Product Description Wye-Delta Open Transition Starting Electric Fire Pump Controllers Description—Firetrol® FTA1300 Wye-Delta, Open Transition Starting Fire Pump Controllers are used with delta-wound squirrel cage motors. FTA1300 controllers are of the open circuit transition type in which the motor circuit is opened during the transition from start to run. The controller monitors, displays and records fire pump system information. Actuating the controller by the pressure switch, START pushbutton or deluge valve contact closes the start contactor connecting the motor to the line in the wye connection. The motor will draw approximately 33% of its normal inrush current and develop approximately 33% of its normal starting torque. After a time delay, the motor is automatically reconnected in delta, applying full voltage to the motor windings. These controllers are recommended especially for use with generator sets. Approvals—Firetrol fire pump controllers are listed by Underwriters’ Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features—The following are included as standard with each controller: Voltage surge protector Main Disconnect Switch sized for connected motor horsepower and voltage Fire pump Circuit Breaker Motor contactor Suitable for use as Service Equipment • FTA1300 Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition Built-in Start and Stop push-buttons to bypass automatic start circuits Door mounted display/interface panel featuring a 40 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators Single handle Isolating Disconnect Switch/Circuit Breaker mechanism POWER ON LED PUMP RUN LED PHASE FAILURE LED PHASE REVERSAL LED LOW PRESSURE LED DELUGE OPEN LED INTERLOCK ON LED TRANSFER SWITCH NORMAL LED (If unit ordered with Automatic Power Transfer Switch) TRANSFER SWITCH EMERGENCY LED (If unit ordered with Automatic Power Transfer Switch) EMERGENCY ISOLATING SWITCH OFF LED (If unit ordered with Automatic Power Transfer Switch) Minimum Run Timer / Off Delay Timer Daylight Savings Time option Weekly Test Timer Motor Acceleration Timer Elapsed Time Meter Digital Pressure Display USB Host Controller and Port Solid State Pressure Transducer Data Log Event Log (3000 Events) True RMS Metering with simultaneous 3 phase display of amps and volts Disk Error message Disk Near Full message Pressure Error message Motor Over 320% message Local Start message Remote Start message Emergency Start message Fail To Start message Undervoltage message Overvoltage message High Speed Open Serial Communications Port NEMA Type 2 enclosure Product Description Power Transfer Switches for Electric Fire Pump Controllers Description—Firetrol® Power Transfer Switches are available completely assembled with Firetrol Electric Fire Pump Controllers; full or reduced voltage types. The power transfer switches are built in two versions: FTA900 — For use when the normal power source is a utility and the emergency power source is a generator set. FTA950 — For use when both the normal and emergency power sources are utilities. The entire package of power transfer switch and controller is completely factory assembled, wired, tested and shipped as a complete unit for easy field connection to the power sources and the fire pump motor. Approvals—Firetrol power transfer switches are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers; UL1008, Automatic Transfer Switches; UL508, Industrial Control Equipment, CSA, Standard for Industrial Control Equipment; and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features—The following are included as standard with each transfer switch: n Emergency power source disconnect switch sized for connected motor horsepower and voltage n (FTA950 only) Fire pump circuit breaker • FTA900 FTA950 n (FTA950 only) Mark II monitors for overcurrent tripping (non-thermal) of circuit breaker and alarm indicator for phase failure/phase reversal n 3-pole, double throw transfer switch mechanism, electrically operated, mechanically held n Control module providing for the following: Differential voltage sensing on all phases of the normal power source Voltage sensing of the emergency power source Frequency sensing of the emergency power source Transfer time delay to compensate for momentary power outages of the normal source Retransfer from emergency to normal source is automatically delayed unless the emergency source fails Cool-down timer for unloaded running of the generator set after retransfer to the normal power source Instantaneous retransfer to normal if the emergency source fails and the normal source is available 3 second transfer restart delay to reduce current surges when transferring to or from the emergency source NO and NC engine control contacts to start the generator set when the normal power source fails n Transfer Switch Normal LED n Transfer Switch Emergency LED n Emergency Isolating Switch Open LED n Test Selector Switch n Transfer By-pass Switch n Silence Alarm Pushbutton n Emergency Isolating Switch Open and Transfer Switch in Emergency Audible Alarms n Output contacts (NO and NC) for Generator Start, Emergency Isolating Switch Open and Transfer Switch position indicators n Standard Withstand Rating, emergency side only FTA900 (Generator set equipped with molded case circuit breaker) 100-150A, 22,000A RMS Sym., 200-480V; 10,000A RMS Sym., 550-600V 260-400A, 35,000A RMS Sym ., 200-480 V; 10,000A RMS Sym., 550-600 V 600-800A, 50,000A RMS Sym., 200-480V; 10,000A RMS Sym., 550-600V (See Options for higher ratings) FTA950—See Options n NEMA Type 2 enclosure (IEC IP11) Specifications Electric Fire Pump