QUICKTRONIC® MH Electronic Metal Halide Systems

advertisement
www.sylvania.com
QUICKTRONIC® MH
Electronic Metal Halide Systems
Normal Ballast Factor
Professional Series
Lamp / Ballast Guide
QTP 2x20MH/UNV
QTP 1x20MH/SQ UNV
QT 1x20MH/SLIM 120V
M156*; C156
QTP 1x39MH/UNV
QTP 2x39MH/UNV
QTP 1x39MH/SQ UNV
QT 1x39MH/SLIM 120V
M130*; C130
QTP 1x70MH/UNV
QTP 1x70MH/SQ UNV
QT 1x70MH/SLIM 120V
M139*/M98: C139/C98
*earlier reference obsolete
Key System Features
•
•
•
•
•
•
•
•
•
Constant power regulation
Universal input voltage
High power factor
Low harmonic distortion
Small size and lightweight
80ºC case temperature
UL, FCC
End-of-life shut down
Internal IDTP (Insulation Detection
Thermal Protector)
• QUICK 60+® warranty
• RoHS compliant
• Lead-free solder, printed circuit
board and manufacturing process
Application Information
SYLVANIA QUICKTRONIC MH
is ideally suited for:
• Track lighting
• Downlighting
• Landscape lighting
• Retail
• Hospitality
• Institutional
• Commercial
ECS054R7 – 10/2010
Small and efficient, QUICKTRONIC MH
ballasts operate silently and provide
energy savings up to 15% compared to
magnetic ballasts.
New smaller sizes allow for more flexible
fixture designs and applications while
maintaining the features and system
advantages of the standard size ballast.
The Mini Slim and Mini Square are 50%
smaller than the standard sized can.
Installation is simplified by our singlepiece ballasts that incorporate the ballast,
capacitor, ignitor and mounting brackets
of conventional systems. Two lightweight
mounting styles allow for easy assembly
in any fixture application.
QUICKTRONIC MH eHID ballasts are RoHS
compliant and feature lead-free solder,
printed circuit boards and manufacturing
process.
Setting the standard for quality,
QUICKTRONIC MH ballasts are also
covered by our QUICK 60+® warranty,
the first and most comprehensive system
warranty in the industry.
System Information
SYLVANIA QUICKTRONIC MH ballasts and
SYLVANIA METALARC® POWERBALL®
CERAMIC lamps are perfectly matched to
provide optimal system performance.
Our electronically controlled system delivers
several advantages over conventional
components, including improved lumen
maintenance and extended photometric life.
The superior power regulation design
produces consistently brilliant light output
and color throughout the life of the lamp.
This circuitry also provides constant light
output during periods of fluctuating supply
voltage.
All QUICKTRONIC MH eHID ballasts are
equipped with an end-of-life shut down
function. This prevents continuous starting
after lamps extinguish which may cause
permanent damage to the ballast.
All low wattage (</= 150W) QUICKTRONIC
universal input voltage (120-277V) eHID
ballasts are equipped with an internal IDTP
(Insulation Detection Thermal Protector).
This is a precision temperature gauge that
will shut the ballast down at the maximum
case temperature to prevent internal
Enclosure Styles
F = Feet Mount for track light fixtures
(All leads exit side of ballast, as shown on next page.)
J = J-Box Mount with PEM studs for recessed downlight fixtures
(All leads exit middle/bottom of ballast, as shown on next page.)
damage of electronic components. The
internal thermal protection feature affords
an original equipment manufacturer (OEM)
the ability to remove all external thermal
protection devices. In order to maximize
the benefits of this unique feature the
ballast must be properly installed.
(See “installation notes” for detail).
QT MH
QTP 1x100MH/UNV
M90/M140*; C90
SYLVANIA QUICKTRONIC MH electronic HID
(eHID) ballasts feature a state of the art
electronic design to deliver performance
levels unattainable with standard magnetic
lighting systems.
