GENERAL NOTES 1. SPARE CONDUIT AT MAINLINE AND ARTERIAL ROAD PAVEMENT CROSSINGS SHALL BE CAPPED PAY ITEM NOTES 20. ALL CONDUIT TRENCHES SHALL BE BACKFILLED COMPLETELY TO PROVIDE SAFE CROSSING BY THE AT BOTH ENDS. (TO BE PLACED ON THE FIRST TABULATION OF QUANTITIES SHEET) END OF EACH WORKING DAY OR WHENEVER THE WORK ZONE BECOMES INACTIVE. DO NOT OPEN ANY AREA THAT CAN NOT BE BACKFILLED IN THE SAME DAY/NIGHT OPERATION. 2. PRIOR TO ANY EQUIPMENT ORDER, SUBMIT FOR APPROVAL EQUIPMENT SPECIFICATION OR DESIGN DATA FOR ALL MATERIAL PROPOSED FOR THE PROJECT. THESE MUST SPECIFICALLY INCLUDE: 1. 21. A) LUMINAIRE PHOTOMETRICS ITEM 715-1-AB: INCLUDES CONDUCTORS AS INDICATED IN THE PLANS AND DESIGN STANDARDS. DESIGN QUANTITY SHALL BE BASED ON LINEAR FEET OF SINGLE CONDUCTOR. ALL EXCESS DIRT AND DEBRIS EXCAVATED FROM POLE FOUNDATIONS SHALL BE REMOVED DAILY TO AREAS APPROVED BY THE ENGINEER AND PAID FOR INCIDENTAL TO LIGHT POLE INSTALLATION. B) POLE STRENGTH CALCULATIONS 2. ITEMS 630-2-AB: INCLUDES CONDUITS, ELBOWS, SWEEPS, CONNECTING HARDWARE, TRENCHING C) POLE FRANGIBILITY TEST AND BACKFILL AS PER THE PLANS AND DESIGN STANDARS. THE LINEAR FOOT PRICE FOR 22. MAINTAIN ACCESS TO ALL SIDE STREETS, PRIVATE AND COMMERCIAL DRIVEWAYS AT ALL TIMES D) BOLT SPECIFICATIONS AND BOLT CIRCLE DIAMETER CONDUIT SHALL ALSO INCLUDE THE COST OF RESTORING SIDEWALKS AND PAVEMENT TO THEIR DURING THE CONSTRUCTION OPERATION. E) POLE SHOP DRAWINGS ORIGINAL CONDITION. SOD SHALL BE REPLACED IN LIKE KIND OF THE ADJACENT SURROUNDING. F) LOAD CENTER ELECTRICAL EQUIPMENT (INCLUDING SERVICE DISCONNECTS) 23. THE LIGHTING SYSTEM WILL BE MAINTAINED BY________UPON FINAL ACCEPTANCE. 3. ITEM 715-7-AB: INCLUDES NEMA 3R SERVICE DISCONNECT ON LOAD SIDE OF METER, BASE MOUNTED 3. UTILITY OWNERS: ENCLOSURES, 480-120V CONTROL POWER TRANSFORMER, FUSES, SURGE PROTECTIVE DEVICE ON 24. UPON FINAL ACCEPTANCE OF THE PROJECT, THE ENGINEER SHALL FORWARD A COMPLETE SET OF NOTE TO DESIGNERS AS-BUILT PLANS WITH ALL CHANGES MARKED IN RED TO THE ATTENTION OF:__________ OUTSIDE OF ENCLOSURE, CONDUIT, FEEDER CONDUCTORS FROM THE POWER COMPANY POINT OF MAINTENANCE ENGINEER:______________(ADDRESS). SERVICE TO THE LOAD CENTER, PULL BOX, AND ALL MISCELLANEOUS HARDWARE FOR A COMPLETE INSTALLATION AS PER PLANS AND STANDARD INDEX 17504. INCLUDES THE COST OF FURNISHING LIST ALL UTILITY OWNERS AFFECTED BY THIS PROJECT PER EXAMPLE BELOW: AND INSTALLING TYPE N-11 CONCRETE POLE AND ALL FEES FOR INSPECTION OF CONNECTION 25. ANY EXISTING SIGNALIZATION LOOPS SYSTEM DAMAGED DURING THE CONDUIT INSTALLATION SHALL BE OF THE ELECTRICAL SERVICE. REPAIRED. THE COST SHALL BE INCIDENTAL TO ITEM NO. 715-2-AB. MRS. JEANNIE A. TALHOUK. FLORIDA POWER CORP: 4121 ST. LAWRENCE DRIVE. NEW PORT RICHEY, FL 34653 (813) 372-5102. 