Product Description Autotransformer Starting Electric Fire Pump

advertisement
Product Description
Autotransformer Starting Electric
Fire Pump Controllers
• FTA1800
„ Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition
„ Built-in Start and Stop push-buttons to bypass
automatic start circuits
„ Door mounted display/interface panel featuring
a 40 Character Vacuum Fluorescent Display,
Membrane Type User Control Push-buttons and
easy to read LED Indicators
„ Single handle Isolating Disconnect Switch/Circuit
Breaker mechanism
Description—Firetrol® FTA1800 Autotransformer
Starting Fire Pump Controllers use an autotransformer to supply reduced voltage when starting the
motor. The controller is of the closed circuit type
where the motor circuit remains closed during the
transition from start to run resulting in minimum line
disturbance.
The controller monitors, displays and records fire
pump system information.
The autotransformer has three taps for selection of
starting current and torque; 50% tap for 150% current and 25% torque, 65% tap (factory setting) for
250% current and 42% torque and the 80% tap for
384% current and 64% torque.
Approvals—Firetrol fire pump controllers are listed
by Underwriters’ Laboratories, Inc., in accordance
with UL218, Standard for Fire Pump Controllers,
CSA, Standard for Industrial Control Equipment,
and approved by Factory Mutual. They are built to
meet or exceed the requirements of the approving
authorities as well as NEMA and the latest editions
of NFPA 20, Installation of Centrifugal Fire Pumps,
and NFPA 70, National Electrical Code.
Standard Features—The following are included as
standard with each controller:
„ Voltage surge protector
„ Main Disconnect Switch sized for connected motor horsepower and voltage
„ Fire pump Circuit Breaker
„ Suitable for use as Service Equipment
„ Motor contactor
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
Transition Contactor and Autotransformer
POWER ON LED
PUMP RUN LED
PHASE FAILURE LED
PHASE REVERSAL LED
LOW PRESSURE LED
DELUGE OPEN LED
INTERLOCK ON LED
TRANSFER SWITCH NORMAL LED (If unit
ordered with Automatic Power Transfer Switch)
TRANSFER SWITCH EMERGENCY LED (If unit
ordered with Automatic Power Transfer Switch)
EMERGENCY ISOLATING SWITCH OFF LED
(If unit ordered with Automatic Power Transfer
Switch)
Minimum Run Timer / Off Delay Timer
Daylight Savings Time option
Weekly Test Timer
Motor Acceleration Timer
Elapsed Time Meter
Digital Pressure Display
USB Host Controller and Port
Solid State Pressure Transducer
Data Log
Event Log (3000 Events)
True RMS Metering with simultaneous 3 phase
display of amps and volts
Disk Error message
Disk Near Full message
Pressure Error message
Motor Over 320% message
Local Start message
Remote Start message
Emergency Start message
Fail To Start message
Undervoltage message
Overvoltage message
High Speed Open Serial Communications Port
NEMA Type 2 enclosure
Specifications
Electric Fire Pump Controllers
Main Fire Pump Controller
The main fire pump controller shall be a factory
assembled, wired and tested unit and shall conform
to all the requirements of the latest edition of NFPA
20, Standard for the Installation of Stationary Pumps
for Fire Protection and NFPA 70, National Electrical
Code.
The controller shall be listed by Underwriters
Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, and Canadian
Standards Association CSA-C22.2, Standard for
Industrial Control Equipment (cULus), approved by
Factory Mutual and approved by the City of New York
for fire pump service.
Starting Method
The controller shall be of the combined manual
and automatic type designed for:
Full Voltage Starting
Wye (Star)-Delta Open Transition Starting
Wye (Star)-Delta Closed Transition Starting
Part Winding Starting
Primary Resistance Reduced Voltage Starting
Autotransformer Reduced Voltage Starting
of the fire pump motor having the horsepower, voltage, phase and frequency rating shown on the plans
and drawings. The controller components shall be
housed in a NEMA Type 2 (IEC IP11) drip-proof, wall
mounted enclosure.