SPECIFICATION DATA
Catalog #
Date
Type
Project
Prepared by
®
MH QUICKTRONIC
SYSTEMS
Comments
Professional Series
Electronic Metal Halide Systems, Universal Voltage (120-277V)
Item
Number
OSRAM SYLVANIA
Description
Input
Voltage
(VAC)
Input
Current
(AMPS)
Lamp
Type 1
Performance Guide
Rated
Ballast
Input System
Lumens No. of Internal Factor System Wattage Efficacy
(lm)
Lamps IDTP2
(BF) Lumens
(W)
(lm/W)
51968
51969
QTP2X20MH UNV F3
QTP2X20MH UNV J3
120-277 0.38/0.16 20W T4.5
1700
2
Yes
1.0
3400
46
74
51910
51911
QTP1x39MH/UNV-F
QTP1x39MH/UNV-J
120-277 0.39/0.17
39W T6
3400
1
Yes
1.0
3400
44
77
51970
51971
QTP2X39MH UNV F3
QTP2X39MH UNV J3
120-277 0.75/0.33
39W T6
3400
2
Yes
1.0
6800
89
76
51912
51913
QTP1x70MH/UNV-F
QTP1x70MH/UNV-J
120-277 0.67/0.29
70W T6
7000
1
Yes
1.0
7000
79
89
51914
51915
QTP1x100MH/UNV-F
QTP1x100MH/UNV-J
120-277 0.96/0.41 100W E17
9700
1
Yes
1.0
9700
110
88
1: Data based on ceramic lamp types except where noted.
2: Internal IDTP - Insulation Detection Thermal Protector (see system information for detail).
3: Ballast can operate 1 or 2 lamps, cap off unused leads individually for 1 lamp operation.
QT MH
Installation Notes
1. Proper ballast mounting must be followed to allow for maximum thermal dissipation:
a. F can ballast should be mounted with the “feet” side placed tightly against the inside of the fixture
b. J can ballast should be mounted with the PEM Stud side placed tightly against the inside of the fixture
2. Lamp holders and conductors:
a. Use minimum 4kV pulse rated lamp holder.
b. Use minimum 4kV pulse rated or UL style 3561 wire for lamp connections. The red lead must be connected to center terminal
of lamp. Do not connect any lamp lead to neutral or ground.
3. Grounding:
a. The ballast case and fixture must always be grounded. The grounding helps assure safety, proper lamp starting, and acceptable
EMI/RFI performance. Install ballast in accordance with national and local electrical codes.
4. Auto shut down function including end-of-life and thermal protection:
a. Disconnect power when servicing. Cycle power to reset ballast after auto shutdown.
5. Control: Do not operate with dimmer or occupancy sensor.
More installation considerations are in the QUICKANSWER section of the Ballast Technology and Specification Guide.
Ballast shall be a metal halide
SYLVANIA QUICKTRONIC MH electronic
ballast with universal input voltage.
Specifications
Voltage Range: ±10% of 120-277V
rated line (108-305V)
Input Frequency: 50/60 Hz
Power Factor: >98%
Low THD: <10%
Starting Temp: -22°F/-30°C min.
Lamp Frequency: 165Hz Square Wave
UL listed and UL listed to Canadian
safety standard, Type 1, Outdoor
Suitable for recessed use
80°C Max. Case Temperature,
Thermally Protected
FCC 47CFR Part 18 Non-Consumer
Sound Rated A
ANSI C62.41 Cat. A Transient Protection
Remote Mounting capability 3
Lamp current crest factor: <1.2
RoHS Compliant 4
3 Remote Mounting (max. wire length from
ballast case to lampholder): Typically 6ft.
but varies by application. For remote
mounting distances up to 15 ft, use #18
AWG minimum 7.5kV pulse rated wire.
Output wires should be enclosed in 1/2"
metal conduit to minimize EMI (electromagnetic interference). Wire and ground
ballast, fixture, conduit & lighting system
per NEC (National Electric Code).
4 Complies with European Union
Restriction of Hazardous Substances
Directive.
System Life / Warranty
QUICKTRONIC products are covered
by the QUICK 60+® warranty, a
comprehensive lamp and ballast
system warranty. For additional
details, refer to the QUICK 60+
warranty bulletin.