4. ITEM 715-4-ABC: INCLUDES THE POLE, BRACKET ARM, LUMINAIRE WITH LAMP, ANCHOR 26. WHEN THE SOIL IS EXPOSED, PREPARE TEMPORARY STABILIZATION AS SOON AS PRACTICABLE. BOLTS WITH LOCK NUTS AND WASHERS, FRANGIBLE TRANSFORMER TYPE BASE. (EXCEPT FOR POLES BUT IN NO CASE SHALL THE TIME BE GREATER THAN SEVEN (7) CALENDAR DAYS. 4. THE LOCATIONS OF EXISTING UTILITIES AS SHOWN ON THESE PLANS ARE APPROXIMATE AND BASED ON THE INFORMATION FURNISHED TO THE ENGINEER BY THE UTILITY OWNER(S) AND ARE MOUNTED ON BRIDGE STRUCTURES. RETAINING WALLS OR BARRIER WALLS. WHICH SHALL HAVE NON-FRANGIBLE BASES), STANDARD FOUNDATION, OR SPECIAL FOUNDATION FOR INDICATED POLES, 27. EXISTING LIGHTING EQUIPMENT POWER SOURCES SHALL BE VERIFIED BY THE CONTRACTOR PRIOR TO SHOWN AS NOTICE TO THE CONTRACTOR THAT UNDERGROUND UTILITIES EXIST. BEFORE EXCAVATING, SODDING AROUND CONCRETE SLAB WHEN NOT IN SIDEWALK, AS INDICATED IN DESIGN STANDARDS. COMMENCING DEMOLITION/REMOVAL WORK. NOTIFY THE UTILITY COMPANY OWNER(S) AND REQUEST THEM TO LOCATE AND STAKE THEIR UNDERGROUND FACILITIES. UTILITIES ARE TO BE ADJUSTED BY OTHERS AS DIRECTED BY 28. ALL POLES MOUNTED ON BRIDGES, RETAINING WALLS OR BARRIER WALLS SHALL HAVE PULL BOXES THE ENGINEER. AS SPECIFIED IN FDOT STANDARD INDEX NO. 21210. * 5. PROVIDE NOTICE TO THE UTILITY OWNER(S) BEFORE EXCAVATION, NOTICE TO BE GIVEN TO THE UTILITY NOTE TO DESIGNERS 29. ALL ROADSIDE LIGHTING PULL BOXES SHALL BE RATED H-20 OR HS-20. ALL PULL BOX OWNER A MINIMUM OF TWO (2) DAYS. EXCLUDING SATURDAY, SUNDAY AND LEGAL HOLIDAYS. METAL COVERS SHALL BE MARKED "STREET LIGHTING" AND SHALL BE PROVIDED WITH A NOT ALL UTILITY COMPANIES ARE MEMBERS OF "SUNSHINE" (1-800-432-4770). WWW.SUNSHINE811.COM. GROUND LUG. 1. THE FLORIDA TURNPIKE ENTERPRISE IS NOT A MEMBER OF SUNSHINE ONE CALL. REMOVE, EDIT OR ADD GENERAL NOTES AS NECESSARY TO ASSURE COMPATIBILITY WITH YOUR PARTICULAR PROJECT. 30. REFERENCE THE BRIDGE STRUCTURAL PLANS FOR THE EMBEDDED ELECTRICAL ITEMS: CONDUIT. 6. THE LOCATION OF THE POLES, CONDUCTORS, CONDUITS, JUNCTION BOXES AND SERVICE POLES ARE 2. ADD ADDITIONAL PAY ITEM NOTES FOR ITEMS THAT ARE NOT COVERED BY THE STANDARDS. PULL BOX, JUNCTION BOX AND THEIR LOCATIONS. DIAGRAMMATIC ONLY AND MAY BE SHIFTED BY THE ENGINEER TO ACCOMMODATE LOCAL CONDITIONS AND EXISTING UTILITY LOCATIONS. 31. CONDUIT LOCATIONS AS SHOWN ON THE PLANS ARE APPROXIMATE. CONDUIT MUST BE PLACED WITHIN THE RIGHT-OF WAY BUT CAN BE ADJUSTED TO FIT AROUND THE EXISTING AND PROPOSED UTILITIES. 