9 July 2011 Lighting and the 2010 Building Regulations This document is designed to inform lighting professionals of the implications and requirements in Part L of the Building Regulations (for England and Wales), Part J (Scotland) and Part F (Northern Ireland). The UK Government, central and devolved, publishes the full Building Regulations which are legal requirements in all parts of the UK and apply for new and refurbished buildings. Actual compliance is often measured against the latest approved documents which came into force on 1st October 2010.These approved documents take many forms and are seen as minimal acceptable practice levels. Other methods of proving compliance are acceptable provided they can be proved. The Society of Light and Lighting believes that whilst the Building Regulations provide statutory minimum performance for lighting efficiency they do not harness the maximum possible energy reduction by the use of mandatory lighting controls. By far the best method for proving compliance for the conservation of fuel and power would be to use the internationally recognised standard Energy Performance in Buildings EN15193, which details a measure called Lighting Energy Numeric Indicator, or LENI. This standard provides calculation methods to prove compliance to the Energy Performance of Buildings Directive, a legal requirement in Europe, enacted by the building regulations United Kingdom. The methods described in EN 15193 would satisfy the building regulations, maximise savings from lighting controls, and include daylight and good overall lighting design. There are a number of documents required to check overall compliance but for lighting in each country are in fact only very few. For England and Wales; Approved Document L1A – Conservation of fuel and power in New Dwellings Approved Document L1B – Conservation of fuel and power in Existing Dwellings Approved Document L2A – Conservation of fuel and power in New Buildings other than Dwellings Approved Document L2B – Conservation of fuel and power in Existing Buildings other than Dwellings. The lighting requirements can be found in the sections indicated and the requirements are limited to fixed internal or external lighting but not including emergency escape lighting or specialist process and temporary lighting. The lighting requirements appear in the Compliance documents which have the same legal standing as the Regulations. There are two Compliance Documents: Domestic Buildings Services Compliance Guide: 2010 Edition Non-Domestic Buildings Services Compliance Guide: 2010 Edition For Scotland; Domestic Technical Handbook 2010 Non-domestic Technical Handbook 2010 For Northern Ireland; Department of Finance and Personnel Technical Booklet F1: 2006 (domestic) Department of Finance and Personnel Technical Booklet F2: 2006 (non-domestic) As the requirements in Northern Ireland have not changed in 2010 they are not covered here. New or Refurbished (Existing) Buildings In most cases now new build and refurbishments have to conform to the same requirements for lighting and lighting controls Daylighting The Building Regulations relate adequate daylight levels in domestic premises to limiting solar gain in section 4.27 of approved document L1A. The Building Regulations do not specify minimum daylight requirements; however, reducing window area produces conflicting impacts on predicted CO2 emissions: reduced solar gain but increasing use of electric lighting. As a general guide, if the area of glazing is much less than 20% of the total floor area, some parts of the dwelling may experience poor levels of daylight, resulting in increased use of electric lighting. Within section 4.44 of Approved Document L2A there is a recommendation for limiting solar gain to the building fabric and that this is demonstrated for each space in the building that is either occupied or mechanically cooled. The solar gain through the glazing is aggregated over the period from April to September inclusive and should be no greater than Lighting and the 2010 Building Regulations (cont.) what could occur through one of the following reference glazing systems with a defined total solar energy transmittance (g–value) calculated according to BS EN 410. a) For every space that is defined in the NCM database as being side lit, the reference case is an east facing facade with full width glazing to a height of 1.0m