Packaging:
Quantity: 10 pieces per carton
Weight: 6 lbs. per carton
(0.6 lbs each)
Black
White
Black
BALLAST
White
INPUT
Green
Blue
Red
Item Number
51910 QTP 1 x 39 MH / UNV F
INPUT
Green
BALLAST
Blue
Blue/White
Red
Red/White
Case Type (Mounting Style)
QUICKTRONIC PROFESSIONAL
Line Voltage (120-277V)
Number of Lamps (1)
Metal Halide
Primary Lamp Wattage
Max. Case Temp.
Measured at
Warranty Period
Tc Point
<75°C
5 years
<80°C
3 years
OSRAM SYLVANIA
National Customer
Service and Sales Center
1-800-LIGHTBULB
(1-800-544-4828)
www.sylvania.com
Specifications subject to change without notice.
SPECIFICATION DATA
Catalog #
Date
Type
Project
Prepared by
MH QUICKTRONIC
®
Comments
Professional Series
Electronic Metal Halide Systems, Mini Sized
Item
Number
OSRAM SYLVANIA
Description
51958
QT1x20MH 120V SLIM
51959
QTP1x20MH UNV SQ F
51956
QTP1x20MH UNV SQ J
51960
QT1x39MH 120V SLIM
51961
QTP1x39MH UNV SQ F
Performance Guide
Input
Voltage
(VAC)
Input
Current
(AMPS)
Lamp
Type 1
Rated
Ballast
Input System
Lumens No. of Internal Factor System Wattage Efficacy
(lm) Lamps IDTP2 (BF) Lumens (W)
(lm/W)
120
0.20
20W T4.5
1700
1
No
1.0
1700
23
74
120-277 0.19/0.09 20W T4.5
1700
1
Yes
1.0
1700
23
74
120-277 0.19/0.09 20W T4.5
1700
1
Yes
1.0
1700
23
74
Formerly: QT1x20MH UNV SQ
39W T6
3400
1
No
1.0
3400
44
77
120-277 0.38/0.17
120
0.38
39W T6
3400
1
Yes
1.0
3400
44
77
120-277 0.38/0.17
39W T6
3400
1
Yes
1.0
3400
44
77
70W T6
7000
1
No
1.0
7000
79
89
120-277 0.66/0.29
70W T6
7000
1
Yes
1.0
7000
79
89
120-277 0.65/0.27
70W T6
7000
1
Yes
1.0
7000
79
89
Formerly: QT1x39MH UNV SQ
51957
QTP1x39MH UNV SQ J
51962
QT1x70MH 120V SLIM
51963
QTP1x70MH UNV SQ F
120
0.64
Formerly: QT1x70MH 120V SQ
51964
QTP1X70MH UNV SQ J
Installation Notes
1. Proper ballast mounting must be followed to allow for maximum thermal dissipation:
a. F can ballast should be mounted with the “feet” side placed tightly against the inside of the fixture
b. J can ballast should be mounted with the PEM Stud side placed tightly against the inside of the fixture
2. Lamp holders and conductors:
a. Use minimum 4kV pulse rated lamp holder.
b. Use minimum 4kV pulse rated or UL style 3561 wire for lamp connections. The red lead must be connected to center terminal
of lamp. Do not connect any lamp lead to neutral or ground.
3. Grounding:
a. The ballast case and fixture must always be grounded. The grounding helps assure safety, proper lamp starting, and acceptable
EMI/RFI performance. Install ballast in accordance with national and local electrical codes.
4. Auto shut down function including end-of-life and thermal protection:
a. Disconnect power when servicing. Cycle power to reset ballast after auto shutdown.
5. Control: Do not operate with dimmer or occupancy sensor.
More installation considerations are in the QUICKANSWER section of the Ballast Technology and Specification Guide.
Specifications
Input Voltage Range: ±10% of
rated input
Input Frequency: 50/60 Hz
Power Factor: >98%
Low THD: QTP: <10%
QT: <20%
Starting Temp: -22°F/-30°C min.
Lamp Frequency: 165-170Hz
Square Wave
UL Listed, Type 1, Outdoor
Suitable for recessed use
20&39W: 85°C Max. Case Temp.
70W: 90°C Max. Case Temp.
