Blue / BRN: Brown / GRN: Green / YLW: Yellow PNK: Pink / GRY: grey / ORG: Orange Position of M1C,M1F El. Compo. Box M1C Outer shell Cool/heat selector S1S : Selector switch (Fan/Cool-Heat) S2S : Selector switch (Cool-Heat) Front layer Rear layer Position in switch box Detail of M1C 2TW32036-1 ERQ200AW1 A1P A2P A3P A4P A5P BS1∼BS5 C1 C63,C66 DS1,DS2 E1HC F1U F1U,F2U F5U F400U H1P∼H8P [H2P] HAP K1 K2 K3R K4R K5R K7R L1R M1C M1F PS Q1RP Q1DI R10 R50,R59 R95 R1T R1T R2T R3T R4T R5T R6T R7T S1NPH S1NPL S1PH SD1 V1R V1R,V2R X1A,X2A X1M X1M X1M Y1E Y1S Y2S Y3S Z1C∼Z5C Z1F : Printed circuit board (Main) : Printed circuit board (Noise filter) : Printed circuit board (Inverter) : Printed circuit board (Fan) : Printed circuit board (ABC I/P) : Push button switch (Mode, set, return, test, reset) : Capacitor : Capacitor : Dip switch : Crankcase heater B ) (A4P) : Fuse (250V, 8A j T ) (A1P) : Fuse (250V, 3.15A j : Field fuse T ) (A2P) : Fuse (250V, 6.3A j : Pilotlamp (service monitor - orange) : Prepare test ----------- Flickering : Malfunction detection--- Light up : Pilotlamp (service monitor - green) : Magnetic relay : Magnetic contactor(M1C) : Magnetic relay (Y1S) : Magnetic relay (Y2S) : Magnetic relay (Y3S) : Magnetic relay (E1HC) : Reactor : Motor (compressor) : Motor (fan) : Switching power supply (A1P,A3P) : Phase reversal detect circuit : Earth leakage breaker : Resistor (Current sensor) (A4P) : Resistor : Resistor (current limiting) : Thermistor (air) (A1P) : Thermistor (Fin) (A3P) : Thermistor (Suction) : Thermistor (discharge pipe) (M1C) : Thermistor (Heat exch. deicer) : Thermistor (Heat exch. outlet) : Thermistor (liquid pipe) : Thermistor (Accumulator) : Pressure sensor (High) : Pressure sensor (Low) : Pressure switch (High) : Safety devices input : Power module (A4P) : Power module (A3P) : Connector (M1F) : Terminal strip (Power supply) : Terminal strip (Control) (A1P) : Terminal strip (A5P) : Electronic expansion valve (Main) : Solenoid valve (Hot gas) : Solenoid valve (oil return) : Solenoid valve (4-way valve) : Noise filter (ferrite core) : Noise filter (with surge absorber) Cool/heat selector S1S : Selector switch (Fan/Cool-Heat) S2S : Selector switch (Cool-Heat) Power supply (Note 4) Cool/heat selector (Note 5) Cool Male connector: BLU Female connector: WHT Cool Cool Heat Cool/heat selector (Option) Indoor (F1)(F2) Notes: 1. This wiring diagram only applies to the outdoor unit : Field wiring, : Indication of parts outside switchbox 2. 3. : Terminal strip : Connector : Protective earth (screw) : Terminal 4. When using the option adaptor, refer to the installation manual 5. Refer to the installation manual, for connection of the F1 - F2 transmission wiring and how to use BS1∼BS5 and DS1, DS2 switch. 6. Do not operate the unit by short-circuiting protection device S1PH 7. Colours: BLK: Black / WHT: White / RED: Red / BLU: Blue / BRN: Brown / GRN: Green / YLW: Yellow PNK: Pink / GRY: grey / ORG: Orange Position of M1C,M1F El. Compo. Box M1C Outer shell Fan Front layer Rear layer Position in switch box Detail of M1C 2TW32046-1 28 • Air Handling Unit Connection • Heat pump • Air handling unit connection • ERQ-AW1 8 Wiring diagram 8-1 Wiring diagram ERQ250AW1 A1P A2P A3P A4P A5P A6P BS1∼BS5 C1 C63,C66 DS1,DS2 E1HC F1U F1U,F2U F5U F400U H1P∼H8P [H2P] HAP K1 K2 K2M K1R K3R K4R K5R K7R K8R L1R M1C M1F PS Q1RP Q1DI R10 R50,R59 R95 R1T R1T R2T R31T R32T R4T R5T R6T R7T S1NPH S1NPL S1PH, S2PH T1A SD1 V1R V1R,V2R X1A,X2A X1M X1M X1M Y1E Y1S Y2S Y3S Z1C∼Z5C Z1F : Printed circuit board (Main) : Printed circuit board (Noise filter) : Printed circuit board (Inverter) : Printed circuit