PHE
Plate Heat Exchangers
FILE NO:
DATE:
SUPERSEDES:
DATE:
113.12L
August 2010
113.12
April, 2009
PHE
Efficient Heat
Transfer in a
Compact Design
Armstrong’s gasketed Plate Heat Exchanger (PHE) product line includes more than
20 different models and offers numerous configurations, connections and material
options, providing a superior heat transfer solution for any HVAC application.
fMarket Challenges
Rising demand for tenant space in commercial buildings and an ever-increasing focus on reducing
energy consumption have created numerous challenges for designers and contractors. These
challenges include the requirement for mechanical room optimisation and energy recovery or free
cooling systems such as water-side economisers, geothermal heating/cooling and deep-lake water
cooling. There is now, more than ever, a growing demand for compact heat exchangers capable
of transferring heat at low approach temperatures to achieve greater temperature crossing, which
saves energy.
In addition, factors such as global warming, high frequency of building conversions, and tighter
plant rooms have led to a demand for heat exchangers that can be maintained easily and are
flexible with regards to future expansion.
Temperature
Tin
Tout
Temperature
Cross
Tout
Tin
Gradient
Temperature
Approach
Plate Heat Exchangers
fAdding Value to Hydronic Systems
Space Savings
Due to their higher heat transfer capabilities, Armstrong X- Series
plate heat exchangers can take up less than other designs, yet
provide the same or better performance. The X-series plate have
an extremely efficient plate pattern that produces higher heat
transfer coefficients, less heat transfer surface area required and
a smaller footprint especially for HVAC applications. For a typical
cooling application of 1500 kw, the SX90-2000 provides the
most compact solution for a given capacity.
Plate
Removal
Space
Plate heat exchanger footprint
Space required in metres (feet) = 0.7 (2.3) x 2.3 (7.5) = 1.6m2 (17.3 ft2)
Based on Model SX96-2000
Project Risk Minimisation
All units are certified for safety by the appropriate agency (i.e. PED, ASME, TSSA, etc). Heat transfer plates can be added,
replaced or removed easily to maintain or increase the system performance. Gaskets are vented between passages, so
there is no cross contamination from a gasket failure. Every unit is provided with a safety shield that surrounds the plates
and gaskets. Double-wall heat transfer plates are available for domestic water applications. Select models are available
with a design pressure up to 24 bar (400 psi).
Maintenance
Single-pass PHE units are designed with all four system connections on the fixed head. This ensures the unit can be
easily maintained without having to break the connecting piping. In addition, plate heat exchangers can be installed in a
corner of a mechanical room to optimise the space. When maintenance is required, plates can be removed and installed
from one side of the unit. The gaskets are simple to replace and do not require any glue.
Installation Advantage
Connections are typically on the same plane for easy piping. Studded flanged connections reduce piping loads on the plate
heat exchanger. Units can be certified at the factory and then shipped disassembled for delivery and installation in tight
quarters. The vertical piping arrangement (inlet on top and outlet on bottom) of PHE Series units makes them ideal for
condensing steam service.
Energy Efficiency
The Armstrong PHE Series achieves the highest efficiency and heat transfer rates by flowing the two media in opposite
directions (counter-current) in a highly turbulent fashion. The temperature gain or loss between the hot fluid and the cold
fluid at a given flow rate is the regeneration rate. With counter-current flows, high turbulence and optimized corrugation,
Armstrong Series PHE units provide regeneration rates of up to 90%.
% Regeneration = ( Tin [hot fluid] - Tout [hot fluid] ) / ( Tin [hot fluid] - Tin [cold fluid] ) x 100
The X Series plates are specifically designed to produce the highest heat
transfer efficiencies.
Armstrong PHE Series heat exchangers offer multiple plate geometries to provide
the optimum heat transfer solution for a given application.
Occupant Comfort
Armstrong PHE Series heat exchangers react quickly to system demand changes,
and provide reduced down-time and longer life span due to corrosion resistant
materials, anti-scaling effect (due to turbulent flow) and ease of maintenance.