Controllers Main Fire Pump Controller The main fire pump controller shall be a factory assembled, wired and tested unit and shall conform to all the requirements of the latest edition of NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection and NFPA 70, National Electrical Code. The controller shall be listed by Underwriters Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, and Canadian Standards Association CSA-C22.2, Standard for Industrial Control Equipment (cULus), approved by Factory Mutual and approved by the City of New York for fire pump service. Starting Method The controller shall be of the combined manual and automatic type designed for: Full Voltage Starting Wye (Star)-Delta Open Transition Starting Wye (Star)-Delta Closed Transition Starting Part Winding Starting Primary Resistance Reduced Voltage Starting Autotransformer Reduced Voltage Starting of the fire pump motor having the horsepower, voltage, phase and frequency rating shown on the plans and drawings. The controller components shall be housed in a NEMA Type 2 (IEC IP11) drip-proof, wall mounted enclosure. Withstand Ratings (Short Circuit Current Ratings) All controller components shall be front mounted, wired and front accessible for maintenance. The minimum withstand rating of the controllers shall not be less than 100,000 Amps RMS Symmetrical at 200-600 Volts*. If the available system fault current exceeds these ratings, the controllers shall be supplied with a withstand rating of 150,000 or 200,000 Amps RMS Symmetrical, as required. *Note: 100,000 Amp withstand rating not available in some larger horsepowers. Consult factory for details. Isolation Switch and Circuit Breaker The controller shall include a motor rated combination isolating disconnect switch/circuit breaker, mechanically interlocked and operated with a single, externally mounted handle. When moving the handle from OFF to ON, the interlocking mechanism shall sequence the isolating disconnect switch ON first, and then the circuit breaker. When the handle is moved from ON to OFF, the interlocking mechanism shall sequence the circuit breaker OFF first, and then the isolating disconnect switch. The isolating disconnect switch/circuit breaker shall be mechanically interlocked so that the enclosure door cannot be opened with the handle in the ON position except by a hidden tool operated defeater mechanism. The isolating disconnect switch/circuit breaker shall be capable of being padlocked in the OFF position for installation and maintenance safety, and shall also be capable of being locked in the ON • FTA1000 -1800 position without affecting the tripping characteristics of the circuit breaker. The controller door shall have a locking type handle and three point cam and roller vault type hardware. The circuit breaker trip curve adjustment shall be factory set, tested and sealed for the full load amps of the connected motor. The circuit breaker shall be capable of being field tested to verify actual pick up, locked rotor, and instantaneous trip points after field installation without disturbing incoming line and load conductors. Operator Interface The fire pump controller shall feature an operator interface with user keypad. The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and pressure conditions shall be displayed with a time and date stamp. The display shall be a 2-line, 20-character, vacuum fluorescent, dot matrix type designed to allow easy viewing from all angles and in all light conditions. The display and interface shall be NEMA rated for Type 2, 3R, 4, 4X, and 12 protection and shall be fully accessible without opening the controller door. The display and user interface shall utilize multiple levels of password protection for system security. A minimum of 3 password levels shall be provided. The display shall be capable of being programmed for any language. Ammeter/Voltmeter The fire pump controller operator interface shall be capable of displaying true RMS digital motor voltage and current measurements for all three phases simultaneously. Displays requiring pushbutton and selector switches to toggle between phases or current and voltage shall not be accepted. Voltage and current shall be measured by True RMS technology to provide the most accurate measurement for all sine waves, including nonsinusoidal waveforms. Average responding meters will not be accepted. Digital Status/Alarm Messages The digital display shall indicate text messages for the status and alarm conditions of: • Motor On • Sequential Start Time • Minimum Run Time • Local Start / Off Delay Time • Remote Start • Fail to Start • System Battery Low • Under Voltage • Over Voltage • Locked Rotor Trip • Over Frequency • Emergency Start • Motor Over 320% • Drive Not Installed • Motor Overload • Disk Error • Printer Error • Disk Near Full • Pressure Error The Sequential Start Timer and Minimum Run Timer/ Off Delay Timer shall be displayed as numeric values reflecting the value of the remaining time. LED Visual Indicators LED indicators, visible with the door closed, shall indicate: • Power On • Emerg. Isolating Switch Open • Pump Running • Low System Pressure • Alarm • Transfer Switch Normal • Deluge Open • Transfer Switch Emergency • Phase Failure • Phase Reversal • Interlock On Data Logging The digital display shall monitor the system and log the following data: • Motor Calls/Starts • Elapsed Motor Run Time • Last Trip Currents • Elapsed Power On Time • Last Breaker Trip • Maximum Run Currents • Minimum Voltages • Minimum Run Currents • Maximum Voltages • Last Motor Run Time • Last Phase Failure • Last Start