Withstand Ratings (Short Circuit Current Ratings)
All controller components shall be front mounted,
wired and front accessible for maintenance. The minimum withstand rating of the controllers shall not be
less than 100,000 Amps RMS Symmetrical at 200-600
Volts*. If the available system fault current exceeds
these ratings, the controllers shall be supplied with a
withstand rating of 150,000 or 200,000 Amps RMS
Symmetrical, as required.
*Note: 100,000 Amp withstand rating not available in
some larger horsepowers. Consult factory for
details.
Isolation Switch and Circuit Breaker
The controller shall include a motor rated combination isolating disconnect switch/circuit breaker,
mechanically interlocked and operated with a single,
externally mounted handle. When moving the handle
from OFF to ON, the interlocking mechanism shall
sequence the isolating disconnect switch ON first, and
then the circuit breaker. When the handle is moved
from ON to OFF, the interlocking mechanism shall
sequence the circuit breaker OFF first, and then the
isolating disconnect switch.
The isolating disconnect switch/circuit breaker
shall be mechanically interlocked so that the enclosure door cannot be opened with the handle in the
ON position except by a hidden tool operated defeater
mechanism. The isolating disconnect switch/circuit
breaker shall be capable of being padlocked in the
OFF position for installation and maintenance safety,
and shall also be capable of being locked in the ON
•
FTA1000
-1800
position without affecting the tripping characteristics
of the circuit breaker. The controller door shall have
a locking type handle and three point cam and roller
vault type hardware. The circuit breaker trip curve
adjustment shall be factory set, tested and sealed
for the full load amps of the connected motor. The
circuit breaker shall be capable of being field tested to
verify actual pick up, locked rotor, and instantaneous
trip points after field installation without disturbing
incoming line and load conductors.
Operator Interface
The fire pump controller shall feature an operator
interface with user keypad. The interface shall monitor
and display motor operating conditions, including all
alarms, events, and pressure conditions. All alarms,
events, and pressure conditions shall be displayed
with a time and date stamp. The display shall be a
2-line, 20-character, vacuum fluorescent, dot matrix
type designed to allow easy viewing from all angles
and in all light conditions. The display and interface
shall be NEMA rated for Type 2, 3R, 4, 4X, and 12
protection and shall be fully accessible without opening the controller door. The display and user interface
shall utilize multiple levels of password protection for
system security. A minimum of 3 password levels
shall be provided. The display shall be capable of
being programmed for any language.
Ammeter/Voltmeter
The fire pump controller operator interface shall
be capable of displaying true RMS digital motor
voltage and current measurements for all three
phases simultaneously. Displays requiring pushbutton and selector switches to toggle between
phases or current and voltage shall not be accepted.
Voltage and current shall be measured by
True RMS technology to provide the most accurate
measurement for all sine waves, including nonsinusoidal waveforms. Average responding meters
will not be accepted.
Digital Status/Alarm Messages
The digital display shall indicate text messages
for the status and alarm conditions of:
• Motor On
• Sequential Start Time
• Minimum Run Time
• Local Start
/ Off Delay Time
• Remote Start
• Fail to Start
• System Battery Low
• Under Voltage
• Over Voltage
• Locked Rotor Trip
• Over Frequency
• Emergency Start
• Motor Over 320%
• Drive Not Installed
• Motor Overload
• Disk Error
• Printer Error
• Disk Near Full
• Pressure Error
The Sequential Start Timer and Minimum Run Timer/
Off Delay Timer shall be displayed as numeric values
reflecting the value of the remaining time.