fTechnical Data
Flow Range:
Duty:
fMaterials of Construction
Up to 630 L/s (10,550 gpm)
Up to 15,000 kW
(50,000,000 btu/hr)
Plates:
Gaskets:
Height
Max. Fluid Temperature:
Nitrile Gaskets:
120 °C (250 °F)
EPDM Gaskets:
160 °C (320 °F)
Max. Working Pressure: 2757 kPa, 24 bar (400 psi)
304 and 316 Stainless Steel
Titanium, SMO 254, Hastelloy,
Incolloy, Nickel
Nitrile, EPDM, Viton, PTFE
Length
Width
fCapacities, Dimensions & Weights
Model
Max. Flow Connection
Size
Rate - l/s (gpm)
M7
3.5 (60)
M9
3.5 (60)
SX13
25 (250)
SX19
15 (250)
S26
25 (450)
S36
40 (650)
SX29
60 (1000)
SX49
60 (1000)
S38
60 (1000)
S66
130 (2200)
S76
130 (2200)
S/SX96 130 (2200)
S48
240 (4000)
S106
240 (4000)
S136
240 (4000)
S156
630 (10550)
S229
630 (10550)
Double-Wall Models
SX13D 15 (250)
SX19D 15 (250)
SX29D 60 (1000)
SX49D 60 (1000)
S66D 130 (2200)
Height
Width
Max. Length Max. Surface
Area - m2 (ft2)
Weight
Frame
Ea. Plate
25
25
65
50
65
75
100
100
100
150
150
150
200
200
200
350
350
(1.0)
(1.0)
(2.0)
(2.0)
(2.5)
(3.0)
(4.0)
(4.0)
(4.0)
(6.0)
(6.0)
(6.0)
(8.0)
(8.0)
(8.0)
(14.0)
(14.0)
660
890
790
990
1220
1400
1120
1350
1350
1930
1980
2360
1600
2300
2700
2620
3225
(26.0)
(35.0)
(31.0)
(39.0)
(48.0)
(55.0)
(44.0)
(53.0)
(53.0)
(76.0)
(78.0)
(93.0)
(63.0)
(90.0)
(106.0)
(103.0)
(127.0)
205
205
355
355
380
430
540
540
510
610
685
685
760
860
860
1145
1145
(8.0)
(8.0)
(14.0)
(14.0)
(15.0)
(17.0)
(21.0)
(21.0)
(20.0)
(24.0)
(27.0)
(27.0)
(30.0)
(34.0)
(34.0)
(45.0)
(45.0)
660
890
1680
1680
2440
2700
2440
2440
2720
3960
4270
4270
2440
4270
4270
4270
4270
(26.0)
5
(35.0)
15
(66.0)
35
(66.0)
55
(96.0)
85
(106.0) 125
(96.0)
140
(96.0)
195
(107.0)
90
(156.0) 365
(168.0) 410
(168.0) 545
(96.0)
135
(168.0) 585
(168.0) 730
(168.0) 930
(168.0) 1305
(65)
(145)
(390)
(615)
(935)
(1325)
(1490)
(2100)
(975)
(3910)
(4420)
(5890)
(1490)
(6300)
(7850)
(10030)
(14060)
50.0
70.0
140.0
210.0
360.0
590.0
480.0
560.0
570.0
1070.0
1340.0
1550.0
1040.0
2340.0
2870.0
5230.0
6210.0
(115)
0.5
(160)
0.5
(300)
0.9
(460)
0.9
(790)
2.3
(1300)
2.3
(1070)
1.8
(1230)
2.3
(1260)
2.3
(2380)
4.5
(2980)
5.0
(3430)
6.8
(2310)
3.6
(5200)
6.3
(6370)
7.7
(11630) 7.7
(13800) 12.0
(1)
(1)
(2)
(2)
(5)
(5)
(4)
(5)
(5)
(10)
(11)
(15)
(8)
(14)
(17)
(17)
(26)
65
50
100
100
150
(2.0)
(2.0)
(4.0)
(4.0)
(6.0)
790
990
1120
1350
1930
(31.0)
(39.0)
(44.0)
(53.0)
(76.0)
355
355
540
540
610
(14.0)
(14.0)
(21.0)
(21.0)
(24.0)
1680
1680
2440
2440
3960
(66.0)
(66.0)
(96.0)
(96.0)
(156.0)
(290)
(460)
(1120)
(1575)
(2930)
140.0
210.0
480.0
560.0
1070.0
(300)
(460)
(1070)
(1230)
(2380)
(4)
(4)
(8)
(10)
(20)
Note: · Dimensions are in mm (inches) and weights in kg (lbs)
· Frame weight is based on the maximum frame length, 10 bar (150 psi) design
· Dimensions based on 0.6 mm thick plates
25
45
105
145
270
1.8
1.8
3.6
4.6
9.0
Contact your local representative for information on additional models and capacities.
Plate Heat Exchangers
fCertifications
fStandard Connection Types
Safety: PED, ASME, CRN
Performance: ARI
fHow It Works
The Armstrong PHE Series uses robust stainless steel plates (standard construction)
as the primary medium for heat transfer. Alternate materials such as SMO 254, a
corrosion resistant steel alloy, and titanium are available on request. Each plate is
stamped with an optimised corrugated design. The series of plates create alternating
independent channels for both the process and service fluids. The two medium
circuits are configured to induce true counter-current flow, enabling the heat
exchanger to perform at extremely low temperature approaches. This is further
improved by using Armstrong X Series plates. As each fluid passes through its
individual channel, it flows over the ‘chevrons’ (the corrugated pattern), which
increases fluid turbulence, and increases heat transfer through the plates. Heat is
transferred from one medium to the other. The Armstrong PHE Series
uses a gasketed seal to separate the service side from the process side.