having a framing factor of 10% and the normal solar energy transmittance (g– value) of 0.68. b) for every space that is defined in the NCM database as top lit, and whose average zone height is not greater than 6 m, the reference case is a horizontal roof of the same total area that is 10% glazed as viewed from the inside out and having rooflights that have a framing factor of 25% and a normal solar energy transmittance (g-value) of 0.68. c) for every space that is defined in the NCM database as being top lit and his average zone height is greater than 6 m, the reference case is a horizontal roof of the same total area that is 20% glazed as viewed from the inside out and having rooflights that have a framing factor of 16% and normal solar energy transmittance (gvalue) of 0.46. Whilst the implications of these recommendations are ambiguous, it would seem to suggest that daylight be restricted in order to control solar gain. Lighting Fixed internal lighting Fixed external lighting Lighting designers should work closely with thermal engineers to ensure that the benefits of daylight are maximised for the users within the space and not sacrificed simply for energy efficiency. Commissioning The building regulations require that a notice be given that commissioning has been carried out according to a procedure approved by the Secretary of State. This notice should include a declaration confirming that a commissioning plan has been followed so that every system has been inspected and commissioned in an appropriate sequence and to a reasonable standard, and the results of tests confirm that the performance is reasonably in accordance with the actual building design. Such declarations should be signed by a person suitably trained, qualified and having relevant experience such as a member of the Lighting Industry Commissioning Scheme. Lighting in new and existing Domestic buildings Fixed internal and external lighting should meet the minimum standards for efficacy and controls in table 40 of the domestic building compliance guide. Table 40: recommended minimum standards for fixed internal and external lighting New and replacement systems a) In the areas affected by the building work, provide low energy light fittings (fixed lights or lighting units) that number not less than three per four of all the light fittings in the main dwelling spaces of those areas (excluding infrequently accessed spaces used for storage, such as cupboards and wardrobes). b) Low energy light fittings should have lamps with the luminous efficacy greater than 45 lamp lumens per circuit watt and total output greater than 400 lamp lumens. c) Light fitting whose supplied power is less than five circuit watts are excluded from the overall count of the total number of light fittings. Where fixed external lighting is installed, provide light fittings with the following characteristics: a) either: i. the lamp capacity not greater than 100 lamp watts per light fitting; and ii. all lamps automatically controlled so as to switch off after the area lit by the fitting becomes unoccupied; and iii. all lamps automatically controlled so as to switch off when daylight is sufficient b) Or i. lamp efficacy greater than 45 lumen per circuit watt; and ii. all lamps automatically controlled so as to switch off when daylight is sufficient; and iii. light fittings controllable manually by occupants. Supplementary information Light fittings may be either: - dedicated fittings which will have separate control gear and will take only low energy lamps (e.g. pin-based fluorescent or compact fluorescent lamps); or - standard fittings supplied with low energy lamps with integrated control gear (e.g. bayonet or Edison screw base compact fluorescent lamps). Light fittings with GLS tungsten filament lamps or tungsten halogen lamps would not meet the standard. The energy saving trust publication GI 020, “Low energy domestic lighting", gives guidance on identifying suitable locations for fixed energy efficient lighting. Lighting and the 2010 Building Regulations (cont.) Whilst the above targets do not in themselves remove technologies such as tungsten filament lamps, provided such lamps could be made to exceed the requirements, the building regulations do stipulate that lamps such as tungsten halogen or tungsten halogen reflector lamps, would not be considered as complying with the above targets. In addition, in