Miniature circuit breakers A.6 Series E – E3000 – NE3000 – E4500 – E6000 Extensions – – – – Add-on RCD’s Display contacts Shunt trips Tele L Undervoltage release mU Busbar systems Accessories A.12 Series C – C3000 / C4500 / C6000 Extensions – Display contacts – Shunt trips Tele L A.14 Series G – G10000 – Gti10000 – Gti – Guc Extensions – – – – – Add-on RCD’s Display contacts Shunt trips Tele L Undervoltage releases mU Motor operated MCB’s Busbar systems Accessories A.22 Series Hti – Hti10000 (MD125) Extensions – Add-on RCD’s – Display contacts – Shunt trips Tele L Accessories A 1 MCB’s - Advantages Five good reasons to appreciate the GE Power Controls miniature circuit breakers A - Line protection - People protection 2 1. Total protection GE Power Controls MCB’s provide the best answer to the obligation of circuit protection. They give comprehensive protection to circuits against: – Overload currents (0.5A to 125A) – Short-circuit currents (3000 up to 50000 A) – Earth fault currents (30mA up to 1000mA) - combined with add-on RCD’s – The handle being sealable or equipped with padlock bracket avoids dangerous operation changes (ON / OFF) – The handle provides a clear indication of the contact position: OFF: a green line is visible ON: a red line is visible – Top and bottom protection caps give save installation facilities – Sealing accessories for top and bottom connections allow protection of original wiring – Adequate printing of all data on the front provides long-term identification 2. Total quality – The MCB’s are able to accomplish the line protection for more than 10,000 times, by a simple manual, or motor operated reset – The quality of the shells can cope with the hardest ambient circumstances (-25°C to +55°C) – All MCB’s are current limiting MCB’s, the let-through energy being reduced far below the standard limits. Energy limiting class: 3 (not for Series NE3000) – The low let-through peak-currents ensure the long life-time of the contacts of isolators or loadbreak switches upstream – The emission of ionised gases are limited to the severest restrictions (35 mm grid distance) 3. A wide range GE Power Controls offers: – MCB’s for household in accordance with: IEC 898 - B, C and D tripping characteristics – MCB’s for industry in accordance with: IEC 947-2 - instantaneous tripping 3-5 In, 5-10 In, 10-20 In – Add-on RCD’s in accordance with: IEC 1009 - BS 4293 4. Stock reducing system The residential and industrial markets are covered by four appropriate series of MCB’s: Series E, Series C, Series G, Series H. Their external advantages allow the consumer to extend the MCB at any time with: – A wide range of add-on RCD’s / people protection – Five types of display contacts – Shunt trip releases – Accessories 5. Time saving connections Insulated or non insulated busbar systems with maximum connection possibilities, can be very fast put on the top or bottom terminals of the MCB’s. Selection of MCB’s The GE Power Controls offer Type Application Standard AC IEC 898 Household and Short-circuit Series capacity 3000 E3000 / C3000 4500 E4500 / C4500 6000 E6000 / G6000 / C6000 10000 G10000 10 kA 10 kA 15-50 kA Gti10000 Hti10000 Gti similar installations DC Selection of MCB’s depends on Industrial IEC 947-2 12V to 250V Standard AC breakers See AC series 250V / 440V Special AC/DC breakers Series Guc Standard Serial name IEC 947-2 3000 4500 6000 10000 E3000 C3000 E4500 C4500 E6000 C6000 A.8 A.12 A.10 A.12 A.11 A.12 Page 3 – Rated current: equipment rating – Rated voltage: number of poles for breaking – Rated breaking capacity: short-circuit current at point of installation – Type of system: earthed / insulated IEC 898 Short-circuit capacity A – Distribution system: voltage, polarity, ... – Application, standards and approvals – Prospective short-circuit current – Required service / continuity – Admissible current in the cable – Expected inrush currents of load 10 kA 15-50 kA 10 kA 6000 Gti Hti10000 Guc6000 A.18 A.24 A.19 G10000 Gti10000 A.16 Special DC A.17 Instantaneous tripping B C D B C D B C D B C D B C D B C D B C D 3/5 5/1010/20 3/5 5/1010/20 3/5 5/1010/20 B C Thermal setting (A) 0.5 1 2 4 6 10 16 20 25 32 (40) 40 50 63 80 100 – – – – x x x x x x x – – – – – x x x x x x x x x – – – – – x x x x x x x x x – – – – – – – – – – – – – – – – – – – x – x x x x x x – – – – – – – – – – – – – – – – – – – – – – x x x x x x x – – – – – x x x x x x x x x – – – – – x x x x x x x x x – – – – – – – – – – – – – – – – – – – – – 125 – – – – – – – – – Ambient temperature (°C) 30 30 30 (40)Add-on RCD’s not available Polarity – 1P+N in 1 module, see Series C on A.12 – Standard available: 1P, 2P, 3P, 3P+N – On request: 1P+N (2 modules), 4P Use at D.C. See A.19 – – – – x x x x x x – – – – – – x – x x x x x x – – – – – – – – – – – – – – – – – – – – – – x x x x x x x x x x – – – – x x x x x x – x x x x x x x x x x x x x – x x x x x x x x x x x x x – – – – – – – – x x x x x x – x x x x x x x x x x x x x – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – x x x x x x – x x x x x x x x x x x x x – x x x – – – – – – – – – – – – – – – – – – – – – – x x x x x x – – – – – – – – – – – – – – – – – – – 30 30 30 30 40 – – – 40 x x x 40 – – 30 – – – – – – – – – – x x x x x x x x x x x x – – x x x x x x x x – x x x – – – – – – – – – – – – – – – – – – – – G6000 – – x – x x x x x x – – – – – – – – – – – – – – – – – – – – – – x x x x x x – x x x x x x x x x x x x x – x x x x x x x x x x x x x – – – – x x x x x x x x x x – – – – MCB’s - Standards A 4 IEC 898 standard IEC 947-2 standard Circuit breakers are intended for the protection against overcurrents of wiring installations in buildings and similar applications: They are designed for use by uninstructed people and for not being maintained. Low voltage switchgear and controlgear Part 2: circuit breakers Tripping characteristic curves t (s) This standard applies to circuit breakers, the main contacts of which are intended to be connected to circuits, the rated voltage of which does not exceed 1000V A.C. or 1500V D.C. Circuit breakers for use in industrial environments (for use by instructed people). Tripping characteristic curves 3600 t (s) 3600 120 60 10 120 60 1 10 0.1 1 B C D 0.01 1 1.13 1.45 3 5 10 20 2.55 0.1 In 0.01 Magnetic release 1 1.05 1.30 An electromagnet with plunger ensures instantaneous tripping in case of short circuit. The IEC 898 distinguishes three different types, following the current for instantaneous release: type B, C, D. B Test current 3 In 5 In Tripping time t ≥ 0.1s t < 0.1s C 5 In 10 In t ≥ 0.1s t < 0.1s D 10 In 20 In t ≥ 0.1s t < 0.1s Applications Only for