7. ALUMINUM POLES. LUMINAIRES AND BASES SHALL BE FABRICATED IN ACCORDANCE WITH AASHTO'S WHERE PLANNED LOCATION OF LIGHTING CONDUIT RUNNING 30" UNDER PAVEMENT IS FOUND TO CONFLICT "STANDARD SPECIFICATIONS FOR STRUCTURAL SUPPORTS FOR HIGHWAY SIGNS. LUMINAIRES AND WITH UNDERGROUND UTILITIES. THE LIGHTING CONDUIT POSITION SHALL BE ALTERED VERTICALLY OR TRAFFIC SIGNALS" AND SHALL HAVE BEEN TESTED BY FHWA-APPROVED METHODS. CERTIFICATION HORIZONTALLY TO AVOID THE CONFLICT AS RECOMMENDED BY THE CONTRACTOR AND APPROVED BY THE FOR TESTS SHALL BE SUBMITTED WITH THE SHOP DRAWINGS. ENGINEER. A 24" ABSOLUTE MINIMUM DEPTH SHALL BE MAINTAINED WHERE LIGHTING CONDUITS ARE RELOCATED CLOSER THAN 30" BELOW THE GROUND SURFACE AND SHALL BE PLACED IN AN ADDITIONAL 8. SUBMITTAL DATA SHALL INCLUDE COMPUTER PRINTOUTS SHOWING HORIZONTAL FOOT-CANDLE LEVELS TO BE 3" PVC SLEEVE OR BACKFILLED WITH A MIN. OF 4"x4" OF CONCRETE. COST OF SUCH TREATMENT WILL OBTAINED USING THE SUBMITTED LUMINAIRES ON THIS PROJECT. AT FINAL INSPECTION THE CONTRACTOR BE INCIDENTAL TO PAY ITEMS PROVIDED. SHALL VERIFY THE HORIZONTAL FOOT-CANDLE LEVELS ON THE ROADWAY WITH AN APPROVED AND PROPERLY CALIBRATED LIGHT METER. 32. PREPARE ACCURATELY DIMENSIONED "AS BUILT" PLANS OF FINAL POLE. CONTROLLER, CABLE AND CONDUIT LOCATIONS. PLANS SHALL BE REVIEWED AND APPROVED BY THE 9. ALL ELECTRICAL WORK SHALL MEET ALL REQUIREMENTS OF THE LATEST ADOPTED EDITIONS OF THE ENGINEER. COST OF SUCH PREPARATION SHALL BE INCIDENTAL TO PAY ITEMS PROVIDED. NATIONAL ELECTRICAL CODE, THE NATIONAL ELECTRICAL SAFETY CODE, AND THE STATE OF FLORIDA D.O.T. STANDARD SPECIFICATIONS FOR ROAD AND BRlDGE CONSTRUCTION. ALL COMPONENTS SHALL BE 33. ALL SPLICES SHALL BE MADE IN PULL BOXES ONLY. PROPERLY GROUNDED AND BONDED PER N.E.C. REQUIREMENTS. 34. SPLICES AND CONNECTIONS MADE IN PULL BOXES SHALL BE LIMITED TO THE SERVICE POINT AND 10. INSTALL SURGE PROTECTIVE DEVICES. PROPERLY GROUNDED IN POWER (SECONDARY) ENTRANCES. SEE GENERAL NOTE 15 CONDUIT JUNCTION WITH MULTI- DIRECTIONAL CONDUITS AS INDICATED ON PLANS. THE CONNECTION MADE AT THESE POINTS SHALL BE MADE PER FDOT SPECIFICATIONS. FASTEN WITH APPROVED 11. IN ACCORDANCE WITH N.E.C., IDENTIFY ALL CIRCUITS AND EQUIPMENT WITH "LAMACOID TAGS". INSTALL SIMILIAR TAGS OF STAINLESS STEEL, IDENTIFYING CIRCUIT FOR EACH LUMINAIRE AT ACCESS ADHESIVE (NO SCREW OR 35. INSPECT ALIGNMENT OF EACH INDIVIDUAL POLE AND FIXTURE AS FOLLOWS: RIVETS) HANDHOLE FOR EACH POLE. 36. POLE ALIGNMENT: WITHIN ONE HALF DEGREE ON VERTICAL +/-. CONFIRM VERTICAL 12. NOTIFY_______(POWER COMPANY'S NAME)_____AT LEAST 48 HOURS PRIOR TO ANY INSTALLATION THAT IS LOAD CENTER DESIGNATION ALIGNMENT. VIEWING FROM ADJACENT SERIES OF POLES. IN BOTH DIRECTIONS. WITHIN 10 FEET OF ENERGIZED ELECTRICAL CONDUCTORS. ______(POWER COMPANY'S NAME)________., AT 37. FIXTURE ALIGNMENT: WITHIN ONE