LED Visual Indicators
LED indicators, visible with the door closed, shall
indicate:
• Power On
• Emerg. Isolating Switch Open
• Pump Running • Low System Pressure
• Alarm
• Transfer Switch Normal
• Deluge Open • Transfer Switch Emergency
• Phase Failure • Phase Reversal
• Interlock On
Data Logging
The digital display shall monitor the system and
log the following data:
• Motor Calls/Starts
• Elapsed Motor Run Time
• Last Trip Currents
• Elapsed Power On Time
• Last Breaker Trip
• Maximum Run Currents
• Minimum Voltages • Minimum Run Currents
• Maximum Voltages • Last Motor Run Time
• Last Phase Failure • Last Start Currents
• Last Phase Reversal • Min/Max Frequency
• Min/Max Pressure
Event Recording
Memory - The controller shall record all operational and alarm events to system memory. All events
shall be time and date stamped and include an index
number. The system memory shall have the capability
of storing 3000 events and allow the user access to
the event log via the user interface. The user shall
have the ability to scroll through the stored messages
in groups of 1, 10, or 100.
USB Host Controller - The controller shall have a
built-in USB Host Controller. A USB port capable of
accepting a USB Flash Memory Disk (aka: flash drive,
thumb drive, memory stick, etc..) shall be provided.
The controller shall save all operational and alarm
events to the flash memory on a daily basis. Each
saved event shall be time and date stamped. The total
amount of historical data saved shall solely depend
on the size of the flash disk utilized. The controller
shall have the capability to save settings and values
to the flash disk via the user interface.
Serial Communications - The controller shall
feature a RS485 serial communications port for use
with 2 or 4 wire Modbus RTU communications.
Solid State Pressure Transducer
The controller shall be supplied with a solid state
pressure transducer with a range of 0-300 psi (0-20.7
bar) ±1 psi. The solid state pressure switch shall be
used for both display of the system pressure and control of the fire pump controller. Systems using analog
pressure devices or mercury switches for operational
control will not be accepted.
The START, STOP and SYSTEM PRESSURE
shall be digitally displayed and adjustable through
the user interface. The pressure transducer shall be
mounted inside the controller to prevent accidental
damage. The pressure transducer shall be directly
pipe mounted to a bulkhead pipe coupling without
any other supporting members. Field connections
shall be made externally at the controller coupling to
prevent distortion of the pressure switch element and
mechanism.
Operation
A digitally set On Delay (Sequential Start) timer
shall be provided as standard. Upon a call to start,
the user interface shall display a message indicating
the remaining time value of the On Delay timer.
The controller shall be field programmable for
manual stop automatic stop. If set for automatic
stopping, the controller shall allow the user to select
either a Minimum Run Timer or an Off Delay Timer.
Both timers shall be programmable through the user
interface.
A nonadjustable restart delay timer shall be
provided to allow the residual voltage of the motor to
decay prior to restarting the motor. At least 2 seconds,
but no more than 3 seconds, shall elapse between
stopping and restarting the pump motor.
A weekly test timer shall be provided as standard.
The controller shall have the ability to program the
time, date, and frequency of the weekly test. In addition, the controller shall have the capability to display
a preventative maintenance message for a service
inspection. The message text and frequency of occurrence shall be programmable through the user
interface.
A Lamp Test feature shall be included. The user
interface shall also have the ability to display the
status of the system inputs and outputs.
The controller shall not start the fire pump motor
under a single-phase condition. If the motor is already
running when a phase loss occurs, the controller shall
continue to run the motor, but still display a Phase
Failure alarm.
The fire pump controller software shall be automatically upgradable through the USB port by simply
inserting a flash disk with the new software. Fire pump
controllers that require laptop computers, handheld
equipment or specialized devices for software upgrades shall be prohibited.
The controller shall be a Firetrol brand.
(919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27518 USA
SP1000-20 (03-10-09)
©ASCO 2006
Sequence of Operation
Autotransformer Fire Pump Controllers
Introduction
Reference to Wiring Schematic, Publication
WS1800-50.
Note: Firetrol schematics are drawn showing the
equipment in a de-energized state.
