DC INPUT AND RELAY OUTPUT MODULES M-201 A M-209
Part Number
M-201 (1 group of 8 24 Vdc inputs and 1 group of 4 NO relay)
M-202 (1 group of 8 48 Vdc inputs and 1 group of 4 NO relay)
M-203 (1 group of 8 60 Vdc inputs and 1 group of 4 NO relay)
M-204 (1 group of 8 24 Vdc inputs and 1 group of 4 NC relay)
M-205 (1 group of 8 48 Vdc inputs and 1 group of 4 NC relay)
M-206 (1 group of 8 60 Vdc inputs and 1 group of 4 NC relay))
M-207 (1 group of 24 Vdc inputs and 1 group of 2 NO and 2 NC relay)
M-208 (1 group of 48 Vdc inputs and 1 group of 2 NO and 2 NC relay)
M-209 (1 group of 60 Vdc inputs and 1 group of 2 NO and 2 NC relay)
Description
This combo module with DC Inputs and relay outputs is designed to drive relays, pilot lamps, valves and
other loads up to 5 A and senses the DC input Voltage and converts them to a True or False logic Signal.
It has 1 group of 8 optically isolated 24/48/60 Vdc inputs (M-201, M-204, M-207/M-202, M-205, M-208/M203, M-206, M-209) and 4 relay outputs (M-201 to M-209). The relays can drive loads ranging from 24 Vdc
to 110 Vdc or from 24 to 250 Vac. Two screw terminals are reserved for each relay output, though they are
isolated between them.
Fig. 1- DC INPUT AND RELAY OUTPUT MODULE M-201
Technical Specifications
ARCHITECTURE:
Umber of Groups
Number of Vdc Inputs
Number of Outputs
2
8
4
ISOLATION:
Groups are individually isolated
8 individually isolated relay contacts. The power supply for the groups is individually isolated.
The driver for each relay is
5000 Vac
optically Isolated from IMB up to:
1
DC Inputs And Relay Outputs
INTERNAL POWER:
Provided by the IMB bus:
Total Maximum Dissipation
Indicator Of Source
5 Vdc, @ 60 mA typical
0.3 W
None
For the VDC Inputs:
ARCHITECTURE:
Number of Points
8
ISOLATION:
Isolation up to
5000 Vac
EXTERNAL POWER:
Voltage Source For The Inputs:
Typical Consumption
Source Indicator
18-30 Vdc (M-201, M-204, M-207)
36-60 Vdc (M-202, M-205, M-208)
45-75 Vdc (M-203, M-206, M-209)
65 mA
Green LED
INPUTS:
On State Level (True Logic)
OFF State Level (False Logic)
Typical Impedance
Status Display
Indicator Logic:
Typical Input Current
15-30 Vdc (M-201, M-204, M-207)
30-60 Vdc (M-202, M-205, M-208)
38-75 Vdc (M-203, M-206, M-209)
0-5 Vdc (M-201, M-204, M-207)
0-9 Vdc (M-202, M-205, M-208)
0-12 Vdc (M-203, M-206, M-209)
3k 9 Ω (M-201, M-204, M-207)
7k5 Ω (M-202, M-205, M-208)
10 kΩ (M-203, M-206, M-209)
Red LED
On When Active: Transistor Conducting
7.5 mA
SWITCHING INFORMATION:
Minimum Voltage (0 to 1)
Maximum Voltage (1 to 0)
Typical Hysteresis
Time From “0” To “1”
Time From “1” To “0”
15 Vdc (M-201, M-204, M-207)
30 Vdc (M-202, M-205, M-208)
38 Vdc (M-203, M-206, M-209)
5 Vdc (M-201, M-204, M-207)
9 Vdc (M-202, M-205, M-208)
12 Vdc (M-203, M-206, M-209)
10 Vdc (M-201, M-204, M-207)
21 Vdc (M-202, M-205, M-208)
26 Vdc (M-203, M-206, M-209)
18 ms
40 ms
For the Relay Ouputs:
ARCHITECTURE
Number Of Outputs
2
4
DC Inputs And Relay Outputs
ISOLATION:
Group is individually isolated
Optical Isolation up to:
Each Relay has two dedicated Terminals
5000 Vac (Before the Relay Isolation it self)
Voltage Source for each Group
Maximum Current Per Group
Maximum Consumption Per Point
Indicator Of Source Per Group
20-30 Vdc
67 mA
16,8 mA
Green LED
Vac Range:
Vdc Range:
Maximum Current For 250 Vac:
Maximum Current For 30 Vdc :
Status Display:
Indicator Logic:
Leakage:
20-250 Vac
20-110 Vdc
5A (Resistive); 2A (Inductive)
5A (Resistive); 2A (Inductive)
Red LED
ON if the relay coil is active
500 µA @ 100 Vac
EXTERNAL SOURCE:
OUTPUTS:
SWITCHING INFORMATION:
RC Protection Circuit
Time To activate
Time to deactivate
62 Ω in series with 0.0 uF
10 ms
10 ms
Mechanic Switching Cycles:
100.000 operations minimum @ 5 A 250 Vac
ELECTRICAL SERVICE LIFE:
DIMENSIONS AND WEIGHT:
Weight
39,9 x 137,0 x 141,5 mm
(1,57 x 5,39 x 5,57 in)
0.298 Kg
One Cable
Two Cables
14 AWG (2 mm2)
20 AWG (0.5 mm2)
Dimensions (W x H x D)
CABLE:
Note:
To increase the service of life of the contacts and to protect the module from potential reverse voltage damage,
externally connect a clamping diode in parallel with each inductive DC Load or connect and RC snubber circuit
with each inductive AC Load.