DEGREE OF HORIZONTAL +/-. USING CALIBRATED LEVEL ALONG INSTALLATION SITE OR TAKE OTHER SAFETY PRECAUTIONS AS NECESSARY. EXTREME CAUTION SHALL 8" IT'S OPTION, SHALL ASSIST THE F.D.O.T.CONTRACTOR TO COVER UP ENERGIZED CONDUCTORS AT BOTH AXES OF CUT-OFF FIXTURE FACE, WITH LENS ONLY: NO FIXTURE REFRACTOR SHALL BE CIRCUIT NUMBER BE EXERCISED AT ALL TIMES IN PERFORMANCE OF WORK AROUND THE PRIMARY, HIGH VOLTAGE COMPONENTS. 38. ALL CONDUITS SHALL BE MANDREL TESTED AND CLEANED. CONDUITS PLACED FOR FUTURE USE SHALL HAVE. ƒ" POLYESTER CORD PULLED IN PLACE AND CAPPED WITH NOTATION INSIDE 13. PULLING INSTRUCTIONS: CONNECT PULLING DEVICES TO COPPER WIRE AND NOT TO JACKET AND MEET CONDUIT AS TO LOCATION OF OPPOSITE END. PLACE DUCT MARKER OR PULL BOXES TO MARK MANUFACTURER'S REQUIREMENTS. USE PULLING COMPOUND PER MANUFACTURER'S REQUIREMENTS. ALL ENDS OF EMPTY CONDUI TS. POLE NUMBER BENDS SHALL NOT BE LESS THAN RECOMMENDED BY N.E.C. OR N.E.S.C. FOR CABLE USED. PULL CABLE SHALL BE POLYESTER. STEEL CABLE OR FISH TAPES NOT ALLOWED. 39. ALL LIGHT POLES, PULL BOXES AND LOAD CENTERS SHALL NOT BE INSTALLED WITHIN ANY AREAS (I.E. DITCHES, ETC.) THAT MAY CAUSE WATER INTRUSION. 14. STAKE ALL POLE LOCATIONS AND REQUEST UTILITY COMPANIES TO LOCATE AND STAKE UNDERGROUND UTILITIES PRIOR TO EXCAVATING. 40. AS PART OF THE 7 DAY TEST BURNING PERIOD, EACH CIRCUIT SHALL BE LABELED WITH THE LOAD AMPERAGE READING AT THE LOAD CENTER PANEL. 15. ALL ROADWAY LIGHTING AND ILLUMINATED OVERHEAD SIGNS SHALL HAVE AN IDENTIFICATION TAG. TAGS SHALL BE 2"x 8" IN SIZE WITH BLACK LETTERS ON YELLOW BACKGROUND ATTACHED WITH 41. 2" A LABEL SHALL BE PROVIDED ON POLES WITH OBSTRUCTION LIGHTS TO INDICATE THAT TWO SEPARATE APPROVED ADHESIVE (NO RIVETS OR SCREWS). COST OF TAGS SHALL BE INCLUDED IN THE BID VOLTAGES ARE PROVIDED AND INSTALLED WITHIN THE LIGHT POLES. ALSO INDICATE THAT THE 120 VOLT ITEMS FOR LIGHT POLE COMPLETE. TAGS SHALL BE PLACED 5 FEET ABOVE GRADE AND FACING THE CIRCUIT IS "HOT" 24 HOURS A DAY. THE LABEL SHALL BE SUBMITTED TO THE PROJECT ENGINEER FOR ROADWAY. BEFORE ORDERING TAGS, COORDINATE WITH TURNPIKE ROADWAY MAINTENANCE FOR PROPER APPROVAL OF THE WORDING AND PLACEMENT LOCATION. POLE IDENTIFICATION TAG DETAIL NUMBERING SEQUENCE OF LOAD CENTER AND CIRCUITS. N.T.S. 42. THE CONTRACTOR SHALL REMOVE ALL OUT OF SERVICE ROADWAY LIGHTING SYSTEM COMPONENTS INCLUDING 16. ALL CONDUITS UNDER ROADWAY (AND/OR SIDEWALK) SHALL BE INSTALLED PRIOR TO INSTALLATION OF ROADWAY BASE AND SURFACE (OR CONCRETE), EXCEPT WHERE OTHERWISE SPECIFIED IN THE PLANS. UNDERGROUND AND SURFACE MOUNT CONDUITS, CONDUCTORS, POLE BASES, POLES, PULL BOXES, SERVICE POINTS, LOAD CENTERS, AND ALL OTHER ANCILLARY COMPONENTS RELATED TO THE LIGHTING SYSTEM NOTED IN THE PLANS. 