213B Legacyt Line Heat Pump with Puronr Refrigerant 1 1/2 To 5 Nominal Tons Wiring Diagrams CONNECTION DIAGRAM *CHS BLK or RED BLK *CH BLK CONT RED or BLK L1 208/230 1Ø POWER SUPPLY L1 L2 BLU BLK 11 21 23 23 BLK COMP BLU S H C C R YEL CAP BLU BRN YEL *SC BRN 5 *SR EQUIP GND * CHS YEL RED RED RVS *HPS BLU/PNK Y DR OF1 OF2 O R SPEED UP C Y O W2 R E L W3 G C Y O W2 R E L -LEGENDFACTORY POWER WIRING FIELD POWER WIRING FACTORY CONTROL WIRING FIELD CONTROL WIRING CONDUCTOR ON CIRCUIT BOARD COMPONENT CONNECTION 1/4-INCH QUICK CONNECT TERMINALS FIELD SPLICE CAP JUNCTION CAPACITOR (DUAL RUN) *CH CRANKCASE HEATER *CHS CRANKCASE HEATER SWITCH COMP COMPRESSOR CONT CONTACTOR CB CIRCUIT BOARD DFT DEFROST THERMOSTAT C RVS ORN SPEED UP PNK PNK DFT INDOOR UNIT TERMINAL BLOCK G INDOOR THERMOSTAT (NOTE #5) NOTES: 1. Compressor and fan motor furnished with inherent thermal protection. 2. To be wired in accordance with national electric code (N.E.C.) And local codes. 3. N.E.C. Class 2, 24 V circuit, min. 40 va required, 60va on units installed with LLS. 4. Use copper conductors only from disconnect to unit. 5. Must use thermostat and sub-base as stated in pre-sale literature. 6. If indoor section has a transformer with a grounded secondary, connect the grounded side to "C" on the circuit board. 7. If any of the original wire, as supplied, must be replaced, use the same or equivalent wire. 8. Check all electrical connections inside control box for tightness. 9. Do not attempt to operate unit until service valves have been opened. 10. Use conductors suitable for at least 75ºC (167ºF). CAUTION CIRCUITRY CONT C *HPS *DTS 90 60 FIELD SELECTED TIME PERIOD 30 BETWEEN DEFROST CYCLES (MINUTES) JUMPERED TEST PINS (USE METAL OBJECT), FIELD SPEED-UP CYCLE HEAT CYCLE: 90 MIN. ACCELERATED TO 21 SEC. 60 MIN. ACCELERATED TO 14 SEC. 30 MIN. ACCELERATED TO 7 SEC. DEFROST CYCLE: 10 MIN. ACCELERATED TO 2 SEC. CONDENSING UNIT CHARGING INSTRUCTIONS For use with units using R-410A refrigerant HK32EA001 1. Compressor damage may occur if system is over charged. 2. This unit is factory charged with R-410A in DISCHARGE TEMP. SWITCH *DTS accordance with the amount shown on the rating HIGH PRESSURE SWITCH *HPS plate. The charge is adequate for most systems using matched coils and tubing not over 15 feet long. LIQUID LINE SOLENOID VALVE *LLS Check refrigerant charge for maximum efficiency. LOW PRESSURE SWITCH *LPS See Product Data Literature for required Indoor air OUTDOOR FAN MOTOR OFM Flow Rates and for use of line lengths over 15 feet. REVERSING VALVE SOLENOID RVS 3. Relieve pressure and recover all refrigerant before system repair or final disposal. Use all service ports START CAPACITOR *SC and open all flow-control devices, including solenoid START RELAY *SR valves. START THERMISTOR *ST 4. Never vent refrigerant to atmosphere. * MAY BE FACTORY OR FIELD INSTALLED Use approved recovery equipment. DEFROST RELAY AND *LPS ORN DFT C Y O W2 R T1 BRN/YEL C LOGIC DR YEL/BLU C DFT LOGIC Y Y T1 YEL WHT BLK ORN RED DFT R R CB CAP C W2 BLU/PNK YEL/PNK 30 60 90 W1 CONT 23 23 C F OF2 *ST +t° O O *DTS YEL/PNK OF1 YEL/BLU BRN/YEL *LPS OFM DR * CH BLK H L2 R S *SC 1 *SR BLK DR C 5 2 2 1 OFM EQUIP GND COMP CONT 11 21 *ST F YEL +t° YEL SCHEMATIC DIAGRAM (LADDER FORM) TABLE I - SUPERHEAT CHARGING TABLE (SUPERHEAT ºF AT LOW-SIDE SERVICE PORT) EVAPORATOR ENTERING AIR º F WB. OUTDOOR TEMP ºF 50 52 54 56 58 60 