the Scottish 2010 Domestic Technical Handbook (DTH) lighting to common areas of domestic buildings should follow the guidance for dwellings with the following exception: - all fixed light fittings and lamps provided to corridors, stairs and other circulation areas should be low energy type, controls to such lighting to enable safe use of the areas in question are identified in DTH Section 4.6. - the dwelling should have an electric lighting system providing at least one lighting point to every circulation space, kitchen, bathroom, toilet and other space having floor area of 2m² or more. - any lighting point serving a stair should have the controlling switch at, or in immediate vicinity of, the stair landing on each story. - DTH Sections 4.6.2 recommends that common areas should have artificial lighting capable of providing a uniform lighting level, at floor level, of not less than 100 lx on stair flights and landings and 50 lx elsewhere within circulation areas. Lighting should not present sources of glare and should avoid creation of areas of strong shadow that may cause confusion or miss-step. A means of automatic control should be provided to ensure that lighting is operable during the hours of darkness. In respect of domestic lighting, fixed light fittings include only the main light sources in the room and not display feature lighting such as picture lights, kitchen wall cupboard lights, or over mirror. A light fitting may contain one or more lamps and a group of lamps operated by the same switch could be counted as one fitting, e.g. a pair of wall lights; low energy light fittings should include the provision of lamps/bulbs. Lighting in new and existing Non-Domestic buildings A) General and Display lighting in new and existing non-domestic buildings should meet the minimum standards for efficacy (averaged over the whole area of the applicable of space in the building) in Table 44 of the non-domestic compliance guide below. Process and emergency lighting are not subject to these targets. Table 44: Recommended minimum lighting efficacy Lighting Minimum lighting efficacy, % General lighting in office, industrial and storage areas The average initial efficacy should be not less than 55 luminaire lumens per circuitwatt. In calculating the average luminaire lumens per circuitwatt, the circuit-watts for each luminaire may first be multiplied by the control factors in Table 45. Note: The value entered in the NCM tools for calculating the C02 emission rate for new buildings (BER) should be the value before the control factor is applied, since NCM tools already take account of additional controls by reducing the BER. The average initial efficacy should be not less than 55 lamp lumens per circuit-watt. The average initial efficacy should be not less than 22 lamp lumens per circuit-watt. General lighting in other types of space Display lighting in new and existing buildings Table 45: Luminaire control factors limiting new Light output control Control factor A. the luminaire is in a daylit space and its light output is controlled by photoelectric switching or dimming control, with or without override. B. the luminaire is in a space that is likely to be unoccupied for a significant number of operating hours, and where a sensor switches off the lighting in the absence of occupants but switching on is done manually except where this would be unsafe. C. circumstances a. and b. combined. D. none of the above. 0.9 and existing buildings 0.9 0.85 1.0 Lighting and the 2010 Building Regulations (cont.) Where designers are using the SBEM software tools to calculate the BER for a building they should note that the control factor is accounted for within the software, and should not be applied to luminaire efficacy in this case. B) Metering of lighting for new and existing buildings (to record the lighting energy consumption) should meet the minimum standards in Table 46. Table 46: recommended minimum standards for metering of general and display lighting in new and existing buildings Standard Metering for general more display lighting A) kWh meters on dedicated lighting circuits in the electrical distribution; or B) local power meter coupled to or integrated in the lighting controls of a lighting or building management system; or C) lighting management system that can calculate the consumed energy and make this information available to a building