resistive loads such as: - electrical heating - water heater - stoves Usual loads such as: - lighting - socket outlets - small motors Control and protection of circuits having important transient inrush currents (large motors) Thermal release The release is initiated by a bimetal strip in case of overload. The standard defines the range of release for specific overload values. Reference ambient temperature is 30°C. Test current Tripping time 1.13 In t ≥ 1h (In ≤ 63A) t ≥ 2h (In > 63A) t < 1h (In ≤ 63A) t < 2h (In > 63A) 1s < t < 60s (In ≤ 32A) 1s < t < 120s (In > 32A) 1.45 In 2.55 In 3 5 10 20 In Magnetic release An electromagnet with plunger ensures instantaneous tripping in case of short circuit. The standard leaves the calibration of magnetic release to manufacturer’s decision. GE Power Controls offers instantaneous tripping ranges – release between 3 and 5 In – release between 5 and 10 In – release between 10 and 20 In Thermal release The release is initiated by a bimetal strip in case of overload. The standard defines the range of release for two special overload values. Reference ambient temperature is 40°C. Test current 1.05 In 1.30 In Tripping time t ≥1h (In ≤ 63A) t ≥2h (In > 63A) t <1h (In ≤ 63A) t < 2h (In > 63A) MCB’s - Identification IEC 898 serial name • Standard values of rated short-circuit capacity in this catalogue: 3000A 4500A 6000A 10000A rated short-circuit capacity (Icn) • and energy limiting class rated current preceded by the • symbol of instantaneous tripping • ON and OFF position (reference ambient air temperature is 30°C) • contact configuration Rated short-circuit capacity (Icn) rated voltage(s) • Test of sequence of operations: O - t - CO O represents an opening operation CO represents a closing operation followed by an automatic opening t represents the time interval between two successive short-circuit operations (3 min.) country of manufacturing • After the test • catalogue number (10 digits) • reference number (6 digits) • quality approval • trade mark The circuit breakers are capable, without maintenance of withstanding a dielectric strength test at a test voltage of 900V. More over the circuit breakers are capable of tripping when loaded with 2.8In, within the time corresponding to 2.55 In but > 0.1 s. Attention All MCB’s are tested for emission of ionized gases during short-circuit; grid distance 35 mm (EN 60898) IEC 947-2 Rated ultimate short-circuit breaking capacity (Icu) serial name • rated short-circuit capacities • Icu, Ics rated current In • • ON and OFF position rated operational voltage(s) Ue • and range of rated frequency • contact configuration suitable for isolation country of manufacturing • • catalogue number (10 digits) Test of sequence of operations: O - t - CO (explanation see IEC 898 above) After the tests – The circuit breakers are capable of withstanding a dielectrical strength test at a test voltage of 1000V – Overload releases shall be tested with a load of 2.5 In and trip within the time corresponding to 2 In but > 0.1 s. • reference number (6 digits) • instantaneous tripping range • utilisation category and reference temperature • claim of compliance with standard • trade mark Rated service short-circuit breaking capacity (Ics) The sequence of operations is O - t - CO - t - CO (explanation see IEC 898) followed by: - a test of the dielectric withstand on twice its rated insulation voltage - a verification of overload releases on In - a verification of tripping when loaded with 1.45 In within the time of 1h (for In ≤ 63A) and 2 h (for In > 63A) Category A: Without a short-time withstand current rating A 5 Series E & NE - MCB’s - Product description Miniature circuit breakers Series E 1 Shells Self extinguishing and thermoplastic material. A Dimensions : 18 mm width per pole,depth 68mm,hight 86mm 2 Outgoing terminal (top) 6 1 2 3 4 4 3 5 6 5 6 7 8 11 8 9 7 9 10 10 11 10 11 Box terminal delivered in open position IP20. Suitable for 2 copper cables of the same section from 1 up to 25mm2. Screw combined cross and slot head, M5. Suitable for pin type busbar systems. Arc chamber The arc chamber exists of 9 special shaped plates. (only for Series E) Electromagnet Equipped with a plunger for instantaneous opening of the contacts. The combination of the magnet,the arc guide 8 and the arc chamber 3 ensures a high breaking capacity,a high selectivity and a long life. Handle 0 (OFF) position: green line visible. I (ON) position: red line visible. Sealable in 0 and I position. The trip-free mechanism anables the opening of the contacts in case of an electrical fault even when the handle is locked or held in the I (ON) position. The MCB is an isolator (IEC 408) due to his secure interruption. Fixed contact Moving contact The neutral closes earlier and opens later than the line contacts, protecting the load for 400V line voltages. Arc guide The arc guide is connected with the bimetal. In case of high currents (short-circuit), the current does not effect or dammage the bimetal but is deviated throug the magnet and the arc guide to the arc chamber. Bimetal Ensures the breaking in case of small currents (overload). Incoming terminal (bottom) The box terminal is delivered in open position. Suitable for copper cables from 1 up to 25mm2 (or 2 X 10mm2). Screw combined cross and slot head, M5. Suitable for pin or fork type busbar systems IP20 shroud optional (see A.28) Sealing plates optional (see A.28) DIN-rail clip At the bottom of the breaker. Active and passive position : – Active position : normal position on the DIN-rail – Passive position : de-activated spring effect to remove the MCB from the DIN-rail. Push the clip down, the breaker stays on the DIN-rail and can be easely removed or positioned. A clip can be removed or added to the MCB per pole. SERIES E - MCB’S A 7 Technical data Number of poles Width Depth Rated voltage (IEC) Use at D.C. (mm) 1 18 2 36 3 54 3+N 72 (mm) (V~) 68 230/400 68 230 68 400 68 400 Highest rated current (A) Number of switching operations at 230V, In, cosϕ = 0.9 Insulation resistance (MΩ) 40 40 40 10000 >106 10000 >106 10000 >106 10000 >106 Dielectric rigidity >2.5 >2.5 >2.5 >2.5 (kV) 40 Influence of ambient temperature The thermal calibration of the MCB’s was carried out at an ambient temperature of 30°C. Ambient temperatures different from 30°C influence the bimetal and this results in earlier or later thermal tripping (see curve). At D.C. the magnetic tripping current is ± 40% higher than at A.C. Shock resistance (in x, y, z direction) 20g with shock duration of 10ms (minimum 18 shocks) 40g with shock duration of 5ms (minimum 18 