62 64 67 68 70 72 74 76 55 60 65 70 75 82 85 90 95 100 105 110 115 11 11 12 12 12 13 17 20 24 6 6 7 7 7 7 12 16 21 - - - - - - - - - - 3 7 12 18 - - - - - - - - - - - - - - 7 14 - - - - - - - - - - - - - - 3 11 -- -- -- -- -- -- -- -- *6 -- -- -- -- -- -- -- -- 4 24 22 19 16 13 8 7 -- -- -- -- -- -- -- -- -- 4 25 23 21 20 18 15 14 12 10 8 6 -- -- -- -- -- -- -- -- -- -- -- 5 -- -- -- -- -- -- -- -- -- -- -- 3 25 23 21 18 16 12 11 8 -- -- -- -- -- -- -- -- -- -- 6 -- -- -- -- -- -- -- -- -- -- 4 -- -- -- -- -- -- -- -- -- -- 3 25 23 22 20 18 16 15 14 12 11 9 7 6 25 23 22 20 19 17 16 15 14 12 11 10 8 Where a dash (- -) appears do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be weighed in. Note: Superheat ºF is at low-side service port, allow a tolerance of +/- 3 ºF Note: Indoor dry bulb between 70 ºF and 80 ºF * Optimum performance point, 82 ºF outdoor ambient and (80 ºF dry bulb), (67 ºF wet bulb) indoor conditions. (DOE B Test Conditions) TABLE II - REQUIRED SUCTION TUBE TEMPERATURE ºF (MEASURED AT LOW-SIDE SERVICE PORT) SUPERHEAT SUCTION PRESSURE AT SERVICE PORT PSIG. TEMP. ºF 108 112 117 121 126 131 139 141 146 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 43 45 45 47 47 49 49 51 51 53 53 55 55 57 57 59 59 61 61 63 63 65 65 67 67 69 69 71 71 73 73 75 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 Fig. 1 – Wiring Diagram — Model sizes 1--1/2 -- 5 tons, 208/230--1 COOLING ONLY CHARGING PROCEDURE 1. Operate unit a minimum of 10 minutes before checking charge. 2. Measure suction pressure by attaching an accurate gage to suction valve service port. 3. Measure suction temperature by attaching an accurate thermistor type or electronic thermometer to the suction line at service valve. 4. Measure outdoor air dry-bulb temperature with a thermometer. 5. Measure indoor air (entering indoor coil) wet-bulb temperature with a sling psychrometer. 6. Refer to Table I. Find outdoor temperature and evaporator entering air wet-bulb temperature. At this intersection, note superheat. Where a dash (- -) appears on table do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be weighed in, adding or removing 0.6 oz/ft of 3/8 liquid line above or below 15 ft. respectively. 7. Refer to Table II. Find superheat temperature located in step 6 and suction pressure. At this intersection note suction line temperature. 8. If unit has a higher suction line temperature than charted temperature, add refrigerant until charted temperature is reached. 9. If unit has a lower suction line temperature than charted temperature, remove and recover refrigerant until charted temperature is reached. 10. When adding refrigerant, charge in liquid form into the suction service port using a flow-restricting device. 11. If outdoor air temperature or pressure at suction valve changes, charge to new suction line temperature indicated on chart. 12. This procedure is valid when indoor air flow is within +/- 21% of its rated cfm. 336749-101 REV. A 336749-101 REV. A L2 208/230 3Ø POWER SUPPLY CONNECTION DIAGRAM BLU BLU L1 ALERT! (NOTE #11) L3 YEL BLK or RED PRM *CH COMP EQUIP GND OFM BLK BLK YEL T3 YEL BLK OF1 *CHS YEL/BLU BRN/YEL DR CAP PRM CONT 24V COM C RVS O O DFT W2 BLU/PNK DFT LOGIC R R BLU/PNK DR Y Y BLK OF2 *CH YEL/BLU *HPS *LPS YEL/PNK CONT 13 23 OFM BRN/YEL L1 L3 L2 CONT 24V COM T2 T1 CONT 11 21 BRN BLK or RED YEL/PNK L3 L2 L1 CAP YEL EQUIP GND * CHS L2 PRM T3 23 13 T2 T1 BLK 21 11 L3 SCHEMATIC DIAGRAM (LADDER FORM) L1 COMP CONT DR T1 Y OF1 T1 BLK C OF2 SPEED UP O C Y O W2 R 60 90 120 30 CB BLK YEL WHT ORN RED PNK R R C Y O W2 R E L W3 G C Y O W2 R E L -LEGEND- ORN G INDOOR UNIT TERMINAL BLOCK INDOOR THERMOSTAT (NOTE #5) RVS ORN or BLK ORN or BLK PNK BLK or PNK DFT BLK or PNK NOTE PRM LED INDICATOR OFF: NO 24VAC ON: OK FLASH: PHASE PROBLEM NOTES: 1. Compressor and fan motor furnished with inherent thermal protection. 