17. JACK AND BORE OPERATIONS IF USED SHALL MEET THE REQUIREMENTS OF F.D.O.T.'S UTILITY ACCOMMODATION GUIDE. (LATEST EDITION). 43. ON REMOVED SIGN STRUCTURES, THE CONTRACTOR SHALL REMOVE ALL ASSOCIATED WIRING FROM THE PULL BOX TO THE SIGN STRUCTURE, AND RE-SPLICE CONDUCTORS AS NEEDED. 18. AT LOCATIONS WHERE UNDERGROUND UTILITIES ARE IN CLOSE PROXIMITY TO THE LIGHTING POLE FOUNDATIONS OR CONDUIT RUN, AS DETERMINED BY THE ENGINEER, HAND DIG THE FIRST 4 FEET OF THE HOLE FOR THE POLE FOUNDATION AND CONDUIT RUN. 44. THE CONTRACTOR MUST REFERENCE THE SIGNING AND PAVEMENT MARKING PLANS FOR THE COST OF INSTALLATION, REMOVAL, AND MODIFICATIONS OF THE SIGN LIGHTING SYSTEMS AND ALL ANCILLARY COMPONENTS ASSOCIATED WITH SIGN LIGHTING. 19. THE CONTRACTOR'S ATTENTION IS DIRECTED TO THE PROVISIONS THAT REQUIRES THE PREPARATION AND APPROVAL OF AN EROSION CONTROL PLAN THAT ADDRESSES PREVENTION CONTROL AND ABATEMENT OF WATER POLLUTION. THE COST OF PREPARING AN EROSION CONTROL PLAN IS INCLUDED IN ITEM________ REVISIONS DATE DESCRIPTION DATE DESCRIPTION STATE OF FLORIDA DEPARTMENT OF TRANSPORTATION ROAD NO. COUNTY PAY ITEM AND GENERAL NOTE SHEET ROADWAY LIGHTING DESIGN FINANCIAL PROJECT ID - $USER$ $DATE$ $TIME$ $FILEA$ SHEET NO. 201 (1 OF 1) FROM SERVICE DISCONNECT 12 GAUGE (MIN.) 304 STAINLESS 60" (MIN) STEEL FREESTANDING CABINET, SURGE PROTECTIVE DEVICE (SEE NOTE 3) NEMA 4X WITH DOUBLE DOORS G N L1L2 120V PHOTO-ELECTRIC CELL 1800VA RATED MERCURY WITH SURGE PROTECTION FOR 2000V PEAK. MAIN MOLDED CASE CIRCUIT BREAKER, 480V, ___ AMP. 2P, SN 60HZ SERVICE ENTRANCE RATED. _____ A.I.C. IN A NEMA 1 ENCLOSURE SS 3-POINT LATCH LOCKING HASP & NYLON ROLLERS ON TOP AND BOTTOM 480-120V, SINGLE PHASE, 3W. 60 HZ, 1.0 KVA CONTROL POWER TRANSFORMER. FUSED PER NEC PART OF LIGHTING CONTACTOR (SHOWN SEPARATE FOR CLARITY) (FUSE RATING TO BE SHOWN IN PLANS) MOLDED CASE CIRCUIT BREAKER, 480V, ___ AMP. 2P, SN 60HZ SERVICE ENTRANCE RATED. _____ A.I.C. NEMA 1 ENCLOSURE (SEE NOTE 6) ANCHOR BOLTS FURNISHED WITH CABINET SEAL BASE OF CABINET WITH CLEAR SILICONE 1" CHAMFER HAND-OFF-AUTO SELECTOR SWITCH PART OF LIGHTING CONTACTOR (SHOWN SEPARATE FOR CLARITY) H A GRADE NEMA 5-15 R GFCI DUPLEX RECEPTACLE WITH WP BOX & COVER ELECTRICALLY HELD LIGHTING CONTACTOR 480V, ___ AMP. 2P, 60HZ, 120V COIL IN A NEMA 1 ENCLOSURE BRANCH CIRCUIT BREAKER RATINGS LOAD CENTER '_' _-2 __ AMPS _-3 __ AMPS _-4 __ AMPS _-5 __ AMPS _-6 __ AMPS _-7 __ AMPS 1 2 3 4 5 6 CLASS II CONCRETE BASE (TYP) 1 '-8" OFF __ AMPS RUBBER SEALANT 8" MIN SERVICE CONTROL PANEL (SEE NOTE 2) _-1 CONTINUOUS HINGE AND HANDLE WITH 480 VOLT, 3 WIRE, M.L.O. ___ AMP PANEL WITH 2 POLE. ______ A.I.C. BRANCH CIRCUIT BREAKERS IN A NEMA 1 ENCLOSURE (SEE TABLE FOR BRANCH BREAKER RATINGS) CONDUIT (TYP) FRONT VIEW GENERAL NOTES 1. CABINET SHALL BE GROUNDED PER NEC AND FDOT STANDARDS AND DETAILED IN THE PLANS. 