board (Fan) : Printed circuit board (ABC I/P) : Printed circuit board (Current sensor) : Push button switch (Mode, set, return, test, reset) : Capacitor : Capacitor : Dip switch : Crankcase heater B ) (A4P) : Fuse (250V, 8A j T ) (A1P) : Fuse (250V, 3.15A j : Field fuse T ) (A2P) : Fuse (250V, 6.3A j : Pilotlamp (service monitor - orange) : Prepare test ----------- Flickering : Malfunction detection--- Light up : Pilotlamp (service monitor - green) : Magnetic relay : Magnetic contactor(M1C) : Magnetic contactor(M2C) : Magnetic Relais (K2M) : Magnetic relay (Y1S) : Magnetic relay (Y2S) : Magnetic relay (Y3S) : Magnetic relay (E1HC) : Magnetic relay (E2HC) : Reactor : Motor (compressor) : Motor (fan) : Switching power supply (A1P,A3P) : Phase reversal detect circuit : Earth leakage breaker : Resistor (Current sensor) (A4P) : Resistor : Resistor (current limiting) : Thermistor (air) (A1P) : Thermistor (Fin) (A3P) : Thermistor (Suction) : Thermistor (discharge pipe) (M1C) : Thermistor (discharge pipe) (M2C) : Thermistor (Heat exch. deicer) : Thermistor (Heat exch. outlet) : Thermistor (liquid pipe) : Thermistor (Accumulator) : Pressure sensor (High) : Pressure sensor (Low) : Pressure switch (High) : Current sensor (A6P) : Safety devices input : Power module (A4P) : Power module (A3P) : Connector (M1F) : Terminal strip (Power supply) : Terminal strip (Control) (A1P) : Terminal strip (A5P) : Electronic expansion valve (Main) : Solenoid valve (Hot gas) : Solenoid valve (oil return) : Solenoid valve (4-way valve) : Noise filter (ferrite core) : Noise filter (with surge absorber) Power supply (Note 4) Cool/heat selector (Note 5) Cool Cool Male connector: BLU Female connector: WHT Cool Heat Cool/heat selector (Option) Fan Indoor (F1)(F2) Notes: 1. This wiring diagram only applies to the outdoor unit : Field wiring 2. 3. : Terminal strip : Connector : Protective earth (screw) : Terminal 4. When using the option adaptor, refer to the installation manual 5. Refer to the installation manual, for connection of the F1 - F2 transmission wiring and how to use BS1∼BS5 and DS1, DS2 switch. 6. Do not operate the unit by short-circuiting protection device S1PH 7. Colours: BLK: Black / WHT: White / RED: Red / BLU: Blue / BRN: Brown / GRN: Green / YLW: Yellow PNK: Pink / GRY: grey / ORG: Orange Position of M1C,M2C,M1F El. Compo. Box M1C M2C Outer shell Front layer Rear layer Position in switch box Detail of M1C,M2C Cool/heat selector S1S : Selector switch (Fan/Cool-Heat) S2S : Selector switch (Cool-Heat) 2TW32056-1 • Air Handling Unit Connection • Heat pump 29 • Air handling unit connection • ERQ-AW1 8 Wiring diagram 8-2 External connection diagram ERQ-AW1 Power supply Main switch Outdoor unit Switch Power supply Fuse 1 Main switch 2 wires cable (Transmission line) 2 wires cable (Power line) 2 3 4 5 6 7 8 9 Switch Fuse 2 wires cable (Power line) Control box 10 11 All wiring, components and materials to be produced on the site must comply with the applicable local and national codes. Use copper conductors only. For more details, see wiring diagram. Install a circuit breaker for safety. All field wiring and components must be installed by a licensed electrician. All field wiring and components must be provided by a licensed electrician and must comply with the relevant local and national codes. Wiring shown are general points-of-connection guides only and are not intended for or to include all details for a specific installation. Be sure to install the switch and the fuse to the power line of each equipment. Install the main switch that can interrupt all power sources in an integrated manner because this system consists of the equipment utilizing the multiple power sources. If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. For detailed control box side connection, see control box manual and wiring diagram. 