Threaded
Internal
Threaded
External Alloy
Studded
Studded
Alloy Liner
Ferrule
Flanged
fDesign Features
1 All connections are threaded or studded to the cover in 4 The bars that hold the plates are corrosion resistant for
order to eliminate nozzle loads caused by the piping.
ease of maintenance.
2 Gaskets are double-vented at the port area to eliminate 5 Heavy
cross contamination of the fluids. Gaskets are attached
mechanically to the plate without glue. They attach to
the plate only one way, eliminating assembly errors and
wasted time during servicing. The gaskets are visible
from outside the unit so proper installation is
guaranteed.
3 Tightening
duty pressure-retaining headers are designed
using the latest stress calculation data, as per PED and
ASME, to ensure lengthy and safe service.
6 Heat
transfer plates are stamped using an H or W
pattern according to the application requirements.
7 An aluminum safety shield covers the top and sides of
bolts are designed so that all tightening
is done from the fixed end (nuts at the moveable end
are locked). Bolts are coated for corrosion resistance.
This makes servicing the heat exchanger quicker and
easier.
the plate pack.
4
6
3
7
5
2
1
fTypical Specifications
1.1 Furnish a plate heat exchanger as manufactured and designed by Armstrong completely assembled, inspected and
tested to meet the thermal and hydraulic requirements of the schedule.
1.2 The heat exchanger design shall be in full accordance with the governing safety code: PED, ASME, TSSA.
1.3 The individual heat transfer plates that shall be pressed from a single sheet of 304SS, 316SS or titanium with a 2B
finish in one step. The plate thickness shall be determined by the manufacturer to meet the design pressures and
temperature. The plates shall be provided with a herringbone corrugation with a depth, spacing and thickness to meet
a full differential pressure across the plate of 1.3 to 1.5 times the design pressure without deformation or failure.
1.4 Each plate shall have a gasket made from nitrile, EPDM or other material that shall be compatible with all the
operating fluids and rated for continuous service at the design temperature. The gasket cross section shall be tent
shaped, resulting in better sealing with less compressive stress.
1.5 Gaskets shall have vent grooves in the unused area of the plate to prevent intermixing of the fluids and to cause any
leak by the gasket to be visually evident from outside the heat exchanger. The gasket groove in each plate shall be
of the proper depth to contain 100% of the gasket profile.
1.6 Gaskets, unless otherwise approved, shall be of the glue-free clip-on type that mechanically attach to a specific Ushaped hole at the outer edge of the plate. Gasket clips shall be visible from the outside to verify proper installation.
Glue-free gaskets that wrap around the outer edge of the plate and can be damaged shall not be used. For certain
applications, glued on gaskets may be acceptable.
1.7 The pressure-retaining frame shall be designed and built to guarantee dependable operation and easy maintenance
for the life of the heat exchanger. The frame shall be bolted together for ease of assembly and field installation. The
unit covers shall be of sufficient uniform thickness and tightening bolt configuration to withstand all loadings.
1.8 The covers and all other carbon steel parts shall be cleaned, prepared and painted in accordance with Armstrong
standards. For heat exchangers that are 1270 mm (50") or taller, the moveable cover shall be provided with a roller
assembly to easily move it during assembly and plate inspection.
1.9 The preferred connection arrangement is all four connections on the fixed front cover. Flow arrangement shall be
vertical. A diagonal flow pattern is not acceptable. Connections shall be integral with the cover in either studded DIN
or BSP type to eliminate nozzle pipe loadings and leakage in the connection area.
2.0 The carrying bars for the plates and tightening bolts shall be stainless steel or zinc-coated carbon steel for rust
prevention and ease of maintenance. Painted surfaces are not acceptable.
2.1 The frame and carrying bars shall be designed to allow for a plate expansion of at least 20% capacity while still
providing maintenance space.
2.2 All units are to be provided with an aluminum safety shield for personal protection and to protect the plates and
gaskets from the elements.
2.3 If ARI Certification is required, the supplier and the equipment must be listed at www.ahridirectory.org for liquid to
liquid heat exchangers.
Additional Armstrong Solutions
The IVS Sensorless pump is designed to meet the needs of energy-efficient pumping systems in today's
buildings. Traditional pumping systems, incorporating constant-speed pumps, waste energy through
crude throttling valve flow control. Lifetime cost analysis shows that the capital cost of a constant-speed
pump is typically only 5% of its lifetime cost.
Armstrong Integrated Limited
Wenlock Way
Manchester
United Kingdom, M12 5JL
T: +44 (0) 8444 145 145
F: +44 (0) 8444 145 146
S. A. Armstrong Limited
23 Bertrand Avenue
Toronto, Ontario
Canada, M1L 2P3
T: 001 416 755 2291
F: 001 416 759 9101
For Armstrong locations worldwide, please visit www.armstrongintegrated.com
Download