Currents • Last Phase Reversal • Min/Max Frequency • Min/Max Pressure Event Recording Memory - The controller shall record all operational and alarm events to system memory. All events shall be time and date stamped and include an index number. The system memory shall have the capability of storing 3000 events and allow the user access to the event log via the user interface. The user shall have the ability to scroll through the stored messages in groups of 1, 10, or 100. USB Host Controller - The controller shall have a built-in USB Host Controller. A USB port capable of accepting a USB Flash Memory Disk (aka: flash drive, thumb drive, memory stick, etc..) shall be provided. The controller shall save all operational and alarm events to the flash memory on a daily basis. Each saved event shall be time and date stamped. The total amount of historical data saved shall solely depend on the size of the flash disk utilized. The controller shall have the capability to save settings and values to the flash disk via the user interface. Serial Communications - The controller shall feature a RS485 serial communications port for use with 2 or 4 wire Modbus RTU communications. Solid State Pressure Transducer The controller shall be supplied with a solid state pressure transducer with a range of 0-300 psi (0-20.7 bar) ±1 psi. The solid state pressure switch shall be used for both display of the system pressure and control of the fire pump controller. Systems using analog pressure devices or mercury switches for operational control will not be accepted. The START, STOP and SYSTEM PRESSURE shall be digitally displayed and adjustable through the user interface. The pressure transducer shall be mounted inside the controller to prevent accidental damage. The pressure transducer shall be directly pipe mounted to a bulkhead pipe coupling without any other supporting members. Field connections shall be made externally at the controller coupling to prevent distortion of the pressure switch element and mechanism. Operation A digitally set On Delay (Sequential Start) timer shall be provided as standard. Upon a call to start, the user interface shall display a message indicating the remaining time value of the On Delay timer. The controller shall be field programmable for manual stop automatic stop. If set for automatic stopping, the controller shall allow the user to select either a Minimum Run Timer or an Off Delay Timer. Both timers shall be programmable through the user interface. A nonadjustable restart delay timer shall be provided to allow the residual voltage of the motor to decay prior to restarting the motor. At least 2 seconds, but no more than 3 seconds, shall elapse between stopping and restarting the pump motor. A weekly test timer shall be provided as standard. The controller shall have the ability to program the time, date, and frequency of the weekly test. In addition, the controller shall have the capability to display a preventative maintenance message for a service inspection. The message text and frequency of occurrence shall be programmable through the user interface. A Lamp Test feature shall be included. The user interface shall also have the ability to display the status of the system inputs and outputs. The controller shall not start the fire pump motor under a single-phase condition. If the motor is already running when a phase loss occurs, the controller shall continue to run the motor, but still display a Phase Failure alarm. The fire pump controller software shall be automatically upgradable through the USB port by simply inserting a flash disk with the new software. Fire pump controllers that require laptop computers, handheld equipment or specialized devices for software upgrades shall be prohibited. The controller shall be a Firetrol brand. (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27518 USA SP1000-20 (03-10-09) ©ASCO 2006 Specifications Fire Pump Controller Power Transfer Switches Main Fire Pump Controller with Transfer Switch The main fire pump controller shall be factory assembled and wired with a power transfer switch listed by Underwriters’ Laboratories, Inc. for transfer switch and fire pump service. The power transfer switch shall be approved by Factory Mutual. The power transfer switch and fire pump controller shall be factory assembled, wired and tested as a single unit and shall conform to all requirements of the latest edition of NFPA 20, Centrifugal Fire Pumps and NFPA 70, National Electrical Code. Power Transfer Switch for Generator Set Emergency Power Source The power transfer switch shall be housed within the fire pump controller enclosure or in a NEMA Type 2 (IEC IP11) drip-proof enclosure attached directly to the fire pump controller. Where the power transfer switch is provided in an attached enclosure, the enclosures shall be fitted so that the assembly constitutes a single unit. The fire pump controller/power transfer switch shall be factory assembled, wired and tested as a unit prior to shipment. The power transfer switch shall include a motor rated disconnect/isolating switch capable of interrupting the motor locked rotor current. The disconnect/isolating switch shall be mechanically interlocked so that the enclosure door cannot be opened with the handle in the ON position except by a hidden tool operated defeater mechanism. The disconnect/isolating switch shall be capable of being padlocked in the OFF position with up to three padlocks for installation and maintenance safety, and shall also be capable of being locked in the ON position. The enclosure door shall have a locking type