Energizing The Controller
1. Close the Isolating switch/Circuit breaker by moving
the handle to the “ON” position.
Note: The unmarked, red, “Interlock” jumper wire, located
between terminals #1 & #10 on the Relay PC board,
(TB1), will prevent the MarkII unit from starting the electric
motor automatically. This jumper wire should only be
removed after the pressure settings have been input,
and the system pressurized at, or above the Stop set
point.
2. The factory programmed MarkII unit will begin
initialization. Upon completion, the display will confirm
the system pressure, the time, date, and “Interlock ON”,
which is an alarm condition and will cause the yellow
alarm LED to flash. Any other existing alarm conditions
(low system pressure, phase reversal, phase failure,
deluge open), will also be sequentially and continuously
displayed at this time, until each is rectified.
3. With the “interlock” jumper still in place, the electric
motor can only be started by depressing the START
push-button, located on the flange of the controller
enclosure, or by engaging the Emergency Run
Mechanism. After all alarm conditions have been
rectified, and the system pressurized at or above the
Stop pressure setting, then the “interlock” jumper may
be removed for the controller’s automatic operation
(“standby”). With the “interlock” jumper removed, a drop
in system pressure to the MarkII’s set start point, will
start the electric motor.
4. The deluge valve contacts are only operational if the
factory jumper has been removed and a normally closed
deluge valve contact has been placed between terminals
1 and 8 of the Relay PC board, (TB1). The Remote Start
is only operational if a normally open, momentarily closed
contact is wired to terminals 6 and 7 of the Relay PC
board, (TB1). If engaged, the Emergency Run Mechanism
will cause the pump motor to run as described in the
Emergency Starting and Stopping section.
Automatic Start and Stop
1). The controller pressure transducer initiates the
automatic start circuits for the pump motor. When
pressure falls at or below the MarkII Start setting, relay
1CR is energized. 1CR normally open contact, closes
•
FTA1800
to the coils of 1S & 2S starters, allowing voltage to the
motor windings. (see section Pump Motor Starting
Sequence for more information). An autotransformer is
connected to minimizing line disturbances during starting.
At the same time the MarkII initiates the internal
transition time, factory set for 2 seconds. Once this
expires, 6CR is energized. 6CR normally open contact
closes to the coil of 1M starter, 1S coil is de-energized
and mechanically locked out (motor circuit remains
closed during transition), allowing the motor to be directly
connected to the power source.
Note: Allow the motor to either run for 5 minutes, or
allow 5 minutes between starts, for initial start component
cool down period.
The minimum run time is a part of the MarkII Menu,
“Timer Settings”. The minimum run time factory setting
is 10 minutes. In this mode, minimum run time begins
when the pressure falls at or below the “Start” set point,
calling for the pump motor to run. When pressure drops,
this signals the MarkII to output via the Relay PC board,
directly to the 1CR relay coil. The relays normally open
contact closes, allowing line voltage to the coils of 1S &
2S contactors. The contactors’s 3 normally open
contacts close, allowing voltage through the
autotransformer, to the motor. After a 2 second delay,
6CR relay coil is energized. 6CR normally open contact
closes, allowing line voltage to the coil of 1M contactor,
and de-energizing 1S contactor (motor circuit remains
closed during transition). The 1M’s 3 normally open
contacts close, allowing direct line voltage to the motor,
and the motor now runs at full speed. Simultaneously,
the minimum run function of the MarkII is activated,
maintaining voltage on the 1CR relay, keeping the motor
running until the 10 minutes expire. At this time, with
pressure restored at or above the Stop set point, 1CR
and 6CR coils will de-energize, re-opening the normally
open contacts, de-energizing the 1M and 2S coils,
causing the motor to stop.
If pressure is restored at or above the Stop set point
of the MarkII, and even if the minimum run time has not
yet expired, the manual STOP push button, located on
the flange of the controller can be depressed to manually
stop the engine. This also resets the minimum run time
function of the MarkII.
Manual Start and Stop
The pump motor may be manually started by using
either the START push-button mounted on the flange of
the enclosure or by using a normally open, momentarily
closed, remote start push-button connected to terminals
6 and 7.
When the START push-button is depressed, or a
remote start signal is seen through terminals 6 & 7, the
MarkII will output through the relay pc board to 1CR relay
coil and the sequence of events described in section
“Automatic Start & Stop” will begin. The MarkII minimum
run time feature will not be activated.
The pump motor will continue to run until the STOP
push-button is depressed. When the STOP push-button
is depressed, 1CR relay coil is de-energized, interrupting
the voltage to 1M & 2S coils, which causes the motor to
stop.
Deluge Valve Operation
To operate the controller utilizing a deluge valve, the
wire jumper between terminals 1 and 8 must be removed
and a normally closed, open to run deluge valve contact
wired in its place.
When the deluge valve contact opens, relay 1CR
coil is energized, and the sequence of events described
in section “Automatic Start & Stop” will begin. The MarkII
minimum run time feature is also activated.
When the deluge valve contact closes, and minimum
run time expires, relays 1CR & 6CR are de-energized,
interrupting the voltage to 1M & 2S coils, which causes
the motor to stop.
Shutdown Interlock Operation
The shutdown interlock, if used, is a normally open,
closed to interlock contact wired to terminals 1 and 10.
When the interlock contact is closed, relay 1CR
cannot be energized by inputs to the MarkII from the
pressure transducer, or the deluge valve. The controller
may be started manually by depressing the START push
button. See the specific starting operation for more
details.
out 1S (motor circuits remain closed during transition).
The motor is automatically connected directly to the
power source, applying full voltage to the motor.
Emergency Starting and Stopping
The controller is equipped with an emergency run
mechanism for use in the event of a coil burnout or other
electrical problem which would prevent normal starting
of the pump motor. The mechanism attempts to both
electrically and mechanically start the pump motor.
When the emergency run mechanism is utilized,
the 1M coil is energized, closing the contacts leading to
the motor windings. This, in effect, attempts to
electrically start the pump motor.
The emergency run mechanism also manually
closes the 1M contactor, starting the motor at full voltage.
This will run the motor as long as the main three phase
power is available.
If the pump motor is running via the emergency run
mechanism, DO NOT release the mechanism to stop
the motor. Place the isolating switch/circuit breaker
handle in the off position, then release the emergency
run mechanism. Releasing the mechanism while the
motor is running could result in damage to the motor or
the motor contactors.
Note: The emergency run mechanism is not intended
for, nor should it be used as a testing device. Its sole
purpose is to attempt to start the pump motor in the
event of a failure.
Pump Motor Starting Sequence
Whenever relay 1CR, and sequentially, after transition
time expires, 6CR coils are energized, line voltage is
allowed to the coils of the motor starting contactors.
During Autotransformer starting, the following sequence
occurs.
1). 1CR contact closes, energizing contactors 1S & 2S.
1S & 2S connect the motor to the power source, through
the autotransformer. The autotransformer is used to
supply reduced voltage when starting the motor. The
autotransformer has three taps for selection of starting
current and torque: 50% tap for 150% current and 25%
torque, 65% tap for 250% current and 42% torque and
the 80% tap for 384% current and 64% torque.
2). When the MarkII transition time expires (factory set
at 2 seconds), 6CR relay is energized, allowing contactor
1M to energize, de-energizing and mechanically locking
…XXXGJSFUSPMDPN…4BMFT0GGJDF$BSZ/$64"
SQ1800-20 (04-17-07)
‹$6&2
FIELD CONNECTIONS
FTA1800
AUTOTRANSFORMER FIRE PUMP CONTROLLERS - LINE AND MOTOR
FIELD WIRE TERMINAL CAPACITY
TEF
05-06-02
FC1800-51
TEF
05-06-02
1
1
Download