shocks) Vibration resistance (in x, y, z direction) 3g in frequency range 10 to 55Hz (operating time at least 30 mins) according to IEC 77 §16.3 and DIN 40046 part 8 Storage temperature From -55°C up to + 55°C according to IEC 88 part 2-1 (duration 96 hours) Operating temperature IEC 898, 30°C From – 5 up to 40°C according to IEC 60898 % In Use at 400Hz 140 At 400Hz the magnetic tripping current is approximately 50% higher than at AC 50/60 Hz. 120 Voltage drop and energy loss 100 80 60 0 10 20 30 40 50 60 °C In(A) Voltage drop (V) Energy loss (W) 2 4 6 10 16 20 25 32 40 0.82 0.57 0.21 0.13 0.11 0.14 0.10 0.09 0.08 1.6 2.3 2.3 1.3 1.8 2.8 3.0 3.0 4.7 On request per short-circuit capacity Let-through energy (I2 t)-A2s Let-through peak currents (Id)-kA SERIES E3000 - MCB’s Standard IEC 898 A 8 3000 B C D Poles In (A) Mod. 12 12 12 12 12 12 12 12 12 – – V/099-013106 V/099-013110 V/099-013116 V/099-013120 V/099-013125 V/099-013132 V/099-013140 V/099-003102 V/099-003104 V/099-003106 V/099-003110 V/099-003116 V/099-003120 V/099-003125 V/099-003132 V/099-003140 V/099-033102 V/099-033104 V/099-033106 V/099-033110 V/099-033116 V/099-033120 V/099-033125 V/099-033132 V/099-033140 1 1 1 1 1 1 1 1 1 2 4 6 10 16 20 25 32 40 1 1 1 1 1 1 1 1 1 6 6 6 6 6 6 6 6 6 – – V/099-013206 V/099-013210 V/099-013216 V/099-013220 V/099-013225 V/099-013232 V/099-013240 V/099-003202 V/099-003204 V/099-003206 V/099-003210 V/099-003216 V/099-003220 V/099-003225 V/099-003232 V/099-003240 V/099-033202 V/099-033204 V/099-033206 V/099-033210 V/099-033216 V/099-033220 V/099-033225 V/099-033232 V/099-033240 2 2 2 2 2 2 2 2 2 2 4 6 10 16 20 25 32 40 2 2 2 2 2 2 2 2 2 4 4 4 4 4 4 4 4 4 – – V/099-013306 V/099-013310 V/099-013316 V/099-013320 V/099-013325 V/099-013332 V/099-013340 V/099-003302 V/099-003304 V/099-003306 V/099-003310 V/099-003316 V/099-003320 V/099-003325 V/099-003332 V/099-003340 V/099-033302 V/099-033304 V/099-033306 V/099-033310 V/099-033316 V/099-033320 V/099-033325 V/099-033332 V/099-033340 3 3 3 3 3 3 3 3 3 2 4 6 10 16 20 25 32 40 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 – – V/099-013506 V/099-013510 V/099-013516 V/099-013520 V/099-013525 V/099-013532 V/099-013540 V/099-003502 V/099-003504 V/099-003506 V/099-003510 V/099-003516 V/099-003520 V/099-003525 V/099-003532 V/099-003540 V/099-033502 V/099-033504 V/099-033506 V/099-033510 V/099-033516 V/099-033520 V/099-033525 V/099-033532 V/099-033540 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 2 4 6 10 16 20 25 32 40 4 4 4 4 4 4 4 4 4 40 A: add-on RCD not available Short-circuit capacity (kA) Un IEC 898 230/400V~ 230V~ 400V~ IEC 947-2 230V~ 400V~ 1P 2P 3 – – – 3 – 5 3 10 5 3P Icn – – 3 Icu 10 5 3P + N – – 3 – 5 Use at D.C. Short-circuit capacity Max. voltage 1P 2P(1) 3000A 3000A 48V 110V (1) Poles in series On request B x x 4P 1P + N C x x 1P+N in 1 module, see Series C (A.12) Extensions Add-on RCD Display contacts Shunt trips Tele L Undervoltage release mU B.8 A.25 A.27 A.27 Busbar systems D.1 Accessories A.28 Dimensions A.30 Approvals (1) (1) Except D-characteristic D x x SERIES NE3000 - MCB’s Short-circuit capacity: 3000A C Poles In Mod. 12 12 12 12 12 12 12 12 12 V/348-003102 V/348-003104 V/348-003106 V/348-003110 V/348-003116 V/348-003120 V/348-003125 V/348-003132 V/348-003140 1 1 1 1 1 1 1 1 1 2 4 6 10 16 20 25 32 40 1 1 1 1 1 1 1 1 1 6 6 6 6 6 6 6 6 6 V/348-003202 V/348-003204 V/348-003206 V/348-003210 V/348-003216 V/348-003220 V/348-003225 V/348-003232 V/348-003240 2 2 2 2 2 2 2 2 2 2 4 6 10 16 20 25 32 (40) 2 2 2 2 2 2 2 2 2 4 4 4 4 4 4 4 4 4 V/348-003302 V/348-003304 V/348-003306 V/348-003310 V/348-003316 V/348-003320 V/348-003325 V/348-003332 V/348-003340 3 3 3 3 3 3 3 3 3 2 4 6 10 16 20 25 32 (40) 3 3 3 3 3 3 3 3 3 Un IEC 898 230V~ 400V~ 3 3 3 3 3 3 3 3 3 V/348-003502 V/348-003504 V/348-003506 V/348-003510 V/348-003516 V/348-003520 V/348-003525 V/348-003532 V/348-003540 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 2 4 6 10 16 20 25 32 (40) 4 4 4 4 4 4 4 4 4 (40A): add-on RCD not available A 9 Short-circuit capacity (kA) 1P 2P 3 – 3 – 3P Icn – 3 Busbar systems D.1 Accessories A.28 Dimensions A.30 3P + N – 3 SERIES E4500 - MCB’s Standard IEC 898 A 10 4500 B C D Poles In (A) Mod. 12 12 12 12 12 12 12 12 12 – – V/099-012106 V/099-012110 V/099-012116 V/099-012120 V/099-012125 V/099-012132 V/099-012140 V/099-002102 V/099-002104 V/099-002106 V/099-002110 V/099-002116 V/099-002120 V/099-002125 V/099-002132 V/099-002140 V/099-032102 V/099-032104 V/099-032106 V/099-032110 V/099-032116 V/099-032120 V/099-032125 V/099-032132 V/099-032140 1 1 1 1 1 1 1 1 1 2 4 6 10 16 20 25 32 40 1 1 1 1 1 1 1 1 1 6 6 6 6 6 6 6 6 6 – – V/099-012206 V/099-012210 V/099-012216 V/099-012220 V/099-012225 V/099-012232 V/099-012240 V/099-002202 V/099-002204 V/099-002206 V/099-002210 V/099-002216 V/099-002220 V/099-002225 V/099-002232 V/099-002240 V/099-032202 V/099-032204 V/099-032206 V/099-032210 V/099-032216 V/099-032220 V/099-032225 V/099-032232 V/099-032240 2 2 2 2 2 2 2 2 2 2 4 6 10 16 20 25 32 40 2 2 2 2 2 2 2 2 2 4 4 4 4 4 4 4 4 4 – – V/099-012306 V/099-012310 V/099-012316 V/099-012320 V/099-012325 V/099-012332 V/099-012340 V/099-002302 V/099-002304 V/099-002306 V/099-002310 V/099-002316 V/099-002320 V/099-002325 V/099-002332 V/099-002340 V/099-032302 V/099-032304 V/099-032306 V/099-032310 V/099-032316 V/099-032320 V/099-032325 V/099-032332 V/099-032340 3 3 3 3 3 3 3 3 3 2 4 6 10 16 20 25 32 40 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 – – V/099-012506 V/099-012510 V/099-012516 V/099-012520 V/099-012525 V/099-012532 V/099-012540 V/099-002502 V/099-002504 V/099-002506 V/099-002510 V/099-002516 V/099-002520 V/099-002525 V/099-002532 V/099-002540 V/099-032502 V/099-032504 V/099-032506 V/099-032510 V/099-032516 V/099-032520 V/099-032525 V/099-032532 V/099-032540 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 2 4 6 10 16 20 25 32 40 4 4 4 4 4 4 4 4 4 Short-circuit capacity Un IEC 898 230/400V~ 230V~ 400V~ IEC 947-2 230V~ 400V~ 1P 2P 4.5 – – – 4.5 – 5 3 10 5 3P Icn – – 4.5 Icu 10 5 3P + N – – 4.5 – 5 Use at D.C. 1P 2P(1) Short-circuit capacity 4500A 4500A Max. voltage 48V 110V (1) Poles in series On request B&D characteristic: not standard available 40 A: add-on RCD not available 4P 1P+N (2mod) B C D x x x x x x 1P+N in 1 module, see Series C A.12 Extensions Add-on RCD Display contacts Shunt trips Tele L Undervoltage release mU B.8 A.25 A.27 A.27 Busbar systems D.1 Accessories A.28 Dimensions A.30 Approvals (2) (2) Except D-characteristic SERIES E6000 - MCB’s Standard IEC 898 6000 B C D Poles In (A) Mod. 12 12 12 12 12 12 12 12 12 – – V/099-014106 V/099-014110 