3TW27809-1 30 • Air Handling Unit Connection • Heat pump • Air handling unit connection • ERQ-AW1 9 Sound data 9-1 Sound pressure spectrum Octave band sound pressure level dB(0dB=0.0002μ bar) ERQ200AW1 Octave band sound pressure level dB(0dB=0.0002μ bar) ERQ125AW1 approximate threshold hearing for continuous noise Octave band center frequency (Hz) 4D052395E NOTES The operating sound is measured in anechoic chamber, if it is measured under the actual installation conditions, it is normally over the set value due to enviromental noise and sound reflection. front side NOTES 1 Octave band center frequency (Hz) 1 The operating sound is measured in anechoic chamber, if it is measured under the actual installation conditions, it is normally over the set value due to enviromental noise and sound reflection. Location of microphone front side 4D052394B approximate threshold hearing for continuous noise Location of microphone Octave band sound pressure level dB(0dB=0.0002μ bar) ERQ250AW1 approximate threshold hearing for continuous noise 4D052396E Octave band center frequency (Hz) The operating sound is measured in anechoic chamber, if it is measured under the actual installation conditions, it is normally over the set value due to enviromental noise and sound reflection. front side NOTES 1 Location of microphone • Air Handling Unit Connection • Heat pump 31 • Air handling unit connection • ERQ-AW1 9 Sound data 9-2 Sound power spectrum Sound power level(dB) ERQ200AW1 Sound power level(dB) ERQ125AW1 3TW27237-2 Octave band center frequency (Hz) 3TW27247-2 NOTES 1 2 3 NOTES dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6μW/m_ Measured according to ISO 3744 1 2 3 dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6μW/m_ Measured according to ISO 3744 Sound power level(dB) ERQ250AW1 3TW27257-2 Octave band center frequency (Hz) NOTES 1 2 3 32 Octave band center frequency (Hz) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6μW/m_ Measured according to ISO 3744 • Air Handling Unit Connection • Heat pump • Air handling unit connection • ERQ-AW1 10 Installation 10 - 1 Installation method ERQ-AW1 For single unit installation For installation in rows For centralized group layout <Pattern 1> <Pattern 1> <Pattern 1> 300 or more 10 or more 300 or more <Front> <Front> 20 or more 10 or more 10 or more 300 or more 500 or more 20 or more <Front> 10 or more 10 or more 500 or more <Pattern 2> <Pattern 2> 300 or more 10 or more 20 or more 10 or more 600 or more <Front> 20 or more 10 or more <Front> 500 or more 100 or more 100 or more <Front> 10 or more 20 or more 300 or more 10 or more 500 or more 10 or more <Front> 50 or more <Front> 100 or more 50 or more 100 or more 10 or more 500 or more 500 or more <Pattern 3> Wall height unrestricted <Pattern 3> <Pattern 2> 100 or more 300 or more 20 or more 50 or more 100 or more 300 or more Wall height unrestricted <Front> 400 or more <Front> 50 or more 400 or more <Front> 100 or more 50 or more 50 or more 500 or more 200 or more <Front> 100 or more 50 or more <Front> 500 or more 200 or more 50 or more <Front> 100 or more 50 or more 500 or more 50 or more 100 or more 100 or more 50 or more <Unit: mm> <Front> Notes: 1 Heights of walls in case of Patterns 1 and 2: Front: 1500 mm suction side: 500 mm Side: Height unrestricted. Installation space to be shown in this drawing is based on the cooling operation at 35 degrees outdoor air temperature. When the design outdoor air temperature exceeds 35 degrees or the load exceeds maximum ability because of much generation load of heat in all outdoor unit, take the suction side space more broadly than the space to be shown in this drawing. 