Emergency lighting discharge test kits

advertisement
AU
User Instructions
EMERG1W
EMERG2W
PFGEMERG1
PFGEMERG2
EMERG.a1
Emergency Lighting Discharge Test solutions
have been developed to meet the needs of
the electrical industry. In accordance to
AS2293.1-2005 and AS/NZS2293.2 1995
‘Emergency Evacuation Lighting for Buildings’, a
discharge test circuit MUST be installed in both
existing and new installations.
Emergency lighting discharge test kits
Operation
The timer, to be set at 2 hours (2hrs for initial
commissioning, 90mins thereafter, completes its
operation, de-energising the contactor coil returning
the contacts to the normally closed position.
Upon engaging the Green push button for 1 second,
the timer starts its operation and energizes the
contactor coil. The four normally closed contacts
open, initiating operation of the emergency lights.
In accordance with AS2293.1-2005 4.3.1(b) the test
facility is capable of being manually reset. If the red
push button is pressed the timer resets & is ready for
the green push button to start the timing cycle again.
These breakers are not supplied as
part of the standard test package.
GENERAL LIGHTING
FROM 6A MCB
CONTROL
N
CIRCUIT 1
1
EM1-1
2
EMERGENCY LIGHTING
PUSH BUTTON
SVN391M
Red
1
2
GENERAL LIGHTING
CIRCUIT 2
3
4
EMERGENCY LIGHTING
A1
Green
4
3
EM1-2
B1 EET A2
GENERAL LIGHTING
EZN004
TIMER
CIRCUIT 3
5
EET
15
18
A1
EM1
EM1-3
6
EMERGENCY LIGHTING
A2
ESC226 / ESC441
CONTACTOR
GENERAL LIGHTING
CIRCUIT 4
7
EM1-4
8
EMERGENCY LIGHTING
Kit contents in relation to product purchased
1 - Standalone solutions prewired in plastic enclosures
EMERG1W - Suitable for up to 4 separate test circuits
QTY Cat.Ref
Description
1
ESC441
Contactor - 4NC contacts, 40A
1
SVN391M Push button - 1NO (green) + 1NO (red)
1
EZN004
Delay timer - 0.1sec to 10hrs
1
GD106T
Enclosure - Plastic, 6 module
1
GP106T
Door - suits GD106T, transparent
1
VZ313
Lock - suits GD106T
EMERG2W - Suitable for up to 2 separate test circuits
QTY Cat.Ref
Description
1
ESC226
Contactor - 2NC contacts, 25A
1
SVN391M Push button - 1NO (green) + 1NO (red)
1
EZN004
Delay timer - 0.1sec to 10hrs
1
GD104T
Enclosure - Plastic, 4 module
1
GP104T
Door - suits GD104T, transparent
1
VZ313
Lock - suits GD104T
Module width
1
1
1
4
-
2 - Add On accessory for PERFORMA panelboards (Classic, Apex, Apex PLUS, Elite) - Note: loose components, wiring required.
PFGEMERG1 - Suitable for up to 4 separate test circuits
PFGEMERG2 - Suitable for up to 2 separate test circuits
QTY Cat.Ref
Description
Module width
QTY Cat.Ref
Description
1
ESC441
Contactor - 4NC contacts, 40A
3
1
ESC226
Contactor - 2NC contacts, 25A
1
SVN391M Push button - 1NO (green) + 1NO (red) 1
1
SVN391M Push button - 1NO (green) + 1NO (red)
1
EZN004
Delay timer - 0.1sec to 10hrs
1
1
EZN004
Delay timer - 0.1sec to 10hrs
Module width
1
1
1
1
Module width
3
1
1
6
-
EMERG.a1
2
Hager Electro Pty. Ltd. - Unit 1/170 Power St. Glendenning NSW 2761 - Tel. 1300 850 253 - www.hagerelectro.com.au
EMERG.a1
Double with electronic ballast
Single with electronic ballast
Electro
nic
nic
