ELG3311: Solutions for Assignment 1 Problem 2-6: A 15-kVA 8000/230-V distribution transformer has an impedance referred to the primary of 80 + j300Ω. The components of the excitation branch referred to the primary side are RC = 350 kΩ and XM = 70 kΩ. (a) If the primary voltage is 7967 V and the load impedance is ZL = 3.0 +j1.5 Ω, what is the secondary voltage of the transformer? What is the voltage regulation of the transformer? (b) If the load is disconnected and a capacitor of –j4.0 Ω is connected in its place, what is the secondary voltage of the transformer? What is its voltage regulation under these conditions? Solution: (a) The turns ratio is a = 8000 / 230 = 34.78 The load impedance referred to the primary side is Z LP = a 2 Z L = (34.78) 2 (3.0 + j1.5) = 3629 + j1815 Ω The referred secondary current is I SP = VP 7967∠0° = = 1.87∠ − 29.7° A P + Z L (80 + j 300) + (3629 + j1815) Z iP The referred secondary voltage is VSP = I SP Z LP = (1.87∠ − 29.7°)(3629 + j1815) = 7588∠ − 3.1° V The actual secondary voltage is VSP 7588∠ − 3.1° = = 218.2∠ − 3.1° V VS = a 34.78 The voltage regulation is VP − VSP 7967 − 7588 = × 100% = 4.99% VR = 7588 VSP 1 (b) The turns ratio is a = 8000 / 230 = 34.78 The load impedance referred to the primary side is Z LP = a 2 Z L = (34.78) 2 (− j 4.0) = − j 4839 Ω The referred secondary current is I SP = VP 7967∠0° = = 1.75∠89.0° A P + Z L (80 + j 300) + (− j 4839) Z iP The referred secondary voltage is VSP = I SP Z LP = (1.75∠89.0°)(− j 4839) = 8468∠ − 1.0° V The actual secondary voltage is VS = VSP 8468∠ − 1.0° = = 243.2∠ − 1.0° V a 34.78 The voltage regulation is VP − VSP 7967 − 8468 = × 100% = −5.92% VR = 8468 VSP 2 Problem 2-7: A 5000-kVA 230/13.8-kV single-phase power transformer has a per-unit resistance of 1 percent and a per-unit reactance of 5 percent (data taken from the transformer’s nameplate). The open-circuit test performed on the low-voltage side of the transformer yielded the following data: VOC = 13.8 kV, IOC = 15.1 A, POC = 44.9 kW (a) Find the equivalent circuit referred to the low-voltage side of this transformer. (b) If the voltage on the secondary side is 13.8 kV and the power supplied is 4000 kW at 0.8 PF lagging, find the voltage regulation of the transformer. Find its efficiency. Solution: (a) The components of the excitation branch relative to the low-voltage side (secondary side) are YEX = GC − jBM = θ = − cos −1 I OC 15.1 = = 0.0010942 VOC 13.8k POC 44.9k = − cos −1 = −77.56° VOC I OC (13.8k )(15.1) YEX = YEX ∠θ = GC − jBM = 0.0010942∠ − 77.56° = 0.0002358 − j 0.0010685 RC = 1 1 = = 4240 Ω GC 0.0002358 XM = 1 1 = = 936 Ω BM 0.0010685 The base impedance of this transformer referred to the low-voltage side (secondary side) is Z base = 2 Vbase (13.8k ) 2 = = 38.09 Ω 5000k S base So that REQ = 1% Z base = (0.01)(38.09) = 0.38 Ω X EQ = 5% Z base = (0.05)(38.09) = 1.90 Ω The resulting equivalent circuit is shown below 3 REQ ,S = 0.38 Ω X EQ,S = 1.9 Ω RC ,S = 4240 Ω X M ,S = 936 Ω (b) The secondary current is IS = Pout 4000 kW = = 362.3 A VS PF (13.8 kV)(0.8) θ = − cos −1 PF = − cos −1 (0.8) = −36.87° I S = 362.3∠ − 36.87° A The voltage on the primary side of the transformer (referred to the secondary side) is VPS = VS + I S Z EQ,S = 13800∠0° + (362.3∠ − 36.87°)(0.38 + j1.9) = 14330∠1.9° V The voltage regulation of the transformer is VR = VPS − VS 14330 − 13800 × 100% = × 100% = 3.84% VS 13800 The transformer copper losses and core losses are Pcopper = I S2 REQ ,S = (362.3) 2 (0.38) = 49.9 kW Pcore = (VPS ) 2 (14330) 2 = = 48.4 kW RC 4240 Therefore the efficiency of this transformer at these conditions is 4 η= Pout Pout + Pcopper + Pcore × 100% = 4000 kW × 100% = 97.6% 4000 kW + 49.9 kW + 48.4 kW Problem 2-8: A 200-MVA, 15/200-kV single-phase power transformer has a per-unit resistance of 1.2 percent and a per-unit reactance of 5 percent (data taken from the transformer’s nameplate). The magnetizing impedance is j80 per unit. (a) Find the equivalent circuit referred to the low-voltage side of this transformer. (b) Calculate the voltage regulation of this transformer for a full-load current at power factor of 0.8 lagging. (c) Assume that the primary voltage of this transformer is a constant 15 kV, and plot the secondary voltage as a function of load current for currents from no load to full load. Repeat this process for power factors of 0.8 lagging, 1.0, and 0.8 leading. Solution: (a) The base impedance of this transformer referred to the low-voltage side (primary) is Z base = 2 Vbase (15k ) 2 = = 1.125 Ω S base 200M So that REQ = 1.2% Z base = (0.012)(1.125) = 0.0135 Ω X EQ = 5% Z base = (0.05)(1.125) = 0.0563 Ω And X M = (80) Z base = (80)(1.125) = 90 Ω The equivalent circuit referred to the low-voltage side of this transformer is shown below REQ , P = 0.0135Ω X EQ , P = 0.0563Ω RC , P = not − spcified X M , P = 90Ω 5 (b) The current on the secondary side of the transformer (referred to the primary side) is I SP = Pout 200 MW = = 16667 A VS PF (15 kW )(0.8) θ = − cos −1 PF = − cos −1 (0.8) = −36.87° I SP = 16667∠ − 36.87°A The voltage on the primary side of the transformer is VP = VSP + I SP Z EQ , P = 15000∠0° + (16667∠ − 36.87°)(0.0135 + j 0.0563) = 15755∠2.24°V Therefore the voltage regulation of the transformer is VR = VP − VSP VSP × 100% = 15755 − 15000 × 100% = 5.03% 15000 (c) This problem is repetitive in nature, and is ideally suited for MATLAB. A program to calculate the secondary voltage of the transformer as a function of load is shown below: % % % % % % M-file: prob2_8.m M-file to calculate and plot the secondary voltage of a transformer as a function of load for power factors of 0.8 lagging, 1.0, and 0.8 leading. These calculations are done using an equivalent circuit referred to the primary side. % Define values for this VP = 15000; % amps = 0:166.67:16667; % Req = 0.0135; % Xeq = 0.0563; % transformer Primary voltage (V) Current values (A) Equivalent R (ohms) Equivalent X (ohms) % Calculate the current values for the three % power factors. The first row of I contains % the lagging currents, the second row contains % the unity currents, and the third row contains % the leading currents. I(1,:) = amps .* ( 0.8 - j*0.6); % Lagging I(2,:) = amps .* ( 1.0 ); % Unity 6 I(3,:) = amps .* ( 0.8 + j*0.6); % Leading % Calculate VS referred to the primary side % for each current and power factor. aVS = VP - (Req.*I + j.*Xeq.