handle and three point cam and roller type vault hardware. A auxiliary contract shall be provided on the transfer switch to prevent starting of the emergency generator set when the transfer switch or the main fire pump controller are being serviced. The automatic transfer switch shall consist of an inherently double throw power transfer switch mechanism and a microprocessor control panel to provide automatic operation. The transfer switch and control panel shall be of the same manufacturer. The automatic transfer switch shall be an ASCO 7000 series with a group 5 control panel. The transfer switch shall be electrically operated and mechanically held. The electrical operator shall be a momentarily energized, single solenoid mechanism. The switch shall be mechanically interlocked to ensure only two possible positions, normal or emergency. Switches having a neutral position shall not be permitted. • FTA900 950 The switch shall be positively locked and unaffected by momentary outages, so that contact pressure is maintained at a constant value and contact temperature rise is minimized for maximum reliability and operating life. All main contacts shall be silver composition and inspection of all contacts shall be possible from the front of the switch without disassembly of operating linkages and without disconnection of power. Designs utilizing components of molded case circuit breakers, contactors, or parts thereof, which are not intended for continuous duty, repetitive switching or transfer between two active power sources are not acceptable. The transfer switch control panel shall have a 4 line, 20 character LCD display and keypad for viewing all available data and setting desired operational parameters. Voltage and frequency on both the normal and emergency sources shall be continuously monitored. The normal source pick up shall be set at 95% of nominal voltage and the emergency source pick up set at 90% of nominal voltage and 95% nominal frequency. Source status screens shall be provided for both normal & emergency to provide digital readout of voltage, frequency and phase rotation on all 3 phases. The transfer switch shall have visible pilot light indication for the following conditions: TRANSFER SWITCH IN NORMAL, TRANSFER SWITCH IN EMERGENCY, NORMAL SOURCE ACCEPTED, EMERGENCY SOURCE ACCEPTED and EMERGENCY ISOLATION SWITCH OPEN. Remote alarm contacts shall be supplied as standard for the following conditions: EMERGENCY SOURCE ISOLATION SWITCH OPEN, NORMAL POWER AVAILABLE, EMERGENCY POWER AVAILABLE and TRANSFER SWITCH POSITION. An audible alarm shall sound if: EMERGENCY ISOLATION SWITCH OPEN and TRANSFER SWITCH IN EMERGENCY. A SILENCE ALARM push-button shall be supplied . A selector switch shall be supplied to manually test the transfer to emergency and the retransfer to normal power. The power transfer switch shall be a Firetrol FTA900 for normal utility power and engine generator set emergency power. Power Transfer Switch for Second Utility Emergency Power Source The power transfer switch shall be housed within the fire pump controller enclosure or in a NEMA Type 2 (IEC IP11) drip-proof enclosure attached directly to the fire pump controller. Where the power transfer switch is provided in an attached enclosure, the enclosures shall be fitted so that the assembly constitutes a single unit. The fire pump controller/power transfer switch shall be factory assembled, wired and tested as a unit prior to shipment. The power transfer switch shall include a motor rated combination isolating disconnect switch/circuit breaker, mechanically interlocked and operated with a single, externally mounted handle. When moving the handle from OFF to ON, the interlocking mechanism shall sequence the isolating disconnect switch closed first, and then the circuit breaker. When the handle is moved from ON to OFF, the interlocking mechanism shall sequence the circuit breaker open first, and then the isolating disconnect switch. The isolating disconnect switch/circuit breaker shall be mechanically interlocked so that the enclosure door cannot be opened with the handle in the ON position except by a hidden tool operated defeater mechanism. The isolating disconnect switch/circuit breaker shall be capable of being padlocked in the OFF position for installation and maintenance safety, and shall also be capable of being locked in the ON position without affecting the tripping characteristics of the circuit breaker. The enclosure door shall have a locking type handle and three point cam and roller type vault hardware. The circuit breaker trip curve adjustment shall be factory set, tested and sealed for the connected full load amps of the motor. The fire pump controller/power transfer switch shall have data logging capability for historical operation recording and to aid in annual test, service and trouble shooting. The data logging shall be accessible by front mounted interface panel and also by saving the information via the standard USB port. The data file shall be in text (.txt) format and easily readable by most common text editing or word processing software. The circuit breaker shall be capable of being field tested to verify actual pick up, locked rotor, and instantaneous trip points after field installation without disturbing incoming line and load conductors. The automatic transfer switch shall consist of an inherently double throw power transfer switch mechanism and a microprocessor control panel to provide automatic operation. The transfer switch and control panel shall be of the same manufacturer. The automatic transfer switch shall be an