Part III: Transfer Equipment Applications and Considerations transfer equipment used in optional standby systems Transfer Equipment Used in Optional Standby Systems for Commercial Applications by Chad Kennedy T ransfer equipment installations can be extremely complex, even for optional standby arrangements that are critical to business operation. This is the final installment in a series of articles examining transfer equipment used in optional standby systems for commercial applications. In Part I of this series, we covered the fundamentals of transfer equipment used in optional standby systems and the use of key interlocks to provide a safe, simple, and reliable means of transfer. Part II explored transfer equipment options along with guidance, questions to ask, and considerations for each system. This article will focus on transfer equipment for 3-phase, grounded systems. It will discuss requirements for the selection of three- or four-pole transfer and the impact to code-compliant installations. It will also discuss larger, more complex transfer applications found in data centers and hospitals. Three- or Four-Pole Transfer? One of the most common questions that arises when discussing transfer equipment is “do we need to switch the neutral?” The decision to use three- or four-pole transfer equipment requires that we understand and evaluate the potential for impact to other system design requirements such as equipment ground-fault protection, system stability and safety, and code compliance. The general rule of switching the neutral when ground-fault protection is required or desired must be balanced with how the alternate source is connected to the electrical system. The NEC permits the standby generator to be connected as a separately or non-separately derived system and this should be the first question asked when reviewing a system design plan. A separately derived system is defined in Article 100 as “A premises wiring system whose power is derived from a source of electrical energy or equipment 78 IAEI NEWS September.October 2009 www.iaei.org fault and protect the system. Failure to use four pole transfer equipment for a separately derived system would adversely affect the equipment groundfault protection and ability to recognize load unbalance. A more complicated and costly modified differential ground fault system would have to be designed and installed. transfer equipment used in optional standby systems equipment in order to provide the normal and alternate sources with mutually exclusive grounded circuit conductors (neutral), see figure 1. This is an important requirement since for separately derived systems the generator is required to be grounded per NEC 250.30. The use of four-pole transfer equipment and resulting separation of the systems allow the overcurrent protective device to recognize load unbalance current and avoid nuisance ground-fault tripping. Figure 2 illustrates that Figure 1 Figure 1. Four-pole transfer equipment used for separately derived system connection this is accomplished by preventing Four pole transfer equipment used for separately derived system connection. the neutral current from having a parallel path through the equipment grounding conductor (EGC). Another benefit of using four-pole transfer equipment in a separately derived system is demonstrated in figure 3. When a real ground fault occurs the current is not allowed to return to the source using the grounded conductor (neutral). This allows the overcurrent protective device to accurately recognize k-edit Optional Standby Systems for Commercial Applications Part III 052609.doc the fault and protect the system. Kennedy Failure to use four-pole transfer equipment for a separately derived system would adversely affect the equipment ground-fault protecFigure 2 imbalance current path with four-pole transfer equipment. Note that having the service neutral dis- tion and ability to recognize load Figure 2. Load Load imbalance current path with four pole transfer equipment. Note that having the service connected from the load prevents neutral current from returning through the main bonding jumper (MBJ) and equip- unbalance. A more complicated and neutral disconnected from the load prevents neutral current from returning through the main ment ground to the alternate source. costly modified differential groundbonding jumper (MBJ) and equipment ground to the alternate source. other than a service. Such systems have no direct electri- fault system would have to be designed and installed. cal connection, including a solidly connected grounded circuit conductor, to supply conductors originating in Four-Pole Transfer another system.” Section 702.10 specifies that portable System Considerations – generators can also be connected as a separately or non- System Stability and Safety separately derived system. Understanding if the system NEC 250.30(A)(1) requires separately derived systems was designed as separately or non-separately derived to have a system bonding jumper similar to the main connection is essential for transfer applications. Plan- bonding jumper required for services. A concern and ning for one type of system and getting the other can potential issue arises if the system bonding jumper is not installed or has been removed. When the load is translead to serious system performance issues. ferred to the alternate source the electrical system no longer has a ground reference, see figure 4. This situation Four-Pole Transfer System Considerations – can lead to system stability issues with abnormal phaseGround Fault Separately Figure 3 derived systems require four-pole transfer to-ground voltages which potentially damage electronic k-edit Optional Standby Systems for Commercial Applications Part III 052609.doc www.iaei.org Kennedy September.October 2009 IAEI NEWS 79 Figure 2 Load imbalance current path with four pole transfer equipment. Note that having the service transfer equipment used in optional standby systems neutral disconnected from the load prevents neutral current from returning through the main bonding jumper (MBJ) and equipment ground to the alternate source. with sensitive electronic components and should be considered in the system design. For this very reason, there are industries and engineers that will not consider switching the neutral due to the risk of loss to expensive electronics that are running or communicating with vital operations. Four-Pole Transfer System Considerations – Code Compliance It may be challenging to determine if code requirements have been met for a separately derived system when the alternate source is not on-site. This is often the case Figure 3. Example Figure 3 of possible ground-fault current flow with four-pole transfer equipment. A ground fault on the load of the transfer equipment cannot return to the alternate