V/099-014116 V/099-014120 V/099-014125 V/099-014132 V/099-014140 V/099-004102 V/099-004104 V/099-004106 V/099-004110 V/099-004116 V/099-004120 V/099-004125 V/099-004132 V/099-004140 V/099-034102 V/099-034104 V/099-034106 V/099-034110 V/099-034116 V/099-034120 V/099-034125 V/099-034132 – 1 1 1 1 1 1 1 1 1 2 4 6 10 16 20 25 32 (40) 1 1 1 1 1 1 1 1 1 12 12 12 V/099-016140 V/099-016150 V/099-016163 V/099-006140 V/099-006150 V/099-006163 V/099-036140 V/099-036150 V/099-036163 1 1 1 40 50 63 1 1 1 6 6 6 6 6 6 6 6 6 – – V/099-014206 V/099-014210 V/099-014216 V/099-014220 V/099-014225 V/099-014232 V/099-014240 V/099-004202 V/099-004204 V/099-004206 V/099-004210 V/099-004216 V/099-004220 V/099-004225 V/099-004232 V/099-004240 V/099-034202 V/099-034204 V/099-034206 V/099-034210 V/099-034216 V/099-034220 V/099-034225 V/099-034232 – 2 2 2 2 2 2 2 2 2 2 4 6 10 16 20 25 32 (40) 2 2 2 2 2 2 2 2 2 6 6 6 V/099-016240 V/099-016250 V/099-016263 V/099-006240 V/099-006250 V/099-006263 V/099-036240 V/099-036250 V/099-036263 2 2 2 40 50 63 2 2 2 4 4 4 4 4 4 4 4 4 – – V/099-014306 V/099-014310 V/099-014316 V/099-014320 V/099-014325 V/099-014332 V/099-014340 V/099-004302 V/099-004304 V/099-004306 V/099-004310 V/099-004316 V/099-004320 V/099-004325 V/099-004332 V/099-004340 V/099-034302 V/099-034304 V/099-034306 V/099-034310 V/099-034316 V/099-034320 V/099-034325 V/099-034332 – 3 3 3 3 3 3 3 3 3 2 4 6 10 16 20 25 32 (40) 3 3 3 3 3 3 3 3 3 4 4 4 V/099-016340 V/099-016350 V/099-016363 V/099-006340 V/099-006350 V/099-006363 V/099-036340 V/099-036350 V/099-036363 3 3 3 40 50 63 3 3 3 3 3 3 3 3 3 3 3 3 – – V/099-014506 V/099-014510 V/099-014516 V/099-014520 V/099-014525 V/099-014532 V/099-014540 V/099-004502 V/099-004504 V/099-004506 V/099-004510 V/099-004516 V/099-004520 V/099-004525 V/099-004532 V/099-004540 V/099-034502 V/099-034504 V/099-034506 V/099-034510 V/099-034516 V/099-034520 V/099-034525 V/099-034532 – 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 2 4 6 10 16 20 25 32 (40) 4 4 4 4 4 4 4 4 4 3 3 3 V/099-016540 V/099-016550 V/099-016563 V/099-006540 V/099-006550 V/099-006563 V/099-036540 V/099-036550 V/099-036563 3+N 3+N 3+N 40 50 63 4 4 4 40 - 50 - 63A: Series G For add-on RCD 63A: order Series G10000 (A.18) A 11 Short-circuit capacity (kA) Un IEC 898 230/400V~ 230V~ 400V~ IEC 947-2 230V~ 400V~ 1P 2P 6 – – – 6 – 6 3 10 6 3P Icn – – 6 Icu 10 6 3P + N – – 6 – 6 Use at D.C. Short-circuit capacity Max.voltage 1P 2P(1) 6000A 6000A 48V 110V (1) Poles in series On request 4P 1P+N (2 mod) B x x C x x 1P+N in 1 module, see Series C (A.12) Extensions Add-on RCD Display contacts Shunt trips Tele L Undervoltage release mU B.8 A.25 A.27 A.27 Busbar systems D.1 Accessories A.28 Dimensions A.30 Approvals (2) (40): Add-on RCD’s not available (2) Except D-characteristic D x x SERIES C - MCB’s Standard IEC 898 A Series C is a miniature circuit breaker 1P + N in one module, neutral on the right. This MCB garantees the single phase protection in TT or TNS distribution systems only. (Neutral not protected, switched only) 12 TT Network TN-S Network L1 L2 L3 N PE L1 L2 L3 N PE C3000 C 12 12 12 12 12 12 12 V/099-003002 V/099-003006 V/099-003010 V/099-003016 V/099-003020 V/099-003025 V/099-003032 Poles In (A) 1P+N 1P+N 1P+N 1P+N 1P+N 1P+N 1P+N 2 6 10 16 20 25 32 Mod. 1 1 1 1 1 1 1 C4500 12 12 12 12 12 12 12 3000 Short-circuit capacity (kA) 4500 B C – V/099-012006 V/099-012010 V/099-012016 V/099-012020 V/099-012025 V/099-012032 V/099-002002 V/099-002006 V/099-002010 V/099-002016 V/099-002020 V/099-002025 V/099-002032 Poles In (A) 1P+N 1P+N 1P+N 1P+N 1P+N 1P+N 1P+N 2 6 10 16 20 25 32 Mod. 1 1 1 1 1 1 1 Un EN 60 898 Series C3000 Series C4500 Series C6000 IEC 947-2 Series C4500 Series C6000 IEC 947-2 Series C4500(1) Series C6000(1) 1P+N 230V~ 3 4.5 6 230V~ 6 7.5 400V~ 2 3 (1) Phase only Use at D.C. Max.voltage C6000 6000 C 12 12 12 12 12 12 12 V/099-004002 V/099-004006 V/099-004010 V/099-004016 V/099-004020 V/099-004025 V/099-004032 Poles In (A) 1P+N 1P+N 1P+N 1P+N 1P+N 1P+N 1P+N 2 6 10 16 20 25 32 Mod. 1 1 1 1 1 1 1 1P+N 48V Terminal capacity 10 mm2 flexible copper cable 16 mm2 rigid copper cable On request Neutral on the left. Extensions Display contacts Shunt trips Tele L A.25 A.27 Dimensions A.30 Approvals (2) (2) Except D-characteristic Notes A 13 SERIES G - MCB’s - Product description Miniature circuit breakers Series G 3 A 2 1 Shells 1 Self extinguishing and thermosetting material. Dimensions :18 mm width per pole, depth: 68mm, hight: 90mm. 14 Outgoing terminal (top) 2 The box terminal is delivered in open position. Suitable for 2 copper cables of the same section, or 2 different cables with 1 step of difference. Cable capacity from 0.5 up to 25mm2. The screw combined cross and slot head, M5. IP20 shroud for cables Ø 7 mm optional (A.28). Suitable for pin type busbar systems. 4 3 Arc chamber The arc chamber exists of 12 special shaped plates. 4 Electromagnet Equipped with a plunger for instantaneous opening of the contacts. The combination of the magnet, the blow-out magnet 8 , the arc guide and the arc chamber 3 ensures the high breaking capacity, high selectivity and a long life. 5 Handle 0 (OFF) position: green line visible. I (ON) position: red line visible. – Sealable in 0 and I position. – A trip-free mechanism will make the breaker trip in case of an electrical fault, even when locked or held in the I(ON) position. – The contacts of the series G6000, Gti10000 have a manual depending closing. The series G10000, Gti have an independent closing by means of a spring-operated quick-make mechanism. The MCB fulfils the requirement of an isolator (IEC 418) 5 6 Fixed contact 7 Moving contact The neutral closes earlier and opens later than the line contacts, protecting the load for 400V line voltage. 12 8 Blow-out magnet 13 11 8 9 6 10 7 The blow-out magnet exists of two windings and an arc guide connected with the bimetal. In case of short-circuit, the current does not effect or dammage the bimetal but is deviated through the blow-out magnet and the fixed contact 6 to the arc chamber. 9 Bimetal Ensures the breaking in case of overload. 10 Incoming terminal (bottom) A box terminal combined cross and slot head screw, M5 suitable for copper cables from 1 up to 35mm2 or 2 X 16mm2. Delivered with half open box an lifted screw head. When unscrewing the screw, the head lifts. However, on pushing the screw head down, the screw and the terminal sink. This allows very easy connection with busbar strips and conductors. Suitable for pin or fork type busbar systems. 