ASCO 7000 series with a group 5 control panel. The transfer switch shall be electrically operated and mechanically held. The electrical operator shall be a momentarily energized, single solenoid mechanism. The switch shall be mechanically interlocked to ensure only two possible positions, normal or emergency. Switches having a neutral position shall not be permitted. The switch shall be positively locked and unaffected by momentary outages, so that contact pressure is maintained at a constant value and contact temperature rise is minimized for maximum reliability and operating life. All main contacts shall be silver composition and inspection of all contacts shall be possible from the front of the switch without disassembly of operating linkages and without disconnection of power. Designs utilizing components of molded case circuit breakers, contactors, or parts thereof, which are not intended for continuous duty, repetitive switching or transfer between two active power sources are not acceptable. The transfer switch control panel shall have a 4 line, 20 character LCD display and keypad for viewing all available data and setting desired operational parameters. Voltage and frequency on both the normal and emergency sources shall be continuously monitored. The normal source pick up shall be set at 95% of nominal voltage and the emergency source pick up set at 90% of nominal voltage and 95% nominal frequency. Source status screens shall be provided for both normal & emergency to provide digital readout of voltage, frequency and phase rotation on all 3 phases. The transfer switch shall have visible pilot light indication for the following conditions: TRANSFER SWITCH IN NORMAL, TRANSFER SWITCH IN EMERGENCY, NORMAL SOURCE ACCEPTED, EMERGENCY SOURCE ACCEPTED and EMERGENCY ISOLATION SWITCH OPEN. Remote alarm contacts shall be supplied as standard for the following conditions: EMERGENCY SOURCE ISOLATION SWITCH OPEN, NORMAL POWER AVAILABLE, EMERGENCY POWER AVAILABLE and TRANSFER SWITCH POSITION. An audible alarm shall sound if: EMERGENCY ISOLATION SWITCH OPEN and TRANSFER SWITCH IN EMERGENCY. A SILENCE ALARM push-button shall be supplied . A selector switch shall be supplied to manually test the transfer to emergency and the retransfer to normal power. The transfer switch shall be a Firetrol FTA950 for normal utility power and second utility emergency power. Note: FTA900 and FTA950 power transfer switches are designed for use with Firetrol Electric Fire Pump Controllers, models FTA1000, FTA1250, FTA1300, FTA1350, FTA1500, FTA1800 and FTA1930. (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27518 USA SP900-20 (03-10-09) ©ASCO 2006 Sequence of Operation Wye-Delta Open Transition Fire Pump Controllers Introduction Reference to Wiring Schematic, Publication WS1300-50. Note: Firetrol schematics are drawn showing the equipment in a de-energized state Energizing The Controller 1. Close the Isolating switch/Circuit breaker by moving the handle to the “ON” position. Note: The unmarked, red, “Interlock” jumper wire, located between terminals #1 & #10 on the Relay PC board, (TB1), will prevent the MarkII unit from starting the electric motor automatically. This jumper wire should only be removed after the pressure settings have been input, and the system pressurized at, or above the Stop set point. 2. The factory programmed MarkII unit will begin initialization. Upon completion, the display will confirm the system pressure, the time, date, and “Interlock ON”, which is an alarm condition and will cause the yellow alarm LED to flash. Any other existing alarm conditions (low system pressure, phase reversal, phase failure, deluge open), will also be sequentially and continuously displayed at this time, until each is rectified. 3. With the “interlock” jumper still in place, the electric motor can only be started by depressing the START push-button, located on the flange of the controller enclosure, or by engaging the Emergency Run Mechanism. After all alarm conditions have been rectified, and the system pressurized at or above the Stop pressure setting, then the “interlock” jumper may be removed for the controller’s automatic operation (“standby”). With the “interlock” jumper removed, a drop in system pressure to the MarkII’s set start point, will start the electric motor. 4. The deluge valve contacts are only operational if the factory jumper has been removed and a normally closed deluge valve contact has been placed between terminals 1 and 8 of the Relay PC board, (TB1). The Remote Start is only operational if a normally open, momentarily closed contact is wired to terminals 6 and 7 of the Relay PC board, (TB1). If engaged, the Emergency Run Mechanism will cause the pump motor to run as described in the Emergency Starting and Stopping section. Automatic Start and Stop 1). The controller pressure transducer initiates the automatic start circuits for the pump motor. When pressure falls at or below the MarkII Start setting, relay 1CR is energized. 1CR normally open contact, closes • FTA1300 to the coils of 1M & 1S starters, allowing voltage to the line in the WYE connection. (See section Pump Motor Starting Sequence for more information). At the same time the MarkII initiates the internal transition time, factory set for 2 seconds. Once this expires, 6CR is energized. 