LP500 Installation Instructions EMERGENCY LIGHTING EQUIPMENT ! IMPORTANT SAFEGUARDS ! WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED, INCLUDING THE FOLLOWING: READ AND FOLLOW ALL SAFETY INSTRUCTIONS 1. To prevent high voltage from being present on red & yellow output leads prior to installation, inverter connector must be open. Do not join inverter connector until installation is complete and AC power is supplied to the emergency ballast. 2. This product is for use with 21 through 54 W (2'- 4') T5 or 32 W (4') T8 fluorescent lamps. 3. Make sure all connections are in accordance with the National Electrical Code and any local regulations. 4. To reduce the risk of electric shock, disconnect both normal and emergency power supplies and inverter connector of the emergency ballast before servicing. 5. This emergency ballast is for factory or field installation in the ballast channel or on top of fixture. 6. This product is suitable for use in damp locations where the ambient temperature is 0ºC minimum, +50ºC maximum. Product is also suitable for installation in sealed and gasketed fixtures. Product is not suitable for heated air outlets and wet or hazardous locations. 7. An unswitched AC power source is required (120 or 277 VAC, 60 Hz). 8. Do not install near gas or electric heaters. 9. Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field replaceable. Contact the manufacturer for information on service. 10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. 11. Do not use this product for other than intended use. 12. Servicing should be performed by qualified service personnel. CAUTION: Verify that all replacement lamp types marked on the installed luminaire are also identified as suitable for use with this inverter/charger pack. SAVE THESE INSTRUCTIONS THIS PRODUCT CONTAINS A RECHARGEABLE NICKEL-CADMIUM BATTERY. THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY. 10/30/13 © Philips Emergency Lighting 236 Mt. Pleasant Rd. • Collierville, TN USA 38017-2752 • Tech Support 888-263-4638 • Fax 901-854-1630 • www.philips.com/bodine 70100501 INSTALLATION WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON RED & YELLOW OUTPUT LEADS PRIOR TO INSTALLATION, inverter CONNECTOR MUST BE OPEN. DO NOT JOIN inverter CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED TO THE EMERGENCY BALLAST. NOTE: Make sure that the necessary branch circuit wiring is available. An unswitched source of power is required. The emergency ballast must be fed from the same branch circuit as the AC ballast. STEP #1 INSTALLING THE EMERGENCY BALLAST ILLUSTRATION 1 >Disconnect AC power from the fixture. Remove the ballast channel cover and install the emergency ballast in the ballast channel (see Illustration 1). >Remote mounting distance must be less than half the maximum remote mounting distance for the AC ballast. Consult AC ballast manufacturer before remote installation. STEP #2 INSTALLING THE TEST SWITCH >Refer to Illustration 2 and install the test switch through the ballast channel cover of a troffer or through the side of a strip fixture. ILLUSTRATION 2 Fixture >Drill a 1/2" hole and install the switch as shown. >Refer to the wiring diagrams on the following pages and wire the test switch so that it removes AC power from both the emergency ballast and the AC ballast at the same time. STEP #3 Hex Nut Test Button Push to Test Test Switch Leads Hex Nut INSTALLING THE CHARGING INDICATOR LIGHT >Refer to Illustration 3A or 3B and install the charging indicator light so that it will be visible after the fixture is installed. ILLUSTRATION 3A ILLUSTRATION 3B Fixture Fixture Charging Indicator Light Charging Indicator Light Violet (+) Violet (+) Brown (–) Brown (–) 5/8" Black Bushing 1/2" White Bushing 1/2" White Bushing 5/8" Black Bushing 1/2" Punch STEP 1 STEP 2 NOTE: After installing the charging indicator light and test switch, mark each with the appropriate label. If a detached charging indicator light is used, connect by matching wire colors and install as shown above. 2 INSTALLATION STEP #4 WIRING THE EMERGENCY BALLAST >Select the appropriate wiring diagram and connect the emergency ballast to the AC ballast and lamp(s). Make sure all connections are in accordance with the National Electrical Code and any local regulations. >After installation is complete, supply AC power to the emergency ballast and join the inverter connector. >At this point, power should be connected to both the AC ballast and the emergency ballast, and the Charging Indicator Light should illuminate indicating the battery is charging. >A short-term discharge test may be conducted after the emergency ballast has been charging for one hour. Charge for 24 hours before conducting a long-term discharge test. Refer to OPERATION. > In a readily visible location, attach the label "CAUTION - This Unit Has More Than One Power Connection Point. To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses And Emergency Power Supplies Before Servicing." OPERATION When AC power is applied, the charging indicator light is illuminated, indicating that the battery is being charged. When power fails, the emergency ballast automatically switches to emergency power (internal battery), operating one lamp at reduced illumination. When AC power is restored, the emergency ballast returns to the charging mode and delays AC ballast operation for approximately three seconds to prevent false-tripping of AC ballast (end-of-lamp-life) shutdown circuits. This emergency ballast will operate one 21 through 54 W (2'- 4') T5 or 32 W (4') T8 lamps for a minimum of 90 minutes. MAINTENANCE Although no routine maintenance is required to keep the emergency ballast functional, it should be checked periodically to ensure that it is working. The following schedule is recommended: 1. 2. 3. Visually inspect the charging indicator light monthly. It should be illuminated. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds. One lamp should operate at reduced illumination. Conduct a 90-minute discharge test once a year. One lamp should operate at reduced illumination for at least 90 minutes. ! REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL ! EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS. WIRING DIAGRAMS for 1-LAMP emergency operation FIG A ONE (1) LAMP RAPID START BALLAST FIG B ONE (1) LAMP INSTANT START BALLAST WALL SWITCH HOT WALL SWITCH WHT/RED B L K TEST SWITCH B L K INVERTER CONNECTOR CHARGING INDICATOR LIGHT (CAP UNUSED LEAD) RED WHITE VIOLET BROWN BLACK 120V OR ORANGE 277V WHITE COMMON HOT RED E MB EA RL GL EA NS CT Y YELLOW TEST SWITCH B L K BLU/WHT BLUE RED BLUE BLUE RED TEST SWITCH B L K CHARGING INDICATOR LIGHT (CAP UNUSED LEAD) COMMON WHITE VIOLET BROWN BLACK 120V OR ORANGE 277V WHITE RED E MB EA RL GL EA NS CT Y YELLOW LAMP YEL/BLK BLU/WHT BLUE BLUE WHT/BLK BLK WHT WHT FIG D RED 1 LAMP INSTANT START BALLAST TWO (2) LAMP INSTANT START BALLAST WALL SWITCH WHT/RED INVERTER CONNECTOR RED BLK TWO (2) LAMP RAPID START BALLAST B L K CHARGING INDICATOR LIGHT COMMON WALL SWITCH HOT INVERTER CONNECTOR (CAP UNUSED LEAD) 1 LAMP RAPID START BALLAST WHT/BLK FIG C WHT/RED B L K LAMP YEL/BLK RED WHITE VIOLET BROWN BLACK 120V OR ORANGE 277V WHITE HOT RED E MB EA RL GL EA NS CT Y YELLOW YEL/BLK WHT/RED B L K LAMP 1 (EMERGENCY) TEST SWITCH B L K BLU/WHT BLUE BLUE BLUE RED RED 2 LAMP RAPID START BALLAST WHT/BLK INVERTER CONNECTOR CHARGING INDICATOR LIGHT (CAP UNUSED LEAD) LAMP 2 COMMON YELLOW RED WHITE VIOLET BROWN BLACK 120V OR ORANGE 277V WHITE RED E MB EA RL GL EA NS CT Y YELLOW LAMP 1 (EMERGENCY) YEL/BLK BLU/WHT BLUE BLUE WHT/BLK YELLOW BLK BLK WHT WHT 3 BLUE 2 LAMP INSTART START BALLAST RED LAMP 2 EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS. WIRING DIAGRAMS for 1-LAMP emergency operation FIG F THREE (3) LAMP INSTANT START BALLAST FIG E THREE (3) LAMP RAPID START BALLAST WALL SWITCH WALL SWITCH HOT WHT/RED B L K INVERTER CONNECTOR TEST SWITCH WHITE VIOLET CHARGING INDICATOR LIGHT B L K BROWN (CAP UNUSED LEAD) BLACK 120V OR ORANGE 277V WHITE COMMON HOT RED RED E MB EA RL GL EA NS CT Y YELLOW LAMP 1 (EMERGENCY) YEL/BLK TEST SWITCH BLU/WHT BLU/WHT BLU/WHT BLUE YELLOW BLUE BLUE YELLOW 3 LAMP RAPID START BALLAST WHT/BLK WHT/RED B L K B L K LAMP 2 WHT/RED WHITE VIOLET CHARGING INDICATOR LIGHT BROWN (CAP UNUSED LEAD) BLACK 120V OR ORANGE 277V WHITE COMMON LAMP 3 BLUE BLUE BLUE 3 LAMP INSTANT START BALLAST WHT/BLK BLK WHT RED WHT BLUE LAMP 2 LAMP 3 RED FIG H FOUR (4) LAMP INSTANT START BALLAST E MB EA RL GL EA NS CT Y HOT YELLOW LAMP 1 (EMERGENCY) YEL/BLK TEST SWITCH YELLOW YELLOW BLU/WHT RED BLUE RED BLU/WHT 4 LAMP RAPID START BALLAST BLU/WHT WHT/RED B L K B L K LAMP 2 LAMP 3 RED INVERTER CONNECTOR WHITE VIOLET CHARGING INDICATOR LIGHT (CAP UNUSED LEAD) BROWN BLACK 120V OR ORANGE 277V WHITE COMMON BROWN RED E MB EA RL GL EA NS CT Y LAMP 1 (EMERGENCY) YELLOW YEL/BLK BLU/WHT BLUE YELLOW BLUE BLUE WHT BLUE BLUE 4 LAMP INSTANT START BALLAST WHT/BLK BROWN BLK RED LAMP 4 WHT LAMP 2 LAMP 3 YELLOW BLK FIG I TWO (2) LAMP RAPID START BALLAST - SERIES YELLOW RED LAMP 4 FIG J TWO (2) LAMP PROGRAM RAPID START OSRAM BALLAST WALL SWITCH WALL SWITCH HOT WHT/RED WHITE VIOLET CHARGING INDICATOR LIGHT BROWN (CAP UNUSED LEAD) BLACK 120V OR ORANGE 277V WHITE COMMON HOT RED RED INVERTER CONNECTOR B L K WHITE LAMP 1 (EMERGENCY) YEL/BLK BLU/WHT RED WHT/BLK TEST SWITCH OR YELLOW BLK RED RED INVERTER CONNECTOR B L K BROWN BLACK 120V ORANGE 277V RED E MB EA RL GL EA NS CT Y WALL SWITCH HOT B L K VIOLET COMMON WALL SWITCH TEST SWITCH WHITE CHARGING INDICATOR LIGHT (CAP UNUSED LEAD) FIG G FOUR (4) LAMP RAPID START BALLAST B L K RED INVERTER CONNECTOR E MB EA RL GL EA NS CT Y YELLOW WHT/RED B L K LAMP 1 (EMERGENCY) YEL/BLK TEST SWITCH B L K BLU/WHT BLUE BLUE BLUE RED RED 2 LAMP RAPID START BALLAST WHT/BLK LAMP 2 RED INVERTER CONNECTOR WHITE VIOLET CHARGING INDICATOR LIGHT (CAP UNUSED LEAD) BROWN BLACK 120V YELLOW OR ORANGE 277V WHITE COMMON YELLOW RED E MB EA RL GL EA NS CT Y YELLOW LAMP 1 (EMERGENCY) YEL/BLK BLU/WHT RED BLUE RED WHT/BLK BLK BLK WHT WHT FIG K FOUR (4) LAMP RAPID START BALLAST - SERIES BLUE BLUE 2 LAMP RAPID START BALLAST LAMP 2 YELLOW YELLOW FIG L TWO (2) LAMP RAPID START STEP DIMMING BALLAST WALL SWITCH HOT WHT/RED B L K TEST SWITCH B L K RED RED INVERTER CONNECTOR WHITE VIOLET CHARGING INDICATOR LIGHT BROWN (CAP UNUSED LEAD) BLACK 120V OR ORANGE 277V WHITE COMMON E MB EA RL GL EA NS CT Y COMMON YELLOW WHT/RED LAMP 1 (EMERGENCY) YEL/BLK INVERTER CONNECTOR ORANGE CHARGING INDICATOR LIGHT ORANGE BLU/WHT RED BLUE RED BLUE BLUE 4 LAMP RAPID START BALLAST WHT/BLK BROWN BROWN LAMP 2 TEST SWITCH LAMP 3 HOT BLK (CAP UNUSED LEAD) YELLOW YELLOW BROWN BLACK 120V OR ORANGE 277V RED E MB EA RL GL EA NS CT Y YELLOW LAMP 1 (EMERGENCY) YEL/BLK BLU/WHT BLUE BLUE BLUE WHT/BLK BLU/WHT BLK WHITE VIOLET WHITE BLK BLU/WHT WHT RED LAMP 4 S1 S1 S2 GRAY WHT RED 2 LAMP RAPID START STEP DIMMING BALLAST RED LAMP 2 YELLOW YELLOW BLK BLK S1 OPEN - 2 LAMP OPERATION S1 CLOSED - 4 LAMP OPERATION The white/black lead must connect to the white lead of the step-dimming ballast associated with the emergency ballast only. Connections to other ballasts or fixtures could result in abnormal operation and cause product damage. WIRING DIAGRAMS for Emergency-Only fixtures FIG M ONE (1) 21 W - 54 W LAMP WITHOUT AC BALLAST CAP HOT B L K TEST SWITCH B L K WHITE VIOLET CHARGING INDICATOR LIGHT BROWN (CAP UNUSED LEAD) BLACK 120V OR ORANGE 277V WHITE COMMON CAP RED WHT/RED RED INVERTER CONNECTOR E MB EA RL GL EA NS CT Y YELLOW LAMP YEL/BLK BLU/WHT CAP BLUE CAP WHT/BLK 4