11 DIN-rail clip 10 11 – At the bottom of the breaker. – Active and passive position. Active position: normal position on the DIN-rail. Passive position: de-activated spring effect to remove the MCB easely from the DIN-rail. Push the clip down, the breaker stays on the DIN-rail and can be easely removed or positioned. – A clip can be removed or added to the MCB per pole. 12 Shroud Provides IP 20 on the incoming terminal. Standard on series G.The shroud will brake while removing. 13 Sealing plate To be inserted in the shroud. Makes the incoming terminal sealable per pole. See A.28. SERIES G - MCB’S Influence of ambient temperature The thermal calibration of the MCB’s was carried out at an ambient temperature of 30°C. Ambient temperatures different from 30°C influence the bimetal and this results in earlier or later thermal tripping. 0.5 - 6A % In 140 120 100 80 60 Technical data 0 Number of poles 1 2 3 3P+N 18 68 36 68 54 68 72 68 Rated voltage Series G (V~) (IEC) Series Guc (V~) (V ) 230/400 250 400 440 400 – 400 – Highest rated current (A) Number of switching operations at 220V, cosϕ = 0.9 at 415V, cosϕ = 0.9 Insulation resistance (mΩ) 63 63 63 63 10000 10000 >106 10000 10000 >106 10000 10000 >106 10000 10000 >106 Dielectric rigidity 4 4 4 4 Width Depth (mm) (mm) (kV) Use at D.C. 20g with shock duration of 10ms (minimum18 shocks) 40g with shock duration of 5ms (minimum18 shocks) Vibration resistance (in x, y, z direction) 3g in frequency range 10 to 55Hz (operating time at least 30 mins) according to IEC 689-2 6/90 Storage temperature From -55°C up to +55°C according to IEC 88 part 2-1 (duration 96 hours) Operating temperature From -25°C up to+ 55°C according to VDE 0664 parts 1 and 2. 20 30 40 50 60 °C 10A % In 140 120 100 80 60 0 10 20 30 40 50 60 °C Voltage drop and energy loss At D.C. the magnetic tripping current is ± 40% higher than at AC Shock resistance (in x, y, z direction) 10 In(A) 0.5 1 2 4 6 10 16 20 25 32 40 50 63 Voltage drop (V) 3.100 1.700 0.900 0.500 0.318 0.140 0.128 0.110 0.092 0.103 0.088 0.090 0.088 Energy loss (W) 1.55 1.7 1.8 2 1.91 1.4 2.05 2.2 2.31 3.28 3.5 4.5 5.56 Internal resistance (mΩ) 6200 1700 450 125 53 14 8 5.5 3.7 3.2 2.2 1.8 1.4 16 - 40A % In 140 120 100 80 60 0 10 20 30 40 50 60 °C 50 - 63A % In 140 On request per short-circuit capacity – Let-through values I2 t (A2s) – Let-through peak currents (Id)-kA – Influence of ambient temperature at 40°C (IEC 947-2) 120 100 80 Use at 400Hz At 400 Hz the magnetic tripping current is approximately 50% higher than at AC 50/60Hz. 60 0 10 1P - - - - - - - - - nP 20 30 40 50 60 °C A 15 SERIES G10000 - MCB’s Standard IEC 898 B C D Poles 12 12 12 12 12 12 12 12 12 12 12 12 12 – – – – V/099-017106 V/099-017110 V/099-017116 V/099-017120 V/099-017125 V/099-017132 V/099-017140 V/099-017150 V/099-017163 V/099-07100 V/099-07101 V/099-07102 V/099-07104 V/099-07106 V/099-07110 V/099-07116 V/099-07120 V/099-07125 V/099-07132 V/099-07140 V/099-07150 V/099-07163 V/099-037100 V/099-037101 V/099-037102 V/099-037104 V/099-037106 V/099-037110 V/099-037116 V/099-037120 V/099-037125 V/099-037132 – – – 1 1 1 1 1 1 1 1 1 1 1 1 1 0.5 1 2 4 6 10 16 20 25 32 40 50 63 1 1 1 1 1 1 1 1 1 1 1 1 1 6 6 6 6 6 6 6 6 6 6 6 6 6 4 – – – – V/099-017206 V/099-017210 V/099-017216 V/099-017220 V/099-017225 V/099-017232 V/099-017240 V/099-017250 V/099-017263 – V/099-07200 V/099-07201 V/099-07202 V/099-07204 V/099-07206 V/099-07210 V/099-07216 V/099-07220 V/099-07225 V/099-07232 V/099-07240 V/099-07250 V/099-07263 V/099-07265 V/099-037200 V/099-037201 V/099-037202 V/099-037204 V/099-037206 V/099-037210 V/099-037216 V/099-037220 V/099-037225 V/099-037232 – – – – 2 2 2 2 2 2 2 2 2 2 2 2 2 2 0.5 1 2 4 6 10 16 20 25 32 40 50 63 (63) 2 2 2 2 2 2 2 2 2 2 2 2 2 2.5 4 4 4 4 4 4 4 4 4 4 4 4 4 3 – – – – V/099-017306 V/099-017310 V/099-017316 V/099-017320 V/099-017325 V/099-017332 V/099-017340 V/099-017350 V/099-017363 – V/099-07300 V/099-07301 V/099-07302 V/099-07304 V/099-07306 V/099-07310 V/099-07316 V/099-07320 V/099-07325 V/099-07332 V/099-07340 V/099-07350 V/099-07363 V/099-07365 V/099-037300 V/099-037301 V/099-037302 V/099-037304 V/099-037306 V/099-037310 V/099-037316 V/099-037320 V/099-037325 V/099-037332 – – – – 3 3 3 3 3 3 3 3 3 3 3 3 3 3 0.5 1 2 4 6 10 16 20 25 32 40 50 63 (63) 3 3 3 3 3 3 3 3 3 3 3 3 3 4 A 16 10000 3 3 3 3 3 3 3 3 3 3 3 3 3 2 – – – – V/099-017506 V/099-017510 V/099-017516 V/099-017520 V/099-017525 V/099-017532 V/099-017540 V/099-017550 V/099-017563 – V/099-07500 V/099-07501 V/099-07502 V/099-07504 V/099-07506 V/099-07510 V/099-07516 V/099-07520 V/099-07525 V/099-07532 V/099-07540 V/099-07550 V/099-07563 V/099-07565 V/099-037500 V/099-037501 V/099-037502 V/099-037504 V/099-037506 V/099-037510 V/099-037516 V/099-037520 V/099-037525 V/099-037532 – – – – 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N In 0.5 1 2 4 6 10 16 20 25 32 40 50 63 (63) Mod. 4 4 4 4 4 4 4 4 4 4 4 4 4 5.5 (63): For add-on RCD’s 63A Short-circuit capacity (kA) Un IEC 898 230/400V~ 230V~ 400V~ IEC 947-2 230V~ 400V~ 1P 2P 10 – – – 15 10 15 4 30 15 3P Icn – 15 10 Icu(1) 30 15 3P + N – 15 10 30 15 (1) Not for: 1P: C-D32, B-C40, B-C50, B-C63 2-3-4P: C40, C50, C63 Use at D.C. Short-circuit capacity Max. voltage 1P 2P(2) 10000A 10000A 48V 110V (2) Poles in series On request B x x 4P 1P+N C x x Extensions Add-on RCD Display contacts Shunt trips Tele L Undervoltage release mU B.8 A.25 A.27 A.27 Busbar systems D.1 Accessories A.28 Dimensions Approvals A.30 (3) (3) Except D-characteristic D x x SERIES Gti10000 - MCB’s 10kA Standard IEC 947-2 3-5 In 5-10 In 10-20 In Poles In Mod. 12 12 12 12 12 12 12 12 12 12 12 12 12 – – – – V/099-056106 V/099-056110 V/099-056116 V/099-056120 V/099-056125 V/099-056132 V/099-056140 V/099-056150 V/099-056163 V/099-046100 V/099-046101 V/099-046102 V/099-046104 V/099-046106 V/099-046110 V/099-046116 V/099-046120 V/099-046125 V/099-046132 V/099-046140 V/099-046150 V/099-046163 V/099-066100 V/099-066101 V/099-066102 V/099-066104 V/099-066106 V/099-066110 V/099-066116 V/099-066120 V/099-066125 V/099-066132 – – – 1 1 1 1 1 1 1 1 1 1 1 1 1 0.5 1 2 4 6 10 16 20 25 32 40 50 63 1 1 1 1 1 1 1 1 1 1 1 1 1 6 6 6 6 6 6 6 6 6 6 6 6 6 4 – – – – V/099-056206 V/099-056210 V/099-056216 V/099-056220 V/099-056225 V/099-056232 V/099-056240 V/099-056250 V/099-056263 – V/099-046200 V/099-046201 V/099-046202 V/099-046204 V/099-046206 V/099-046210 V/099-046216 V/099-046220 V/099-046225 V/099-046232 V/099-046240 V/099-046250 V/099-046263 V/099-046265 V/099-066200 V/099-066201 V/099-066202 V/099-066204 V/099-066206 V/099-066210 V/099-066216 V/099-066220 V/099-066225 V/099-066232 – – – – 2 2 2 2 2 2 2 2 2 2 2 2 2 2 0.5 1 2 4 6 10 16 20 25 32 40 50 63 (63) 2 