RISK CONTROL REDUCE RISK. PREVENT LOSS. SAVE LIVES. Fire protection impairments Are you prepared? A fire protection impairment is any condition that affects the ability of fixed fire protection equipment to detect, control, or suppress a fire in the way it was designed or intended. If fires occur when these detection or suppression systems are impaired, the results can be catastrophic. The destruction may cause loss of life, property and the ability to serve customers. Even if you are fully insured, some loss costs may not be recoverable! Fire Protection Equipment Out of Service! (see other side) FIRE PROTECTION EQUIPMENT OUT OF SERVICE! REMINDER CARD FIRE PROTECTION EQUIPMENT OUT OF SERVICE! (see other side) FIRE PROTECTION EQUIPMENT OUT OF SERVICE! Out of Service! When impaired fire protection equipment is returned to service, complete this side of the card and file it for review by Travelers Risk Control Consultant. Fire Protection Equipment When impaired fire protection equipment is returned to service, complete this side of the card and file it for review by Travelers Risk Control Consultant. REMINDER CARD When impaired fire protection equipment is returned to service, complete this side of the card and file it for review by Travelers Risk Control Consultant. (see other side) Date & Time Restored: Number of Turns to Open Valves: (Compare with number of “Turns to Close Valve” on reverse side.) Pressure/Drain Test Results (For Sprinkler Systems): 1. Notify alarm company if system is monitored. 2. Open control valve to restore protection. 3. Check area of sprinkler drain discharge to prevent injury or water damage. 4. Open 2-inch main drain completely and record flowing water pressure once the pressure stabilizes. 5. Close the drain, and record the static pressure. Static psi Flowing psi 6. Compare drain test results with prior test results. 7. Notify the alarm company that testing is completed. Restored By: Out of Service! Date & Time Restored: Number of Turns to Open Valves: (Compare with number of “Turns to Close Valve” on reverse side.) Pressure/Drain Test Results (For Sprinkler Systems): 1. Notify alarm company if system is monitored. 2. Open control valve to restore protection. 3. Check area of sprinkler drain discharge to prevent injury or water damage. 4. Open 2-inch main drain completely and record flowing water pressure once the pressure stabilizes. 5. Close the drain, and record the static pressure. Static psi Flowing psi 6. Compare drain test results with prior test results. 7. Notify the alarm company that testing is completed. Restored By: Fire Protection Equipment Date & Time Restored: Number of Turns to Open Valves: (Compare with number of “Turns to Close Valve” on reverse side.) Pressure/Drain Test Results (For Sprinkler Systems): 1. Notify alarm company if system is monitored. 2. Open control valve to restore protection. 3. Check area of sprinkler drain discharge to prevent injury or water damage. 4. Open 2-inch main drain completely and record flowing water pressure once the pressure stabilizes. 5. Close the drain, and record the static pressure. Static psi Flowing psi 6. Compare drain test results with prior test results. 7. Notify the alarm company that testing is completed. Restored By: REMINDER CARD Fire protection impairments Thousands of dollars are invested in fire detection and suppression systems; however, the value of the lives, property and operations they protect is much higher. What can I do to control the impairment? Extraordinary precautions should be taken while fire protection is out of service. With a planned impairment, you have time to provide safeguards, supply the necessary equipment to repair the equipment and make temporary provisions. These impairments usually can be addressed without incident. Unplanned impairments are more serious because they do not allow time to offset potential loss. Consider this when you experience a fire protection impairment in your facility. Attend to these impairments immediately! Which fire protection systems are affected by impairments? The following protection systems may be affected by impairments: Fire protection water supplies: Automatic special fire extinguishing systems using: • Underground pipes • Carbon dioxide • Fire pumps • Halon • Valves • Halon-substitute gaseous agent • Foam • Tanks used as sprinkler or hydrant water sources • Automatic sprinkler systems: Dry or wet chemical extinguishing agent • Wet pipe Detection and alarm systems: • Dry pipe • • Deluge • • Preaction • Smoke and heat detection Sprinkler system water flow alarms Fire pump running conditions What are the common causes of impairments? Fire protection impairments can be planned due to building renovations or scheduled inspection and maintenance of fire protection installations. Impairments can also be unplanned due to mechanical damage, freezing, equipment malfunction or improperly closed valves. • • Mechanical damage can include a sprinkler line broken by a lift truck or a yard hydrant struck by a vehicle. Freezing conditions causing impairments include building heat failure or sprinkler piping in inadequately heated spaces. • • Equipment malfunctions may be electrical, mechanical or a combination of both. An example is a diesel-driven fire pump that fails to start during the weekly test. Improperly closed sprinkler valves can occur when employees close the wrong valve or when they fail to restore a valve once repairs are completed. There are seven steps you should follow in the event of a planned or unplanned impairment: 1. Minimize hazards Materials, processes, employee activities and maintenance operations may be hazardous, yet adequately controlled by special protective equipment. When this protective equipment is out of service, hazards should be minimized by reducing or completely stopping operations. Some examples include: • • • • Discontinue use and transfer of flammable liquids in buildings if the sprinkler system is out of service. Postpone scheduled maintenance involving cutting, welding, grinding or similar hot work if protection in the work area is out of service. Control smoking when fire protection is out of service. Schedule planned impairments during off hours or weekends when production hazards are reduced. Note: Some fire prevention authorities and codes may require building evacuation when automatic fire protection is impaired. 