source using the grounded circuit when a portable generator is intended to conductor (neutral) but instead must return through the equipment grounding conductor or bus. be the alternate source. Will the portable k-edit Optional Standby Systems for Commercial Applications Part III 052609.doc Kennedy generator have the system bonding jumper installed? devices and controls. Stability can also be affected if the The lack of a proper system bonding jumper can result system has significant unbalanced line-to-neutral loads causing imbalanced line-to-neutral voltages. Since the in an unsafe system condition by allowing the system to alternate source is not grounded and four-pole trans- lose its reference to ground (ungrounded system) and by fer equipment was used, detection and locating system preventing the installed equipment ground-fault protecground faults become complicated. Failure to locate and tion from performing as designed. repair single phase-to-ground faults can result is serious power system damage if the fault escalates to a multiple Three-Pole Transfer System Considerations phase-to-ground fault. The most common transfer system solutions are threeFour-pole transfer equipment solutions often have pole. Non-separately derived systems will require an option to include an overlap or break before making three-pole transfer equipment because the alternate contact for the (neutral) grounded circuit conductor. source generator is connected as a feeder. This conLine-to-neutral voltage disturbances caused by switch- nection uses the normal source main bonding jumper ing the grounded circuit conductor can cause problems which connects the grounded conductor (neutral) to grounding electrode conductor as the grounding means for the alternate source grounded conductor. NEC-2005 250.24(A)(5) specifies that “A grounding connection shall not be made to any grounded conductor on the load side of the service disconnecting means except as otherwise permitted in this article.” However, NEC-2008 indicates the following: “A grounded conductor shall not be connected to normally non-current-carrying metal parts of equipment, to equipment grounding conductor(s), or be reconnected to ground on the load side of the service disconnecting Figure 4 means except as otherwise permitFigure 4. Four-pole transfer equipment where the alternate source generator does not have a system bonding jumper Four pole transfer equipment where the alternate source generator does not have a system bonding jumper. 80 IAEI NEWS September.October 2009 Four Pole Transfer System Considerations – Code Compliance It may be challenging to determine if code requirements have been met for a separately derived system when the alternate source is not on-site. This is often the case when a portable www.iaei.org generator system bonding jumper condition. It is still important to understand the generator bonding because if three pole transfer is used and the generator is bonded there will be a parallel path for neutral current flow along the equipment grounding conductors between the service and generator. Potential ungrounded system stability and safety concerns which can arise in four pole transfer systems do not occur in three pole transfer systems. There is a continuous, directused in optional standby systems transfer equipment connection to the grounded circuit conductor and service Main Bonding Jumper. and system ground faults. This is a benefit for installations intending to use a portable generator. Unlike the four-pole separately derived situation, three-pole transfer equipment solutions for this case will already provide a modified differential ground-fault system and thus provide equipment groundfault protection regardless of the portable generator system bonding jumper condition. It is still important to understand the generator bonding because if three-pole transfer is used and the generator is bonded there will be a parallel path for neutral current flow along the equipment grounding conductors Figure 5. Three-pole transfer equipment used in non-separately derived system Figure 5 between the service and generator. pole transfer equipment used in non-separately derived system. tedThree in this article.” Since this is a non-separately derived Potential ungrounded system stability and safety consystem, load side grounding is only permitted for sepa- cerns which can arise in four-pole transfer systems do not Advanced Applications rate building or structure applications where an equip- occur in three-pole transfer systems. There is a continument grounding conductor is not run with the building ous, direct connection to the grounded circuit conductor k-edit Optional Standby Systems for Commercial Applications Part III 052609.doc Kennedy An example of a non-separately derived system supply. and service main bonding jumper. using three-pole transfer equipment is shown in figure 5. Since the normal and alternate sources share a direct con- Advanced Applications nection to the grounded circuit conductor, installations There are power transfer applications more complex than where equipment ground-fault protection is required for the traditional two source transfer discussed up to this the alternate source will require a modified differential point. In particular, the systems seen in data centers and ground-fault system to properly discern load imbalances hospitals are not only more complex but also much larger than most transfer systems. The following sections will provide basic insight into the systems typically supplied in hospitals and data centers and how optional standby systems are utilized. Data Centers Figure 6 example of the power distribution one-line diagram in a data center Figure 6. Typical Typical example of the power distribution one line diagram in a data center. www.iaei.org Few installations implement the redundancy found in the data center environment. The power distribution and transfer equipment is often seen as a key competitive advantage and decision point for potential customers. This reflects current business reliance on the internet and data access and storage capabilities as part of day-today operation and revenue generation. It is also possible that a September.October 2009 IAEI NEWS 81 transfer equipment used in optional standby systems Photo 1. Part of the main switchgear line-up in a data center data center may be deemed critical to communication such as a telephone exchange or voice-over-Internet protocol (VoIP) where government regulation drives such a facility to be an emergency system. It is also recognized that portable systems are often used to provide back-up while an emergency system is undergoing maintenance. Figure 6 illustrates the basic data center power distribution structure and redundancy. The distribution of power to the data center power distribution units (PDUs) is the primary objective of these systems. Starting at the PDU there are typically two sources of power from redundant uninterruptible power supply (UPS) switchboards. A double pole, double throw switch is one method used to select which source feeds the PDU. The UPS switchboards are also each redundantly supplied from one or multiple UPS modules and a combination source supplied by utility or generator sources. These sources are usually key interlocked with the UPS module providing power to the UPS switchboard under normal conditions. The UPS module is supplied by the main switchgear which usually contains feeds from utility transformers and on-site generators. The utility main breakers, tie breakers, and generator breakers are normally controlled by a programmable logic controller (PLC) based automatic throw-over system to transfer power as needed to supply the PDUs. Although these systems are classified as optional standby systems, the performance of the data center power transfer system exceeds what would normally be supplied for emergency or legally required systems. Photo 1 is an example of just one of the equipment line-ups making up the main switchgear in a data center. Advanced Applications – Hospitals Article 517 details the requirements of power transfer in health care facilities including the division of loads into essential and nonessential systems. A typical hospital power flow diagram is shown in figure 7. The loads classified as emergency are segregated from normal distribution equipment and fed from unique automatic transfer switches. However, there are loads classified as nonessential which must meet Article 702 optional standby system requirements. These loads can be supplied from the same utility and generator sources as the emergency 82 IAEI NEWS September.October 2009 www.iaei.org transfer equipment used in optional standby systems Plan Review and Inspection Transfer equipment applications can range from simplistic installations to very complex optional standby systems for data centers and hospitals. The considerations for three- or four-pole transfer, ground-fault protection of equipment, system stability and safety, as well as code-compliance challenges must be integrated to work as a system. Clearly these considerations have dependencies and therefore must be considered as part of an overall system design to ensure that the optional standby system provides the desired benefits and does not negatively impact normal sysFigure 8 Figure 7. Typical power system transfer structure for hospitals. Neutral connections to ATSs were removed for tem performance. In particular, Typical power system transfer structure for hospitals. Neutral connections to ATSs were clarity. understanding the design intent removed for clarity. loads as long as they originate from separate vertical as separately or non-separately derived and attenA Final note on Ground Fault Protection switchboard sections and the wiring is kept entirely sep- tion to four-pole transfer systems using portable Optional standby systems continue to grow in size to not only power a few business critical arate frombutthe 700.5 generators is required to provide a safe, code-comfunctions areemergency being sized tosystem maintainwiring. continuitySection of business for an entire facility. NEC 702 doesthe not exempt a system from ground accordance with NEC 215.10. requires generator to be rated forfault allprotection possibleinloads pliant installation. So here are a few items you can The risk of losing your electrical system for an extended period due to not protecting the orsystem have with some type of load management with priority review: ground fault far outweighs the possible short-term condition of taking the system given loads. system due to a fault. Even ground fault protection downto andemergency saving the distribution on anquestion is always – Is this an NEC 700, 1. The first emergency system is permitted. The only disconnect that exists with regard fault 701 toorground 702 system? protection is in NEC 517.17 where it is prohibited between the generator and the essential system on and Ground-Fault on the load side of theProtection transfer switch of the essential 2. electrical system. Is the system configured as separately or nonA electrical Final Note Remember that ground fault protection protects your electrical system to ensure it will Optional standby systems continue to grow in size separately derived? continue to operate after appropriate maintenance. Removal of ground fault simply provides toanot only power a few business critical functions butis potentially few moments of operations while the switchboard and or system destroyed 3. Does theby transfer switch (3- or 4-pole) match the fault taking arethebeing sizedplace. to maintain continuity of business for configuration of the system’s source? an entire facility. NEC 702 does not exempt a system 4. Is the system grounding system appropriately infrom ground-fault protection in accordance with NEC stalled and bonded? 215.10. The risk of losing your electrical system for an k-edit Optional Standby Systems for Commercial Applications Part III 052609.doc 5. Is this system large enough for ground-fault proextended period due to not protecting the system with Kennedy tection and is it installed? ground fault far outweighs the possible short-term 6. Do we have the appropriate disconnects and overcondition of taking the system down and saving the distribution system due to a fault. Even ground-fault current protection located and sized appropriately? protection on an emergency system is permitted. The 7. Is the alternate source a portable generator? If so, only disconnect that exists with regard to ground-fault how is the system configuration and necessary generator protection is in NEC 517.17 where it is prohibited be- bonding condition communicated? tween the generator and the essential electrical system and on the load side of the transfer switch of the esChad Kennedy is the manager, Industry Standards for Power sential electrical system. Remember that ground-fault Equipment and is a registered professional engineer in the state of protection protects your electrical system to ensure it South Carolina. He has been with Square D for over nineteen years will continue to operate after appropriate maintenance. and has served as the engineering manager for custom switchgear and switchboard design supporting the design of systems for power transfer Removal of ground fault simply provides a few mo- and distribution in industrial, commercial, and retail areas. He is a ments of operation while the switchboard and/or sys- member of NFPA, serving on NEC Panel 13, and is an active particitem is potentially destroyed by the fault taking place. pant in IEEE, UL, NEMA and IAEI. www.iaei.org September.October 2009 IAEI NEWS 83