6CR normally open contact closes to the coil of 2M starter, 1S coil is de-energized and mechanically locked out (open transition), allowing the motor to be reconnected in DELTA, applying full voltage to the windings. Note: Allow the motor to either run for 5 minutes, or allow 5 minutes between starts, for initial start component cool down period. The minimum run time is a part of the MarkII Menu, “Timer Settings”. The minimum run time factory setting is 10 minutes. In this mode, minimum run time begins when the pressure falls at or below the “Start” set point, calling for the pump motor to run. When pressure drops, this signals the MarkII to output via the Relay PC board, directly to the 1CR relay coil. The relays normally open contact closes, allowing line voltage to the coils of 1M & 1S contactors. The contactors’s 3 normally open contacts close, allowing voltage to the line in the WYE connection of the motor. After a 2 second delay, 6CR relay coil is energized. 6CR normally open contact closes, allowing line voltage to the coil of 2M contactor, and de-energizing 1S contactor (open transition). The 2M contactor’s 3 normally open contacts close, allowing reconnection in DELTA of the motor and the motor now runs at full speed. Simultaneously, the minimum run function of the MarkII is activated, maintaining voltage on the 1CR and 6CR relay coils, keeping the motor running until the 10 minutes expire. At this time, with pressure restored at or above the Stop set point, 1CR and 6CR coils will de-energize, re-opening the normally open contacts, de-energizing the 1M and 2M coils, causing the motor to stop. If pressure is restored at or above the Stop set point of the MarkII, and even if the minimum run time has not yet expired, the manual STOP push button, located on the flange of the controller can be depressed to manually stop the engine. This also resets the minimum run time function of the MarkII. Manual Start and Stop The pump motor may be manually started by using either the START push-button mounted on the flange of the enclosure or by using a normally open, momentarily closed, remote start push-button connected to terminals 6 and 7. When the START push-button is depressed, or a remote start signal is seen through terminals 6 & 7, the MarkII will output through the relay pc board to 1CR relay coil and the sequence of events described in section “Automatic Start & Stop” will begin. The MarkII minimum run time feature will not be activated. The pump motor will continue to run until the STOP push-button is depressed. When the STOP push-button is depressed, 1CR & 6CR relay coils are de-energized, interrupting the voltage to 1M & 2M coils, which causes the motor to stop. Deluge Valve Operation To operate the controller utilizing a deluge valve, the wire jumper between terminals 1 and 8 must be removed and a normally closed, open to run deluge valve contact wired in its place. When the deluge valve contact opens, relay 1CR coil is energized, and the sequence of events described in section “Automatic Start & Stop” will begin. The MarkII minimum run time feature is also activated. When the deluge valve contact closes, and minimum run time expires, relays 1CR & 6CR are de-energized, interrupting the voltage to 1M & 2M coils, which causes the motor to stop. Shutdown Interlock Operation The shutdown interlock, if used, is a normally open, closed to interlock contact wired to terminals 1 and 10. When the interlock contact is closed, relay 1CR cannot be energized by inputs to the MarkII from the pressure transducer, or the deluge valve. The controller may be started manually by depressing the START push button. See the specific starting operation for more details. The controller is equipped with an emergency run mechanism for use in the event of a coil burnout or other electrical problem which would prevent normal starting of the pump motor. The mechanism attempts to both electrically and mechanically start the pump motor. When the emergency run mechanism is utilized, the 1M & 2M coils are energized, closing the contacts leading to the motor windings. This, in effect, attempts to electrically start the pump motor in DELTA. The emergency run mechanism also manually closes the 1M and 2M contactors, starting the motor in DELTA. This will run the motor as long as the main three phase power is available. If the pump motor is running via the emergency run mechanism, DO NOT release the mechanism to stop the motor. Place the isolating switch/circuit breaker handle in the off position, then release the emergency run mechanism. Releasing the mechanism while the motor is running could result in damage to the motor or the motor contactors. Note: The emergency run mechanism is not intended for, nor should it be used as a testing device. Its sole purpose is to attempt to start the pump motor in the event of a failure. Pump Motor Starting Sequence Whenever relay 1CR, and sequentially, after transition time expires, 6CR coils are energized, line voltage is allowed to the coils of the motor starting contactors, 1M & 2M. During Part Winding starting the following sequence occurs. 1). 1CR contact closes, energizing contactors 1M & 1S. 1M & 1S connects motor to the line in the WYE connection. The motor draws approximately 33% of its normal inrush current and develops approximately 33% of its normal starting torque. 