2. To be wired in accordance with National Electric Code (N.E.C.) and local codes. 3. N.E.C. class 2, 24V circuit, min. 40 VA required. 4. Use copper conductors only, from disconnect to unit. 5. Must use thermostat and sub-base as stated in pre-sale literature. 6. If indoor section has a transformer with a grounded secondary, connect the grounded side to "C" on the circuit board. 7. If any of the original wire, as supplied, must be replaced, use the same or equivalent wire. 8. Check all electrical connections inside control box for tightness. 9. Do not attempt to operate unit until service valves have been opened. 10. It is imperative to connect 3Ø field power to unit with correct phasing. The Phase Rotation Monitor will not allow the contactor to be energized if the phasing is not correct. If phasing is reversed, simply interchange any two of the three power connections on the field side. 11. Use conductors suitable for at least 75ºC (167ºF). C *HPS *LPS 90 FIELD SELECTED TIME PERIOD 60 BETWEEN DEFROST CYCLES (MINUTES) 30 SPEED JUMPERED TEST PINS (USE METAL OBJECT), FIELD SPEED-UP CYCLE UP HEAT CYCLE: 90 MIN. ACCELERATED TO 21 SEC. 60 MIN. ACCELERATED TO 14 SEC. 30 MIN. ACCELERATED TO 7 SEC. DEFROST CYCLE: 10 MIN. ACCELERATED TO 2 SEC. ORN DFT HK32EA001 C BRN/YEL C LOGIC CONT YEL/BLU CONDENSING UNIT CHARGING INSTRUCTIONS For use with units using R-410A refrigerant TABLE I - SUPERHEAT CHARGING TABLE (SUPERHEAT ºF AT LOW-SIDE SERVICE PORT) COOLING ONLY CHARGING PROCEDURE EVAPORATOR ENTERING AIR º F WB. OUTDOOR TEMP ºF 50 52 54 56 58 60 62 64 67 68 70 72 74 76 1. Operate unit a minimum of 10 minutes before checking charge. 25 2. Measure suction pressure by attaching an accurate gage to suction valve service port. 23 3. Measure suction temperature by attaching 22 65 an accurate thermistor type or electronic 20 70 thermometer to the suction line at service valve. 19 4. Measure outdoor air dry-bulb temperature 75 with a thermometer. 82 17 85 16 5. Measure indoor air (entering indoor coil) wet-bulb temperature with a sling psychrometer. 90 15 6. Refer to Table I. Find outdoor temperature and 14 95 evaporator entering air wet-bulb temperature. 100 12 At this intersection, note superheat. Where a 11 105 dash (- -) appears on table do not attempt to 110 10 charge system under these conditions or 8 115 refrigerant slugging may occur. Charge must be weighed in, adding or removing 0.6 oz/ft of Where a dash (- -) appears do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be weighed in. 3/8 liquid line above or below 15 ft. respectively. Note: Superheat ºF is at low-side service port, allow a tolerance of +/- 3 ºF 7. Refer to Table II. Find superheat temperature Note: Indoor dry bulb between 70 ºF and 80 ºF located in step 6 and suction pressure. At this * Optimum performance point, 82 ºF outdoor ambient and (80 ºF dry bulb), intersection note suction line temperature. (67 ºF wet bulb) indoor