management system or in an exportable file format. (This could involve logging the hours run and the dimming level, and relating this to the installed load.) C) Lighting controls in new and existing buildings should meet the minimum standards in Table 47 of the non-domestic compliance guide, or follow the guidance in BRE Digest 498 Selecting lighting controls. Display lighting, where provided, should be controlled on dedicated circuits that can be switched off at times when people will not be inspecting exhibits or merchandise or being entertained. Table 47: Recommended controls for general and display lighting in new and existing buildings *note description of Local manual switching given Space classification (see key terms) Control type Owned Manual switch by the door Shared Flexible manual switching, e.g. local pull cords or wireless transmitter Local manual switching* Temporarily owned Occasionally visited Unowned Local manual switching* Managed Time switching; or centralised manual in “key terms”. Time switching Lighting and the 2010 Building Regulations (cont.) Lamp/Gear and Luminaire performance to meet the targets in new and existing Non-Domestic buildings The table below offers generic lamp information Type of Space Nominal Lamp Watts Lamp Type and shows what Light Output Ratio a luminaire would need to achieve with and without the various controls options to comply with the current nondomestic targets. For Office, Industrial & Storage Spaces Typical lamp Lumens Typical Total Circuit Watts Required LOR with No controls to achieve 55LL/ cW Required LOR with Daylight OR Presence controls to achieve 55LL/ cW Required LOR with Presence AND Daylight controls to achieve 55LL/ cW 900 1800 1200 1250 2400 2500 1800 3600 2050 2200 4400 2900 5800 2850 3500 7000 3200 6400 4800 9600 1200 2400 3600 4800 1350 2700 4050 5400 1900 3800 1750 3500 5250 7000 2600 5200 3300 6600 3350 6700 10050 3100 6200 4300 8600 4450 8900 5200 10400 6550 13100 6450 12900 15 28 19.5 18.5 37.5 36 26.5 51 28.7 34.5 68 33.8 72.8 39.7 44.1 89.6 46 89 61.1 121.1 16 31 47.1 62.3 18.2 36 52.4 70.1 22.5 45.5 25.7 48.8 76 99 30.5 61 38.5 76.5 35 69.8 106.5 40.4 83.4 52.5 107 57.5 114.5 54 106.8 65.6 136.8 85.8 166.6 91.7 85.6 89.4 81.4 85.9 79.2 81.0 77.9 77.0 86.3 85.0 64.1 69.0 76.6 69.3 70.4 79.1 76.5 70.0 69.4 73.3 71.0 72.0 71.4 74.1 73.3 71.2 71.4 65.1 65.9 80.8 76.7 79.6 77.8 64.5 64.5 64.2 63.8 57.5 57.3 58.3 71.7 74.0 67.2 68.4 71.1 70.8 57.1 56.5 55.1 57.4 73.2 71.0 82.5 77.0 80.4 73.3 77.3 71.3 72.9 70.1 69.3 77.6 76.5 57.7 62.1 69.0 62.4 63.4 71.2 68.8 63.0 62.4 66.0 63.9 64.8 64.2 66.7 66.0 64.0 64.3 58.6 59.3 72.7 69.0 71.7 70.0 58.1 58.1 57.8 57.4 51.7 51.6 52.5 64.5 66.6 60.4 61.6 64.0 63.7 51.4 50.8 49.6 51.7 65.8 63.9 77.9 72.7 76.0 69.2 73.0 67.3 68.8 66.2 65.5 73.3 72.3 54.5 58.7 65.1 58.9 59.8 67.2 65.0 59.5 59.0 62.3 60.4 61.2 60.7 63.0 62.3 60.5 60.7 55.4 56.0 68.7 65.2 67.7 66.1 54.8 54.8 54.5 54.2 48.8 48.7 49.5 60.9 62.9 57.1 58.2 60.4 60.1 48.5 48.0 46.8 48.8 62.2 60.4 For Other Spaces Typical Lamp Lumens / Circuit Watt 1 x 13 2 x 13 1 x 18 1 x 18 2 x 18 2 x 18 1 x 26 2 x 26 1 x 28 1 x 32 2 x 32 1 x 36 2 x 36 1 x 38 1 x 40 2 x 40 1 x 42 2 x 42 1 x 55 2 x 55 1 x 14 2 x 14 3 x 14 4 x 14 1 x 18 2 x 18 3 x 18 4 x 18 1 x 21 2 x 21 1 x 24 2 x 24 3 x 24 4 x 24 1 x 28 2 x 28 1 x 35 2 x 35 1 x 36 2 x 36 3 x 36 1 x 39 2 x 39 1 x 49 2 x 49 1 x 54 2 x 54 1 x 58 2 x 58 1 x 70 2 x 70 1 x 80 2 x 80 TC-D TC-D TC-D/T TCL TC-D/T TCL TC-D/T TC-D/T 2D TC-T TC-T TC-L TC-L 2D TC-L TC-L TC-T TC-T TC-L TC-L T5 (HE) T5 (HE) T5 (HE) T5 (HE) T8 T8 T8 T8 T5 (HE) T5 (HE) T5 (HO) T5 (HO) T5 (HO) T5 (HO) T5 (HE) T5 (HE) T5 (HE) T5 (HE) T8 T8 T8 T5 (HO) T5 (HO) T5 (HO) T5 (HO) T5 (HO) T5 (HO) T8 T8 T8 T8 T5 (HO) T5 (HO) 60 64 62 68 64 69 68 71 71 64 65 86 80 72 79 78 70 72 79 79 75 77 76 77 74 75 77 77 84 84 68 72 69 71 85 85 86 86 96 96 94 77 74 82 80 77 78 96 97 100 96 75 77 LED Display Lighting Please check the luminaire manufacturers published data for the LED measured in the luminaire For the vast majority of display light sources the manufacturer publishes Intensity values rather than lumen out puts, please refer to the lamp supplier for efficacy figures Lighting and the 2010 Building Regulations (cont.) Key terms space becomes unoccupied. Office area means a space that involves predominantly desk-based tasks, e.g. Open Plan or individual offices, classrooms, seminar or