*I); % Refer the secondary voltages back to the % secondary side using the turns ratio. VS = aVS * (200/15); % Plot the secondary voltage (in kV!) versus load plot(amps,abs(VS(1,:)/1000),'b-','LineWidth',2.0); hold on; plot(amps,abs(VS(2,:)/1000),'k--','LineWidth',2.0); plot(amps,abs(VS(3,:)/1000),'r-.','LineWidth',2.0); title ('\bfSecondary Voltage Versus Load'); xlabel ('\bfLoad (A)'); ylabel ('\bfSecondary Voltage (kV)'); legend('0.8 PF lagging','1.0 PF','0.8 PF leading'); grid on; hold off; The resulting plot of secondary voltage versus load is shown below: 7 Problem 2-14: A 13.2-kV single-phase generator supplies power to a load through a transmission line. The load’s impedance is Zload = 500 ∠36.87°Ω , and the transmission line’s impedance is Zline = 60 ∠53.1°Ω . (a) If the generator is directly connected to the load, what is the ratio of the load voltage to the generated voltage? What are the transmission losses of the system? (b) If a 1:10 step-up transformer is placed at the output of the generator and a 10:1 transformer is placed at the load end of the transmission line, what is the new ratio of the load voltage to the generated voltage? What are the transmission losses of the system now? (Note: The transformers may be assumed to be ideal.) Solution: (a) In the case of the directly-connected load, the line current is I line = I load = VG 13.2∠0°kV = 23.66∠ − 38.6°A = Z line + Z load 60∠53.1° + 500∠36.87° The load voltage is 8 Vload = I load Z load = (23.66∠ − 38.6°)(500∠36.87°) = 11.83∠ − 1.73°kV The ratio of the load voltage to the generated voltage is ratio = Vload 11.83 kV = = 0.896 13.2 kV VG The resistance in the transmission line is Rline = Z line cosθ = (60)(cos 53.1°) = 36Ω The transmission losses in the system are 2 Ploss = I line Rline = (23.66) 2 (36) = 20.1 kW (b) In this case, a 1:10 step-up transformer precedes the transmission line a 10:1 stepdown transformer follows the transmission line. If the transformers are removed by referring the transmission line to the voltage levels found on either end, then the impedance of the transmission line becomes ′ = a 2 Z line = (1 / 10) 2 (60∠53.1°) = 0.60∠53.1°Ω Z line The current in the referred transmission line and in the load becomes ′ = I load = I line VG 13.2∠0°kV = = 26.37∠ − 36.89° A ′ + Z load 0.60∠53.1° + 500∠36.87° Z line The load voltage is Vload = I load Z load = (26.37∠ − 36.89°)(500∠36.87°) = 13.185∠ − 0.02°kV The ratio of the load voltage to the generated voltage is ratio = Vload 13.185k = = 0.9989 VG 13.2k The current in the transmission line is I line = aI load = (1 / 10)(26.37) = 2.637 A The losses in the transmission line are 9 2 Ploss = I line Rline = (2.637) 2 (36) = 250W Problem 2-15: A 5000-VA, 480/120-V conventional transformer is to be used to supply power from a 600-V source to a 120-V load. Consider the transformer to be ideal, and assume that all insulation can handle 600 V. (a) Sketch the transformer connection that will do the required job. (b) Find the kilovoltampere rating of the transformer in the configuration. (c) Find the maximum primary and secondary currents under these conditions. Solution: (a) The common winding must be the smaller of the two windings, and NSE = 4 NC. The transformer connection is shown below: (b) The kVA rating of the transformer is S IO = N SE + N C 4NC + NC SW = (5000) = 6250VA NC NC (c) The maximum primary current for this configuration