2. STUB-OUT ONE (1) SPARE 2" PVC CONDUIT BELOW GRADE AND BEYOND CONCRETE BASE. 7 CAP ENDS AND INDICATE LOCATION OF STUB-OUT INSIDE CABINET COPPER NEUTRAL BUS COPPER GROUND BUS 26" (MIN) ELECTRICAL PANELS AND CONTROLS ____ KVA TOTAL DEMAND LOAD: ____ KVA CIRCUIT _-1 CIRCUIT _-2 ALUM. BACKPLATE CIRCUIT _-3 CIRCUIT _-4 INSULATED BUSHING (TYP) CIRCUIT _-5 CIRCUIT _-6 55"( MIN) TOTAL CONNECTED LOAD: UNDERDECK DAYTIME CIRCUIT CIRCUIT _-7 GROUND GROUND SEAL CONDUIT ENTRY (TYP) 2" MIN ALL SIDES NOTES: P.E. Controller 4'-0"(MAX) SERVICE SLAB SLOPE 1" FOR DRAINAGE 1. ALL WIRING INSIDE SERVICE CONTROL PANEL SHALL BE INSTALLED IN INTERMEDIATE METAL CONDUIT. 2" 2. CONTRACTOR SHALL FURNISH ENCLOSURE SIZED FOR THE EQUIPMENT (SEE ENCLOSURE DETAIL THIS SHEET). 3. SURGE PROTECTIVE DEVICE (SPD): SPD UNIT SHALL BE WIRED INSIDE THE ENCLOSURE AS PER FDOT STANDARD INDEX 17504. SPD UNIT SHALL BE MOUNTED ON THE OUTSIDE OF THE ENCLOSURE AND COMPLY WITH UL 1449 LATEST ADOPTED EDITION. 4. SHOP DRAWINGS REQUIRED FOR ALL EQUIPMENT ASSOCIATED WITH THE LOAD CENTER. 5. LOAD CENTER/SERVICE POINTS SHALL BE PROVIDED WITH A MINIMUM OF 20% SPARE CAPACITY. Side or Back of Enclosure CUT A 2" HOLE IN THE SIDE OF THE LIGHTING CONTROL PANEL ENCLOSURE FOR THE OPERATION AND MOUNTING OF THE P.E. CONTROLLER. USE PLEXIGLASS AND A CLEAR SILICONE SEALANT TO COVER HOLE, INSTALL P.E. CONTROLLER. SIDE VIEW 6. BREAKER AND WIRING INSTALLED WHEN DAYTIME LIGHTING CIRCUIT IS REQUIRED. LOAD CENTER ENCLOSURE DETAIL PHOTO ELECTRIC CONTROLLER DETAIL LOAD CENTER SCHEMATIC DIAGRAM N.T.S. N.T.S. N.T.S. REVISIONS DATE DESCRIPTION DATE DESCRIPTION STATE OF FLORIDA DEPARTMENT OF TRANSPORTATION ROAD NO. COUNTY SHEET FLORIDA TURNPIKE LOAD CENTER DETAILS FINANCIAL PROJECT ID $USER$ $DATE$ $TIME$ $FILEA$ NO. 202 (1 OF 2) 1 KEYED NOTES 3 1 240/480 V SINGLE PHASE 3-WIRE "LIST POWER COMPANY" ELECTRIC SERVICE. SAFETY SWITCH ON SEVICE SIDE OF METER WHEN REQUIRED BY POWER COMPANY. 2 480V, ___AMP ENCLOSED BREAKER 3 2#___ AWG & 1__ AWG (N) IN _" RIGID GALVANIZED STEEL CONDUIT 4 METER AS REQUIRED. HEIGHT SPECIFIED BY POWER COMPANY. 5 1#__ AWG INSULATED COPPER GROUND WIRE IN 1" RIGID GALVANIZED STEEL CONDUIT 6 COPPER CLAD GROUND ROD(S), MIN. †" DIA. 20' LONG, 6' MIN. SEPARATION BETWEEN THEM 7 480V ENCLOSED BREAKER NEMA 3R SERVICE ENTRANCE RATED WITH NEUTRAL AND GROUND KITS 8 2#___ AWG, 1#___ AWG (N), & 1#___ AWG (G) IN _" RIGID GALVANIZED STEEL CONDUIT 4 7 5 CONCRETE POLE PRESTRESSED TYPE P-II, 12' LONG REFER TO FDOT STANDARD INDEX 17504 DETAIL "B", UNDERGROUND FEED 4 6 18 13 15 7 14 17 8 16 12 9 5 2 12 10 15 13 11 PANEL BOARD, ___ AMP, 480V, SINGLE PHASE, 3-WIRE WITH CIRCUIT BREAKERS AND GROUND BAR AS INDICATED PULL BOX REFER TO GENERAL (27-1/2" X 18" X 12"). COVER MARKED ROADWAY LUMINAIRE CONNECTED TO CIRCUIT _-2 "ELECTRIC" 8 MAIN CIRCUIT BREAKER ___ AMPS, 2-POLE, 480V, ___ AIC 14 ___ AMP, 2-POLE, ELECTRICALLY HELD CONTACTOR 15 FREE STANDING NEMA 4X STAINLESS STEEL ENCLOSURE WITH TWO DOORS 16 PHOTOELECTRIC SWITCH _____ VA 14 2 1 2" 13 6 1 OF 2 4'-0" 11 5 DETAIL ON SHEET 6 SURGE PROTECTIVE DEVICE (SPD) PAD CENTER ENCLOSURE CONTROL TRANSFORMER 1 KVA SINGLE PHASE, 480V PRIMARY 120V SECONDARY 12 CONCRETE NOTE 6 ON LOAD 3 8" 9 9 10 _-1 __/2 __/2 _-2 _-3 __/2 __/2 _-4 _-5 __/2 __/2 _-6 _-7 __/2 _____ VA RISER DIAGRAM SPARE CONDUIT 17 "LIST POWER COMPANY" CONCRETE SERVICE POLE 18 "LIST POWER COMPANY" TRANSFORMER REFER TO GENERAL _____ VA _____ VA NOTE 2 ON LOAD CENTER ENCLOSURE DETAIL ON SHEET _____ VA _____ VA CONDUIT (TYP.) N.T.S. 1 OF 2 _____ VA _____ VA _-2P SPACES TOTAL CONNECTED LOAD: ____ KVA TOTAL DEMAND LOAD: ____ KVA ONE LINE DIAGRAM N.T.S. REVISIONS DATE DESCRIPTION DATE DESCRIPTION STATE OF FLORIDA DEPARTMENT OF TRANSPORTATION ROAD NO. COUNTY SHEET FLORIDA TURNPIKE SERVICE POINT DETAILS FINANCIAL PROJECT ID $USER$ $DATE$ $TIME$ $FILEA$ NO. 202 (2 OF 2) INTERCHANGE 21 5' 21 5' LIGHTING LIMITS 1 TYP. 215' 215' CROSS ROAD ON-RAMP TOLL PLAZA INTERCHANGE INTERCHANGE 215' 215' LIGHTING LIMITS OFF-RAMP LIGHTING LIMITS TOLL PLAZA 2 2 1 REFER TO TABLES 7.3.1 AND 7.3.2 OF TPPPH VOLUME I, CHAPTER 7 FOR ILLUMINATION LEVELS. 2 LIMITS OF 2.0 AVERAGE INITIAL FOOT-CANDLES ON THE APROACH AND DEPARTURE OF A RAMP TOLL PLAZA AS PER TABLES 7.3.1 AND 7.3.2. MAINLINE 21 5' (NOT APPLICABLE FOR AET ONLY PLAZAS) NOTES: 1. THE CROSS ROAD LIGHTING LIMITS SHOWN ARE APPLICABLE WHENEVER THE CROSS 21 5' ROAD IS NOT TO BE ILLUMINATED BEYOND THE INTERCHANGE LIGHTING LIMITS SHOWN. 2. THE MAINLINE LIGHTING LIMITS SHOWN ARE APPLICABLE WHENEVER THE MAINLINE IS NOT CONTINUOSLY ILLUMINATED BEYOND THE INTERCHANGE LIGHTING LIMITS SHOWN. 3. PLEASE NOTE THAT IF THE LENGTH OF THE INTERCHANGE MAINLINE BETWEEN LIGHTED INTERCHANGES IS LIGHTING LIMITS 0.5 MILES OR LESS, THEN THAT SECTION OF THE MAINLINE WILL BE ILLUMINATED REGARDLESS OF WHAT THAT THE LIGHTING JUSTIFICATION INTERCHANGE LIGHTING LIMITS REPORTS INDICATES. N.T.S. REVISIONS DATE DESCRIPTION DATE DESCRIPTION STATE OF FLORIDA DEPARTMENT OF TRANSPORTATION ROAD NO. COUNTY SHEET INTERCHANGE LIGHTING LIMITS FINANCIAL PROJECT ID - kn835rc - NO. 203 (1 OF 1) 3/8/2016 9:03:59 AM $FILEA$ 21 5' LIGHTING LIMITS 21 5' LIGHTING LIMITS PARKING WALKWAYS SITE BLDG. 21 5' FOOT-CANDLES