conditions. (DOE B Test Conditions) 8. If unit has a higher suction line temperature than charted temperature, add refrigerant TABLE II - REQUIRED SUCTION TUBE TEMPERATURE ºF until charted temperature is reached. (MEASURED AT LOW-SIDE SERVICE PORT) 9. If unit has a lower suction line temperature SUCTION PRESSURE AT SERVICE PORT PSIG. SUPERHEAT than charted temperature, remove and recover TEMP. ºF 108 112 117 121 126 131 139 141 146 refrigerant until charted temperature is reached. CAUTION 0 35 37 39 41 43 45 47 49 51 37 39 41 43 45 47 49 51 53 10. When adding refrigerant, charge in liquid 2 1. Compressor damage may occur if system is 39 41 43 45 47 49 51 53 55 form into the suction service port using a 4 over charged. 6 41 43 45 47 49 51 53 55 57 2. This unit is factory charged with R-410A in flow-restricting device. 43 45 47 49 51 53 55 57 59 11. If outdoor air temperature or pressure at accordance with the amount shown on the rating 8 plate. The charge is adequate for most systems 10 45 47 49 51 53 55 57 59 61 suction valve changes, charge to new using matched coils and tubing not over 15 feet 12 47 49 51 53 55 57 59 61 63 suction line temperature indicated on chart. long. Check refrigerant charge for maximum 14 49 51 53 55 57 59 61 63 65 12. This procedure is valid when indoor air efficiency. See Product Data Literature for 16 51 53 55 57 59 61 63 65 67 flow is within +/- 21% of its rated cfm. required Indoor air Flow Rates and for use of 18 55 57 59 61 65 69 FACTORY POWER WIRING FIELD POWER WIRING FACTORY CONTROL WIRING FIELD CONTROL WIRING CONDUCTOR ON CIRCUIT BOARD COMPONENT CONNECTION 1/4 - INCH QUICK CONNECT TERMINALS FIELD SPLICE JUNCTION CAP CAPACITOR *CH CRANKCASE HEATER *CHS CRANKCASE HEATER SWITCH COMP COMPRESSOR CONT CONTACTOR CB CIRCUIT BOARD DFT DEFROST THERMOSTAT DR DEFROST RELAY AND CIRCUITRY *HPS HIGH PRESSURE SWITCH *LPS LOW PRESSURE SWITCH OFM OUTDOOR FAN MOTOR line lengths over 15 feet. PRM PHASE ROTATION MONITOR 3. Relieve pressure and recover all refrigerant RVS before system repair or final disposal. Use all REVERSING VALVE service ports and open all flow-control devices, SOLENOID including solenoid valves. 4. Never vent refrigerant to atmosphere. * MAY BE FACTORY OR FIELD INSTALLED. Use approved recovery equipment. 11 11 12 12 12 13 17 20 24 24 6 6 7 7 7 7 12 16 21 22 - - - - - - - - - - 3 7 12 18 19 - - - - - - - - - - - - - - 7 14 16 - - - - - - - - - - - - - - 3 11 13 -- -- -- -- -- -- -- -- *6 8 -- -- -- -- -- -- -- -- 4 7 -- -- -- -- -- -- -- -- -- 4 55 60 25 23 21 20 18 15 14 12 10 8 6 -- -- -- -- -- -- -- -- -- -- -- 5 -- -- -- -- -- -- -- -- -- -- -- 3 25 23 21 18 16 12 11 8 -- -- -- -- -- -- -- -- -- -- 6 -- -- -- -- -- -- -- -- -- -- 4 -- -- -- -- -- -- -- -- -- -- 3 53 55 57 59 61 63 65 20 22 24 26 28 30 57 59 61 63 65 67 59 61 63 65 67 69 61 63 65 67 69 71 63 65 67 69 71 73 63 65 67 69 71 73 75 67 69 71 73 75 77 25 23 22 20 18 16 15 14 12 11 9 7 6 67 69 71 73 75 77 79 71 73 75 77 79 81 Fig. 2 – Wiring Diagram — Model size 2--1/2 -- 5 tons, 208/230--3 2 336751-101 REV. A A 336751-101 REV. L2 460 3Ø POWER SUPPLY CONNECTION DIAGRAM BLU BLU L1 L3 ALERT! (NOTE #11) 11 21 13 23 OFM OFR COMP T1 YEL 1 3 CONT 11 21 EQUIP GND BRN BLK YEL BRN/YEL OFR BLK BRN/YEL OFM T2 T3 CONT 13 23 * CHS BRN/YEL L1 L3 L2 CONT 24V COM *CH L3 L2 L1 L3 CAP YEL PRM L2 PRM T3 YEL EQUIP GND BLK or RED BLK * CHS T1 BLK BLK SCHEMATIC DIAGRAM (LADDER FORM) L1 COMP T2 CONT * CH YEL/BLU PRM CONT 24V COM CAP RVS YEL/BLU BLK or RED O O C DR OF1 OF2 OFR W2 *LPS YEL/PNK *HPS YEL/PNK BLU/PNK R R DFT BLU/PNK YEL/BLU DFT LOGIC DR Y Y DR T1 Y OF1 C T1 BLK C OF2 SPEED UP O 60 90 120 30 CB BLK YEL WHT ORN RED C Y O W2 R E L W3 G C Y O W2 R E L G INDOOR UNIT TERMINAL BLOCK ORN or BLK ORN or BLK PNK PNK R R RVS ORN BLK or PNK DFT BLK or PNK FACTORY POWER WIRING FIELD POWER WIRING FACTORY CONTROL WIRING FIELD CONTROL WIRING CONDUCTOR ON CIRCUIT BOARD COMPONENT CONNECTION 1/4 - INCH QUICK CONNECT TERMINALS FIELD SPLICE JUNCTION CAPACITOR CAP CRANKCASE HEATER *CH CRANKCASE HEATER SWITCH *CHS COMPRESSOR COMP CONTACTOR CONT CIRCUIT BOARD CB DEFROST THERMOSTAT DFT DEFROST RELAY AND DR CIRCUITRY HIGH PRESSURE SWITCH *HPS LOW PRESSURE SWITCH *LPS OUTDOOR FAN MOTOR OFM OUTDOOR FAN RELAY OFR PHASE ROTATION MONITOR PRM REVERSING VALVE RVS SOLENOID * MAY BE FACTORY OR FIELD INSTALLED. NOTE 8. Check all electrical connections inside control box for tightness. 9. Do not attempt to operate unit until service valves have been opened. 10. It is imperative to connect 3Ø field power to unit with correct phasing. The Phase Rotation Monitor will not allow the contactor to be energized if the phasing is not correct. If phasing is reversed, simply interchange any two of the three power connections on the field side. 11. Use conductors suitable for at least 75ºC (167ºF). CAUTION 1. Compressor damage may occur if system is over charged. 2. This unit is factory charged with R-410A in accordance with the amount shown on the rating plate. The charge is adequate for most systems using matched coils and tubing not over 15 feet long. Check refrigerant charge for maximum efficiency. See Product Data Literature for required Indoor air Flow Rates and for use of line lengths over 15 feet. 3. Relieve pressure and recover all refrigerant before system repair or final disposal. Use all service ports and open all flow-control devices, including solenoid valves. 4. Never vent refrigerant to atmosphere. Use approved recovery equipment. CONT CONDENSING UNIT CHARGING INSTRUCTIONS For use with units using R-410A refrigerant TABLE I - SUPERHEAT CHARGING TABLE (SUPERHEAT ºF AT LOW-SIDE SERVICE PORT) PRM LED INDICATOR EVAPORATOR ENTERING AIR º F WB. OFF: NO 24VAC OUTDOOR ON: OK TEMP ºF 50 52 54 56 58 60 62 64 67 68 70 72 74 76 FLASH: PHASE PROBLEM NOTES: 55 11 12 12 12 13 17 20 24 24 25 25 25 25 11 1. Compressor and fan motor furnished with inherent 6 6 7 7 7 7 12 16 21 22 23 23 23 23 60 thermal protection. 65 - - - - - - - - - - 3 7 12 18 19 21 21 22 22 2. To be wired in accordance with National Electric Code (N.E.C.) and local codes. - - - - - - - - - - - - - - 7 14 16 18 20 20 20 70 3. N.E.C. class 2, 24V circuit, min. 40 VA required. - - - - - - - - - - - - - - 3 11 13 16 18 18 19 75 4. Use copper conductors only, from disconnect to unit. - - - - - - - - - - - - - - - - * 6 8 12 15 16 17 82 5. Must use thermostat and sub-base as stated in pre-sale - - - - - - - - - - - - - - - - 4 7 11 14 15 16 85 literature. - - - - - - - - - - - - - - - - - - 4 8 12 14 15 90 6. If indoor section has a transformer with a grounded - - - - - - - - - - - - - - - - - - - - 6 10 12 14 95 secondary, connect the grounded side to "C" on the 100 - - - - - - - - - - - - - - - - - - - - 4 8 11 12 circuit board. 