2). When the MarkII transition time expires (factory set at 2 seconds), 6CR relay is energized, allowing contactor 2M to energize, de-energizing and mechanically locking out 1S (open transition). The motor is automatically reconnected in DELTA, applying full voltage to the motor. Emergency Starting and Stopping XXXGJSFUSPMDPN 4BMFT0GGJDF$BSZ/$64" SQ1300-20 (04-17-07) $6&2 Sequence of Operation Automatic Power Transfer Switch Generator Set Emergency Source Introduction Reference to Wiring Schematic, Publication WS900-55. Note: Firetrol schematics are drawn showing the equipment in a de-energized state. Energizing the Controller 1. Close the isolating switch/circuit breaker handle on the main controller. Depending on the position of the transfer switch, the TRANSFER SWITCH IN NORMAL or the TRANSFER SWITCH IN EMERGENCY LED , located on the MarkII interface will illuminate. If the transfer switch is in the emergency position, and the normal source power is satisfactory, the transfer switch contactor will transfer to the normal source shortly after energizing the main controller. Since the transfer switch isolating switch is open, EMERGENCY ISOLATING SWITCH OFF led will be illuminated, and the ALARM led will be flashing. The audible alarm will sound indicating the isolating switch is open. Press the ALARM SILENCE keypad to acknowledge the alarm. 2. Close the isolating switch handle on the transfer switch controller, and the EMERGENCY ISOLATING SWITCH OFF led will extinguish. 3. With the controller energized, the normal conditions are TRANSFER SWITCH NORMAL led illuminated, and POWER AVAILABLE led illuminated. None of the control relays will be energized. 4. Under the cover of the transfer switch control panel (CP), relays NR and SE will energize. CAUTION: With the transfer switch isolating switch/circuit breaker in the off position, voltage is still present in the transfer switch compartment. Both the transfer switch and main controller must be turned off to completely deenergize this equipment. Transfer Switch Sequence - Normal to Emergency When one or more phases of the normal power source fail, or the normal source voltage drops below 85% of nominal (this range is adjustable from 70 - 85%), control panel relay SE de-energizes and control panel relay NR begins a timing cycle. The timing cycle is either 1 or 3 seconds, factory setting is 3 seconds. The time delay is to override momentary power outages or voltage dips. If power is restored to normal before the end of the timing cycle, the cycle is reset to zero and relay SE energizes. If normal power is not restored before the time delay expires, relay NR de-energizes. This signals the generator to start through a normally open contact to terminals 70 and 71 (normally open, closed to start generator) and a normally closed contact to terminals 62 and 63 (normally closed, open to start generator). The control panel starts to monitor the voltage and the frequency of the emergency source. When both reach acceptable pickup points (90% nominal voltage, 95% frequency), the control panel will accept the emergency source. When the emergency source is accepted, the control panel relay ER begins a timing cycle to delay transfer to the • FTA900 emergency source. The cycle is adjustable from 0 - 5 minutes, factory setting is 0. Relay ER energizes, normally open contacts on the relay close completing a circuit that supplies voltage from the emergency source to the transfer switch contactor coil TS. The coil is energized and the transfer switch contactor operates. All of the transfer switch contacts (main, control, and auxiliary) reverse position. Control contacts on the transfer switch contactor open, disconnecting the transfer switch contactor coil TS from the emergency source. The coil is now de-energized, inertia completes the physical movement of the transfer switch contactor to the full emergency position. The load is now connected to the emergency source. Transfer Switch Sequence - Emergency to Normal The sequence to retransfer the load to the normal source begins when the control panel senses the normal source voltage is restored (exceeds a selectable setting of 90% or 95%, factory setting is 90%). When the normal source is accepted, the control panel relay SE begins a timing cycle to delay the retransfer to normal. The cycle is adjustable between 1 second and 30 minutes, factory setting is 30 minutes. This delay is to assure the normal source has stabilized prior to reconnecting. If the normal source voltage drops below the dropout point before the time cycle ends, the cycle is reset to zero. At the end of the timing cycle, control panel relay SE energizes, normally open contacts on the relay close, completing a circuit that supplies voltage from the normal source to the transfer switch contactor coil TS. The transfer switch contactor operates, changing to the normal position. Control contacts on the transfer switch contactor open, disconnecting the transfer switch coil TS from the normal source. The coil is de-energized and inertia completes the physical movement of the transfer switch to the full normal position. The load is reconnected to the normal source. If the emergency source should fail and the normal source has been satisfactorily restored, the load is immediately reconnected to the normal source, bypassing the 30 minute time cycle. Once the retransfer sequence is completed, control panel relay NR begins a 5 minute timing cycle. This allows the engine and generator to run in an unloaded, cool down state. When the time cycle is complete, relay NR deenergizes, signaling the generator to stop. Load Disconnect Feature The load disconnect feature is used to isolate the pump motor during the transfer process. When the motor is disconnected during a pump running condition, the motor is “free spinning” making it, in effect, a generator. To avoid connecting it to a power source in this state, the circuit to the motor contactor coil(s) in the fire pump controller is interrupted for 3 seconds before the transfer switch operates. The motor will slow to an acceptable speed, or stop completely prior