2. Provide temporary protection Numerous temporary safeguards are available when protection is impaired. • Notify the plant brigade. • Bring extra portable fire extinguishers to the area. • • Use a fire hose that is preconnected to hydrants and stretched into affected areas. Use tie-ins through cross-connections from an in-service sprinkler system to an impaired system. 3. Expedite repairs Use the maximum amount of effort and the minimum amount of time to restore fire protection. • • 5. Intensify watchman service, employee patrols or fire watches In many cases, the impairment will eliminate automatic fire detection capability. Therefore, it is necessary to provide substitute methods for prompt detection of a fire or a dangerous condition. One substitute is to have capable, competent personnel conduct scheduled tours of the affected areas. If standard watchman service is provided, conduct tours throughout the affected area at more frequent intervals. Clearly explain the procedures for summoning fire department aid. 6. Provide notification and use a tag system The impairment notification and valve closed tag system was developed to: • • Make employees, fire brigade and fire department personnel aware of the shut valve by using prominent shut-valve tagging. Help ensure that protection is restored following maintenance and repairs. You should notify your local Travelers office, by phone or by fax, in the event of an unplanned impairment OR when a planned impairment cannot be completed in one day, OR when you need advice or assistance in managing a serious fire protection impairment. For a planned impairment, provide as much advance notice as possible. In addition, your Risk Control Consultant may recommend other procedures for your location based on the operations and exposures to loss present. Our Risk Control Consultants can advise you on methods to help limit the increased loss exposure during the impairment period. Use the valve tag system to ensure that systems are fully restored after repairs or maintenance are completed. For planned impairments, have all replacement parts on hand before the system is shut down. 7. Manage the impairment – provide responsibility and authority Schedule work to occur continuously once the job is started. A competent individual should be selected to manage and properly control the entire impairment. This individual should have authority over all activities involved in controlling the increased exposure to loss created by the impairment. These activities include minimizing hazards, providing temporary protection, expediting repairs, providing notification and tagging, conducting surveillance, and confirming restoration. 4. Notify the public fire department Seek assistance from local fire authorities when impairments occur. Depending on the severity, the fire department may assign personnel and equipment to the site until the impairment is resolved and protection is restored. Or an officer may personally evaluate the problem and alert the other fire companies of the impairment at your facility. Shut Off By: Approved By: Precautions Taken (See Travelers Fire Protection Impairments Brochure): a.m./p.m. Shut Off By: Approved By: a.m./p.m. Precautions Taken (See Travelers Fire Protection Impairments Brochure): Fire Protection System No./Name: Area Controlled: Date & Time Shut Off: Number of Turns to Close Valves: Reason for Fire Protection Equipment Shut-Off: Shut Off By: Approved By: a.m./p.m. Precautions Taken (See Travelers Fire Protection Impairments Brochure): Fire Protection System No./Name: Area Controlled: Date & Time Shut Off: Number of Turns to Close Valves: Reason for Fire Protection Equipment Shut-Off: Complete this side of tag and attach it to the control point (valve, switch, panel) of the impaired fire protection equipment. Complete this side of tag and attach it to the control point (valve, switch, panel) of the impaired fire protection equipment. Complete this side of tag and attach it to the control point (valve, switch, panel) of the impaired fire protection equipment. Fire Protection System No./Name: Area Controlled: Date & Time Shut Off: Number of Turns to Close Valves: Reason for Fire Protection Equipment Shut-Off: FIRE PROTECTION EQUIPMENT OUT OF SERVICE! FIRE PROTECTION EQUIPMENT OUT OF SERVICE! FIRE PROTECTION EQUIPMENT OUT OF SERVICE! REMINDER CARD Post this tag in a conspicuous place in your office as a reminder to restore impaired fire protection equipment. Fire Protection System No./Name: Area Controlled: Date & Time for Shut-Off: a.m./p.m. Anticipated Date & Time for Restoration: a.m./p.m. REMINDER CARD Post this tag in a conspicuous place in your office as a reminder to restore impaired fire protection equipment. Fire Protection System No./Name: Area Controlled: Date & Time for Shut-Off: a.m./p.m. Anticipated Date & Time for Restoration: a.m./p.m. REMINDER CARD Post this tag in a conspicuous place in your office as a reminder to restore impaired fire protection equipment. Fire Protection System No./Name: Area Controlled: Date & Time for Shut-Off: a.m./p.m. Anticipated Date & Time for Restoration: a.m./p.m. travelers.com The Travelers Indemnity Company and its property casualty affiliates. One Tower Square, Hartford, CT 06183 The information provided in this document is intended for use as a guideline and is not intended as, nor does it constitute, legal or professional advice. Travelers does not warrant that adherence to, or compliance with, any recommendations, best practices, checklists, or guidelines will result in a particular outcome. In no event will Travelers or any of its subsidiaries or affiliates be liable in tort or in contract to anyone who has access to or uses this information. Travelers does not warrant that the information in this document constitutes a complete and finite list of each and every item or procedure related to the topics or issues referenced herein. Furthermore, federal, state or local laws, regulations, standards or codes may change from time to time and the reader should always refer to the most current requirements. This material does not amend, or otherwise affect, the provisions or coverages of any insurance policy or bond issued by Travelers, nor is it a representation that coverage does or does not exist for any particular claim or loss under any such policy or bond. Coverage depends on the facts and circumstances involved in the claim or loss, all applicable policy or bond provisions, and any applicable law. © 2008-2013 The Travelers Indemnity Company. All rights reserved. Travelers and the Travelers Umbrella logo are registered trademarks of The Travelers Indemnity Company in the U.S. and other countries. 59258 Rev. 10-13