2 2 2 2 2 2 2 2 2 2 2 2 2.5 4 4 4 4 4 4 4 4 4 4 4 4 4 3 – – – – V/099-056306 V/099-056310 V/099-056316 V/099-056320 V/099-056325 V/099-056332 V/099-056340 V/099-056350 V/099-056363 – V/099-046300 V/099-046301 V/099-046302 V/099-046304 V/099-046306 V/099-046310 V/099-046316 V/099-046320 V/099-046325 V/099-046332 V/099-046340 V/099-046350 V/099-046363 V/099-046365 V/099-066300 V/099-066301 V/099-066302 V/099-066304 V/099-066306 V/099-066310 V/099-066316 V/099-066320 V/099-066325 V/099-066332 – – – – 3 3 3 3 3 3 3 3 3 3 3 3 3 3 0.5 1 2 4 6 10 16 20 25 32 40 50 63 (63) 3 3 3 3 3 3 3 3 3 3 3 3 3 4 3 3 3 3 3 3 3 3 3 3 3 3 3 2 – – – – V/099-056506 V/099-056510 V/099-056516 V/099-056520 V/099-056525 V/099-056532 V/099-056540 V/099-056550 V/099-056563 – V/099-046500 V/099-046501 V/099-046502 V/099-046504 V/099-046506 V/099-046510 V/099-046516 V/099-046520 V/099-046525 V/099-046532 V/099-046540 V/099-046550 V/099-046563 V/099-046565 V/099-066500 V/099-066501 V/099-066502 V/099-066504 V/099-066506 V/099-066510 V/099-066316 V/099-066520 V/099-066525 V/099-066532 – – – – 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 0.5 1 2 4 6 10 16 20 25 32 40 50 63 (63) 4 4 4 4 4 4 4 4 4 4 4 4 4 5.5 (63): For add-on RCD’s 63A A 17 Short-circuit capacity (kA) Un IEC 947-2 230V~ 400V~ 1P 2P 3P 3P + N 20 10 20 10 Icu 10 – 20 10 Use at D.C. Short-circuit capacity Max. voltages 1P 2P(1) 6000A 6000A 48V 110V (1) Poles in series On request 4P 1P+N B x x C x x Extensions Add-on RCD Display contacts Shunt trips Tele L Undervoltage release mU B.8 A.25 A.27 A.27 Busbar systems D.1 Accessories A.28 Dimensions A.30 D x x SERIES Gti - MCB’s 15kA up to 50kA Standard IEC 947-2 3-5 In Icu (kA) 5-10 In Icu (kA) 10-20 In Icu (kA) 12 12 12 12 12 12 12 12 12 12 12 12 12 – – – – V/099-059106 V/099-059110 V/099-059116 V/099-058120 V/099-057125 V/099-057132 V/099-057140 V/099-057150 V/099-057163 – – – – 25 25 25 20 15 15 15 15 15 V/099-040100 V/099-040101 V/099-040102 V/099-040104 V/099-049106 V/099-049110 V/099-049116 V/099-048120 V/099-047125 V/099-047132 – – – 50 50 50 50 25 25 25 20 15 15 – – – V/099-067100 V/099-067101 V/099-067102 V/099-067104 V/099-067106 V/099-067110 V/099-067116 V/099-067120 V/099-067125 V/099-067132 – – – 50 50 50 50 15 15 15 15 15 15 – – – 1 1 1 1 1 1 1 1 1 1 1 1 1 0.5 1 2 4 6 10 16 20 25 32 40 50 63 6 6 6 6 6 6 6 6 6 6 6 6 6 4 – – – – V/099-059206 V/099-059210 V/099-059216 V/099-059220 V/099-059225 V/099-058232 V/099-058240 V/099-057250 V/099-057263 V/099-057265 – – – – 25 25 25 25 25 20 20 15 15 15 V/099-040200 V/099-040201 V/099-040202 V/099-040204 V/099-049206 V/099-049210 V/099-049216 V/099-049220 V/099-049225 V/099-048232 – – – – 50 50 50 50 25 25 25 25 25 20 V/099-067200 V/099-067201 V/099-067202 V/099-067204 V/099-067206 V/099-067210 V/099-067216 V/099-067220 V/099-067225 V/099-067232 – – – – 50 50 50 50 15 15 15 15 15 15 – – – – 2 2 2 2 2 2 2 2 2 2 2 2 2 2 0.5 2 1 2 2 2 4 2 6 2 10 2 16 2 20 2 25 2 32 2 40 2 50 2 63 2 (63) 2.5 4 4 4 4 4 4 4 4 4 4 4 4 4 3 – – – – V/099-059306 V/099-059310 V/099-059316 V/099-059320 V/099-059325 V/099-058332 V/099-058340 V/099-057350 V/099-057363 V/099-057365 – – – – 25 25 25 25 25 20 20 15 15 15 V/099-040300 V/099-040301 V/099-040302 V/099-040304 V/099-049306 V/099-049310 V/099-049316 V/099-049320 V/099-049325 V/099-048332 – – – – 50 50 50 50 25 25 25 25 25 20 – – – – V/099-067300 V/099-067301 V/099-067302 V/099-067304 V/099-067306 V/099-067310 V/099-067316 V/099-067320 V/099-067325 V/099-067332 – – – – 50 50 50 50 15 15 15 15 15 15 – – – – 3 3 3 3 3 3 3 3 3 3 3 3 3 3 0.5 1 2 4 6 10 16 20 25 32 40 50 63 (63) 3 3 3 3 3 3 3 3 3 3 3 3 3 2 – – – – V/099-059506 V/099-059510 V/099-059516 V/099-059520 V/099-059525 V/099-058532 V/099-058540 V/099-057550 V/099-057563 V/099-057565 25 25 25 25 25 20 20 15 15 15 V/099-040500 V/099-040501 V/099-040502 V/099-040504 V/099-049506 V/099-049510 V/099-049516 V/099-049520 V/099-049525 V/099-048532 – – – – 50 50 50 50 25 25 25 25 25 20 – – – – V/099-067500 V/099-067501 V/099-067502 V/099-067504 V/099-067506 V/099-067510 V/099-067516 V/099-067520 V/099-067525 V/099-067532 – – – – 50 50 50 50 15 15 15 15 15 15 – – – – 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N A 18 Poles In Mod. 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 2 3 3 3 3 3 4 0.5 4 1 4 2 4 4 4 6 4 10 4 16 4 20 4 25 4 32 4 40 4 50 4 63 4 (63) 5.5 (63): For add-on RCD’s 63A Short-circuit capacity (kA) Un IEC 947-2 230V~ 400V~ 1P 2P Icu 3P 3P+N See catalogue number Use at D.C. Short-circuit capacity Max. voltage 1P 2P(1) 10000A 10000A 48V 110V (1) Poles in series On request 4P 1P+N B x x C x x Extensions Add-on RCD Display contacts Shunt trips Tele L Undervoltage release mU B.8 A.25 A.27 A.27 Busbar systems D.1 Accessories A.28 Dimensions A.30 D x x SERIES Guc - DC breakers Series Guc 6000 Universal current breaker AC & DC 1P 250V - 2P 440V A B C Poles In (A) 12 12 12 12 12 12 12 12 12 12 12 12 12 – – – – V/099-086106 V/099-086110 V/099-086116 V/099-086120 V/099-086125 V/099-086132 V/099-086140 V/099-086150 V/099-086163 V/099-076100 V/099-076101 V/099-076102 V/099-076104 V/099-076106 V/099-076110 V/099-076116 V/099-076120 V/099-076125 V/099-076132 V/099-076140 V/099-076150 V/099-076163 1 1 1 1 1 1 1 1 1 1 1 1 1 0.5 1 2 4 6 10 16 20 25 32 40 50 63 1 1 1 1 1 1 1 1 1 1 1 1 1 6 6 6 6 6 6 6 6 6 6 6 6 6 – – – – V/099-086206 V/099-086210 V/099-086216 V/099-086220 V/099-086225 V/099-086232 V/099-086240 V/099-086250 V/099-086263 V/099-076200 V/099-076201 V/099-076202 V/099-076204 V/099-076206 V/099-076210 V/099-076216 V/099-076220 V/099-076225 V/099-076232 V/099-076240 V/099-076250 V/099-076263 2 2 2 2 2 2 2 2 2 2 2 2 2 0.5 1 2 4 6 10 16 20 25 32 40 50 63 2 2 2 2 2 2 2 2 2 2 2 2 2 19 Mod. Short-circuit capacity (IEC 60898) In(A) 6000 0.5 - 63 1P 2P 250V= 440V= poles in series Extensions Add-on RCD Display contacts Shunt trips Tele L Undervoltage release mU B.8 A.25 A.27 A.27 Busbar systems D.1 Accessories A.27 Dimensions A.30 Selection table Standard Series Rated current range (A) Voltage D.C. 48 110 125 250 440 0.5-1-2-4-6-10-16 20-25-32-40-50-63 kA* Poles kA* Poles kA* Poles kA* Poles kA* Poles 80-100-125 – Rated current: equipment rating – Rated voltage: number of poles for breaking – Rated breaking capacity: short-circuit current at point of installation – Type of system: earthed / insulated IEC 898 E3000 2-40A 3 1 3 2 E4500 2-40A 4.5 1 4.5 2 E6000 2-63A 6 1 6 2 G10000 0.5-63A 10 1 10 2 Guc 0.5-63A 6 1 2-63A 6 1 6 2 Gti 0.5-63A 10 1 10 2 Hti10000 80-125A *Breaking capacity 2 – – – – IEC 947-2 Gti10000 6 10 2 10 4 The time constant T≤15ms For 50/63A C-char. and 63A, B-char. (T≤4ms) Number