105 - - - - - - - - - - - - - - - - - - - - 3 6 9 11 7. If any of the original wire, as supplied, must be replaced, 110 - - - - - - - - - - - - - - - - - - - - - - 5 7 10 use the same or equivalent wire. 115 - - - - - - - - - - - - - - - - - - - - - - 3 6 8 INDOOR THERMOSTAT (NOTE #5) -LEGEND- *HPS *LPS 90 FIELD SELECTED TIME PERIOD 60 BETWEEN DEFROST CYCLES (MINUTES) 30 SPEED JUMPERED TEST PINS (USE METAL OBJECT), FIELD SPEED-UP CYCLE UP HEAT CYCLE: 90 MIN. ACCELERATED TO 21 SEC. 60 MIN. ACCELERATED TO 14 SEC. 30 MIN. ACCELERATED TO 7 SEC. DEFROST CYCLE: 10 MIN. ACCELERATED TO 2 SEC. ORN DFT HK32EA001 C BRN/YEL C LOGIC C Y O W2 R YEL/BLU COOLING ONLY CHARGING PROCEDURE 1. Operate unit a minimum of 10 minutes before checking charge. 2. Measure suction pressure by attaching an accurate gage to suction valve service port. 3. Measure suction temperature by attaching an accurate thermistor type or electronic thermometer to the suction line at service valve. 4. Measure outdoor air dry-bulb temperature with a thermometer. 5. Measure indoor air (entering indoor coil) wet-bulb temperature with a sling psychrometer. 6. Refer to Table I. Find outdoor temperature and evaporator entering air wet-bulb temperature. At this intersection, note superheat. Where a dash (- -) appears on table do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be weighed in, adding or removing 0.6 oz/ft of Where a dash (- -) appears do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be weighed in. 3/8 liquid line above or below 15 ft. respectively. Note: Superheat ºF is at low-side service port, allow a tolerance of +/- 3 ºF 7. Refer to Table II. Find superheat temperature Note: Indoor dry bulb between 70 ºF and 80 ºF located in step 6 and suction pressure. At this * Optimum performance point, 82 ºF outdoor ambient and (80 ºF dry bulb), intersection note suction line temperature. (67 ºF wet bulb) indoor conditions. (DOE B Test Conditions) 8. If unit has a higher suction line temperature than charted temperature, add refrigerant TABLE II - REQUIRED SUCTION TUBE TEMPERATURE ºF until charted temperature is reached. (MEASURED AT LOW-SIDE SERVICE PORT) 9. If unit has a lower suction line temperature SUCTION PRESSURE AT SERVICE PORT PSIG. SUPERHEAT than charted temperature, remove and recover TEMP. ºF 108 112 117 121 126 131 139 141 146 refrigerant until charted temperature is reached. 0 35 37 39 41 43 45 47 49 51 37 39 41 43 45 47 49 51 53 10. When adding refrigerant, charge in liquid 2 39 41 43 45 47 49 51 53 55 form into the suction service port using a 4 6 41 43 45 47 49 51 53 55 57 flow-restricting device. 43 45 47 49 51 53 55 57 59 11. If outdoor air temperature or pressure at 8 10 45 47 49 51 53 55 57 59 61 suction valve changes, charge to new 12 47 49 51 53 55 57 59 61 63 suction line temperature indicated on chart. 14 49 51 53 55 57 59 61 63 65 12. This procedure is valid when indoor air 16 51 53 55 57 59 61 63 65 67 flow is within +/- 21% of its rated cfm. 18 55 57 59 61 65 69 20 22 24 26 28 30 53 55 57 59 61 63 65 57 59 61 63 65 67 59 61 63 65 67 69 61 63 65 67 69 71 63 65 67 69 71 73 63 65 67 69 71 73 75 67 69 71 73 75 77 67 69 71 73 75 77 79 Fig. 3 – Wiring Diagram — Model size 3, 4, and 5 tons, 460/3 3 71 73 75 77 79 81 336752-101 REV. A A 336752-101 REV. EBryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 02/10 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. 4 Catalog No. WD213B---01 Replaces: New