2 If the above wall heights are exceeded then h1/2 and h2/2 should be added to the front and suction side service spaces respectively as shown in the figure on the right. 3 When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available always bearing in mind the need to leave enough space for a person to pass between units and wall and for (If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits.) 4 The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably. <suction side> 50 or more 3D051451N 10 - 2 Fixation and foundation of units ERQ-AW1 Foundation bolt Type: JA Size: M12 Nut Spring washer Four bolts are required Frame 3 thread ridges or more Foundation bolt executing method Drain ditch (Smooth down grade of about 1/50) Y ditch Except: 125 models Drain ditch When building a foundation on the ground When building a foundation on the concrete floor When installing multiple units in connection Model ERQ125A7W1B ERQ200A7W1B ERQ250A7W1B A 497 792 792 B 697 992 992 X - XCross section NOTES 1 2 3 4 5 6 The proportions of cement: sand: gravel for the concrete shall be 1:2:4, and the reinforcement bars that their diameter are 10mm, (approx. 300mm intervals) shall be placed. The surface shall be finished with mortar. The corner edges shall be chamfered. When the foundation is built on a concrete floor, rubble is not necessary. However, the surface of the section on which the foundation is built shall have rough finish. A drain ditch shall be made around the foundation to thoroughly drain water from the equipment installation area. When installing the equipment on a roof, the floor strength shall be checked, and water-proofing measures shall be taken. Y Ditch is not necessary for 125 models. 3TW32039-6 • Air Handling Unit Connection • Heat pump 33 • Air handling unit connection • ERQ-AW1 11 Operation range ERQ-AW1 Cooling Indoor temp. (°CWB) Range for operation Range for warming up operation Outdoor temperature (°CWB) Range for pull down operation Range for operation Outdoor temperature (°CDB) Heating Indoor temp. (°CDB) NOTES 1 These figures assume the following operating conditions. 2 3 Indoor and outdoor units: • Equivalent piping length 7.5m • Level difference 0m Depending on operation and installation conditions, the indoor unit can change over to freeze-up operation (indoor de-icing). To reduce the freeze-up operation (indoor de-icing) frequency it is recommended to install the outdoor unit in a location not exposed to wind. 4TW25797-3C 34 • Air Handling Unit Connection • Heat pump Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product. ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment. Daikin units comply with the European regulations that guarantee the safety of the product. Naamloze Vennootschap Zandvoordestraat 300 B-8400 Oostende, Belgium www.daikin.eu BE 0412 120 336 RPR Oostende VRV® products are not within the scope of the Eurovent certification programme. The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V.. Copyright Daikin Prepared in Belgium by Lannoo (www.lannooprint.be), a company whose concern for the environmont is set in the EMAS and ISO 14001 systems. Responsible Editor: Daikin Europe N.V., Zandvoordestraat 300, B- 8400 Oostende Daikin’s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental issues. For several years Daikin has had the intension to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste.