MS-1233 Series MS-1233 Series Damper, Proportional, Non-Spring Return Actuators These actuators provide electronic proportional control of small dampers not requiring the return to normal position upon power interruption. Typically used with terminal units in VAV systems in conjunction with the PP-8121 controller. Also used with TP-8101 room controller for mixing boxes in constant volume double duct systems. Features: • Variable Vdc or variable mAdc. • Direct coupling to damper shaft. Requires no damper linkage. • Optional two SPDT auxiliary switch models. Model Chart Model No. MS-1233 MS-1233-002 MS-1233-100 MS-1233-102 Control Input 2 to 15 Vdc at 2 mA 4 to 20 mAdc Start Point 6 Vdc (factory set), adjustable 2 to 12 Vdc 4 mAdc (fixed) Span 3 Vdc (fixed) for full actuator stroke 16 mAdc (fixed) for full actuator stroke Power Supply Available SPDT Aux.a Switches (Adj.) +20 Vdc, 50 mA None +20 Vdc, 50 mA None 2 2 a 5 amps @ 24 Vdc (AC 50/60 Hz), Pilot Duty 100 VA. Switches have gold contacts suitable for dry circuit switching. Specifications Control type Reversible proportional shaft rotation can stop at any point in the stroke. Power requirements Volts 24 AC (+10%, -15%). Hz 50/60. Full load amps 0.21. Torque 20 lb-in. (2.3 N-m). The damper must withstand 35 lb-in. (4.0 N-m) of torque if travel is less than the fixed actuator stroke set by the internal torque switches. Nominal Damper Area Actuator sizing should be done in accordance with damper manufacturer’s specifications. Output shaft Rotation Fixed at 90° (+5, -0°). Factory set CCW end as viewed from cover side of actuator. Torque switches limit travel in CW and CCW directions reducing the need for travel adjustment and preventing over-stress on dampers. Construction Hollow. No load timing Three minutes, 45 seconds nominal. Auxiliary switch Adjustable SPDT. Refer to Model Chart. FCC Complies with Class B testing according to the rules and regulations of part 15 radio frequency devices (including television), sub part J, computing devices. 223 MS-1233 Series Specifications (Continued) Environment Ambient temperature limits Shipping and storage: -40 to 140°F (-40 to 60°C). Operating: 40 to 140°F (4 to 60°C). Humidity 5 through 95% RH, non-condensing. Locations NEMA Type 1. Vibration Maximum 1G in any plane. Atmosphere Avoid locations with corrosive fumes, vapors, abrasive dust, explosive conditions, high radio frequency, or electromagnetic generating devices. Connections Coded screw terminals that will accept up to 16 gage wire. Case Galvanized steel. Mounting Any position over a 1/2 in. (12.7 mm) diameter damper shaft [minimum length 1-1/8 in. (29 mm)]. Dimensions 5-1/8 H x 5-1/4 W x 3-1/4 D in. (130 x 133 x 83 mm). Accessories Model No. AM-111 AM-112 AM-113 AM-115 AM-122 AM-125 AM-132 AM-165 Description Crank arm for 5/16 in. diameter damper shaft. Crank arm for 3/8 in. diameter damper shaft. Crank arm for 1/2 in. diameter damper shaft. Crank arm for 7/16 in. diameter damper shaft. Linkage connector, straight type. 5/16 in. x 20 in. damper rod. Linkage connector, ball type. Mounting kit, includes crank arm, 1/2 in. diameter shaft and bearing mounting bracket. Typical Applications 24 Vac Power Blue Control 1 Signal 2-15 Vdc 24H 8 COM 9 MS-1233 1 9 Vdc actuator rotates clockwise. 6 Vdc actuator rotates counterclockwise as viewed from cover side of actuator. 2 10K W Impedance Yellow 2 OP1 12 IV1 Impedance 10K W Red +20 Vdc 10 Figure 1 Actuator Heating/Cooling with 2 to 15 Vdc Input. 224 MS-1233 Series Terminals 24 Vac Power Control Signal 2-15 Vdc H 8 24H Blue (COM) Yellow (OP1) 9 COM 12 IV1 Impedance 10KW Red (+20) 10 +20 Vdc 11 IV2 Override Imp. 2.5KW 1 C1 2 N.C.1 N.O.1 Max. Vac 24 or Vdc Power 3 G H MS-1233-002 †† 4 24 Vac Max 5 N.C.2 C2 N.O.2 6 G † Control Signal 9 Vdc actuator rotates clockwise. * 6 Vdc actuator rotates counterclockwise. * * As viewed from cover side of actuator. † Two-position heating or cooling device. Switch #2 may be readjusted from 10˚ from the CW end to the CW or CCW end or at any point between. †† Indicating device, relay, bell, light or input to a microprocssor-based controoler in any energy management system. For a continuous voltage signal position indication, use terminals 9(-) and 12(+) which typically provide a 6Vdc (CCW end) to 9 Vdc (CW end) sinal. Figure 2 Two Aux. Switches for Actuator Position Indication and Heating/Cooling Schemes with 2 to 15 Vdc Input. 1 250Ω Impedance 2 Signal between terminals 9 and 12: The 20 mA actuator rotates clockwise. The 4 mA actuator rotates counterclockwise as viewed from cover side of actuator. 24 Vac Power 4-20mA Control Signal 2 (–) (+) 1 24H 8 COM 9 2 MS-1233-10X 12 Figure 3 Actuator with 4 to 20 mA Input. 24 Vac Power Two-Position Thermostat TC-1101 Temp. Drop 1 10K W Impedance 24H 8 COM 9 MS-1233 1 IV1 12 +20 Vdc 10 Figure 4 Typical Two-Position Control. 225