to reconnecting to the power source. Load Disconnect - Sequence of Operation When the control panel accepts the source of power to be transferred to, control panel relay OP will energize. A normally open contact of relay OP closes and the MarkII will de-energize relay 1CR in the fire pump controller, (if voltage for the control circuit is available). With relay 1CR deenergized, the circuit to the motor contactor coil(s) is interrupted and the motor will slow. After a 3 second delay, the control panel will initiate a transfer sequence. When the transfer sequence is completed, relay OP de-energizes signaling the MarkII to re-energize relay 1CR , if necessary, to start the pump motor. If the fire pump starting causes have been satisfied prior to the transfer sequence, the momentary interruption of power will reset the controller to a standby state and the motor will not restart. Limit Switches Firetrol brand fire pump controllers utilize auxiliary limit switch contacts in the disconnecting means of the fire pump controller and the transfer switch controller. The limit switches inhibit the transfer switch operation when the disconnects are opened to perform maintenance to either controller. Additionally, a limit switch is used to indicate the position of the emergency source isolating switch. Auxiliary limit switch AUX1 closes when the emergency source isolating switch is opened. It will signal the MarkII to illuminate the EMERGENCY ISOLATING SWITCH OFF LED, the ALARM LED, and energizes the audible alarm circuit. A set of alarm contacts from 21CR relay are provided for remote monitoring of the isolating switch position. Terminals 66 and 67 provide a normally closed, open to alarm contact, terminals 68 and 69 provide a normally open, close to alarm contact. Auxiliary limit switch AUX2 inhibits the generator from starting if the emergency isolating switch is opened. The AUX2 contact on generator control terminals 62 and 63 closes when the isolating switch is opened. This inhibits the circuit from opening to start the generator. The AUX2 contact, to generator control terminal 70, opens when the isolating switch is opened. This inhibits the circuit from closing to start the generator. Auxiliary limit switch AUX3 is located in the disconnecting means of the fire pump controller. The switch contact opens when the disconnecting means is placed in the off position or trips open due to a motor overload. When the switch contact is opened, the load is inhibited from transferring to the emergency source. Standard Alarms and Indicators The MarkII provides 3 standard LEDs for transfer switch equipped controllers. An audible alarm is located on the flange of the controller, and an Alarm Silence keypad. The green LED for TRANSFER SWITCH NORMAL will illuminate when the transfer switch is in the normal position, and the power source is from the main controller utility service. The TRANSFER SWITCH EMERGENCY LED illuminates, when the transfer switch is in the emergency position, and the power source is from the emergency generator. At the same time, the MarkII energizes the audible alarm circuit. An explanation of the EMERGENCY ISOLATING SWITCH OFF LED is covered in the Limit Switch section. When relay 21CR is energized, indicating the Emergency Isolating Switch is open, or if the transfer switch is in the emergency position, the audible alarm sounds. The alarm will sound until either the ALARM SILENCE keypad is pressed, the Emergency Isolating switch is closed, or the transfer switch reconnects to normal utility power. Test Switch A spring return, two position selector switch is provided for test of the transfer switch. The switch is located on the flange of the transfer switch compartment. The test simulates a power failure and will transfer the load to the emergency source. Rotate the NORMAL-TEST switch to the right (Test) position. It will be necessary to hold the switch in this position until the generator starts and provides acceptable power for the transfer switch contactor to operate to the emergency position. This should take no longer than 15 seconds. Failure to transfer indicates a serious condition requiring immediate investigation. Retransfer to Normal Timed/Immediate Located beneath the NORMAL-TEST switch on the flange of the transfer switch compartment is a second spring return, two position selector switch. The switch is used to override the retransfer to normal time delay cycle. The switch is normally in the Timed position. To initiate an immediate retransfer to the normal power source, rotate the TIMED-IMMEDIATE selector switch to the IMMEDIATE position. If the normal power source is acceptable, the transfer switch contactor will transfer back to the normal source. Phase Reversal The MarkII monitors the condition of the normal source power at the line side of the contactor. If the MarkII detects a phase reversal, a normally closed output contact opens initiating a generator test start. Once the emergency source power is acceptable, the transfer switch contactor will change to the emergency source. After the retransfer to normal time delay period (30 minutes) expires, and if the normal source phase reversal is corrected, the transfer switch contactor will retransfer to the normal source. Remote Position Indication To supervise the position of the transfer switch at a remote location, a set of alarm contacts are provided. Terminals 81 and 82 provide an open in normal, closed in emergency contact. Terminals 83 and 84 provide a closed in normal, open in emergency contact. XXXGJSFUSPMDPN 4BMFT0GGJDF$BSZ/$64" SQ900-20 (04-17-07) $6&2