AS PER TABLE 7.3.5 OF LIGHTING LIMITS LIGHTING LIMITS 21 5' PARKING LOT AND SITE: 1.5 AVERAGE INITIAL TPPPH VOLUME I, CHAPTER 7. BLDG. PERIMETER AND WALKWAYS: 2.0 AVERAGE INITIAL FOOT-CANDLES AS PER TABLE 7.3.5 OF TPPPH VOLUME I, CHAPTER 7. LIMITS OF 1.7 AVERAGE INITIAL FOOT-CANDLES FOR NON-ILLUMINATED ROADWAYS NOTES: 1. THE MAINLINE LIGHTING LIMITS SHOWN ARE APPLICABLE WHENEVER THE MAINLINE IS NOT CONTINUOUSLY ILLUMINATED. SERVICE PLAZA LIGHTING LIMITS N.T.S. REVISIONS DATE DESCRIPTION DATE DESCRIPTION STATE OF FLORIDA DEPARTMENT OF TRANSPORTATION ROAD NO. COUNTY SHEET SERVICE PLAZA LIGHTING LIMITS FINANCIAL PROJECT ID - kn835rc - NO. 204 (1 OF 1) 3/8/2016 9:11:06 AM $FILEA$ MAINLINE TOLL PLAZA DEPARTURE MAINLINE TOLL PLAZA APPROACH PARKING LOT MAINLINE TOLL PLAZA ADMINISTRATION BUILDING MAINLINE TOLL PLAZA CANOPY (TYP.) 215' 215' TUNNEL { MAINLINE MEDIAN 1 215' 215' MAINLINE TOLL MAINLINE TOLL PLAZA LIGHTING PLAZA LIGHTING LIMITS LIMITS 2 MAINLINE TOLL PLAZA APPROACH MAINLINE TOLL PLAZA DEPARTURE MAINLINE TOLL PLAZA APPROACH AND DEPARTURE LIGHTING LIMITS 1 N.T.S. REFER TO TABLES 7.3.1. AND 7.3.2 OF TPPPH VOLUME I, CHAPTER 7 FOR MAINLINE ILLUMINATION LEVELS. 2 LIMITS OF 2.0 AVERAGE INITIAL FOOT-CANDLES ON THE APPROACH AND DEPARTURE OF A RAMP TOLL PLAZA, AS PER TABLES 7.3.1. AND 7.3.2. OF TPPPH VOLUME I, CHAPTER 7. FOR REFERENCE ONLY (NOT APPLICABLE FOR AET ONLY TOLLING) NOTES: 1. THE MAINLINE LIGHTING LIMITS SHOWN ARE APPLICABLE WHENEVER THE MAINLINE IS NOT CONTINUOUSLY ILLUMINATED. REVISIONS DATE DESCRIPTION DATE DESCRIPTION STATE OF FLORIDA DEPARTMENT OF TRANSPORTATION ROAD NO. COUNTY SHEET MAINLINE TOLL PLAZA LIGHTING LIMITS FINANCIAL PROJECT ID - $USER$ - NO. 205 (1 OF 1) $DATE$ $TIME$ $FILEA$ PARKING LOT MAINLINE TOLL PLAZA ADMINISTRATION BUILDING MAINLINE TOLL PLAZA CANOPY (TYP.) 98' 98' ROADWAY LIGHTING/TOLL PLAZA INTERFACE PULL BOX E E E E E E E E E E E E TUNNEL { MAINLINE MEDIAN E E E E E E E E E E E E LEGEND: ROADWAY LUMINAIRE FED FROM ROADWAY LIGHTING LOAD CENTER MAINLINE TOLL PLAZA APPROACH AND DEPARTURE LIGHTING LOCATION ROADWAY LUMINAIRE FED FROM E PLAZA STAND-BY GENERATOR PANEL NOTES: N.T.S. 1. THE EXACT LOCATION OF THE LUMINAIRES SHALL BE AS DICTATED BY THE LIGHTING ROADSIDE PULL BOX CALCULATIONS. CONDUIT, UNDERGROUND 2. CONDUIT, UNDERPAVEMENT ROADWAY LIGHTING BRANCH CIRCUIT CONDUITS SHALL NOT BE INSTALLED THROUGH THE TOLL FOR REFERENCE ONLY PLAZA ADMISTRATION BUILDING/TUNNEL AREA. (NOT APPLICABLE FOR AET ONLY TOLLING) REVISIONS DATE DESCRIPTION DATE DESCRIPTION STATE OF FLORIDA DEPARTMENT OF TRANSPORTATION ROAD NO. COUNTY SHEET MAINLINE TOLL PLAZA LIGHTING LOCATION FINANCIAL PROJECT ID - $USER$ - NO. 206 (1 OF 1) $DATE$ $TIME$ $FILEA$