P O W E R E D BY I N N O VAT I O N THOUGHTLEADERSHIP TECHTIP SERIES TOPIC: The Rationale for Equivalency of Force Constant and Back EMF Constant in Linear Motors Scope: Customers have inquired as to why the Airex linear motor specification values for back-EMF (KE) and force constant (KF) are equal. This question arises because some linear motor manufacturers define these parameters as unequal. This TechTip Series provides insight into how Airex defines and tests these values and will clarify outstanding questions around the equivalency of the linear motor force constant and back-EMF constant. Discussion: The force constant (KF) is a measure of how much force a motor develops per unit of applied current, while the back-EMF constant (KE) is a measure of how a motor behaves as a generator when the coils move relative to the magnetic field. To start, there are two decisions regarding methodology explaining why Airex has set the force constant and back-EMF constant to be equal in its work with linear motors. First, when analyzing an ironless linear motor application, Airex operates in metric “SI” units (previously “MKS”) in lieu of English units. As a result, the values for KE (volts/meter/second) and KF (newton/ampere) have the same numerical value. Airex applies this methodology because it eliminates various scaling factors and requires additional constants. Since the two parameters are developed in the same physical configuration and magnetic field, they are, therefore, based on the “same principles”. Secondly, Airex rates both KE and KF using “minimum expected” peak values instead of root-mean-square (RMS) values. Both of these methods help illuminate the equality Airex imposes on force constant and back-EMF constant. Next, in order to further demonstrate the rationale of these chosen methods, it is necessary to recognize that an Airex linear motor uses a distributed coil. Furthermore, the magnetic field is fairly constant over a relatively wide area of each magnet, in relation to coil width, such that the “minimum peak” value is valid over a particular commutation cycle step width. The resulting voltage generated is called the back-EMF and is a direct consequence of the “Generator Equation” as depicted below. The force constant is a direct result of the “Motor Force Equation”, also shown below, where 1 ampere of current is applied to the motor coil and with the coil physically located within its commutation step location. Additionally, the force constant is treated as a “minimum peak” value. These two basic principles, the “Motor Force Equation” and “Generator Equation” are at work in all motors regardless of number of phases or construction type. Motor Force Equation: (1) F = Blin Where: F = Motor force, Newton (N) B = Magnetic Flux Density, Tesla (T) l = Length of conductor, meter (m) i = Current, Ampere (A); equal to 1 for force constant n = number of turns (dimensionless) Generator Equation: (2) V = Blvn Where: V = Generated voltage, volts/meter/second (V/m/s) v = relative velocity between coil and magnetic field, meters/second (m/s) w w w . a i r e x . c o m P O W E R E D BY I N N O VAT I O N THOUGHTLEADERSHIP TECHTIP SERIES m 2 kg V => Since the fundamental units defining the volt are and the fundamental units for a newton are s3 A mkg N => 2 whereas kg = kilogram, S = second and A = ampere, it is, therefore, clear that the value of s KE in (V/m/s) must have the same numerical value as KF in (N/ampere). Both are directly related by the strength of the magnetic field, the length and number of coil conductors exposed to the magnetic field. As an example, consider a motor phase with a 1 newton/ampere KF, which will have a KE of 1 volt per meter per second. When moving at a speed of 1m/s, the motor will develop a peak voltage of 1 volt (peak to peak = 2 volts, approximately RMS = .7 volts) while the center of the coils within each motor phase passes directly over the center of the magnets. A current of 1 ampere applied to a phase of the same motor will produce a force of 1 newton. Since an Airex linear motor contains distributed coils, the force constant for a single phase will be the same as the “line to line” force constant for a Delta connected motor. The WYE connection will yield a force constant and back-EMF constant equal to the “square-root of 3” times the force constant of either a single phase or the Delta connection. To summarize, Airex uses methodology which apportions KE and KF to be set as equal. Moreover, the effect of KE and KF is clear from the physical effort exerted when manually “pushing” the motor coil through the magnet track with the motor phase leads short circuited together. The faster one pushes the motor through the magnet track, the more current flows through the short-circuited motor phases and the more resistant the motor is to the motion. This linear motor evaluation, as described here, provides empirical evidence and explains why Airex sets equal values for both the force constant and the back-EMF constant. Reference: Please contact an Airex representative on this or any TechTip as well as for assistance with motor sizing and selection. Airex Corporation 15 Lilac Lane Somersworth, NH 03878 T: 603-841-2040 F: 603-692-4317 E: info@airex.com w w w . a i r e x . c o m