Electro
(Low Power Factor >0.9)
Double - with starter
(High Power Factor <0.9)
Double - with starter
(Low Power Factor >0.9)
Single - with starter
(High Power Factor <0.9)
Single - with starter
Fluorescent tubes (T5)
with electronic transformer
Halogen ELV (12 or 24V)
Tungsten Halogen Lamps 230V
Incandescent lamps
CFL with integrated electronic ballast
CFL with external electronic ballast
15 - 18
20
36
40
42
58
65
80
115
140
15 - 20
36
40 - 42
58 - 80
115
2 x 18
2 x 20
2 x 36
2 x 40
2 x 42
2 x 58
2 x 65
2 x 80
2 x 115
2 x 18
2 x 20
2 x 36
2 x 40
2 x 42
2 x 58
2 x 65
2 x 80
2 x 115
15 - 20
36
40 - 42
58 - 80
115
2 x 18
2 x 20
2 x 36
2 x 40
2 x 42
2 x 58
2 x 65
2 x 80
2 x 115
40
60
75
100
150
200
300
500
1000
20
35
50
75
100
150
5-7
9 - 11
15 - 26
5 - 15
18 - 26
Lamp wattage
(W)
20
19
15
13
12
9
8
7
5
5
11
11
11
10
10
20
19
15
13
12
9
8
7
5
11
11
10
10
10
10
7
7
5
11
11
11
10
10
11
11
10
10
10
10
7
7
5
50
33
27
20
13
10
7
4
2
40
33
24
20
11
6
15
13
11
27
20
Rated output (per pole)
25A
40A
70
70
60
60
55
35
35
30
20
16
36
34
29
27
25
50
50
44
40
40
27
27
22
16
34
29
27
27
27
25
23
20
17
36
34
29
27
25
34
29
27
27
27
25
23
20
17
76
67
63
41
29
22
15
9
4
135
82
60
52
35
20
49
40
36
86
63
63A
100
100
90
90
83
56
56
48
32
26
57
53
45
42
39
78
78
69
63
63
42
42
35
25
53
45
42
42
42
39
36
31
25
57
53
45
42
39
53
45
42
42
42
39
36
31
25
120
105
100
65
45
35
23
14
7
210
129
94
82
55
31
76
63
57
135
100
(Low Power Factor >0.9)
Metal - Halide Lamp
(High Power Factor <0.9)
Metal - Halide Lamp
(Low Power Factor <0.9)
High Pressure sodium lamps
(High Power Factor >0.9)
High Pressure sodium lamps
(Low Power Factor >0.9)
vapour lamps
Low pressure sodium
(High Power Factor <0.9)
vapour lamps
Low pressure sodium
(Low Power Factor >0.9)
vapour lamps
High pressure mercury
(High Power Factor <0.9)
vapour lamps
High pressure mercury
LED
12V external driver Dimmable
230V integrated driver
LED high bay lighting
Dimmable, GU 10
230V integrated driver
LED
dimmable, E27 / GU10
LED 230V integrated Driver, Non
LED’s
Discharge lamps
Type
4 - 12
17 - 22
30 - 40
50
4 - 12
17 - 22
30 - 40
50
100
150
200
1 - 10
15
50
80
125
250
400
700
50
80
125
250
400
700
1000
18
35
55
90
135
180
18
35
55
90
135
180
35
50
70
110
150
250
400
1000
35
50
70
110
150
250
400
1000
35
70
150
250
400
1000
35
70
150
250
400
1000
Lamp wattage
The table below indicates the number of lamps (or dual fittings) that can be connected to each pole of the contactor on 230V 50hz circuits.
Compact Fluorescent Lamps (CFL’s)
Type
Lighting load
(W)
27
20
14
11
60
44
31
24
0
0
0
60
44
14
9
5
3
1
0
11
8
5
3
1
0
0
10
6
6
4
3
2
7
6
5
3
2
2
14
12
9
8
7
4
1
1
9
9
6
5
5
3
1
0
24
15
7
5
2
0
10
8
5
5
1
0
Rated output (per pole)
25A
40A
86
63
44
35
159
118
82
65
6
4
4
108
75
32
24
18
10
6
4
26
22
15
9
5
3
2
18
10
9
6
4
4
15
13
13
13
5
5
30
22
18
14
10
6
4
2
13
13
13
13
13
7
5
3
42
26
14
9
6
3
22
22
12
9
5
2
63A
135
100
70
55
250
185
130
102
7
5
5
170
118
50
37
28
15
9
5
40
34
23
14
8
5
3
21
13
12
9
6
5
24
23
19
16
7
6
35
25
19
16
12
7
5
3
25
24
18
16
14
10
7
5
55
34
17
12
7
4
39
39
22
18
7
3
Download