Data Acquisition and Logging Software Minigraph Recorders

advertisement
419.P.N:Layout 2
7/23/10
9:23 AM
Page 1
Model
LoveLink™III
Data Acquisition and Logging Software
Designed for Love Temperature Controller Interface
LoveLink™III Data Acquisition and Logging Software is the second generation of data
acquisition software from Love Controls. This easy to use program allows connection of up
to 40 controls on a single computer port. Data logging can be set up by individual control
with varying logging periods. LoveLink™III Software is compatible with all Love Controls
2600, 8600, 16A, 16L, 16S, 32A, and 32DZ Series controls.
Series
1200
Other Requirements
To communicate with controls equipped with Options 992 or 996, RS-485 Serial
Communications, from an RS-232 communications port, an RS-485 to RS-232
converter (Mother Node) is needed. The converter models recommended are the
Love Models 351, 352, and 356 (See page 416). For RS-485 systems a 120-ohm
resistor is also needed to terminate the last control on the control network. Shielded
twisted pair cable is recommended for wiring the controls together.
Windows® is a registered trademark of Microsoft Corporation
Windows NT® is a registered trademark of Microsoft Corporation
Minigraph Recorders
Temperature and Process Inputs
3/16 X 5/16
[4.76 X 7.94]
MOUNTING SLOTS
5-5/8
[142.88]
6-3/8
[161.93]
6-7/8
[174.63]
11/16
[11.48]
Minigraph Recorders combine compact size, durability, accuracy and low cost for an
exceptional value. Units are widely used in applications ranging from commercial,
industrial, and process to laboratory, field, marine, aerospace and more.
Series 1200 Minigraph Recorders use a unique stylus which records on special pressure
sensitive paper. No messy ink pens, reservoirs or ink cartridges are used, eliminating
maintenance problems and data loss caused by dry pens.
Stock temperature recorders come complete with 6" long x 3/16" dia. K type thermocouple
protected by a 304 SS sheath with 8 ft. fiberglass insulated cable. They will record a full
31 days of information on a single 62 ft. x 2-9/16" wide paper roll. Stock units operate from
a 120 VAC power source; special units are available for 240 VAC or 12 VDC.
Model
1201-11-09-04
1201-12-09-04
1201-20-09-04
1201-21-09-04
1202-05-09-04
1202-12-09-04
1203-01-09-04
1204-05-09-04
Range
0-100 mV
0-1V
4-20 mA
4-20 mA
0-200°F
0-1000°F
-20 to 130°F
0-300 V
CALL TO ORDER:
Input Type
DC Voltage
DC Voltage
DC Current
0-14 PH
Type K T/C
Type K T/C
Thermistor
AC Voltage
U.S. Phone 219 879-8000
2-1/4
[57.15]
3-5/8
[92.08]
5/8
[15.88]
SPECIFICATIONS
Pen Response Speed: 1 second full
scale. Stylus strikes chart once in two
seconds. Dot density depends on chart
speed.
Temperature Limits: 32 to 122°F (0 to
50°C).
Accuracy: ±2% of span for DC and
temperature inputs; ±3% of span for
AC inputs.
1-5/16
[33.35]
13/16
[20.64]
4-13/32
[111.92]
Power Supply: Standard: 120 VAC,
60 Hz, 3W nominal; Optional: 240
VAC, 60 Hz, 3W nominal or 12 VDC,
20 mA nominal.
Chart Size: 2-9/16˝ wide x 62´ long, 21/8˝ active width (65 mm wide x 19 m
long, 54 mm active width).
Housing Size: 3-5/8˝ wide x 5-5/8˝
height x 4-5/8˝ depth. (92 mm wide x
143 mm height x 111 mm depth).
Weight: 3-1/2 Ib (1.6 kg).
Charts (Packed 6 per box)
Major/Minor Division
8/40
10/50
15/75
10/47
12/60
14/70
Parts No.
MG651-691630
MG651-691760
MG651-691770
MG651-691950
MG651-691650
MG651-220920
•
U.K. Phone (+44) (0)1494-461707
•
Australia Phone (+61) (0) 2 4272 2055
419
Data Acquisition
Software
FEATURES
• Address and store data for up to 40 controls
• Data logging at individually adjustable rates
• On-screen graphing for up to 10 zones
• Upload and download control configuration profiles
• Save and retrieve profiles to/from disk
• Easy to use operator interface
• Supports Love Series 2600, 8600, 16A, 16L, 32A & 32DZ controls,
and Series PP45 indicators
• Low cost
Control Requirements
The temperature controls supported by LOVELINK™III software are the Love 2600,
8600, 16A, 16L, 32A, and 32DZ Series (with Options 992 or 996, RS-485 Serial
Communications; or Options 993 or 995, RS-232 Serial Communications). (Note:
The 32A and 32DZ Series supports RS-485 communications only.
DATA LOGGERS & RECORDERS
Computer Requirements
The LOVELINK™III software application will run on Windows® 95/98 and Windows®
NT™ Workstation 4.0 (Service Pack 3 recommended), Windows® 2000, and
Windows® XP Software. The hardware requirements for each of these operating
systems can be found in the documentation provided with that operating system.
One available RS-232 or RS-485 port is needed to communicate with the
temperature control(s). A minimum of 4 MB of hard disk space is needed for the
LOVELINK™III software application files, and additional hard disk space is needed
to store temperature log files. Log file size will vary depending on the Duration and
Rate selected for the controls and the number of controls on line.
Download