conference rooms. Absence detection means a type of control which switches the lighting off, or dims it down, after the space becomes unoccupied, but where switching on is done manually. Daylit space means any space: A) within six metres of a window wall, provided that the glazing area is at least 20% of the internal area of the window wall; or B) Below roof lights provided that the glazing area is at least 10% of the floor area. The normal light transmittance of the glazing should be at least 70%; if the light transmittance is below 70%, glazing area should be increased proportionately for space to be defined as daylit. Space classification for control purposes: (these definitions are given in more detail in BRE information paper IP6/96 People and lighting controls and BRE digest 498 Selecting lighting controls. Owned space means a space such a small room for one or two people who control the lighting, e.g. cellular office or consulting room. Shared space means a multi-occupied area, e.g. Open Plan office or factory production area. Temporarily owned space means a space where people are expected to operate the lighting controls while they are there, e.g. hotel room or meeting room. Occasionally visited space means a space where people generally stay for a relatively short period of time when they visit the space, e.g. a storeroom or toilet. Un-owned space means a space where individual users require lighting but are not expected to operate the lighting controls, e.g. a corridor or atrium. Managed space means a space where lighting is under the control of a responsible person, e.g. a hotel lounge, restaurant or shop. Local manual switching means, in local or flexible manual switching, the distance on plan from any local switch to the luminaire it controls should generally be not more than six metres, or twice the height of the light fitting above the floor if this is greater. Where the space is a daylit space served by side windows, the perimeter row of lighting should in general be separately switched. Photoelectric control means a type of control which switches or dims lighting in response to the amount of incoming daylight. Presence detection means a type of control which switches the lighting on when someone enters a space, and switches that off, or dims it down, after the Lamp lumens means the sum of the average initial (100 hour) lumen output of all the lamps in the luminaire. Circuit-watt means the power consumed in lighting circuits by lamps and, where applicable, their associated control gear (including transformers and drivers) and power factor correction equipment. Lamp lumens per circuit-watt means the total lamp lumens summed for all luminaires in the relevant areas of the building, divided by the total circuit-watts for all the luminaires. LOR means the light output ratio of the luminaire, which means the ratio of the total light output of the luminaire under stated practical conditions to that of the lamp or lamps contained in the luminaire under reference conditions. Luminaire lumens per circuit-watt means the (lamp lumens x LOR) summed for all luminaires in the relevant areas of the building, divided by the total circuitwatts for all the luminaires. Light fitting means a fixed light or lighting unit that can comprise one or more lamps and lampholders, control gear and an appropriate housing. The control gear may be integrated in the lamp or located elsewhere in one year fixed flight. Fixed external lighting means lighting fixed to an external surface of the dwelling supplied from the occupier’s electric system. It excludes lighting in common areas of blocks of flats in other communal access ways. Fixed building services means any part of, or any controls associated with fixed internal or external lighting systems but does not include emergency escape lighting or specialist process lighting Specialist process lighting means lighting intended to illuminate specialist tasks within a space, rather than the space itself. It could include theatre spotlights, projection equipment, production lighting in TV and photographic studios, medical lighting in operating theatres and doctors’ and dentists’ surgeries, illuminated signs, coloured or stroboscopic lighting, and art objects with integral lighting such as sculptures, decorative fountains and chandeliers. © Society of Light & Lighting 2011. 222 Balham High Road Balham SW12 9BS