Thermally Protected
FCC 47CFR Part 18 Non-Consumer
Sound Rated A
ANSI C62.41 Cat. A Transient Protection
Remote Mounting capability3
Lamp current crest factor: <1.2
All Slim ballasts have a plastic can.
All others are metal.
RoHS Compliant 4
3 Remote Mounting (max. wire length from
ballast case to lampholder): Typically 6ft.
but varies by application. For remote
mounting distances up to 15 ft, use #18
AWG minimum 7.5kV pulse rated wire.
Output wires should be enclosed in 1/2"
metal conduit to minimize EMI (electromagnetic interference). Wire and ground
ballast, fixture, conduit & lighting system
per NEC (National Electric Code).
4 Complies with European Union Restriction
of Hazardous Substances Directive.
System Life / Warranty
QUICKTRONIC products are covered
by the QUICK 60+® warranty, a
comprehensive lamp and ballast
system warranty. For additional
details, refer to the QUICK 60+
warranty bulletin.
Packaging:
Quantity: 40 pieces per carton
Weight: 36 lbs. per carton
(0.9 lbs each)
White
Black
BALLAST
Max. Case Temp.
Measured at
Tc Point
70W: <90°C
<80°C
20 & 39W: <85°C
<75°C
INPUT
Green
Blue
Red
Item Number
51961 QTP 1 x 39 MH / UNV SQ F
Case Type (Mounting Style)
QUICKTRONIC PROFESSIONAL
Case Type
Number of Lamps (1)
Line Voltage (120-277V)
Primary Lamp Wattage
Metal Halide
Warranty Period
3 years
5 years
3 years
5 years
OSRAM SYLVANIA
National Customer
Service and Sales Center
1-800-LIGHTBULB
(1-800-544-4828)
www.sylvania.com
Specifications subject to change without notice.
QT MH
1: Data based on ceramic lamp types except where noted.
2: Internal IDTP - Insulation Detection Thermal Protector (see system information for detail).
Ballast shall be a metal halide SYLVANIA
QUICKTRONIC MH electronic ballast.
SPECIFICATION DATA
Catalog #
Date
Type
Project
Prepared by
MH QUICKTRONIC
®
Comments
Professional Series
Electronic Metal Halide Systems Universal Voltage (120-277V)
Performance Guide
J Case
Ballast shall be a metal halide
SYLVANIA QUICKTRONIC MH electronic
ballast with universal input voltage.
F Case
7.0"
(177.8mm)
7.0"
(177.8mm)
4.6"
(117.2mm)
5.0"
(128mm)
2.85"
(72.4mm)
QT MH
3.4"
(87.3mm)
2.0"
(50.8mm)
1.4"
(35.6mm)
Tc measurement
point
4.6"
(117.2mm)
3.4"
(87.3mm)
1.4"
(35.6mm)
PEM studs on 2" centers
(#8-32 x 0.375" long)
SQ F Case
75.3mm
3.0"
30.3mm
1.2"
Tc measurement
point
SQ J Case
254.1mm
10.0"
90.0mm
3.5"
65.0mm
2.6"
Mount
86.0mm
3.4"
Mount
4.0mm
0.2"
(2)PL
WIRE LENGTH
178mm
(7.0")
254mm
10.0"
©2010 OSRAM SYLVANIA
PEM STUD #8-32 x .375" LONG
Slim Case
127.8mm
5.0"
75.3mm
(3.0")
254mm
10.0"
120.0mm
4.7"
44.2mm
1.7"
132.0mm
5.2"
MOUNT LOC
140.0mm
5.5"
30.0mm
1.2"
37.6mm
(1")
50.8mm
(2.0")
39.25mm
(1.5")
90mm
(3.5")
The maximum case temperature
test point is located on the bottom
of the case and is designated
by “Tc” symbol.
OSRAM SYLVANIA
National Customer
Service and Sales Center
1-800-LIGHTBULB
(1-800-544-4828)
www.sylvania.com
Specifications subject to change without notice.
SYLVANIA, QUICK60+, METALARC and
the system solution are registered trademarks of OSRAM SYLVANIA Inc. QUICKTRONIC and POWERBALL are registered trademarks of OSRAM GmbH.
Download