of operations at In: 4000 The magnetic tripping current is ± 40% higher than at AC. – It is not permissible to use two single pole MCB’s where a two pole MCB is necessary. SERIES Guc - DC breakers Connection schemes The special Guc circuit breaker is equipped with a permanent magnet requiring polarities to be respected. A BOTTOM SUPPLY TOP SUPPLY 20 1P + - 250 V + - 250 V 1 1 2 + 2 + LOAD LOAD 2P - Insulated system: provide the number of poles necessary for breaking on each polarity + - 440 V + - 440 V 1 3 1 3 2 + 4 - 2 + 4 - LOAD LOAD One polarity of the DC supply is earthed: provide the number of poles necessary for breaking a maximum short-circuit current on the polarity not connected to earth. + - 440 V + - 440 V 1 3 1 3 2 + 4 - 2 + 4 - LOAD LOAD The centre point of the DC supply is earthed: provide the number of poles necessary to break the short-circuit current under a voltage U/2 at each polarity. + - 440 V + - 440 V 1 3 2 + LOAD 4 - 1 3 2 + 4 - LOAD Notes A 21 SERIES Hti - MCB’s - Product description Miniature circuit breakers Series Hti 1 Shells A Self extinguishing, thermosetting and tropcalised material; Dimensions: 27 mm width per pole, depth: 80 mm, height: 94 mm. Advice: if mounted in an enclosure the DIN-rail distance should be 200 mm 22 1 2 Outgoing terminal (top) Box clamp terminal with spring guide for copper cables up to 70 mm2 IP20 shroud optional. Slot head screw 8 x 0.75 2 3 Arc chamber 4 The arc chamber exists of 11 special shaped plates. Two incorporated arc guides: one on the fixed contact, one on the moving contact. 4 Electromagnet Solenoid operation for instantenous tripping. The combination of the magnet, the arc guides and the arc chamber ensures a high breaking capacity, a high selectivity and a long life. 3 5 Handle Green: contacts open. Red: contacts closed. Sealable in 0 and I position. The built-in trip-free mechanism will make the breaker trip in case of an electrical fault even when the handle is locked or held in the I position. The MCB fulfils the requirements of an isolator (IEC 408) 6 8 6 Fixed contact 7 7 Moving contact 8 Arc guides 5 Under electrical fault conditions the moving contact moves away from the fixed contact and the resulting arc is guided into the arc chamber. The connection with the bimetal prevents dammage in case of high currents (short-circuit) of the bimetal strip. 9 12 9 Bimetal Ensures tripping in case of small currents (overload). 10 Incoming terminal (bottom) Identical to the top terminal 2 11 11 DIN-rail clip 10 – At the bottom of the breaker. – Active and passive position Active position: secures MCB on the DIN rail Passive position: by pushing down with a screw driver The breaker remains on the DIN rail and can be easely positioned and removed. – A clip can be removed or added to the MCB per pole. 12 Shroud To be inserted into the outgoing and incoming terminals. Provides IP20 2 12 SERIES Hti - MCB’S A 23 Technical data Use at D.C. Number of protected poles Width (mm) 1 27 2 54 3 81 4 108 At D.C. the magnetic tripping current is ± 40% higher than at AC Depth Rated voltage (IEC) (mm) (V~) 70 230/400 72 400 80 400 80 400 Shock resistance (in x, y, z direction) Highest rated current (A) Number of switching operations at 230V~, cosϕ = 0.9 125 10000 125 10000 125 10000 125 10000 Insulation resistance Dielectric rigidity >106 4 >106 4 >106 4 >106 4 (mΩ) (kV) Influence of ambient temperature The thermal calibration of the MCB’s was carried out at an ambient temperature of 40°C. Ambient temperatures different from 40°C influence the bimetal and this results in earlier or later thermal tripping (see curve). IEC 947-2, 40°C % In 140 20g with shock duration of 10ms (minimum18 shocks) 40g with shock duration of 5ms (minimum18 shocks) Vibration resistance (in x, y, z direction) 3g in frequency range 10 to 55Hz (operating time at least 30 mins) according to IEC 689-2 6/90 Storage temperature From -55°C up to +55°C according to IEC 88 part 2-1 (duration 96 hours) Operating temperature From -25°C up to+ 55°C according to VDE 0664 parts 1 and 2 Use at 400Hz At 400 Hz the magnetic tripping current is approximately 50% higher than at AC 50/60Hz. 120 100 Voltage drop and energy loss In(A) Voltage drop (V) Energy loss (W) Internal resistance (mΩ) 80 100 125 0.075 0.075 0.076 6 7.5 9.5 0.9 0.75 0.6 80 60 0 10 20 30 40 50 60 °C On request Let-through values I2 t (A2s) Let-through peak currents (Id)-kA SERIES Hti - MCB’S 10kA Standard IEC 947-2 A 24 3-5 In 5-10 In 10-20 In Poles In Mod. 1 1 1 V/099-56180 V/099-56192 V/099-56197 V/099-46180 V/099-46192 V/099-46197 V/099-66180 V/099-66192 V/099-66197 1 1 1 80 100 125 1.5 1.5 1.5 1 1 1 V/099-56280 V/099-56292 V/099-56297 V/099-46280 V/099-46292 V/099-46297 V/099-66280 V/099-66292 V/099-66297 2 2 2 80 100 125 3 3 3 1 1 1 V/099-56380 V/099-56392 V/099-56397 V/099-46380 V/099-46392 V/099-46397 V/099-66380 V/099-66392 V/099-66397 3 3 3 80 100 125 4.5 4.5 4.5 1 1 1 V/099-56480 V/099-56492 V/099-56497 V/099-46480 V/099-46492 V/099-46497 V/099-66480 V/099-66492 V/099-66497 4 4 4 80 100 125 6 6 6 Short-circuit capacity (kA) Un IEC 898 230/400V~ 230V~ 400V~ IEC 947-2 230V~ 400V~ 1P 2P 10 – – – 10 10 10 4.5 15 10 3P Icn – 10 10 Icu 15 10 3P + N Use at D.C. Short-circuit capacity Max. voltage 2P(1) 4P(1) 10000A 10000A 125V 250V (1) Poles in serie Extensions Accessories 25 V/099-905030 Sealing plate – allows sealing of MCB terminal connections (together with shroud) – delivered standard per pole in add-on RCD 25 V/099-905031 Terminal shrouds – allows IP20 protection – delivered standard per pole in add-on RCD 25 V/099-901025 DIN-rail clip – additional clip for MCB – clip can be removed and placed on another module (pole) Add-on RCD Display contacts Shunt trips Tele L B.8 A.25 A.27 Dimensions A.30 – 10 10 15 10 Display contacts A 25 For Series E, NE, C, G, Hti, Diff-o-Jump and ∆m E, NE, C, DOJ and ∆m Hti Max. 5A / 250V Function Mod. 1 V/099-900101 V/099-902201 Auxiliary contact H 1/2 1 V/099-900102 V/099-902202 Signal contact S + test + reset S 1/2 1 V/099-900103 V/099-902203 Changeable auxiliary/signal contact H/S 1/2 1 1 V/099-900104 V/099-902204 V/099-900114* V/099-902214* Auxiliary contact and changeable auxiliary/signal contact H + H/S 1/2 1 V/099-900105 Auxiliary contact and signal contact H + S + test + reset H+S 1/2 V/099-902205 Functions Signal contact S + test + reset One changeover contact with silver plated contacts 96 95 98 H Maximum current at AC11 and DC 11 For silver and gold plated contacts 5A up to 250V AC 0.5A up to 220V DC 0.7A up to 110V DC 1A up to 60V DC 2A up to 48V DC 4A up to 24V DC