is IP = S IO 6250 = = 10.4 A VP 600 The maximum secondary current is IS = S IO 6250 = = 52.1A VS 120 10 Problem 2-19: A 20-kVA, 20,000/480-V, 60-Hz distribution transformer is tested with the following results: Open-circuit test Short-circuit test (measured from secondary side) (measured from primary side) VOC = 480 V VSC = 1130 V IOC = 1.60 A ISC = 1.00 A POC = 305 W PSC = 260 W (a) Find the per-unit equivalent circuit for this transformer at 60 Hz. (b) What would be the rating of this transformer be if it were operated on a 50-Hz power system? (c) Sketch the per-unit equivalent circuit of this transformer referred to the primary side if it is operating at 50 Hz. Solution: (a) The base impedance of this transformer referred to the primary side is Z base, P = VP2 (20000) 2 = = 20 kΩ S 20k The base impedance of this transformer referred to the secondary side is Z base,S = VS2 (480) 2 = = 11.52 Ω S 20k The open-circuit test yields the values for the excitation branch (referred to the secondary side) YEX = I OC 1.60 = = 0.00333 VOC 480 θ = − cos −1 POC 305 = − cos −1 = −66.6° VOC I OC (480)(1.60) YEX = YEX ∠θ = GC − jBM = 0.00333∠ − 66.6° = 0.00132 − j 0.00306 RC = 1 1 = = 757Ω GC 0.00132 XM = 1 1 = = 327Ω BM 0.00306 11 The excitation branch elements can be expressed in per-unit as RC , pu = RC Z base,S = 757 = 65.7 pu 11.52 X M , pu = XM 327 = = 28.4 pu Z base ,S 11.52 The short-circuit test yields the values for the series impedances (referred to the primary side) Z EQ = VSC 1130 = = 1130 I SC 1.00 θ = cos −1 PSC 260 = cos −1 = 76.7° (1130)(1.00) VSC I SC Z EQ = Z EQ ∠θ = REQ + jX EQ = 1130∠76.7° = 260 + j1100 REQ = 260 Ω X EQ = 1100 Ω The resulting per-unit impedances are R EQ , pu = R EQ Z base , P = 260 = 0.013 pu 20k X EQ , pu = X EQ Z base , P = 1100 = 0.055 pu 20k Therefore the per-unit equivalent circuit is show below REQ , pu = 0.013 pu X EQ , pu = 0.055 pu RC , pu = 65.7 pu X M , pu = 28.4 pu 12 (b) If this transformer were operated at 50 Hz, both the voltage and apparent power would have to be derated by a factor of 50/60, so its ratings would be S 50 = (50 / 60) S 60 = (50 / 60)(20k ) = 16.67 kVA VP ,50 = (50 / 60)VP ,60 = (50 / 60)(20000) = 16667V VS ,50 = (50 / 60)VS ,60 = (50 / 60)(480) = 400V (c) The transformer parameters referred to the primary side at 60 Hz are REQ = Z base REQ , pu = (20k )(0.013) = 260Ω X EQ = Z base X EQ , pu = (20k )(0.055) = 1100Ω RC = Z base RC , pu = (20k )(65.7) = 1.31MΩ X M = Z base X M , pu = (20k )(28.4) = 568kΩ At 50 Hz, the resistances will be unaffected but the reactances are reduced in direct proportion to the decrease in frequency. REQ ,50 = REQ ,60 = 260Ω X EQ ,50 = (50 / 60) X EQ ,60 = (50 / 60)(1100) = 917Ω RC ,50 = RC ,60 = 1.31MΩ X M ,50 = (50 / 60) X M , 60 = (50 / 60)(568) = 473kΩ The base impedance of the transformer operating at 50 Hz referred to the primary side is Z base , P ,50 = VP2 (16667) 2 = = 16.67kΩ S 16.67k 13 The resulting per-unit equivalent circuit referred to the primary at 50 Hz is shown below REQ , pu ,50 = RC , pu ,50 = REQ ,50 Z base, P ,50 RC ,50 Z base , P ,50 = = 260 = 0.016 pu 16.67 k 1.31M = 78.5 pu 16.67 k X EQ , pu ,50 = X M , pu ,50 = X EQ ,50 Z base , P ,50 X M ,50 Z base, P ,50 = = 917 = 0.055 pu 16.67 k 473k = 28.4 pu 16.67 k 14