Recommended Wiring Practices Input Power Wiring Power specs! • Input Power 20-28vac" • Consumption 15VA with No external loads" By connecting pin 40 to earth ground pins 4, 6, 9, 12, 15 &18 are also connected to earth ground. " 24 VAC Primary Secondary Wires Wires Earth Ground Communication Wiring From previous controller" To next controller" Using FTT-10A Free-Topology Transceiver! • 500 meters, 1640 feet, maximum cable length" • 400 meters, 1312 feet, maximum node-to-node distance" Use only approved wiring! • Use Level 4 cable (22 AWG), Twisted Pair" • FTT-10A is Polarity insensitive" Approved Communication Wiring Taco Wire Description (Level 4) Part # WIR-022; 1000 ft. spool 22AWG, Unshielded, Plenum rated, twisted pair Proper Sensor Wiring 10k Precon Type III Thermistor Shield wire cut and taped to wire jacket Note 1 Earth Ground Shield wire connected to Earth Ground Notes 1. Stranded Twisted Shielded Pair, 14 – 22 AWG; 18 AWG recommended Approved Sensor Wiring Taco Wire Description (18AWG) Part # WIR-018; 1000 ft. spool Shielded, Plenum rated, 18AWG stranded twisted shielded pair Proper Controller Grounding 10k Precon Type III Thermistor Shield wire cut and taped to wire jacket Note 1 Earth Ground Shield wire connected to Earth Ground 24 VAC Secondary Wires Notes 1. Stranded Twisted Shielded Pair, 14 – 22 AWG; 18 AWG recommended Earth Ground Primary Wires DXU-3 Power Isolated Example DXU3 Power Sourcing Example DXU3 Power Sinking Example Typical wiring for a Split System, 1 stage heating/cooling, using a DXU-3 Use only Echelon approved cable From previous controller" Terminal block located in unit To next controller" HUM COM/24V W Y Stranded Twisted Shielded Pair, 14 – 22 AWG; 18 AWG recommended G Wiring to condensing unit 10k Precon Type III Thermistor Shield wire cut and taped to wire jacket R 24 VAC Primary Secondary Wires Wires Earth Ground Shield wire connected to Earth Ground Earth Ground Controller switch configurations Triac Outputs • • • • Rated at 1 amp Must wire switching 24 AC voltage to TCxx Terminal Outputs are paired together so they share a TCxx TCxx’s are not tied together Environmental ratings • Temperature: 14 F to 140 F (-10 C to 60 C) • Humidity: 0 to 95 percent, non-condensing Agency Listings and Compliances • UL 916 for the US and Canada • FCC Part 15 Class A