Connections Three or six flat terminals each for max 2.5 mm2 Electrical lifetime Greater than 10,000 operations (IEC 337) AC 11: 50 ON and OFF operations at 1.1 In, 1.1 Un and cos ϕ = 0.7 DC 11: 20 ON and OFF operations at 1.1 In, 1.1 Un and time constant ≤ 15 ms Mechanical connections on the devices and contact positions: printed on the right side of the display contact. * With gold plated contacts Auxiliary contact H One changeover contact with silver plated contacts Technical data 1 0 96 95 98 1 S 0 Man. Aut. Test Reset Changeable auxiliary/signal contact H/S One changeover contact with silver plated contacts Auxiliary contact and changeable auxiliary/signal contact H + H/S Two changeover contacts with silver plated contacts or two changeover contacts with gold plated contacts Auxiliary contact and signal contact H + S + test + reset Two changeover contacts with silver plated contacts 96 95 98 H S H 1 0 S S H 1 0 Man. Aut. 96 95 98 06 05 08 1 S 0 H Man. 1 0 Aut. Test Reset 96 95 98 06 05 08 H S H 1 H H 0 S 1 S H H H 0 H 1 0 Man. Aut. Dimensions, see A.31 SERIES G - Motor operated MCB’s Characteristics Tele M A 26 Motor operated MCB’s – The Tele M device allows to remotely close or open the MCB’s Series G to which it is coupled – Energising of the Tele M can be done by means of a push-button, switch, relay, management processor,... – Silent operation Applications Coupled at the right side of MCB’s Series G in the factory Left side is at disposal for add-on RCD (DOC) or undervoltage release (mU) Width 54 mm (motor only) Terminals for cables 0.75 to 2.5 mm2 Protection degree of terminals IP20 Sealing handle prevents in 0 position closing manually or electrically the breaker in I position setting out of service Automatic stop feature built in power consumption only when closing or opening the MCB electrically Command voltage 240V ± 10% Current In 0.13 A Closing time minimum 1 sec Opening time minimum 0.3 sec Time between successive opening & closing minimum 1 sec Time of successive closing of MCB contacts 0.3 sec Connection examples motor contactor lighting For all circuits with centralised control and individual protection/operation in order to reduce the cable length of the installation – lighting installations, heating and cooling at airports, chemical industries, storage rooms, factories, hospitals,... – control distribution boards – unmanned pumpstations, transmitter stations How to order For safety reasons the device is always delivered coupled with MCB’s Series G e.g. Tele M 21 + G10000 2P C16 or Tele M 21 + V/099-007216 Note - for 1P, 2P, 3P, MCB’s Series G only - 63 A MCB with spacers is not possible Code Display contacts Relay (1) x x x x x x x x Tele M 1 Tele M 2 Tele M 3 Tele M 11 Tele M 21 Tele M 31 Tele M 41 (1) (2) (3) Resetting (2) Manual x x x x x x x Impulse can be < 20 ms After trip of MCB due to overload/short circuit Additionaly for RCCB’s, Diff-o-Jump and RCBO’s Series ∆m Dimensions, see A.31 Electrical x x x x motor contactor lighting Shunt trip / Undervoltage release mU module Tele L module A 27 Shunt trip for remote tripping of all Series E, NE, G, H & ∆m Undervoltage release for all Series E & G The Tele L module makes it possible to remotely switch off the MCB to which it is coupled by energising the terminals of the module. An inbuilt contact in series with the coil prevents burn-out damage if the voltage remains. Manual resetting at the MCB is required. – The mU module provides tripping of the MCB to which it is coupled. The operating threshold is lower than 0.6 Un of the breaker – Nuisance tripping can be eliminated by time-delayed adjusting up to 0.3 sec – Manual resetting at the MCB is required Characteristics Characteristics – Simply coupled to the left or right side of the MCB’s – Modular width of 18 mm – Tunnel terminals with retained screws suitable for copper cables 1 to 35 mm2 bottom terminals 1 to 25 mm2 on top terminals – Material of shells is thermosetting, self extinguishing and tropicalised material – – – – – Emergency stop – Isolation of industrial socket outlets (See connection scheme) V/099-901015 V/099-901016 Rated voltage Closing current Operating time 110 to 415V~ at 110V 0.3A 10 ms 110 to 125V at 240V 0.6A 4 ms at 415V 1A 2 ms 24 to 60V~ 24 to 48V at 48V 2A at 24V 1A Connection scheme 4 ms 10 ms Applications In any case where the power supply undervoltage may cause: – at the load side: automatic running of machines at voltage return to Un – at the source side: not governed inrush currents Applications Cat. no. Simply coupled to the left or the right side of the MCB Modular width of 18 mm Box terminals up to 2.5 mm2 Material of shells is thermosetting, self extinguishing and tropicalised material Coil impedance For Series G 1 V/099-903007 mU module 24V DC 1 V/099-903008 mU module 48V DC 1 V/099-903009 mU module 240V/50Hz ca. 29 Ohm ca. 24 Ohm For Series E 1 Tele L + MCB + Auxiliary contact H V/099-903019 Dimensions, see A.31 mU module 230V/50Hz MCB’s - Accessories A 28 Series E & NE Series G Shroud Shroud (replacement) 10 V/099-904031 25 V/099-901031 Allows sealing of bottom terminal combined with sealing plate – For bottom terminal (IP20) – Allows sealing of bottom terminal combined with sealing plate – Standard on all MCB’s Series G Sealing plate Sealing plate 10 V/099-904030 1P & 2P* * Cut off 1 module in case of 1P MCB 10 V/099-904033 25 V/099-901030 Allows sealing of bottom terminal connection together with shroud 3P & 4P* – delivered standard in add-on RCD * Cut off 1 module in case of 3P MCB DIN-rail clip 25 V/099-904025 Additional clip for MCB DIN-rail clip 25 V/099-901025 – Additional clip for MCB and add-on RCD – Clip can be removed from MCB and placed on the add-on RCD Insulating cap 10 V/099-904022 – For top terminal – Allows connection protection – Delivered standard per pole in add-on RCD Series E, NE, C & G Padlocking bracket 2 V/099-901029 Allows padlocking in ON position and in OFF position Also for Series C Insulating cap 25 V/099-901022 – For top terminal – Allows connection protection – Delivered standard per pole in add-on RCD Protection cap 25 V/099-901033 For top terminal (IP20) Cable ∅ 7 mm Notes A 29 MCB’s - Dimensional drawings Series E, NE and C A 18 36 54 72 68 44 30 45 86 32 6 58 Series G10000 - Gi10000 - Gti - Guc 18 36 54 72 68 58 44 6 63A with spacer 18 45 97 72 45 92 Series Hti 79 58 27 54 81 44 108 45 94 73 MCB’s - Dimensional drawings Display contacts Undervoltage release mU 68 58 44 9 60 43 18 A 31 45 92 45 90 71 Tele M - motor operated Tele L - shunt trip 68 58 44 25 18 45 70 57.5 43 58 53 89 45 90 H S 32 76 Notes A 32