AC Power Systems for Business

advertisement
AC Power Systems
for Business-Critical Continuity™
AC Power Systems
for Business-Critical Continuity™
Model
Standard model
Conversion type
Long back-up time model
Load
100%(4800w)
75%(3600w)
50%(2400w)
25%(1200w)
2 min
5 min
9 min
25 min
+2 Batt Module
6 min
13 min
25 min
50 min
+3 Batt Module
12 min
25 min
50 min
120 min
20 min
40 min
65 min
150 min
30 min
55 min
90 min
210 min
Double conversion
Battery
Module
Rectifier type
IGBT
+1 Batt Module
Rated voltage
220/380Vac single-phase 3-wire or three-phase 4-wire (auto recognizing)
Input parameters
Input voltage range
120-276
Input frequency range
Input power factor
45-55
Single phase >= 0.99 / 3-phase >=0.95
Battery
Charging capability
<3h for recharging to 90% of standard model
Adapt
4.8kW/6kVA +4 Batt Module
UPS
+5 Batt Module
Lead-acid maintenance free battery 12V/7.2AH
+6 Batt Module
40 min
65 min
120 min
280 min
Battery backup time of standard model
>4minutes
+7 Batt Module
50 min
70 min
150 min
310 min
Model of battery module
U16-07C1
+8 Batt Module
60 min
75 min
190 min
400 min
Battery type
Battery module specifications
430W X 660D X 88H (2U rack height), 50kg
Output parameters
Rated power
4.8 kW / 6 kVA
Voltage precision
230Vac±3%
Frequency precision
50+/-0.2%
Output voltage THD
<3% for linear load, <5% for non-linear load
Load crest factor
Expanded battery
module
3:1 (comply with IEC 62040-3)
Step load performance
List of optional parts
100
System parameters and standard
Rack rail
Whether parallel operation can be realized
Parallel output module
Support maximum 3+1 parallel operation
Whether rack mounting mode is supported
System efficiency
Yes
Switching time (power failure)
0
Noise
<51 DB
Language
Yes (optional)
Safety
GB4943-1995
Surge protection
Dimensions
Weight
Warranty
Modbus card
Conducted emission: EN50091-2 EN55022 ClassA
Immunity: EN61000-4-2.3.4.6.8.11 Level III EN61000-4-5 Level IV
Meet installation requirements of IEC60664-1 IV
Be able to withstand at least 6KV/3KA 1/2/50uS+8/20uS
Protection level
IP21
430W X 660D X 88H (2U), with battery
430W×660D×88H 2U
23KG
25KG
1 year
Communication and management
Interface type
USB/intelligent slot (dry contact/SNMP card/Modbus card)
Environmental parameters
Operating temperature
0 - 40˚C
Relative humidity
5 - 95%
Altitude
1500m
SNMP card
Dry contact card
Chinese/English
Whether LCD display is available
EMC
LCD
>91% (with intelligent fan speed regulation function)
Extendable battery
charging module
2U, with 16 internal cells
Used in rack mounting mode
2U, used for 1+ 1 parallel output
Can be changed to LED panel on site
Used for remote TCP/IP-based Web monitoring,
support remote safety shutdown
Used for signal expansion in dry contact communication mode
Used for BMS connection or other industrial application
2U, 192V / 10A for extended battery capacity
Download